Loading...
HomeMy WebLinkAbout2050 CUTTING HORSE DR - DISCLOSURES - 5/10/2016BUILDING LEAKAGE TEST Date of Test: 5/10/2016 Test File: 2050 Cutting Horse Dr DR Horton REM 14.6.1 tectite Customer: DR Horton Technician: Neal Girard - EnergyLogic Project Number: 40106 Building Address: 2050 Cutting Horse Dr Ft Collins, CO 80525 Test Results 1. Airflow at 50 Pascals: 1228 CFM50 (+/- 1.5 %) (50 Pa = 0.2 w.c.) 1.90 ACH50 2. Leakage Area: 67.5 in2 LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 68.6 (+/- 22.2 %) Exponent (n) = 0.737 ( +/- 0.059 ) Correlation Coefficient = 0.99685 4. Test Settings: Test Standard: RESNET Multi -Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate 2. Estimated Design Infiltration Rate Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: 58.2 CFM 0.09 ACH 14.5 CFM per person Winter: 82.3 CFM Summer: 60.4 CFM 0.13 ACH 0.09 ACH Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 69.5 CFM Base Rate: 69.5 CFM No Text