HomeMy WebLinkAbout2050 CUTTING HORSE DR - DISCLOSURES - 5/10/2016BUILDING LEAKAGE TEST
Date of Test: 5/10/2016 Test File: 2050 Cutting Horse Dr DR Horton REM 14.6.1 tectite
Customer: DR Horton Technician: Neal Girard - EnergyLogic
Project Number: 40106
Building Address: 2050 Cutting Horse Dr
Ft Collins, CO 80525
Test Results
1. Airflow at 50 Pascals: 1228 CFM50 (+/- 1.5 %)
(50 Pa = 0.2 w.c.) 1.90 ACH50
2. Leakage Area: 67.5 in2 LBL ELA @ 4 Pa
3. Building Leakage Curve: Flow Coefficient (C) = 68.6 (+/- 22.2 %)
Exponent (n) = 0.737 ( +/- 0.059 )
Correlation Coefficient = 0.99685
4. Test Settings: Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate
2. Estimated Design Infiltration Rate
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
58.2 CFM
0.09 ACH
14.5 CFM per person
Winter: 82.3 CFM Summer: 60.4 CFM
0.13 ACH 0.09 ACH
Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010)
Recommended Whole Bldg Rate: 69.5 CFM
Base Rate: 69.5 CFM
No Text