HomeMy WebLinkAbout6215 SWAINSONS HAWK PL - DISCLOSURES - 1/25/2016City of Fort Collins Residential Mechanical Systems Performance Report Updated 3/7/2014 This form is a record of testing targets and results, with Pass/Fail outcomes. For Information on measurement tools Cityof and testing techniques, see the "Residential New Construction Mechanical Systems Testing Guide." The guide and F ` CoLlInS this form may be periodically updated; check the Building Services web site for the current version. ��- uaiiues This form must be completed and signed by an "Approved Agency," and submitted to Building Services as a requirement for receiving a C.O. Color key Target Measured value to compare with = s - `• Pass: Other or limit target or limits ;: >> data Address / Builder CL_L_ ' HVAC contractor fort Collins As -built changes vs mech design submittal ADCF = Air Density Correction Factor, based on tool, ADCF altitude (5000% air temperature through tool Volumetric flow (CFM 5000') = ADCF x Indicated flow (CFM) ,W and Air Conditioning Date of "Residential Mechanical Systems r Design Submittal" ^ �� information referenced by testing technicians Testing date(s)�- 2. Local Exhaust (Spot Ventilation) Bath exhaust Testing tech (initials) Fl..7 Flow box _ tube duct traverse Air letup ( ADCF �j Other tool X Passive flow hood —Other (note below) through tool (F)l L, Measured Airflow Design Airflow(CFM Minimum Airflow Requirement Indicated Volumetric Exhaust Pickup Location (CFM (CFM 5000') Flow Flow Pass Fail 5000.) + Type of Operation (CFM) (CFM 5000) VlT ✓50 intermittent — 20 Continuous ff!!*lntermittent—20Continuous bf?lfJj !!�'50Intermittent—20Continuous l —50Intermittent —20Continuous 1 50 Intermittent —20 Continuous ❑ T 50 Intermittent — 20 Continuous ❑ _ 50 Intermittent — 20 Continuous ❑ Testing notes Kitchen exhaust N/A - hood does not vent to outside Testing tech (initial Oven fuel was — Electric Minimum airflow requirement (CFM 5000') + operation L. Intermittent 25 Continuous Measured airflow Flow tool — Flow box — Passive flow hood _ itot tube traverse Flow grid Tool location — Interior grille —x haust duct Air temp through ADCF z _Powered flow hood Other (note below) (Exterior termination not OK) tool (F) Indicated flow CFM Volumetric flow CFM 5000' 15Pa8s Fail t Testing notes Residential Mechanical Design Submittal V20140307 Pagel kj, Whole -House Ventilation Systems other than sub -structural floor exhaust Testing tech (initials) Code-minimurn ventilation airflow Q Design ventilation (based on CFA and # of BR) 1 CFM 5000' airflow i �S CFM 5000' _-=Xc aust-only System Suppiyonly C( Q� type — Balancod Target ventilation airflow range 1 1 to CFM 5000' — (codo-minimum) 120%of design flow) Measured Airflow Air Temp Indicated Volumetric Measurement Method Tool Location Through Ali Flow Flow Pass Fail Tool (F} (CFM) (CFM 5000') Total _ WA ✓isassive flow hood 'fpu�d js r, r� y.t 5 exhaust _ Flow box _ Pilot tube traverse alrflow — Flow collar — Other (note below) Total _ WA _ Passive flow hood supply _ Flow box _ Pilot tube traverse loll airflow Flow collar Other (note below) When supply airflow Is circulated by air handler fan, fan speed for measurement Heating Cooling Continuous fan Balanced airflow, in balanced systems Average of measured CFM Target flow range CFM supply + exhaust flows 5000' (average +!- 15%) tO 5000, Pass I Fail Testing notes Sub -structural floor exhaust ❑ NIA -- no sub -structural floor exhaust system Testing tech (initials) Design exhaust airflow (based on Target 5000' Target airflow limits to CFM 5000, approved design) (design +!- 15%) Measured airflow Flow tool — Flow box Passive flow hood — Pilot tube traverse — Flow collar Tool location Air temp through ADCF — Powered flow hood Other (note below) tool (F) Indicated flow CFM Volumetric flow CFM 5000' ❑ Pass ® Fail Heating4. + Cooling Duct Leakage N/A -- No ductwork Testing notes.`, — No ductwork outside conditioned space (incl multiple Sys) Duct leakage data source —Testing tech (initials). Lt 5� f _C /� _ Energy y, tes nC d � � �— Sy Co YS�r9AC_J1� -% Ca k-4;CS4l� J1' _ company, testing date): 2 r 2d% House conditioned floor area [ // Air temp (include full basement) 7 &g sf through tool (F)� ADCF Maximum Allowed Duct Leakage Measured Duct Leakage Test Parameter and Conditions I Normalized I Absolute ar 1nMr-tt System #1 System #2 Leakage Type Timing Air Handler (CFM25 5000' 1100 sf) (CFM25 5000') (CFM25) (CFM25 5000') PassfFallpasisTotal leakage Rough -in Excluded 3 ❑Total leakage Rough -in Included 4dTotal leakage Complete Included 4 Residential Mechanical Design Submittal V20140307 Page 2 For multiple systems, attach one page per system Which parts of house does it serve? System #a� Installed equipment (Be clear about which AC components are installed at time of testing) Testing tech (initials) - Furnace or Boiler Ac or Heat Pump Condenser AC or Heat Pump Colt Manufacturer Model #A c�7 _ Basic fiberglass _ Electrostatic Filter //' I Type17,141gh-efft Basic pleated _ Other:Thickness MERV brand (Jpleated (inches) (optional) Static pressures Setup Speed: ,--neleating __ Cooling _ Cont. fan _ High -stage for multi -stage equipment Blower speed tap: Humidifier damper. _ NIA _ Open (Heating) _ Closed (Cooling) All registers open Zone dampers open SP1 �� r AP Filter (SP1 SP2I--L Testing tech (initials) (Same location SP4 forNSOP, TFSOP) DP Coil t---4—t (SP3-SP4) .5P3 AP Total ESP (SP3-SP2) Cooling: Measured air flow through indoor coil ❑ N/A— no AC installed Testing tech (initials) Design cooling airflowCFM 5000' Target airflow limits W to ' J 1� CFM 5000' (high stage) 1 lfJ (design +1-15%) L-lJ Measured airflow Flow, grid _ 14' Air tem r Flow Resistance plate!size _ 20 through �D ADCF ` NSOP® TFSOP 5c� toot F Correction Factor Measured airflow, no � CFM Indicated airf(ow �j CFM Volumetric airflow r,� CFM effaass adjustment/correction t� Measured AF x FRCF� Indicated AF x AOCF rCJ5�) 5000' 0 Fail Heating: Gas manifold pressure (high stage) Testing tech (initials) Manifold pressure 7 IWC Target manifold P to IWC Measured Z IWC ass OEM spec @ 5000' L limits (spec+/- 5%) �q .� pressure Fail Heating: Temperature rise Testing tech (initials) OEM temperature rise limits to �© F (highstace) V Supply j _ Return _ Temp /�K11asCaution: within 10F Measured temps (F): air (� air rise 1 s Fail ❑ of top of range Residential Mechanical Design Submittal V20140307 Page 3 For multiple systems, attach one page per system System #M Which parts of house does it serve? J� G�1 'T M ` t Installed equipment (Be clear about which AC components are installed at time of testing) Testing tech (initials)/�y� Furnace or Boller AC or Heat Pump Condenser AC or Heat Pump Coil Manufacturer �,,//,,lam� Gam- 2i2-1. a-, � (.?-•1 ,�J < Model # �` Z ltG�lldCJ �� C c l hJ ili t�Zr'--� 0 0 Q`(-F Tjc ( LfAigh-effic Basic fiberglass _ Electrostatic Fiber ,- Type Basic pleated _ Other: Thickness MERV❑ brand �fT� pleated (inches) (optional) Static pressures Setup Speed: _Heating •!Cooling _ Cont. fan High -stage for multi-s age equipment ,wer speed tap: midifler damper _ N/A Open (Heating) _ Closed (Cooling) All registers open Zone dampers open SP1 AP Filter (SP1 - SP2) SP2 Testing tech (initials)®— �• (Sarne location • SP4 �/.-� for NSOP. J 7FSOP) AP Coil ` (SP3-SP4) 1 .SP3 AP Total ESP �l (SP3-SP2) 1 Cooling: Measured air flow through indoor coil ❑ N/A - no AC installed Testing tech (initials) Design cooling airflow 1 04 CFM 5000' Target airflow, limits Q to (-�Z CFM 5000' (high slage) l (design +/_ 15%) {� Measured airflow, Flow grid 14 Air tempFlow�/� ADCF ` NSOP TFSOP Z Flow Resistance o a� t�20 tool (F) plate size Correctioonn F Measured airflow, no (�� CFM Indicated airflow �r� CFM Volumetric airflow I,©�t FM [-lass adjustment/correction _` Measured AF x FRCF J IndicatedAFxADCF ( 5000' ®Fail Heating: Gas manifold pressure (high stage) Testing tech (initials) Manifold pressure Target manifold P OEMs Spec 5000' IWC limits (Spec �2 to 2 p @ � � g(p ) � -J 1 • Measured IWC pressure -� Pass IWC ®Fail Heating: Temperature rise Testing tech (initials) OEM temperature rise limits j I to F - (high stage) l Supply Measured temps (F): air 7 Co _ Return airy-IJ Temp rise r' ass Fail ElCaution: within 10F of top of range Residential Mechanical Design Submittal V20140307 Page 3 Testing tech (initials) Testing approach and targets ❑ N/A: No complete AC system /A: House completed November - April (installing contractor responsible for testing in warm weather) ❑ TXV: Subcooling + SH check ❑ Non-TXV: Superheat ❑ OEM -specific: Approach ❑ Other OEM -specific (documentation required) Temperatures Condenser Non-TXV: Return Target Target Target (F): entering air temp air we[ -bulb temp superheat subcooling approach Subcooling Discharge Condenser Liguid Actual El TXV Pass: Actual SC within +/- pressure saturation line❑F subcooling❑F 3 F of target SC, 2 F min (PSI) (50og'chart) rt) temp (CondT-!igline T) TXV Fail Superheat Suction Evaporator Suction Actual ElNon-TXVPass: Actual SH pressure saturation T❑F line❑F superheat❑F within +/- 5 F of target SH (PSI) (50ce'chart) temp (SurttineT-evapT) Non-TXV Fail TXV checks: ❑ Pass: Field -installed TXV installed in accordance with OEM instructions ❑ Caution: Actual SH outside mfgr range Approach Liquid line �F Actual approach �F ❑ Approach Pass: Actual approach within +/- 1 F of target approach temp (LiglineT- condenser EAT) EApproach Fail Testing notes 00 ootsv 10 Register air flows All registers are out through finish materials and moving air ❑ Pass ®Fail (Remainder of register air flow section under development, not yet being enforced) Pressure balance Testing tech (initials) Testing tech (initials) Room (match names on plans, include basement if there is a door) Room -to -Core Pressure Drop Target Range (Pa) Metasured Pressure Drop (Pa) Pass Fail Qlw�l�� -3to+3 M� -3 to +3 ,. S Z -3 to +3 -3 to +3 } per—` -3 to +3 t -3 to +3 ❑ -3 to +3 ❑ -3 to +3 ❑ -3 to +3 ❑ -3 to +3 ❑ Residential Mechanical Design Submittal V20140307 Page 4 CyCombustion safety testing NIA — no natural -draft combustion appliances / aaas (Appliance Types table must be completed for every home) Appliance types Testing tech (initials) Appliance Combustion Type Draft-hood Natural -draft Induced -draft Natural -draft Power- vent Direct- vent Powered sealed - combustion Electric Furnace #1 LIED El ❑ ❑ ❑ ❑ ElFurnace #2 ❑ El El ❑ ❑ ElBoiler#1 ❑ ❑ ❑ ❑ ❑ ❑ Boiler#2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Water heater#1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Water heater #2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Fireplace #1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Fireplace #2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ Other: ❑ ❑ ❑ ❑ ❑ ❑ ❑ Worst -case depressurization performance House setu These doors are closed: _ # of bath fans on Vented range hood on Clothes dryer on Air handler on Other fans on: Other setup notes: Tested appliances Outdoor temperature F Appliance Location CAZ pressure BPI depressurization limit (Pa wrt outside) Measured net CAZ depressurization (Pa wrt outside) OK (less negative) I Caution (more negative) Spillage BPI maximum limit (seconds) Measured spillage duration (seconds; Pass = duration not exceeding limit Draft pressure' BPI limit (Pa wrt CAZ; Measured (Pa wrt CAZ' Pass = pressure more negative than limit CO concentration in undiluted flue gas BPI maximum limit (ppm' Measured CO (ppm; Pass = CO level not exceeding limit Caution = CO level 25 to 100 ppm Residential Mechanical Design Submittal ❑ OK '.El : Caution ❑ OK ❑ , Caution ❑ OK J.Q Caution 60 60 60 —111WFail ❑ Pass ❑ Pass JJJJFaii ❑ Pass 111[Faii ❑ Pass =Fail El] Pass Fail ❑ Pass Fail 100 100 100 ❑ jPass Fail ❑ jPass =Fail 113ass Fail ❑. Caution 7 ❑. Caution ❑ Caution V20140307 Page 5 9. System Controls System Controls Operating Per Design Intent Local exhaust (all fans) ❑ N/A Pass Fail Whole -house ventilation ❑ N/A Pass Fail Sub -structural floor exhaust WA ❑ Pass Fail Heating (all systems) ❑ WA P ss Fail Cooling (all systems) ❑ NIA Pass Fail Signatures Technician #1 performing inspection and testing documented on this report (Approved Agency) I certify that the tests referenced above, in sections bearing my initials, were performed in accordance with protocols specified by the City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge. Name (print Title Compam Signature and Date Alex Murphy QA Specialist Fort C Ilins Heating and Air zl� a I-," l -- z� Technician #2 performing inspoctlo ndo mg this report (Approved Agency) I certify that the tests referenced above, in sections bearing my initials, were performed in accordance with protocols specified by the City of Fort Collins Building Services Department, and that the reported results are accurate to the best of my knowledge. (print) Title npany I Date Name Cor Signature an( HVAC Contractor (City of Fort Collins license holder) I certify that I have reviewed this report and that the test results are an accurate representation of the performance of the installed mechanical systems. Nai Signature Residential Mechanical Design Submittal V20140307 Page 6