HomeMy WebLinkAbout2662 Geranium Ln - Disclosures/Blower Door Test - 01/15/2016BUILDING LEAKAGE TEST
Date of Test: 1 /15/2016
Customer: CC
Test Results
1. Airflow at 50 Pascals
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building Leakage Curve:
4. Test Settings:
5. Accuracy Level
Test File: 2662 Geranium lane
Technician: Michael Broussard
Project Number:
Building Address: 2662 Geranium Lane
Fort Collins, Colorado
1942 CFM50 (+/- 43.3 %)
2.83 ACH50
106.8 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 126.0 ( +/- 890.9 %)
Exponent (n) = 0.699 ( +/- 2.266 )
Correlation Coefficient = 0.96898
Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
Reduced Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 1/15/2016 Test File: 2662 Geranium lane
Building Information Location Climate Information
Volume
41192
Surface Area
Floor Area
Height
# of Bedrooms
# of Occupants
Year of Construction
Wind Shield
M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Ventilation Weather Factor
0.87
Energy Climate Factor
17.00
Heating Degree Days
6128
Cooling Degree Days
297
Design Winter Wind Speed
7.3 mph
Design Summer Wind Speed
9.4 mph
Design Winter Temp Diff
73 deg F
Design Summer Temp Diff
15 deg F
Equipment Information
Type
Manufacturer
Model
Serial Number
Custom Calibration Date
Fan
Energy Conservatory
Model 3 (110V)
-
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 1/15/2016 Test File: 2662 Geranium lane
Depressurization Test:
Environmental Data
Indoor Temperature (OF)
Outdoor Temperature (OF)
Altitude (ft)
68.0
28.0
6900.0
Data Points
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration
-1 0.4
n/a
n/a
-69.2
-56.5
162.7
2276 2210 4.5 Ring A
-72.3
-59.7
148.7
2178 2114 -3.8 Ring A
-51.6
-38.9
86.0
1668 1619 -0.6 Ring A
-15.0
n/a
n/a
Time Averaging Period: 0
Deviations from Standard RESNET Multi -Point Test - Test Parameters
- Fewer than 8 data points were taken.
- * correlation coefficient outside of normally accepted limits.
* n value and/or correlation coefficient limits are not officially part of the RESNET Multi -Point Test
Standard.
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 1/15/2016 Test File: 2662 Geranium lane
Comments
-46.5 to garage-Passed
, �