HomeMy WebLinkAboutLAKEVIEW ON THE RISE SUBDIVISION - Filed FDT-FIELD DENSITY TEST - 2019-05-03FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0056
03/01/19
03/04/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0019 Sandy lean clay ASTM D698 15.9 106.4 14.9 - 18.9 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Sewer Line Between A-3 and A-4
105 Approx. 5' North Of Manhole
A-3
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0059
03/05/19
03/07/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0002 Sandy lean clay ASTM D698 16.1 107.8 15.1 - 19.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Sewer Line Between Manhole A-4 and A-5
113 Approx. 70' West of Manhole
A-4
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0060
03/06/19
03/07/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0002 Sandy lean clay ASTM D698 16.1 107.8 15.1 - 19.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Building 3, Sanitary Sewer Line
115 Approx. 10' South Of Proposed
Building 3
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0060
03/06/19
03/14/19
Earthwork
Revision 1 - Update location
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0002 Sandy lean clay ASTM D698 16.1 107.8 15.1 - 19.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Building 3, Sanitary Sewer Line
115 Approx. 10' South Of Proposed
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0061
03/06/19
03/07/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0002 Sandy lean clay ASTM D698 16.1 107.8 15.1 - 19.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Sewer Line Between Manhole A-4 and A-5
121 Approx. 100' East Of ManHole
A-5
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0063
03/07/19
03/07/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0003 Lean clay with sand ASTM D698 14.1 108.1 13.1-17.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Storm sewer backfill on Lorien and Debra intersection
124 15' East of Manhole -2' 1 8 121.9 14.8 13.8 107.1 99
Service line for building 2
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0067
03/12/19
03/14/19
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0026 Sandy Lean Clay ASTM D698 16.1 105.6 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Sewerline Backfill
133 30' East of B1 -4' 1 8 120.4 15.1 14.3 105.3 100
134 100' East of B1 -4' 1 8 121.7 17.8 17.1 103.9 98
135 150' East x 10' N of B1 -4' 1 8 120.7 15.8 15.1 104.9 99
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0068
03/12/19
03/14/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0026 Sandy Lean Clay ASTM D698 16.1 105.6 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Sewer line backfill: East of B1
136 20' East of B1 -3' 1 8 121.5 17.7 17.1 103.8 98
137 100' East of B1 -3' 1 8 122.6 17.7 16.9 104.9 99
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0069
03/18/19
03/22/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0043 Brown Sandy Lean Clay ASTM D698 15.1 107.5 14.1 - 18.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Water Line Trench Backfill
141 20' West of Sta. C 8-99 -4' 1 8 122.7 16.4 15.4 106.3 99
142 40' North of Manhole 4 -4' 1 8 121.7 16.9 16.1 104.8 97
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0071
03/19/19
03/22/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0043 Brown Sandy Lean Clay ASTM D698 15.1 107.5 14.1 - 18.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Sewer Line Trench Backfill
144 100' North of Manhole 4 -2' 1 8 123.3 17.3 16.3 106.0 99
145 50' North of Manhole 4 -2' 1 8 120.0 17.5 17.1 102.5 95
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0072
03/19/19
03/22/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0043 Brown Sandy Lean Clay ASTM D698 15.1 107.5 14.1 - 18.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Sewer Line Trench Backfill
148 20' South of Mahole 4 -1' 1 8 122.7 16.3 15.3 106.4 99
149 5' North of Manhole 4 -1' 1 8 123.2 17.2 16.2 106.0 99
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0075
03/21/19
03/26/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0026 Sandy Lean Clay ASTM D698 16.1 105.6 15.1 - 19.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
A-6 storm sewer manhole
163 15' E of a-6 manhole -2' 1 8 115.9 15.7 15.7 100.2 95
164 3' E of A-6 manhole -5' 1 8 121.9 18.7 18.1 103.2 98
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0076
03/21/19
03/26/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0043 Brown Sandy Lean Clay ASTM D698 15.1 107.5 14.1 - 18.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Manhole Backfill
154 5' East of Manhole A6 -2' 1 8 119.1 16.8 16.4 102.3 95
155 20' South of Manhole A6 -1' 1 8 116.5 14.6 14.3 101.9 95
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0078
03/22/19
03/26/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0043 Brown Sandy Lean Clay ASTM D698 15.1 107.5 14.1 - 18.1 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Manhole Backfill
159 5' South of Manhole B1 -1' 1 8 119.7 16.9 16.4 102.8 96
160 5' East of Manhole B3 -1' 1 8 121.4 16.0 15.2 105.4 98
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0079
03/25/19
03/28/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Sewer Line Backfill
165 Approx 40' East and 80' South
of South West Corner Of
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0082
03/26/19
04/02/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Waterline backfill N-S along Debra Drive
172 Intersection of Lorien Ln &
Debra Dr
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0083
03/26/19
04/02/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Waterline backfill
180 200' S of interection for Lorien
Ln
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0091
04/01/19
04/05/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3-18.3 min 95%
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Stoney brook rd water main backfill
189 pt. 16+50 -1' 1 8" 121.7 16.0 15.1 105.7 95
190 pt. 17+50 -1' 1 8" 121.5 15.2 14.3 106.3 95
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0093
04/02/19
04/05/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Waterline backfill
197 Stoney Brook Rd & Debra Dr
intersection
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0094
04/02/19
04/05/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Waterline backfill
198 Stoney Brook Rd & Debra Dr
intersection
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0095
04/03/19
04/05/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Mainline waterline backfill
200 Lorien Ln & Debra Dr
intersection
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0096
04/03/19
04/05/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Mainline waterline backfill
202 100' Lorien Ln & Debra Dr
intersection
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0097
04/04/19
04/05/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Waterline mainline backfill
204 25' W of Rohan Rd & Lorien
Ln intersection
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0098
04/04/19
04/05/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Mainline waterline backfill
206 50' S of Rohan Rd & Lorien Ln
intersection
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0100
04/05/19
04/15/19
Earthwork
Revision 1 - Update report with areas
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Stoney Brooke water mainline
211 150' E of intersection of Toney
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0104
04/16/19
04/23/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Lorien Lane, Between Building 1 and 14
215 Station 11+98 -1' 1 8" 128.9 18.6 16.9 110.3 99
216 Station 12+00 -1' 1 8" 125.2 16.4 15.1 108.8 97
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0105
04/17/19
04/23/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3-18.3 min 95%
2 20181040.0002 Sandy lean clay ASTM D698 16.1 107.8 15.1-19.1 min 95%
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Baggins drive water main backfill.
217 pt. 12+00 -2' 1 8" 130.0 20.1 18.3 109.9 98
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20181040.0112
04/26/19
05/02/19
Earthwork
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
Signature Construction LLC
Attn: Matt Boyle
720 3rd Ave SW
Carmel, IN 46032-2036
Lakeview on the Rise Apartment Development
6740 South College Avenue
Fort Collins, CO
Project
Project Number: 20181040
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20181040.0004 Sandy lean clay ASTM D698 15.3 111.7 14.3 - 18.3 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Debra Dr Mainline waterline, N end of project site.
229 30' S of property line -2' 1 8 126.7 18.0 16.6 108.7 97
230 25' S of property line -1' 1 8 125.3 17.6 16.3 107.7 96
231 28' S of property line 0 1 8 126.0 18.6 17.3 107.4 96
Comments:
Datum: Std. Cnt. M: 610 Std. Cnt. D: 2220
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Weston w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
Lorien lane water main backfill
218 pt. 14+10 -2' 2 8" 123.4 19.6 18.9 103.8 96
219 pt. 17+00 -2' 2 8" 122.6 19.1 18.5 103.5 96
Comments:
Datum: 0'= finished sub-grade Std. Cnt. M: 242 Std. Cnt. D: 2673
Test and/or retest results on this report meet project requirements as noted above.
S/N: 2157 Make: Instrotek Model: 3500 Xplorer Last Cal. Date: 01/02/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Quinn Zamora
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
Comments:
Datum: -1' = From Grade Std. Cnt. M: 619 Std. Cnt. D: 1972
Test and/or retest results on this report meet project requirements as noted above.
S/N: 32847 Make: Troxler Model: 3430 Last Cal. Date: 01/16/2019
Services:
Reported To:
Contractor:
Jeff with Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Taylor Keller
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
Brooke and Laurien Ln
-1' 1 8 127.9 18.8 17.2 109.1 98
212 150' E of intersection of Toney
Brooke and Laurien Ln
0 1 8 125.8 17.9 16.6 107.9 97
Rohan rd waterline
213 200' S of Rohan and Debra Dr 0 1 8 129.9 19.5 17.7 110.4 99
Comments:
Datum: Std. Cnt. M: 618 Std. Cnt. D: 2248
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
0 1 8 128.9 19.4 17.7 109.5 98
207 50' S of Rohan Rd & Lorien Ln
intersection
-1' 1 8 130.6 19.8 17.9 110.8 99
208 Building 8 & 9 water services -1' 1 8 129.0 19.8 18.1 109.2 98
Comments:
Datum: Std. Cnt. M: 615 Std. Cnt. D: 2275
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
-1 1 8 130.9 20.0 18.0 110.9 99
205 25' W of Rohan Rd & Lorien
Ln intersection
0 1 8 129.3 20.0 18.3 109.3 98
Comments:
Datum: Std. Cnt. M: 615 Std. Cnt. D: 2275
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
-1' 1 8 129.2 18.6 16.8 110.6 99
203 100' Lorien Ln & Debra Dr
intersection
0 1 8 127.2 17.9 16.4 109.3 98
Comments:
Datum: Std. Cnt. M: 617 Std. Cnt. D: 2262
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
-1' 1 8 128.3 17.9 16.2 110.4 99
201 Lorien Ln & Debra Dr
intersection
0 1 8 129.0 19.8 18.1 109.2 98
Comments:
Datum: Std. Cnt. M: 617 Std. Cnt. D: 2262
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
0 1 8 125.0 15.7 14.4 109.3 98
199 Stoney Brook Rd & Debra Dr
intersection, 50' E
0 1 8 128.3 18.4 16.7 109.9 98
Comments:
Datum: Std. Cnt. M: 622 Std. Cnt. D: 2280
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
-1' 1 8 123.3 17.2 16.2 106.1 95
Comments:
Datum: Std. Cnt. M: 622 Std. Cnt. D: 2280
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
191 pt. 16+50 -0' 1 8" 126.4 16.3 14.8 110.1 99
192 pt. 17+50 -0' 1 8" 126.0 17.5 16.1 108.5 97
Comments:
Datum: 0'=finish sub-grade. Std. Cnt. M: 542 Std. Cnt. D: 1791
Test and/or retest results on this report meet project requirements as noted above.
S/N: 17271 Make: Troxler Model: 3440 Last Cal. Date: 01/16/2019
Services:
Reported To:
Contractor:
Jeff with Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Quinn Zamora
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
0 1 8 125.0 15.7 14.4 109.3 98
Comments:
Datum: Std. Cnt. M: 622 Std. Cnt. D: 2258
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
0 1 8 129.3 18.5 16.7 110.8 99
173 Intersection of Lorien Ln &
Debra Dr
-1' 1 8 125.9 17.5 16.1 108.4 97
174 50' S of interection for Lorien
Ln
0 1 8 130.3 19.2 17.3 111.1 99
175 50' S of interection for Lorien
Ln
-1' 1 8 126.5 18.3 16.9 108.2 97
176 100' S of interection for Lorien
Ln
0 1 8 124.9 17.3 16.1 107.6 96
177 100' S of interection for Lorien
Ln
-1' 1 8 126.8 17.3 15.8 109.5 98
178 150'' S of interection for Lorien
Ln
0 1 8 127.3 18.6 17.1 108.7 97
179 150'' S of interection for Lorien
Ln
-1' 1 8 126.8 16.9 15.4 109.9 98
Comments:
Datum: Std. Cnt. M: 622 Std. Cnt. D: 2283
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
Building 15
0' 1 8 129.6 18.2 16.3 111.4 100
166 Approx 80' South anf 120' East
Of South West Corner of
Building 15
0' 1 8 130.4 19.6 17.7 110.8 99
167 Approx. 40' West and 30' North
Of South West Corner of
Community Building
0' 1 8 127.2 19.3 17.9 107.9 97
Building 15 Utility Service Backfill
168 Approx. 10' South and 40' East
Oos South West Corner of
Building 15
0' 1 8 130.0 20.0 18.2 110.0 98
Comments:
Datum: 0' = Subgrade Std. Cnt. M: 619 Std. Cnt. D: 1973
Test and/or retest results on this report meet project requirements as noted above.
S/N: 32847 Make: Troxler Model: 3430 Last Cal. Date: 01/16/2019
Services:
Reported To:
Contractor:
Hank & Jeff w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Taylor Keller
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
161 10' South of Sewer Main
Manhole
-1' 1 8 122.5 17.9 17.1 104.6 97
162 5' West of North Sewer Main
Manhole
-2' 1 8 123.0 16.3 15.3 106.7 99
Comments:
Datum: 0'= Finished Grade
Test and/or retest results on this report meet project requirements as noted above.
S/N: 36144 Make: Troxler Model: 3430 Last Cal. Date: 12/12/2018
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Christian Hershberger
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
Retest of Test 147
156 50' South of Manhole 4 -2' 1 8 123.5 16.7 15.6 106.8 99
Comments:
Datum: 0'= Finished Grade
Test and/or retest results on this report meet project requirements as noted above.
S/N: 36144 Make: Troxler Model: 3430 Last Cal. Date: 12/12/2018
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Christian Hershberger
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
Comments:
Datum: Std. Cnt. M: 624 Std. Cnt. D: 2284
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
150 50' North of Manhole 4 -1' 1 8 123.6 18.0 17.0 105.6 98
Comments:
Datum: 0'= Finished Grade
Test and/or retest results on this report meet project requirements as noted above.
S/N: 36144 Make: Troxler Model: 3430 Last Cal. Date: 12/12/2018
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Christian Hershberger
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
146 5' North of Manhole 4 -2' 1 8 120.7 16.1 15.4 104.6 97
147 50' South of Manhole 4 -2' 1 8 119.5 14.3 13.6 * 105.2 98
Comments:
Datum: 0'= Finished Grade
An asterisk (*) appears next to the test results which do not meet the project requirements as noted above.
S/N: 36144 Make: Troxler Model: 3430 Last Cal. Date: 12/12/2018
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Christian Hershberger
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
143 5' North of Manhole 4 -4' 1 8 121.1 15.5 14.7 105.6 98
Comments:
Datum: 0'= Finished Grade
Test and/or retest results on this report meet project requirements as noted above.
S/N: 36144 Make: Troxler Model: 3430 Last Cal. Date: 12/12/2018
Services:
Reported To:
Contractor:
Taylor w/ Signature Construction
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Christian Hershberger
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
138 3' S of B1 -3' 1 8 120.7 16.4 15.7 104.3 99
Building sub grade backfill
139 Building 14 Nw corner -1' 1 8 121.8 17.1 16.3 104.7 99
140 Building 18 Center of pad 0 1 8 119.5 14.4 13.7 105.1 100
Comments:
Datum: Std. Cnt. M: 626 Std. Cnt. D: 2262
Test and/or retest results on this report meet project requirements as noted above.
The percent moisture requirements for test number 140 is not required due to the material acheiveing the minimum percent
compaction.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Hank & Jeff w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
Comments:
Datum: Std. Cnt. M: 2262 Std. Cnt. D: 626
Test and/or retest results on this report meet project requirements as noted above.
The percent moisture requirements for test number 133 is not required to the material acheiving the minimum percent
compaction.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Hank w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Douglas Novosad
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
125 25' North of manhole -2' 1 8 115.9 17.2 17.4 * 98.7 91 *
Storm sewer backfill on Lorien and Debra intersection
126 30' West of Manhole -2' 1 8 121.4 18.0 17.4 * 103.4 96
Comments:
Datum: 0= Finish subgrade elevation
An asterisk (*) appears next to the test results which do not meet the project requirements as noted above.
S/N: 2157 Make: Instrotek Model: 3500 Xplorer Last Cal. Date: 01/02/2019
Services:
Reported To:
Contractor:
Jeff with Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Christopher Rivera
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
-3' 1 8 125.3 19.8 18.8 105.5 98
122 Approx. 20' East Of Manhole
A-5
-3' 1 8 125.2 19.1 18.0 106.1 98
Sewer Line Between A-5 and A-6
123 Approx. 50' West Of Manhole
A-5
-3' 1 8 125.1 20.0 19.0 105.1 97
Comments:
Datum:
Test and/or retest results on this report meet project requirements as noted above.
S/N: Make: Model: Last Cal. Date:
Services:
Reported To:
Contractor:
Hank & Jeff w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Taylor Keller
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
Building 3
-3' 1 8 124.1 19.1 18.2 105.0 97
Building 10, Sewer Service Line
116 Approx 15' North and 15' East
Of Northeast Corner Of
Proposed Building 10
-5' 1 8 125.3 20.0 19.0 105.3 98
117 Approx 15' North and 15' East
Of Northeast Corner Of
Proposed Building 10
-3' 1 8 125.9 19.9 18.8 106.0 98
Sewer Line Between Manhole A-4 and A-5
118 Approx. 80' East of Manhole
A-5
-5 1 8 125.3 19.2 18.1 106.1 98
119 Approx. 60' East of Manhole
A-5
-3' 1 8 127.0 20.3 19.0 106.7 99
120 Approx. 40' West of Manhole
A-5
-5' 1 8 123.9 19.4 18.6 104.5 97
Comments:
Datum: 0' = Finished Grade Std. Cnt. M: 619 Std. Cnt. D: 1972
Test and/or retest results on this report meet project requirements as noted above.
S/N: 32847 Make: Troxler Model: 3430 Last Cal. Date: 01/16/2019
Services:
Reported To:
Contractor:
Hank & Jeff w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Taylor Keller
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
-3' 1 8 124.1 19.1 18.2 105.0 97
Building 10, Water Service Meter
116 Approx 15' North and 15' East
Of Northeast Corner Of
Proposed Building 10
-5' 1 8 125.3 20.0 19.0 105.3 98
117 Approx 15' North and 15' East
Of Northeast Corner Of
Proposed Building 10
-3' 1 8 125.9 19.9 18.8 106.0 98
Sewer Line Between Manhole A-4 and A-5
118 Approx. 80' East of Manhole
A-5
-5 1 8 125.3 19.2 18.1 106.1 98
119 Approx. 60' East of Manhole
A-5
-3' 1 8 127.0 20.3 19.0 106.7 99
120 Approx. 40' West of Manhole
A-5
-5' 1 8 123.9 19.4 18.6 104.5 97
Comments:
Datum: 0' = Finished Grade Std. Cnt. M: 619 Std. Cnt. D: 1972
Test and/or retest results on this report meet project requirements as noted above.
S/N: 32847 Make: Troxler Model: 3430 Last Cal. Date: 01/16/2019
Services:
Reported To:
Contractor:
Hank & Jeff w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Taylor Keller
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
-5' 1 8 123.4 19.7 19.0 103.7 96
114 Approx. 80' West of Manhole
A-4
-3' 1 8 122.3 19.4 18.9 102.9 95
Comments:
Datum: 0' = Finished Grade Std. Cnt. M: 619 Std. Cnt. D: 1972
Test and/or retest results on this report meet project requirements as noted above.
S/N: 32847 Make: Troxler Model: 3430 Last Cal. Date: 01/16/2019
Services:
Reported To:
Contractor:
Hank & Jeff w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Taylor Keller
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
-2' 1 8 124.5 19.4 18.5 105.1 99
106 Approx. 110' North Of Manhole
A-3
-2' 1 8 121.0 17.7 17.1 103.3 97
107 Approx. 50' South Of Manhole
A-4
-3' 1 8 121.5 18.5 18.0 103.0 97
Sewer Line Between Manhole A-4 and A-5
108 Approx. 4' West Of Manhole
A-4
-3' 1 8 120.7 18.7 18.3 102.0 96
109 Approx. 80' West Of Manhole
A-4
-5' 1 8 120.6 18.3 17.9 102.3 96
110 Approx. 10' South Of Station
17+21.30, 39.72 LT
-5' 1 8 123.8 18.3 17.3 105.5 99
111 Retest # 83 -1' 2 8 122.1 19.5 19.0 102.6 99
112 Retest # 84 0' 2 8 122.5 19.5 18.9 103.0 99
Comments:
Datum: 0'=Finished Grade Std. Cnt. M: 614 Std. Cnt. D: 1945
Test and/or retest results on this report meet project requirements as noted above.
S/N: 60674 Make: Troxler Model: 3430 Last Cal. Date: 01/31/2019
Services:
Reported To:
Contractor:
Hank & Jeff w/ Connell
Connell
Craig L. Nelson
Project Manager
Report Distribution:
(1) Signature Construction LLC, Matt Boyle (1) Connell Resources Inc, Jeff Laugel
(1) Signature Construction LLC, Taylor Elizalde (1) Signature Construction LLC, Trevor Rine
(1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Taylor Keller
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated
above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples
tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1