HomeMy WebLinkAboutPROSPECT AND CENTER PEDESTRIAN UNDERPASS PHASE 2 - Filed STRS-STREETS ENGINEER STAMP - 2018-06-05NOTE: ALL ABBREVIATIONS SHOWN ARE NOT NECESSARILY USED. GENERAL NOTES (FOR ALL ELECTRICAL SHEETS) 1. THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE CIVIL DRAWINGS FOR EXACT DIMENSIONS. COORDINATE ALL EQUIPMENT LOCATIONS WITH THE OWNER PRIOR TO ROUGH IN. 2. SITE PLAN DOES NOT INDICATE ALL OF THE UG UTILITY LINES (POWER, TELEPHONE, CABLE, WATER, SEWER, ETC.) REFER TO THE CIVIL DRAWINGS FOR ADDITIONAL INFORMATION. THE CONTRACTOR SHALL FIELD VERIFY THE EXACT LOCATION OF ALL EXISTING UNDERGROUND UTILITY OR SERVICE LINES WITH ALL TRADES PRIOR TO ANY SITE WORK. 3. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ANY NEW ELECTRICAL SERVICE INSTALLATION OR MODIFICATIONS TO THE EXISTING ELECTRICAL SERVICE WITH THE LOCAL UTILITY COMPANY PRIOR TO STARTING ANY WORK. 4. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL COST TO THE OWNER. 5. ALL 120V BRANCH CIRCUITS SHALL BE 3-WIRE (PHASE,NEUTRAL,GROUND). PHASE, NEUTRAL, AND GROUND CONDUCTORS SHALL BE SIZE 12 AWG UNLESS OTHERWISE NOTED. BRANCH CIRCUITS SHOWN AS A SINGLE HOMERUN SHALL NOT BE COMBINED WITH OTHER CIRCUITS. ALL BRANCH CIRCUITS AND FEEDERS SHALL HAVE EQUIPMENT GROUNDING CONDUCTORS INSTALLED IN THE RACEWAY. 6. THE CONTRACTOR SHALL MAINTAIN FIRE-RATINGS FOR ALL CONDUIT PENETRATIONS THROUGH FIRE-RATED CONSTRUCTION. 7. ALL MOUNTING OF ELECTRICAL DEVICES (LUMINAIRES, TRANSFORMERS, PANELS, OUTLETS, CONDUIT RUNS, ETC.) SHALL COMPLY WITH STATE AND LOCAL SEISMIC REQUIREMENTS. 8. COORDINATE THE INSTALLATION OF COMMUNICATIONS CABLING, ROUTING, MOUNTING BOXES, AND TERMINATIONS WITH THE OWNER OR CSU TELECOM, PRIOR TO CONSTRUCTION. 9. THE INFORMATION ON THESE DRAWINGS HAS BEEN ASCERTAINED FROM EXISTING DRAWINGS AND FIELD OBSERVATIONS. THIS INFORMATION IS AS ACCURATE AS CONDITIONS WOULD ALLOW. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE SITE AND BECOME FAMILIAR WITH THE EXTENT OF THE WORK REQUIRED. 10. ON NEW FLOOR PLANS: ALL ITEMS SHOWN IN LIGHT LINE WEIGHT ARE EXISTING TO REMAIN, UNLESS NOTED OTHERWISE. ALL ITEMS SHOWN IN HEAVY LINE WEIGHT ARE NEW OR RELOCATED AS NOTED. 11. ITEMS THAT ARE SHOWN TO BE REMOVED SHALL BE REMOVED IN THEIR ENTIRETY INCLUDING ALL ASSOCIATED CONDUIT, WIRE, AND HANGERS BACK TO THE POINT OF ORIGIN OR THE NEAREST EXISTING ITEM THAT IS REMAINING, UNLESS NOTED OTHERWISE. 12. CONTACT UTILITY COMPANIES FOR RESPECTIVE RELOCATION.UTILITIES WILL BE RESPONSIBLE FOR WORK. CONTRACTOR SHALL EXPOSE EXISTING UTILITIES Tunnel Floor Illuminance (Fc) Average = 6.96 Minimum = 5.3 Avg/Min Ratio = 1.31 Max/Min Ratio = 1.57 Tunnel Floor Illuminance (Fc) Average = 6.96 Maximum = 8.3 Luminaire Schedule Tag Qty Label Description LLF 11 sar2e35-60l4k SAR2E35-60L4K 0.900 4 250W Cobra Type II 125 25S R2 DG 0.900 8 MLHA8 0.900 4 Spaulding Peachtree 1843 53004A 0.900 0.8 0.8 0.7 0.7 0.8 0.7 0.7 0.6 0.8 0.8 0.7 0.6 0.6 0.9 0.8 0.7 0.6 0.6 1.1 1.0 0.8 0.7 0.6 0.5 1.4 1.3 1.0 0.7 0.6 0.5 1.5 1.7 1.7 1.2 0.8 0.6 0.5 1.6 2.0 2.0 1.5 0.9 0.6 0.5 1.9 2.3 2.3 1.6 1.0 0.7 1.8 2.4 2.3 1.6 1.0 0.6 1.5 1.9 2.3 2.1 1.5 0.9 0.4 1.4 1.7 1.9 1.6 1.2 0.7 1.3 1.5 1.5 1.3 1.0 0.6 1.2 1.3 1.3 1.1 0.8 0.5 1.2 1.2 1.2 1.0 0.8 1.2 1.3 1.1 1.0 0.7 1.0 1.3 1.3 1.1 0.9 0.6 1.2 1.4 1.4 1.2 0.9 0.6 1.4 1.7 1.6 1.4 1.0 0.6 1.5 2.1 2.1 1.7 1.1 1.7 2.4 2.4 2.0 1.3 1.8 2.6 2.7 2.3 1.5 1.8 2.7 2.8 2.5 1.7 1.6 2.5 2.6 2.4 1.6 1.5 1.7 2.1 2.3 2.3 1.6 1.9 1.7 1.7 2.0 2.1 1.5 2.3 1.7 1.5 1.9 2.1 1.6 2.8 2.0 1.6 2.2 2.3 1.7 1.1 0.7 1.2 1.6 2.5 3.8 3.3 2.7 2.3 3.0 3.1 2.2 1.2 0.5 1.3 1.5 2.5 3.7 3.5 3.5 4.1 5.1 4.9 3.7 1.7 0.4 6.2 7.2 7.0 6.9 8.0 8.0 7.8 7.9 7.0 7.3 7.2 7.3 5.8 6.2 6.0 5.8 5.8 6.0 6.0 5.9 7.4 7.7 7.5 7.5 8.2 8.1 8.1 8.2 7.6 7.3 7.4 7.5 6.2 6.2 6.3 6.2 6.0 6.3 6.2 6.0 7.6 7.7 7.6 7.6 8.3 8.3 8.3 8.3 7.5 7.2 7.4 7.4 6.2 6.1 6.2 6.1 FLAG NOTES (THIS SHEET): 1. SEE DRAWING E1.03 FOR ENLARGED TUNNEL PLAN AND LIGHTING CIRCUITING. 2. APPROXIMATE LOCATION OF PANEL "LP1". COORDINATE EXACT LOCATION WITH LANDSCAPING PLANS AND OWNER. PANEL IS NOT SHOWN ACTUAL SIZE. MOUNT PANEL ON UNISTRUT RACK ALONG WITH FUSED DISCONNECT AND UTILITY METER. SEE ELECTRICAL ONE-LINE DIAGRAM AND SERVICE PEDESTAL DETAIL ON SHEET E3.01 FOR ADDITIONAL INFORMATION. SERVICE PEDESTAL IS NOT DRAWN TO SCALE. 3. NEW CITY OF FT COLLINS UTILITY 50KVA TRANSFORMER FOR ELECTRICAL SERVICE FEEDING UNDERPASS POWER AND AGGIE SOUTH BUILDING 20. TRANSFORMER SHALL HAVE 3'-0” CLEARANCE ON SIDES AND BACK, AND 10'-0” CLEARANCE IN FRONT. TRANSFORMER PAD AND ANY PRIMARY CONDUIT NECESSARY PROVIDED BY CITY OF FT. COLLINS. REFER TO SHEET E3.01 FOR ONE-LINE DIAGRAM AND ADDITIONAL INFORMATION. 4. SUMP PUMP CONTROL PANEL. PROVIDE BRANCH CIRCUIT FROM PANELBOARD "LP1" CIRCUIT (1,3) FOR 240V, SINGLE PHASE POWER TO THE CONTROL PANEL. REFER TO THE MECHANICAL EQUIPMENT SCHEDULE ON SHEET E3.01 FOR CIRCUIT BREAKER AND FEEDER SIZES. FEEDS FROM CONTROL PANEL TO PUMPS ARE 3 PHASE. ALSO PROVIDE CONTROLS CONDUIT ALONG SIDE POWER CONDUIT. 5. FIBEROPTIC COMMUNICATION BOX MOUNTED ON 4" DEEP CONCRETE PAD. PROVIDE FRONT ACCESS AND 3'-0" CLEAR SPACE ON BOTH SIDES FOR AIR FLOW. PROVIDE 2"C. FROM CSU MANHOLE AM6 TO BOX. PROVIDE 1"C. FROM COMM BOX TO TUNNEL AND OTHER LOCATIONS AS SHOWN FOR CAMERAS. COMM BOX SHALL BE PENTAIR T503020FTTXB WITH BATTERY COMPARTMENT, 800VA HEATER DAH8001B; 80VA COOLING FAN TFP101SS WITH TEP10SS GRILL AND NEMA 3R SHROUD; FAN TEMPERATURE CONTROL SWITCH ATEMNO; GROUND BAR SYSTEM PGS6K; DINRAIL-TS35X7.5-150MM SM-GLB; AND ALL NECESSARY HARDWARE FOR A COMPLETE INSTALLATION. PROVIDE BRANCH CIRCUIT FROM PANEL "LP1" CIRCUITS 7 & 9 FOR 120V POWER. FEEDER SHALL BE (3#10+#10G)3 4"C. ALSO PROVIDE 30A CIRCUIT FROM PANEL "LP1-5" FOR UPS CONNECTION. FEEDER SHALL BE (3#8+#8G)1"C. THE UPS'S AND BATTERIES WITHIN THE COMMUNICATION BOX WILL BE PROVIDED BY CSU TELECOM. 6. PROVIDE WP WALL MOUNTED J-BOX FOR CONNECTION TO LIT RAM LOGO SIGN. SEE SHEETS L2.02 AND L2.03 FOR ADDITIONAL INFORMATION AND MOUNTING LOCATION. 7. POLE MOUNTED LUMINAIRES IN PLANTERS SHALL HAVE CONCRETE POLE BASES. SEE DETAIL ON SHEET E3.01. ALL OTHERS SHALL BE DIRECT BURIED. DIRECT BURIED POLES SHALL BE BURIED AT A DEPTH AS RECOMMENDED BY THE POLE MANUFACTURER. PROVIDE MANUFACTURER RECOMMENDED BACKFILL. B T J X B B J X J X SCALE: NORTH ELECTRICAL SITE PLAN 1"=40' E1.02 PANEL LP1 100S FLAG NOTES (THIS SHEET): 1. EQUIPMENT TO BE PROVIDED IN THIS PHASE (PHASE 4) OF UNDERPASS PROJECT. ROUTE SECONDARY FEEDER TO SUPPORT PEDESTAL LOCATION. 2. REPLACE EXISTING FUSES WITH BUSSMAN CLASS T - JJN 300A FUSES. CSU HOUSING REQUIRES A MINIMUM 4 DAY SCALE: NOTICE FOR ANY OUTAGE. ELECTRICAL ONE-LINE DIAGRAM CSU UNDERPASS AND AGGIE SOUTH BLDG. 20 NONE F M 100S 100A2P WP DISCONNECT SWITCH WITH 100A LPN-RK FUSES CITY OF FT. COLLINS UTILITY SELF CONTAINED METER (COLD SEQUENCE METERING) 100A2P MCB F EXISTING CT CABINET CT M TO EXISTING PANELS 400U 100U-VD EXISTING METER UG UG UG T 50KVA, 120/240V,1Ø,3W PAD MOUNTED TRANSFORMER BY CITY OF FT. COLLINS UTILITY EXISTING 400A2P MAIN DISCONNECT BUILDING 20 UG EXISTING CITY OF FT. COLLINS UNDERGROUND UTILITY VAULT AGGIE SOUTH BUILDING 20 CSU UNDERPASS PROJECT 1 WIRE AND CONDUIT SIZE - 1Ø, 3W FEEDER SCHEDULE (3-500KCMIL)3"C (3#3/0)2"C 100S (3#1+#8G)1-1/2"C 400U C1-314 C1-314 C1-314 C1-314 100U-VD 120/240V, 1Ø, 3W SERVICE NEW PRIMARY FEEDER IN CONDUIT BY CITY OF FT. COLLINS UTILITY EXISTING 400A2P MAIN DISCONNECT #6 CU TO GROUND ROD NOTES: TYPE B A 1. TYPE B LUMINAIRES AND POLE PROVIDED BY CSU. MANUFACTURER, CAT. NUMBER LUMINAIRE SCHEDULE CORNER MOUNT VANDAL RESISTANT LED LUMINAIRE LED POLE MOUNTED LUMINAIRE WITH TYPE II DISTRIBUTION AND ROUND TAPERED FIBERGLASS POLE LED CAT. NO. 1 LED QTY. 1 LAMPS DESCRIPTION KENALL MLHA8-48-F-LG-PP-45L40K-DCC-120-DL-CMB 1SA-SAR2P35-60L4K-120-DB-A-30-VSF-1SA KIM ARCHETYPE VOLT MOUNTING 120 120 15'-0" POLE SURFACE GROUT 4" FIXTURE AS SPECIFIED POLE AS SPECIFIED BASE COLLAR EXTENSION FINISHED GRADE BOLTS. SET ANCHOR BOLTS PER MANUFACTURER'S RECOMMENDATIONS ELECTRICAL CONTRACTOR TO HAND HOLE FIXTURE SUPPLIED WITH ANCHOR PROVIDE _' DIA CONCRETE BASE 3/4" CHAMFER EDGE MIN. 3/4" PVC (TYP), (IN & OUT), ROUTED 30" MIN. BELOW GRADE. PROVIDE REBAR _#_ VERTICAL WITH #_ TIES _" ON CENTER. REFER _' DEEP. REFER TO STRUCTURAL. NO SCALE 5/8"X10'-0" COPPER CLAD GROUND ROD W/ (1)#6 CU TO GROUND LUG IN POLE. POLE HEIGHT SCHEDULE POLE MOUNTING DETAIL FOR FIXTURE "B" PER LUMINAIRE 2 SP-1,2 SUBMERSIBLE PUMP 240-1 3HP x 2 -SINGLE POINT CONNECTION 3.36kVA (3#10+#10G)3/4"C 30A2P MECHANICAL EQUIPMENT SCHEDULE KEY DESCRIPTION LOAD VOLT-∅ FEEDER O.C. PROTECTION C.B. FUSE REMARKS PROVIDE (2) 1"C FOR POWER AND (1) 1"C FOR CONTROLS FROM PANEL "LP1" 120 / 240 VOLT 1 PHASE 4 WIRE SERVICE 100 AMP GROUND BUS 10,000 AIC 100 A MAIN CB 100% NEUTRAL BUS SURFACE MOUNTED T|S|O T|S|O DESCRIPTION L R M|A|E|H PHASE L R M|A|E|H DESCRIPTION L-SOUTH POLES 560 1 L1 2 30 M 840 SUMP PUMP 1 L-NORTH POLES 320 3 L2 4 | M 840 -- SECURITY UPS E 2500 30 5 L1 6 200 L-S. RAM LOGO SECURITY QUAD 180 H 800 20 7 L2 8 200 L-N. RAM LOGO SECURITY QUAD 180 M 80 20 9 L1 10 SP SPR 11 L2 12 SP SP 13 L1 14 SP SP 15 L2 16 SP SP 17 L1 18 SP SP 19 L2 20 SP SP 21 L1 22 SP SP 23 L2 24 SP SP 25 L1 26 SP SP 27 L2 28 SP SP 29 L1 30 SP M 80 LOADS IN M 1680 TOTAL 880 360 A VOLT-AMPERES 400 A TOTAL E 3300 E CONNECTED D.F. DEMAND LIGHTING 1.3 1.25 1.6 CONNECTED 6.7 KVA RECEPT. (FIRST 10 KW) 0.4 1.00 0.4 DESIGN 24.0 KVA RECEPT. (REMAINDER) 0.50 DEMAND 7.4 KVA MOTORS 0.1 1.00 0.1 SPARE 16.6 KVA LARGEST MOTOR 1.7 1.25 2.1 CONNECTED APPLIANCES 1.00 L1 4.4 KVA EQUIPMENT 2.5 1.00 2.5 L2 2.3 KVA HEATING 0.8 1.00 0.8 TRANSFORMER 1.00 OTHER 1.00 TOTAL 6.7 KVA 7.4 KVA ALL CIRCUIT BREAKERS LOAD 27.9 AMPS 31.0 AMPS ARE 20 AMP, 1 POLE DESIGN 100.0 AMPS UNLESS NOTED OTHERWISE SPARE 69.0 AMPS SP = SPACE SPR = SPARE L = LIGHTING R = RECEPTACLE M = MOTOR T= TRANSFORMER H = HEATING S = SUBFEED E = EQUIPMENT A = APPLIANCE O = OTHER NOTES: GENERAL NOTES: 1. POLE BASE REQUIRED ONLY FOR POLE MOUNTED LUMINAIRES LOCATED WITHIN PLANTING AREAS. ALL OTHER POLES SHALL BE DIRECT BURY. CONTROLLER TO SUMP PIT. MAIN DISCONNECT UTILITY METER 1" C-CHANNEL UNISTRUT UG PUMP PANEL NO SCALE SERVICE PEDESTAL DETAIL TO UTILITY XFMR 100A PANEL UG FRONT REAR FROM LP1 TO CNTRL PANEL (3#8+#8G)1"C FROM CNTRL PANEL TO EACH PUMP (FOR PLANTERS ONLY) TO STRUCTURAL. E3.01 ELECTRICAL DETAILS AND ONE-LINE DIAGRAMS NO. REV. DATE project no.: approved by: checked by: drawn by: drawing no.: QA/QC by: date: 1 REVISIONS DESCRIPTION 2 455 Sherman Street, Suite 160 Denver, Colorado 80203 voice: (303) 447-0090 fax: (303) 447-9141 web: collinsengr.com R Know what'sbelow. Call before you dig. 3 4 5 6 7 7600 East Orchard Road, Suite 250-S Greenwood Village, CO 80111-2518 tel: 303.796.6000 Fax: 303.796.6099 www.mkkeng.com CONSULTING ENGINEERS, INC. Mechanical, Electrical & Energy Consultants MKK Project Number: © Copyright 2015 ZJT LSH LSH MRZ 2015.01.0267 9238-25 XTBLK24x36 02/22/2016 W:\01-CO\2015.01.0267 Colorado State University Underpass\DWGS\XTBLK24x36.dwg, 10/26/2015 8:10:27 AM, tatro, zeriah Xrefs: none C1-314 C1-314 ELECTRICAL SITE PLAN NO. REV. DATE project no.: approved by: checked by: drawn by: drawing no.: QA/QC by: date: 1 REVISIONS DESCRIPTION 2 455 Sherman Street, Suite 160 Denver, Colorado 80203 voice: (303) 447-0090 fax: (303) 447-9141 web: collinsengr.com R Know what'sbelow. Call before you dig. 3 4 5 6 7 7600 East Orchard Road, Suite 250-S Greenwood Village, CO 80111-2518 tel: 303.796.6000 Fax: 303.796.6099 www.mkkeng.com CONSULTING ENGINEERS, INC. Mechanical, Electrical & Energy Consultants MKK Project Number: © Copyright 2015 ZJT LSH LSH MRZ 2015.01.0267 9238-25 XTBLK24x36 02/22/2016 W:\01-CO\2015.01.0267 Colorado State University Underpass\DWGS\XTBLK24x36.dwg, 10/26/2015 8:10:27 AM, tatro, zeriah Xrefs: none C1-314 C1-314 6.0 6.1 6.0 5.8 7.3 7.2 6.9 6.7 7.9 7.8 7.5 7.3 6.3 6.2 6.0 5.3 1.1 1.7 2.5 3.4 3.8 2.9 3.6 4.2 3.8 3.1 0.0 0.8 0.9 1.4 2.1 2.9 3.3 2.5 2.1 2.6 2.8 1.9 1.0 0.6 2.6 2.2 1.6 1.8 2.0 1.7 2.0 1.6 1.3 1.5 1.8 1.5 1.5 1.5 1.3 1.5 1.7 1.4 1.5 1.6 1.7 1.8 1.5 1.0 1.8 2.1 2.1 1.8 1.1 1.9 2.2 2.4 2.2 1.4 1.9 2.2 2.5 2.5 1.8 2.1 2.4 2.5 2.0 2.0 2.2 2.3 2.0 1.3 1.8 1.9 1.7 1.2 1.5 1.5 1.4 1.1 1.2 1.2 1.1 1.0 0.9 0.9 0.9 0.7 0.8 0.8 0.8 0.7 0.7 0.8 0.8 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.8 0.7 0.9 0.8 0.8 0.8 1.0 1.0 1.0 0.9 1.1 1.1 1.1 1.1 1.4 1.4 1.3 1.2 1.9 1.9 1.8 1.6 2.4 2.5 2.5 2.2 2.8 3.1 3.2 2.9 2.9 3.4 3.6 3.3 2.6 3.3 3.3 3.0 2.8 2.7 2.4 2.2 2.0 1.7 1.6 1.5 1.3 1.2 1.2 1.1 1.0 1.1 1.0 0.9 0.9 0.9 0.7 0.8 0.8 0.7 0.7 0.7 0.7 0.7 0.8 0.8 0.8 0.8 0.9 0.9 0.9 0.9 1.0 1.0 1.0 1.1 1.2 1.2 1.4 1.4 1.4 2.0 1.9 1.8 2.5 2.6 2.5 3.0 3.2 3.2 3.1 3.4 3.4 2.2 1.4 3.0 3.1 3.0 1.9 1.4 2.5 2.6 2.4 1.6 1.2 1.9 1.9 1.7 1.2 0.9 1.5 1.4 1.3 1.0 0.9 1.1 1.1 1.1 0.9 0.8 0.8 1.0 0.9 0.8 0.7 0.7 0.7 0.7 0.6 MLHA8 1.6 1.7 1.5 1.7 1.9 1.5 1.7 1.9 1.9 1.4 1.6 1.9 1.9 1.5 1.9 1.9 1.5 1.8 1.9 2.0 2.3 2.1 2.3 3.4 2.8 2.3 3.6 4.1 2.9 3.5 4.7 2.6 3.6 4.4 1.9 3.4 2.9 1.9 2.3 2.0 1.2 1.4 1.4 1.0 1.2 1.2 0.9 1.1 1.0 0.7 0.9 0.8 0.6 0.7 0.7 0.6 0.6 0.6 0.7 0.6 0.6 0.7 0.7 0.6 0.9 0.9 0.8 1.1 0.9 1.3 1.3 1.1 2.0 1.8 1.4 2.6 2.4 2.1 3.1 3.3 3.3 3.7 3.1 3.4 2.6 2.7 2.0 2.0 1.4 1.4 1.1 1.1 0.9 0.9 0.8 0.8 0.7 0.7 0.6 0.6 0.7 0.7 0.8 0.8 0.9 0.9 0.9 1.1 1.0 1.0 1.4 1.3 1.3 1.9 1.8 1.8 2.4 2.4 2.5 2.8 3.0 3.2 3.0 3.3 3.6 2.9 3.2 3.4 2.4 2.6 2.7 1.9 2.0 2.0 1.4 1.4 1.4 1.1 1.1 1.1 0.9 0.9 0.9 0.8 0.8 0.8 0.6 0.6 0.7 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.6 0.6 0.8 0.8 0.8 0.9 0.9 0.9 1.1 1.1 1.4 1.4 2.0 2.0 2.6 2.7 2.9 3.2 3.3 3.0 3.4 3.6 2.8 3.1 3.2 2.3 2.5 2.5 1.7 1.8 1.8 1.3 1.4 1.4 1.1 1.1 1.1 1.0 1.0 1.0 0.9 0.8 0.8 0.8 0.8 0.7 0.7 0.8 0.7 0.7 0.6 0.8 0.8 0.7 0.6 0.6 0.9 0.8 0.7 0.6 0.6 1.1 1.0 0.8 0.7 0.6 0.5 1.4 1.3 1.0 0.7 0.6 0.5 1.5 1.7 1.7 1.2 0.8 0.6 0.5 1.6 2.0 2.0 1.5 0.9 0.6 0.5 1.9 2.3 2.3 1.6 1.0 0.7 1.8 2.4 2.3 1.6 1.0 0.6 1.5 1.9 2.3 2.1 1.5 0.9 0.4 1.4 1.7 1.9 1.6 1.2 0.7 1.3 1.5 1.5 1.3 1.0 0.6 1.2 1.3 1.3 1.1 0.8 0.5 1.2 1.2 1.2 1.0 0.8 1.2 1.3 1.1 1.0 0.7 1.0 1.3 1.3 1.1 0.9 0.6 SCALE: NORTH SITE PHOTOMETRIC PLAN NO SCALE E1.01 SITE PHOTOMETRIC PLAN NO. REV. DATE project no.: approved by: checked by: drawn by: drawing no.: QA/QC by: date: 1 REVISIONS DESCRIPTION 2 455 Sherman Street, Suite 160 Denver, Colorado 80203 voice: (303) 447-0090 fax: (303) 447-9141 web: collinsengr.com R Know what'sbelow. Call before you dig. 3 4 5 6 7 7600 East Orchard Road, Suite 250-S Greenwood Village, CO 80111-2518 tel: 303.796.6000 Fax: 303.796.6099 www.mkkeng.com CONSULTING ENGINEERS, INC. Mechanical, Electrical & Energy Consultants MKK Project Number: © Copyright 2015 ZJT LSH LSH MRZ 2015.01.0267 9238-25 XTBLK24x36 02/22/2016 W:\01-CO\2015.01.0267 Colorado State University Underpass\DWGS\XTBLK24x36.dwg, 10/26/2015 8:10:27 AM, tatro, zeriah Xrefs: none C1-314 C1-314 IN THEIR EXISTING LOCATIONS. NEW TRENCH LOCATIONS AND BACKFILL BY CONTRACTOR. 175 North 27th Street, Suite 1312 Billings, MT 59101-2048 406.256.1141 Cheyenne, WY 82001-4368 307.634.7647 500 West 18th Street, Suite 200 Greenwood Village, CO 80111-2518 7600 East Orchard Road, Suite 250-S 303.796.6000 www.mkkeng.com SPD T N F J M PB J J CONSULTING ENGINEERS, INC. 50 years and counting! AFF - ABOVE FINISHED FLOOR AFG - ABOVE FINISHED GRADE AIC - AMPS INTERRUPTING CURRENT AL - ALUMINUM BFG - BELOW FINISHED GRADE CB - CIRCUIT BREAKER CR - CORROSION RESISTANT CU - COPPER EM - EMERGENCY ES - EMERGENCY STOP FLA - FULL LOAD AMPS GFI - GROUND FAULT INTERRUPTER GRC - GALVANIZED RIGID CONDUIT HP - HORSEPOWER IG - ISOLATED GROUND MCA - MINIMUM CIRCUIT AMPS MCB - MAIN CIRCUIT BREAKER MCCB - MOLDED CASE CIRCUIT BREAKER MLO - MAIN LUGS ONLY NC - NORMALLY CLOSED NIC - NOT IN CONTRACT NO - NORMALLY OPEN NTS - NOT TO SCALE OC - OVER CURRENT OL - OVERLOAD SC - SHORT CIRCUIT SPD - SURGE PROTECTIVE DEVICE UG - UNDERGROUND WP - WEATHERPROOF XFMR - TRANSFORMER Mechanical, Electrical & Energy Consultants ABBREVIATIONS 3 M SCHEMATIC WIRING GRAPHICS METER GROUND CONNECTION AS NOTED DISCONNECT SWITCH FUSES MAGNETIC MOTOR STARTER SUBSCRIPTS: MS = MULTISPEED SSRV = SOLID-STATE, REDUCED VOLTAGE VF = VARIABLE FREQUENCY CIRCUIT BREAKER, MOLDED-CASE, THERMAL-MAGNETIC FIXED SUBSCRIPTS: AT = ADJUSTABLE INSTANTANEOUS TRIP EAT = ELECTRONIC ADJUSTABLE TRIP CL = CURRENT LIMITING IC = INSULATED CASE GFCI = GROUND FAULT CIRCUIT INTERRUPTER ST = SHUNT TRIP KI = KEY INTERLOCK ZSI = ZONE-SELECTIVE INTERLOCKING ENCLOSED CIRCUIT BREAKER, MOLDED-CASE, THERMAL-MAGNETIC FIXED ENCLOSED FUSED DISCONNECT SWITCH MOTOR, NUMBER INDICATES HORSEPOWER NOTE: ALL SYMBOLS SHOWN ON LEGEND ARE NOT NECESSARILY USED. ELECTRICAL LEGEND POWER STRAIGHT BLADE DUPLEX RECEPTACLE SUBSCRIPTS: HG = HOSPITAL GRADE HGT = HOSPITAL GRADE TAMPER RESISTANT GFI = GROUND FAULT INTERRUPTER SS = SURGE SUPRRESSION AC = 6" ABOVE COUNTER STRAIGHT BLADE DOUBLE DUPLEX RECEPT. (FOURPLEX) STRAIGHT BLADE SINGLE RECEPTACLE OUTLET WITH SPECIAL DEVICE, AS NOTED WALL MOUNTED OUTLET WITH SPECIAL DEVICE, AS NOTED JUNCTION BOX, AS NOTED OUTLET BOX WALL MOUNTED OUTLET BOX PULL BOX CONNECTION TO MOTOR MAGNETIC MOTOR STARTER SUBSCRIPTS: MS = MULTISPEED SSRV = SOLID-STATE, REDUCED VOLTAGE VF = VARIABLE FREQUENCY SAFETY DISCONNECT SWITCH FUSED DISCONNECT SWITCH COMBINATION DISCONNECT AND STARTER ENCLOSED CIRCUIT BREAKER, MOLDED-CASE, THERMAL-MAGNETIC FIXED SUBSCRIPTS: ST = SHUNT TRIP CONNECTION TO PRE-WIRED EQUIPMENT PANELBOARD SURGE PROTECTIVE DEVICE TRANSFORMER LIGHTING POLE MOUNTED LUMINAIRE SURFACE MOUNTED LUMINAIRE CIRCUITING NEW CONDUIT RUN EXISTING CONDUIT RUN DEMO CONDUIT RUN UNDERGROUND CONDUIT RUN CIRCUIT HOMERUN TO PANEL OR CABINET, NO. OF ARROWS INDICATE NO. OF CIRCUITS CIRCUIT TURNED UP CIRCUIT TURNED DOWN CONDUIT STUB-OUT - CAP & MARK UG E0.01 ELECTRICAL COVER SHEET E1.01 SITE PHOTOMETRIC PLAN E1.02 ELECTRICAL SITE PLAN E1.03 TUNNEL ELECTRICAL PLAN E3.01 ELEC. DETAILS, SCHEDULES AND ONE-LINE DIAGRAM DRAWING INDEX UTILITY CONTACTS: 1. CITY OF FT. COLLINS UTILITY JANET McTAGUE 970-224-6154 OFFICE 970-690-5448 CELL 2. CSU TELECOM JONATHAN FRIEDRICH 970-491-2305 OFFICE 970-567-6556 CELL 3. CENTURY LINK BILL JOHNSON 970-490-7501 OFFICE 970-213-0359 CELL 4. COMCAST DON KAPPERMAN 970-567-0145 CELL 5. XCEL ENERGY STEPHANIE RICH 970-225-7828 OFFICE E0.01 ELECTRICAL COVER SHEET NO. REV. DATE project no.: approved by: checked by: drawn by: drawing no.: QA/QC by: date: 1 REVISIONS DESCRIPTION 2 455 Sherman Street, Suite 160 Denver, Colorado 80203 voice: (303) 447-0090 fax: (303) 447-9141 web: collinsengr.com R Know what'sbelow. Call before you dig. 3 4 5 6 7 ZJT LSH LSH MRZ 9238-25 XTBLK24x36 02/22/2016 W:\01-CO\2015.01.0267 Colorado State University Underpass\DWGS\XTBLK24x36.dwg, 10/26/2015 8:10:27 AM, tatro, zeriah Xrefs: none C1-314 C1-314