HomeMy WebLinkAboutCOLORADO IRON AND METAL - Filed CS-COMMENT SHEETS - 2016-08-0920 April 2008 Troy Jones (aka mini-Mikal...) M. Torgerson Architects via email to: troy@architex.com, markodonnell@frii.com, stroud@realtec.com Troy: For your information, attached is a copy of the Staffs comments for your proposal to change the use of the property at 903 Buckingham in three phases. This proposal was presented before the Conceptual Review Team on April 14, 2008. The comments are offered by staff to assist you in preparing the detailed components of the project application. Modifications and additions to these comments may be made at the time of formal review of this project. If you have any questions regarding these comments or the next steps in the review process, please feel free to call me at 970-221-6206. Sincerely, dnne H. Aspen City Planner Cc: project file Project Planner Cc via email: Peter Barnes Randy Maizland Carie Dann Glen Schlueter Roger Buffington Justin Fields Rob Irish Dana Leavitt ITEM: 903 Buckingham — Colorado Iron and Metal MEETING DATE: April 14, 2008 APPLICANT: Troy Jones M. Torgerson Architects 204 Walnut Fort Collins, CO 80524 LAND USE DATA: Request to change the use of the existing industrial building at 903 Buckingham to light industrial recycling. The property is within the City of Fort Collins and is zoned I —Industrial District. The following departmental agencies have offered comments for this proposal. COMMENTS: Zoning Contact Info: Peter Barnes, 416-2355, pbarnes@fcgov.com 1. Permitted Uses: Light industrial recycling and outdoor storage are permitted uses in the (— Industrial district subject to a Type I (Administrative) Review. Phase I could be done as a minor amendment, but staff recommends that you seek approval for all three phases as a Type I review at the outset. If you choose to seek minor amendment approval for Phase I only, you run the risk that Phase II and III may not be approved. 2. The gravel base shown on the west of the site must be asphalt unless it meets one of the criteria for an exception as listed in definition of "off-street parking area" in Section 5.1.2. If this is not possible, you may request a modification of standards. Current Planning Contact Info: Anne Aspen 221-6206, aaspen@fcgov.com 1. The entire Fort Collins Land Use Code (LUC) is available for your review on the web at httr)://www.colocode.com/ftcollins/landuse/begin.htm 2. This development proposal will be subject to all applicable standards of the Fort Collins Land Use Code (LUC), including Article 3 General Development Standards, and Division 4.28 I —Industrial District. 3. When developing your plans for submittal, pay particular attention to the following sections of the Code: 3.2.1. Landscaping and Tree Protection (you will need to protect existing trees, provide street trees and planting beds, etc. to current standards) 3.2.2 Access, Circulation and Parking (parking maximums, dimensions, HC accessible parking requirements, etc.) 3.2.4 Site Lighting 3.2.5 Trash and Recycling enclosures 4.28 (E)(2)(b) and (c) Industrial District Building Design Standards • 4.28 (E)(3) — Industrial District Site Design Standards 2 4. 1 will have more detailed comments once I have more detailed plans to review. 5. An exhaustive list of submittal requirements for this type of project is available at http://fcgov.com/currentplanning/pdf/project-dev-plan.pdf. There is a submittal checklist at http://fcgov.com/currentplanning/pdf/pdp.pdf. Please let me know if you have any questions about the requirements for your submittal. 6. You will need to set up an appointment to submit your application with the Development Review Center front counter at 221-6750. Incomplete submittals will not be accepted. 7. Please note that postage rates have been raised as of January 2006. The fee for the APO labels will now be $.75 per label. APO labels must be generated for an area 800 feet out from each property line. Engineering Contact Info: Randy Maizland, 416-2292, rmaizland@fcgov.com 1. Larimer County Road impact Fees and a City Street Oversizing Fee will apply to this project. You may contact Matt Baker at (970) 224-6108 for an estimate of the fees. 2. The City's Transportation Development Review Fees will apply to this project. You can get more information about these fees at http://fcgov.com/engineering/dev-review.php 3. The Transportation Impact Study requirement may be waived. Contact Ward Stanford at 221-6820 or wstanford@fcgov.com to discuss. 4. Buckingham is classified as a minor collector. The total right-of-way dedication needed for a minor collector is 76 feet. You will be responsible for dedicating half of the right-of-way, or 38 feet, plus a 9 foot utility easement behind the right-of-way. 5. Any damaged sidewalk, gutter or curb will need to be repaired or replaced. Damaged curb, gutter and sidewalk existing prior to construction, as well as streets, sidewalks, curbs and gutters destroyed, damaged or removed due to construction of this project, shall be replaced or restored in like kind at the Developer's expense prior to the acceptance of completed improvements and/or prior to the issuance of the first Certificate of Occupancy. 6. Utility plans, a Development Agreement (DA), and a Development Construction Permit (DCP) will need to be prepared for this project. A plat is not required but may make sense depending on how many easement dedications you need to make. Each dedication by separate document has a fee whereas all easements are included in the plat fee. 7. Any public improvements must be made according to Larimer County Urban Area Street Standards. 8. You will need to fill in the sidewalks where they are discontinuous along your frontage. Any new sidewalks must be designed to meet current standards including a detached profile and to the proper width. If the existing sidewalk is not wide enough to meet ADA standards or if it is in poor repair, you will be required to repair, widen or replace it altogether. 9. The previous owner was required to post a bond for frontage improvements. The City no longer collects bonds. The developer will need to design and build frontage improvements and provide preliminary off -site design to tie into the church site to the east. 10. You will need to provide some length of concrete or asphalt at the most westerly drive approach to prevent drag out from the site out to the road if you are successful in your request for modification. Poudre Fire Authority Contact Info: Carle Dann, 416-2869, cdann@poudre-fire.org 1. FIRE SPRINKLERS: Poudre Fire Authority fire -sprinkler requirements are based on type of occupancy, type of construction and size of the structure. I will need information specifying whether welding occurs within the structure(s); what type of hazardous materials are used or stored inside or outside; and whether these amounts of hazardous materials exceed the Maximum Allowable Quantities. (This is what determines type of occupancy.) The PFA 3 database shows 903 Buckingham St. as having a fire sprinkler system; however, it needs to be determined if this system is adequate for the type of occupancy/occupancies that Colorado Iron and Metal Works would be. 2. HAZARDOUS MATERIALS: Toxic, corrosive, or reactive materials, or flammable/combustible liquids (as defined in the Uniform Fire Code) if used, stored, or handled on site, must have a Hazardous Materials Impact Analysis (HMIA) completed and supplied to the Planning Department and the Fire Department. (What do you have? How much? How do you prevent it from being a public threat?) FCLUC3.4.5 3. WATER SUPPLY: Fire hydrants, where required, must be the type approved by the water district having jurisdiction and the Fire Department. Hydrant spacing and water flow must meet minimum requirements based on type of occupancy. Minimum flow and spacing requirements include: Commercial, 1,500 gpm at 20 psi residual pressure, spaced not farther than 300 feet to the building, on 600-foot centers thereafter Residential within Urban Growth Area, 1,000 gpm at 20 psi residual pressure, spaced not farther than 400 feet to the building, on 800-foot centers thereafter Residential outside Urban Growth Area, 500 gpm at 20 psi residual pressure, spaced not farther than 400 feet to the building, on 800-foot centers thereafter. 4. WATER SUPPLY: These requirements may be modified if buildings are equipped with automatic fire sprinkler systems. 97UFC 901.2.2.2 5. REQUIRED ACCESS: Fire access roads (fire lanes) shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the PFA's jurisdiction when any portion of an exterior wall of the first story of the building is located more than 150 feet from fire apparatus access as measured by an approved route (from a public street) around the exterior of the building or facility. This fire lane shall: • Be designed as a flat, hard, all-weather driving surface (asphalt or concrete) capable of supporting fire apparatus weights. Compacted road base shall be used only for temporary fire lanes or at construction sites. Have appropriate maintenance agreements that are legally binding and enforceable. Be designated on the plat as an Emergency Access Easement. Maintain the required minimum width of 20 feet throughout the length of the fire lane. A fire lane plan shall be submitted for approval prior to installation. If a fire lane is not provided, all buildings out of access (exceeding the 150-foot requirement) shall be equipped with an approved automatic fire -sprinkler system. 97UFC 901.2.2.1; 901.3; 901.4.2; 902.2.1 6. ADDRESS NUMERALS: Address numerals shall be visible from the street fronting the property, and posted with a minimum of 6 inch numerals on a contrasting background. (Bronze numerals on brown brick are not acceptable). 97UFC901.4.4 Stormwater Contact Info: Glen Schlueter, 221-6065, gschlueter@fcgov.com 1. The applicant indicated that the move to this location would be phased. If there are areas to be paved that will increase the imperviousness area greater than 1000 square feet, a drainage and erosion control report and construction plans would then be required and must be prepared by a Professional Engineer registered in Colorado. Only a grading plan is required when there is between 1000 and 350 square feet of new imperviousness. There are no requirements for less than 350 square feet. 2. Should there need to be a detention area, the two-year historic release rate is 0.2 cfs/acre in the Dry Creek basin. Water quality treatment is required as described in the Urban 0 Storm Drainage Criteria Manual, Volume 3 — Best Management Practices (BMPs). Extended detention is the usual method selected for water quality treatment, but all BMPs are encouraged in addition to the extended detention. The detention areas need to contain enough volume for runoff from the impervious areas so using the area for scrap metal pile would take up that volume. The pond could be oversized to accommodate the scrap metal, but that would be a hard thing to judge of when the pile is too big. If extended detention is to be used for water quality treatment, it can be included in a water quantity pond but should be separate from any scrap metal pile if the plan is to use the pond for scrap metal storage. Separate water quality treatment can be provided onsite or the outlet to the existing pond to the southeast could be modified to treat the runoff; however, the water quality capture volume would need to include all the area draining into the larger pond. The applicant's engineer needs to check the drainage reports for Van Works to verify where detention is being provided and the outfall for the system. 3. The design of this site must conform to the drainage basin design of the Dry Creek Master Drainage Plan as well the City's Design Criteria and Construction standards. 4. The city wide development fee is $4,420/acre ($0.1015/sq.ft.) for new impervious area over 350 sq.ft. No fee is charged for existing impervious area. This fee is to be paid at the time each building permit is issued. The monthly fee information is available on the City's web site at fcgov.com. The section of the code that addresses the monthly fees is Sec. 26-514. Jean Pakech at 221-6375 will calculate the fees if you provide her with a proposed site plan. 5. This site is in the FEMA 500-year Cache La Poudre River floodplain. The only floodplain regulation that applies to this site is no life -safety or emergency response critical facilities are allowed in the 500-year floodplain. There are no floodplain regulations related to this use. Water Wastewater Contact Info: Roger Buffington, 221-6854, rbuffington@fcgov.com 1. Existing mains: 12-inch water main in Buckingham, 24-inch sanitary sewer in N/S alignment in an easement on the west side of the site. 2. The domestic water service to the site is a 1-inch, and the fire line is a 6-inch. 3. Maintain/provide a 30 foot easement (15 feet each side) for the 24-inch sanitary sewer. 4. If any additional connections to sewer are needed, these connections must be made at a manhole. 5. If an increase in size or number of water service(s), development fees and water rights will be due at building permit. Credit will be given for the existing service to the building. Light and Power Contact Info: Justin Fields, jfields@fcgov.com filling in for Rob Irish, 224-6167, rirish@fcgov.com 1. Existing service: There is existing 3-phase 208 service. 2. C-1: You will need to fill out a C-1 form with your project development plan. The form is attached. 3. Fees: Regular development fees will not be assessed on 903 Bukingham, since they were paid previously by Vanworks. If service is extended to 827 or 813 Buckingham regular development fees will apply. Capacity charges or credits may apply, depending on the new power requirements. There will likely be some system modifications which will be your responsibility. This work may include upgrading the transformer to meet the new service requirements. 4. There are currently separate meters for different parts of the building. You may want to consolidate these into one meter if the space will be used by just one business. 5 Environmental Planning Contact Info: Dana Leavitt, 224-6143, dleavitt@fcgov.com 1. Tree protection: Existing trees on the property may require protection during construction or mitigation if they must be removed. Please contact Tim Buchanan, City Forester at 224 6361 or tuchanan@fcgov.com and me to arrange a site visit to review and evaluate the site. 2. Trash and recycling: Any trash enclosures proposed for the project (for office trash and recycling etc, not for metal recycling operations) shall comply with Section 3.2.5 of the Land Use Code. Please review The City of Fort Collins Design Considerations Guidance Document found that http://www.fcgov.com/recycling/pdf/enclosure-guidelines08O4.pdf to determine the size and appropriate design. 0 n c D m � Trt1 � d � n = O m _. co � CD CD 3 CD 5D = o o � a 0 0 0 00 00o 0 0 0 0 Op OD OD 5.0 -i in -i = C1 =i v) r o -n d r S S M O C (� = O v N n N N n v O= tOn m �.M, N O 0 C) " C. c=im� �m .�='��3�p �� ^cam W C Q v r < o C Q_v nci cac5L5 ^'m Wm �ocC aQ �co CD CD`o A cC 5 r—m cD < Dv coi o-0af° m o �c = m 00 CDJ► � c° � ts (OD-, o w c m' m �' 3 I oo m e -,00cn w'= 5 Co M Co 3 Y rt cii {A m m O % _ v O O Q 0 3�...�ay(b��0 °'gy�pm6 m= 0 ... N �m m`� ma. 7e=c o o-CD _ '"v�y _a v� �� pC. � NO 3 S =M= GS '^�Qrt -O < y O O -OS� 0 c y O M -, q1 fD S v C. CD O 0 O e c = fC fD (c CD = l CD K o D w 0 c o n o Z � D rn N ° o . r2 O M m _v m �O Co 3 O fD CAD CD (CD WO a T. A ;K O 3 N 0 0 0 0 0 ww 00 N N 0) O 00 C O 01 01a) m.�i.W.�.NiN" >LOO=CO.Ln,'. N �.N rL to (a rL� CD CD N n N n N a CD = (D co CD m� 0) < = 0 N " CD CD ay0mvQ-a°n=o 'drnCDCoy'CD ow• 3�3� CD ��v Qv_ m r.wr.0) d v m O vCD 9'°' CD cD CD m o No n� (Dy'�6 0 0 CD tea' 0 mco o y m m c o 3 c ° �, -� F CO n�fDo 0 CD CD 3 °,mo=rD 0<'Cp-0 0 SO S(D y O ' ' Q.�cn � N 03 * 5"3 5Fr- 0- �3 =r CD o fD � No to m =�� m Cq - -9�� m �-od%,0a 0° m o ono o 0) CD CD 0 l< C) to _ � w �C � too m CD �� �v c o .. u, m m o� o ,' y o CD m=CD �cnn yc 3 cfDia�mo 30 m wcu°'9�3Ndo03 03 m (Drt;s° - �'o �.m1 3 0 c3i $,m o nn ° = "4 C c = N dp C< = m � v m 3 0� 3 m M sum �o mnm�`o CA -«o� �,CD � �o ° n� _d �_' "tom ° 2!p c nr m �7f7 m m =°'O Oa ,O 0 3 rn0 3� CD m ="O0'C' 1�M CD s 3� MCD CD Ern� ?c CL 0 w cn CO MID ID CD CD Y -o r m 0 Q m oni lit ^rr m CD Cr r p m V� NY --A� W � � fr �.�-�3 3 -, o Z r, c n� O D 0 00 O O O A Ln a CA H D CD n m co 0 2, CD m � 3 O m -, m CD 0 0 A n 0 O co 00 N � O O OD 00 yv ad y a, aym w -v 0-0 -o0 m c m N >C.py m 3 m" m 3 m rto �co) 0"_° CD gy m-° D N O SCD � -m ? m o 0 m m �^^E y �� S CD m C n 3 CD n C. C- O y O O N '. 7 ". C� m -�' nCD c.C.CD — n �' ?.0 u�,0 3 m m y m << S ' y c0) m M--h i CL CL m= O m 0 fCD W CO cr 320 D O rt y O m N -a O C 3 7 w a 0 N m 3 dvo p3 �_0) nc v m ( 3 (n sm C 0 CL CD 0cc =.<<0 M ac ° CLx0 �rM m CD y m 7 m (0 CD N • ^m* " .. y y N C) ... S .. S Ej' n O 0 CL CD 3 w m? C m 0) O CD M m 0 S C C (O 3 N c0 N O M 7 O a o '-- cp ° m 7 3 OCL 0 N (D 7 3 N ? 7 O• 0 O CL C y 3 p C O C' 3 N� 7 . n ycc , m 0 co O m Cc r 0� 3 I :� , cn 7. 3 w Q O n S 3 CD �o C' m <_ CDD '� " w �i S wo m --.0 ;w O m — 0 m m" O O m O ° C- m p g p� rL M .< 7 o 3 S S� =r m e yCL U)_ .a 3 y_ i �`< V' � a o aCL - IV m m cc n= <_ CD 0 m Q o m p O m < n 0. mm n CD Sp m 3< C m O a m d O C O -' y y L. m O. CD <CL 0 0 y W y m m 3 p— S; 'a w y CL CL 0 m O O W C C 7 m C. - O m m Q (DD N �, C- m 7 S d C 4!9 - c� �► f� _ y (SD 'o C-'. CD C N p S N o CCD y d 3 p �< v O 3 S fD G� 3 `� cD << _'>> �+ ,c ..3 m �°,_��d CD 3 d 3v C�n� vv v v m -.,Om CD .0 fD Cp S 0 C 7 m 7 °y' 3 = m Cn n' m-h --h O Q O O G 3 y �. y m 0°- m� �o'� a v 0 Cn ji M a c �,.< m o �'3 o cnm m CL y y (D m CD mC m y m m O CD 7 S CD O S '' -� 0 icy X N CD CL 7 7 N O 7 O_ • S s � o � 0 0 0 0 0 0 0 LTI V M CA C N D C' M