Loading...
HomeMy WebLinkAboutPRESTON CENTER FOURTH - Filed CS-COMMENT SHEETS - 2011-11-29Y �ZIPIeyABSOCIATE9INC Landscape Architecture Urban Design Planning June 28, 2006 Mr. Ted Shepard Fort Collins Planning Department 281 North College Avenue Fort Collins, CO 80524 RE: Harmony One at Preston Center Fourth Filing, Lots 2 & 6 — Major Amendment — Type 1 Response to staff Project Review comments Dear Mr. Shepard: We have reviewed the staff letter dated May 03, 2006 and have the following comments: ITEM: Request for a 5 story Office Building: COMMENTS: Department: Engineering Issue Contact: Dan DeLaughter Topic: General Number:4 Created. 411212006 [4112106] Add General Notes # 47 and 48 to sheet 2. List "none" for variances and private drives since these notes will not apply. Notes have been added. Number:5 Created.411212006 [4112106] Add curb and gutter details for Corbett, and Timberwood. These are needed in case repairs or replacement must be done. Details added. Phone 970.224.5828 Fax 970.224.1662 401 West Mountain Ave. Suite 201 Fort Collins, CO 80521-2604 vfripley.com Number:7 Created.411312006 [4113106] The sidewalks are dimensioned as 6' but labeled as 5.5. Wherever parking overhangs the walk, the minimum width is 6 . Either way, the width should be clarified. Dimensions have been adjusted on the plans. Number: 17 Created. 412612006 [4126106] Offsite easements must be dedicated by separate document. TDRF fees and filing fees will apply. A letter of intent is required if you are planning on providing emergency access as shown on these plans. As discussed at the 4126106 meeting with City staff, it would be acceptable to transition the existing offsite 20' wide double fire lane into the proposed on -site 30' lane, but a detail showing how this would work should be provided, and approved by PFA prior to hearing. The proposed layout has been discussed with PFA and approved. Number. 18 Created: 412612006 [4126106] Please note, if you are not adding a new emergency access easement in the middle of the offsite connection, the emergency aisle would have to be constructed where the existing easements are shown. In other words, the design needs to match the easements. Plans adjusted as such. Topic: Plat Number.2 Created.411212006 [4112106] RESOLVED at 4126106 meeting, all onsite easements will be vacated. Please refer to the redlines on the plat: Fire lane easements are shown on Preston Center 3rd as extending onto your site, along with a circle at the east edge of your property. Any portions of the easement that are not planned to be used should be vacated with the plat. Acknowledged. Number.3 Created. 411212006 [4112106] RESOLVED: on -site easements will be vacated. The drainage easement on the south of the site doesn't match what is shown on Preston Center 3rd plat. Show any portions of the old easement to be vacated. Acknowledged. Number:6 Created.411312006 [4113106] RESOLVED: please add a note stating that "All on -site easements as shown on Preston Center 3rd Filing are to be vacated and rededicated as shown on this plat. " In general, please coordinate better with the original Preston Center 3rd plat. Many easements are either missing completely or modified from their original geometry. One of the easements not shown appears to go directly across your proposed building. Acknowledged. Number:8 Created.411312006 [4113106] The sidewalk is shown along Harmony extending all the way to Ziegler. Will you be building this portion of the walk? If not, please label it as a future sidewalk connection. The walk has been relabeled as "future sidewalk connection" Number.9 Created.411312006 [4113106] Please revise the grading plan to show the sidewalk connection all the way out to Gifford Ct. If the grades are tight in this area, include an enlarged detail showing the sidewalk and irrigation structure. Sidewalk is not included in proposed improvements. Number. 10 Created. 411312006 [4113106] Will the west access be restricted to emergency access only? If so, how? If not, include enough information on the plans to show how this access will line up with the one on the West side of Gifford. Access drive plan updated as such. Number. 11 Created.411312006 [4113106] Please see redlines for minor changes to site and landscape plans. Acknowledged. Topic: Technical Services Comments Number: 19 Created. 412612006 [41261061 Technical Services Comments: 1. Boundary Closes 2. Make sure all easemments are locatable 3. Need note vacating existing easements & rededicate as shown. Acknowledged. Department. Light & Power Issue Contact: Doug Martine Topic: Plat Number.I Created.41612006 [416106] The emergency access & fire lane easements from Gifford Ct. to Ziegler Rd must also be designated as utility easements. The electric utility system will be installed immediately south of the access drive from Gifford Ct. eastward. Also the public access easement along the western side of the building must be a utility easement that encompasses the electric transformer shown. Acknowledged. Department. PFA Issue Contact. Carle Dann Topic: Fire Number. 20 Created. 412612006 [4126106] ACCESS: The Emergency Access Easements from the various filings are difficult to interpret. Bottomline, we acknowledge the 26-foot to 30-foot fire lane that runs west -east to the south of the structure, but we also require a fire lane be dedicated over the north -south drive aisle that connects to Timberwood (see redlines). The EAE must be dedicated on the plat. The fire lane must be visible by painting and signage, and maintained unobstructed. Acknowledged. An EAE has also been added in the parking area to the east of the building. Number. 21 Created. 412612006 [4126106] AUTOMATIC SPRINKERS: The building must be equipped with an approved, automatic fire -sprinkler system. The Fire Department Connection for the sprinkler system must be located on the fire lane side of the building, for accessibility. The building will be equipped with an automatic fire -sprinkler system. This will be address during the building permit process. Number: 22 Created. 412612006 [4126106] STANDPIPE: Buildings 4 or more stories in height must be equipped with a standpipe capable of supplying 100 psi to the highest habitable level; a fire pump may be required to attain that pressure. The Fire Department Connection for the standpipe must be located on the fire lane side of the building, for accessibility. Acknowledged. This will be addressed during the building permit process. Number. 23 Created. 412612006 [4126106] WATER SUPPLY. A fire hydrant(s) is required. Hydrant spacing and water flow must meet minimum requirements based on type of occupancy. Spacing and flow requirements for a commercial structure are 1,500 g.p.m. at 20 psi residual pressure, spaced not further than 300 feet to the building, on 600-foot centers thereafter. An existing fire hydrant was approved and constructed with Filing 3. Number. 24 Created. 412612006 [4126106] ADDRESSING: Address numerals shall be visible from the street fronting the property, and posted with a minimum of six-inch (6) numerals on a contrasting background. (Bronze numerals on brown brick are not acceptable). If the structure is addressed off Harmony Road, we require monument signage at Harmony. Acknowledged. Number. 25 Created. 412612006 [4126106] KNOX BOX. Poudre Fire Authority requires that a Knox Box be mounted near the front entrance on every building with a required automatic fire -sprinkler system. Acknowledged. This will be addressed during the building permit process. Number. 26 Created. 412612006 [4126106] STAIRWELL SIGNAGE. Approved stairwell identification signs shall be posted at each floor level in all enclosed stairways in buildings four or more stories in height. Acknowledged. This will be addressed during the building permit process. Department: Transportation Planning Issue Contact. David Averill Topic: General Number. 27 Created. 412712006 [41271061 Need to install some sidewalk access ramps along that main north/south drive aisle. See redlined site plan from Engineering for specifics. Thanks. Sidewalk access ramps have been added. Department. Stormwater-Water-Wastewaterlssue Contact. Wes Lamarque Topic: Stormwater Number. 14 Created. 412612006 [4126106] Water quality is required for the site. If the regional pond is to be used, the water quality volume needs to be for the entire area that drains to the pond and not just the 3 acres. Water quality can be provided on -site if you just want to supply the volume for the site. The revised calculations and the proposed water quality structure account for the entire area tributary to the filing three water quality/detention pond. Number. 15 Created: 412612006 [4126106] The water quality volume needs to be in addition to the quantity detention. As discussed with stormwater, water quality will not be in addition to detention. Number. 28 Created. 412812006 [41281061 Per Preston Center 3rd Filing partial stormwater certification dated May 18, 2001, the detention pond volume is 4% short of the designed volume. This issue, along with designing water quality mitigation for the entire 3rd filing and reseeding (landscaping) the pond, can be addressed at final compliance. Per phone conversation, the owners of the lots in the third filing will all participate in these requirements for the regional pond. A repay could be put into the development agreement for this project, however the owners may work this out on their own. As discussed with Stormwater the additional 4% volume was accounted for. See section 4.4 in the Final Drainage Report. Topic: WaterMastewater Number. 16 Created. 412612006 [4126106] Water/Wastewater is ready for a hearing. All comments are final compliance items. Acknowledged. Department: Zoning Issue Contact. Peter Barnes Topic: zoning Number. 12 Created. 411712006 [4117106] Each landscape island must contain one or more trees (80 s.f. Of ground area per tree/per island). Some of them only contain shrubs. The landscape islands along the drive, south of the building, do not contain trees because there is an existing 8" water line that runs east and west and minimum separation clearances can not be maintained. Number. 13 Created. 411712006 [4117106] Building height review required per Sec. 3.5.1(G) since the building is taller than 40 A shadow analysis has been submitted. Comments from Current Planning; The plat must be called Preston Center Fourth Filing, being a replat of Lots Two and Six of the Third Filing. The P.D.P. can be called Harmony One at Preston Center Fourth Filing. For marketing purposes, the project may be called Harmony One. Changed as such. The center is allowed a maximum 5.00 spaces per 1,000 square feet of gross floor area. Please describe how the proposed 176 spaces serving a 50,000 square foot building does not put the Third Filing over the 5.00 spaces per 1,000 maximum. 50,000 s.f./ 1,000 s.f. = 50 x 5 = 250 maximum allowed spaces. This building is parked at a ratio of approximately 3.5 spaces per 1,000 square feet. This ratio is under the ratio allowed by the Third Filing. Please let us know if you have any other issues. Sincerely, Sandy McFeron Project Manager V.F. Ripley Associates, Inc. Joe Sparone Project Manager JR Engineering