February 17, 2004
Mr. Ted Shepard
City Planner
City of Fort Collins
Current Planning Department
Re: Atrium Suites PUD, response to Conceptual Review Comments
Dear Ted,
A Design Collaboiatire
The follov&g items are responses to comments from the Conceptual Review of 502
West Laurel Street — Apartment Complex.
1. The proposed project is a 3-story building, with 24 — 2 Bedroom units, and 4 — 1
bedroom units, and managers office, an allowable use, within the zone district,
subject to review by the Planning and Zoning Board; therefore the project is
considered a Type II review. A modification request has been submitted for
allowable floor area to lot ratio, see item no. 2.
2. The lot area is 19,220.86 s.f. and the proposed building has 2063.40 s.f. of
livable floor area. A modification of standards for this requirement was submitted
on February 8, 2004.
3. The building is setback from the Laurel St. front yard 16'-0", the Sherwood side
yard setback is 15'-1", the west side yard adjacent to neighboring property is set
back 5'-C" at the ground level, with the building stepping back on the upper floors,
and the rear yard has connection to the adjacent alley, with and building is
setback from T-11" from neighboring property.
4. The proposed building, site, and landscape have all been designed to meet the
design intent outlined in Section 4.8(E) of the Land Use Code.
5. A public plaza connecting the main entry to Both Laurel and Sherwood streets is
incorporated into the site design. Direct connection to the public sidewalk along
Sherwood St. from the ground floor living units has been provided
6. Parking requirements will be met by providing parking on -site, and through long-
term lease agreements from neighboring properties.
7. Electrical service will be coordinated with Light and Power.
8. Electrical requirements will be coordinated with Light
and Power. New street trees will be planted so as not
Ito interfere with utilities.
9. Refer to drainage study and civil engineering plans for
phmrs•
(970) 2a7.1973
all storm run-off calculations. Water quality measures
f.
(wo, 206.0813
e-nmil
eastpointOfrii.com
corie pom1cme
3207 Kittery Court
' _
Fort Collins, CO 80526
Topic: Site Plan
Number: 9 Created: 3/2/2004
[3/2/04] Please call out the existing ROW widths for the alley, Sherwood, and Laurel, as well as the new ROW being
dedicated along Laurel.
Number. 10 Created: 3/2/2004
[3/2/04] It appears that a 2'-3' column will be in the driveway entrance. Is this correct?
Number: 11 Created: 3/2/2004
[3/2/04] Please clarify how many parking stalls will be removed on Sherwood Street with the additional width of the new
driveway for this project.
Number: 19 Created: 3/2/2004
[3/2/04] Please dimension the on -street parking stalls.
Number: 22 Created: 3/2/2004
[3/21041 If the two first -floor units are supposed to be handicapped accessible, then shouldn't additional sidewalks be
provided so that residents can easily access the front doors from the handicapped parking stalls provided? The current
configuration forces them into the pond, grass, or a very circuitous paved route.
Topic: Utility Plans
Number. 12 Created. 3/2/2004
[3/2/04] Please see the revised utility plan checklist for any additional items.
Number: 13 Created: 3/2/2004
[3/2/04] It would be helpful to have an overall utility plan separate from the grading and drainage plan. It's difficult to
see where everything is going on the current plan.
Number: 14 Created: 3/2/2004
[3/2/04] Sheet 4 - Please label and dimension all ROW, new and existing.
Number: 15 Created: 3/2/2004
(3/2/04] Please label the driveway as being constructed with concrete within the ROW.
Number:1C 1 -Graated:3/212004
the ROW, but
pond, relocate it, or
Number: 17 Created: 3/2/2004
[3/2/04] Please shift the trash enclosure slightly to the south so that the doors do not open into the alley ROW.
Number: 18 Created: 3/2/2004
[3/2/04] Please label the driveway width proposed.
Number: 20 Created. 3/2/2004
[3/2/04] Please use standard detail d-10 for the under -walk drain.
Number: 21 Created: 3/2/2004
[3/2/04] Please remove the drive -over curb and gutter detail since c&g in this area is vertical.
Page 2
Project Comments Sheet
Selected Departments
(ity of fort Collins
Department: Zoning
Date: March 12, 2004
Project: ATRIUM SUITES, 502 W. LAUREL PDP - TYPE 11
All comments must be received by Ted Shepard in Current Planning, no later than
the staff review meeting:
March 17, 2004
Note - Please identify your redlines for future reference
Issue Contact: Peter Barnes
Topic: Zoning
Number: 26 Created: 3/12/2004
[3/12/04] The lot square footage must be shown on the plat, and the lot should be labeled (i-e. Lot 1, or Tract 1, etc).
Number: 27 Created: 3/12/2004
[3/12/04] Show/label bike rack locations.
Number: 28 Created: 3/12/2004
[3/12/04] Something more than just rock mulch is required along the west side of the structure.
Number 29 Created: 3/12/2004
[3/12/04] In the Land Use Statistics box, under "Land Uses", need to clarify that the "Existing Group Home (104
residents)" is going to be abandoned/demolished. Otherwise, one gets the impression that the land uses are going to
be the existing group home plus the new proposed apartments.
Signature
3Id�y
Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _x site Drainage Report Other_
_ Utility __ Redline Utility V Landscape
Page 1
6z STAFF PROJECT REVIEW
(i(Y of Furl Chllim
EAST POINT STUDIO, LLC Date: 03/22/2004
DON BROOKSHIRE
3207 KITTERY CT.
FT. COLLINS, CO 80526
Staff has reviewed your submittal for ATRIUM SUITES, 502 W. LAUREL PDP -
TYPE II, and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Katie Moore
Topic: General
Number: 7 Created: 3/2/2004
[3/2/04] Please see redlines for any additional comments.
Number: 23 Created: 3/2/2004
[3/2/04] The sidewalk on Laurel is required to be a minimum of 6' wide. It is shown
as 4' on the plans so there are two options for widening the walk: remove the walk
and replace it with a 6' walk, or add 4' of concrete to the additional walk per LCUASS
(4' is the minimum width of concrete that is allowed to be added to widen a
sidewalk).
Topic: Landscape Plan
Number: 8 Created: 3/2/2004
[3/2/04] Please show the utilities on the landscape plan, so that the separation
requirements can be verified.
Topic: Plat
Number: 2 Created: 3/2/2004
[3/2/04] Please use the current standard plat language. (See attached.)
Number: 3 Created: 3/2/2004
[3/2/04] According to City records I found, the ROW for Sherwood should be 100',
not 80'.
Number: 4 Created: 3/2/2004
[3/2/04] Please list the reception number or book and page number for the Laurel
Street ROW vacation shown and provide a width for it.
Number: 5
[3/2/04] Please fill in the title block.
Created: 3/2/2004
Number: 6 Created: 3/2/2004
[3/2/04] Please show the 15' utility easement along Laurel. It should match the
utility plans.
Page I
Topic: Site Plan
Number: 9 Created: 3/2/2004
[3/2/04] Please call out the existing ROW widths for the alley, Sherwood, and
Laurel, as well as the new ROW being dedicated along Laurel.
Number: 10 Created: 3/2/2004
[3/2/04] It appears that a 2'-3' column will be in the driveway entrance. Is this
correct?
Number: 11 Created: 3/2/2004
[3/2104] Please clarify how many parking stalls will be removed on Sherwood Street
with the addition of the driveway for this project.
Number: 19 Created: 3/2/2004
[3/2/04] Please dimension the on -street parking stalls.
Number: 22 Created: 3/2/2004
[3/2/04] If the two first -floor units are supposed to be handicapped accessible, then
shouldn't additional sidewalks be provided so that residents can easily access the
front doors from the handicapped parking stalls provided? The current configuration
forces them into the pond, grass, or a very circuitous paved route.
Topic: Utility Plans
Number: 12 Created: 3/2/2004
[3/2/04] Please see the revised utility plan checklist for any additional items.
Number: 13 Created: 3/2/2004
[3/2/04] It would be helpful to have an overall utility plan separate from the grading
and drainage plan. It's difficult to see where everything is going on the current plan.
Number: 14 Created: 3/2/2004
[3/2/04] Sheet 4 - Please label and dimension all ROW, new and existing.
Number: 15 Created: 3/2/2004
[3/2/04] Please label the driveway as being constructed with concrete within the
ROW.
Number: 17 Created: 3/2/2004
[3/2/04] Please shift the trash enclosure slightly to the south so that the doors do not
open into the alley ROW.
Number: 18 Created: 3/2/2004
[3/2/04] Please label the driveway width proposed.
Page 2
Number: 20 Created: 3/2/2004
[3/2/04] Please use standard detail d-10 for the under -walk drain.
Number: 21 Created: 3/2/2004
[3/2/04] Please remove the drive -over curb and gutter detail since c&g in this area is
vertical.
Department: Ligiht & Power Issue Contact: Doug Martine
Topic: Electric
Number: 1 Created: 3/1 /2004
[3/1/041 Normal electric development charges will apply with a credit given for the
existing electric service to be removed. In addition, charges to modify the electric
system will apply for installation costs of an underground power line from the source
in the alley approximately 200 ft. north of this site. A PRELIMINARY estimate of
these costs, based on currently available data, is in the $25,000.00 range. Electrical
heat is discouraged. Coordinate power requirements with Light & Power
Engineering (224-6152).
Department: PFA Issue Contact: Michael Chavez
Topic: General
Number: 33 Created: 3/16/2004
[3/16/041 ADDRESS NUMERALS; Address numerals shall be visible from the street
fronting the property, and posted with a minimum of 6 inch numerals on a
contrasting background. If bronze numerals are used they shall be on a black
background.
Number: 35 Created: 3/16/2004
[3/16/04] WATER SUPPLY: No commercial building shall be greater then 300 feet
from a fire hydrant. Each hydrant must be capable of delivering 1500 gallons per
minute at a residual pressure of 20 psi.
Number: 38 Created: 3/16/2004
[3/16/041 SPRINKLERS REQUIRED: This proposed building shall be fire
sprinklered. Poudre Fire Authority requires a "Knox Box" to be mounted on the front
of every new building equipped with a required fire sprinkler system or required fire
alarm system.
Department: Transportation Planning Issue Contact: Tom Reiff
Topic: Transportation
Number: 34 Created: 3/16/2004
[3/16/041 A Transportation Impact Study or an official waiver from the City's Traffic
Operations Department was not received. Please include the study or official waiver
with the next submittal.
Page 3
Number: 36 Created: 3/16/2004
[3/16/04] It is difficult to tell from the plan sets if there is an accessible ADA route
from the handicap parking stalls to the units. Please clarify this for the next submittal.
Number: 37 Created: 3/16/2004
[3/16/04] Bike parking is required for the new development. Please label and
identify on future plan sets. The bike racks will need to be located in a secure
location near the buildings main entrance and not impede pedestrian traffic.
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: General
Number: 30 Created: 3/16/2004
[3/16/04] Our records indicate that the existing meter is located in the basement of
the current building. This proposed project will need to relocate the meter into a pit
outside. Show and label the location of the proposed meter pit and curb stop. Be
sure to adjust the landscape plan accordingly if the meter conflicts with the proposed
plant material.
Topic: Landscape Plan
Number: 31 Created: 3/16/2004
[3/16/04] Show the proposed meter pit and curb stop location on the landscape
plans and maintain the required landscape/utility separation distances.
See site, landscape and utility plans for other comments.
Department: Zoning Issue Contact: Peter Barnes
Topic: Zoning
Number: 26 Created: 3/12/2004
[3/12/041 The lot square footage must be shown on the plat, and the lot should be
labeled (i.e. Lot 1, or Tract 1, etc).
Number: 27 Created: 3/12/2004
[3/12/04] Show/label bike rack locations.
Number: 28 Created: 3/12/2004
[3/12/041 Something more than just rock mulch is required along the west side of
the structure.
Number: 29 Created: 3/12/2004
[3/12/04] In the Land Use Statistics box, under "Land Uses", need to clarify that the
"Existing Group Home (104 residents)" is going to be abandoned/demolished.
Otherwise, one gets the impression that the land uses are going to be the existing
group home plus the new proposed apartments.
Be sure and return all of your redlined plans when you re -submit and call If you have
any questions regarding these issues.
Page 4
REVISION
RE,;,,, --q- 9
COMMENT SHEET
DATE: April 30, 2004 TO: Technical Services
PROJECT: 47-04A Atrium Suites, 502 W. Laurel PDP —
Type II (LUC)
All comments must be received by Ted Shepard no later than the
staff review meeting:
May 19, 2004 j
ElNo Comment
ElProblems or Concerns (see below or attached)
"PLEASE IDENTIFY YOUR REDLINES FOR FUTURE
REFERENCE"
Cih of Fort Collins
a.' 317641M it , 2:
Project Comments Sheet
Selected Departments
Department: Transportation Planning
Date: May 19, 2004
Project: ATRIUM SUITES, 502 W. LAUREL PDP -TYPE II
All comments must: be received by Ted Shepard in Current Planning, no later than
the staff review meeting:
May 19, 2004
Note - Please identify your redlines for future reference
Issue Contact: Tom Reiff
Topic: Transportation
Number: 37 Created: 3/16/2004
[5/12/04] The bike rack location needs to be moved to a more visible location closer
to the entrance and not located in some remote section of the parking lot
where access to the rack will be constrained when cars are parked in the
stalls directly in front of the rack. See red lines for suggested location.
Srgnattrre
Date
F' _ TOZFSC,C 't� CCPIrVISIONS�CS
€laSite Drainage Report Other—
' ti3it} _--� Redtine v`ilit% Landscape
Page I
Project Comments Sheet
CitvofFort Cot lins Selected Departments
Department: Engineering
Date: May 21, 2004
project: ATRIUM SUITES, 502 W. LAUREL PDP -TYPE II
All comments must be received by Ted Shepard in Current Planning, no later than
the staff review meeting:
May 19, 2004
Note - Please identify your redlines for future reference
Issue Contact: Katie Moore
Topic: General
Number: 7 Created: 3/2/2004
[5/4/04] Repeat.
[3/2/04] Please see redlines for any additional comments.
Topic: Site Plan
Number: 9 Created: 3/2/2004
[5/4104] Clearly delineate the new ROW on Laurel. There is a dimension for the new ROW, but no line showing it.
[3/2/04] Please call out the existing ROW widths for the alley, Sherwood, and Laurel, as well as the new ROW being
dedicated along Laurel.
Topic: Utility Plans
Number: 20 Created: 3/2/2004
[5/4/04] Is the under wal< drain really needed? If so, again, please use D-10 (attached).
[3/2/04] Please use standard detail d-10 for the under -walk drain.
Number: 50
15121104] Please place the back of sidewalk on Laurel at the ROW.
Created: 5/21 /2004
fif f ¢?iZF: IP i W o ISIF TO z"�ECFIVE COMES OP RE`% ISIOINS
Plat Sit- _._-- Drainage Report ..._.�. Otller_
_ Iit Redline I tiliO Landscape
Pace I
PROJECT
1100"i COMMENT SHEET
City of Fort Collins
Current Planninu
DATE: July 27, 2004 TO: Engineering
PROJECT: #7-04B Atrium Suites, 502 W. Laurel —
Modification of Standard - Type I (LUC)
All comments must be received by Ted Shepard no later than the staff
review meeting:
August 11, 2004
Note - PLEASE identify rouyrredlines for
f�u�t�unr�e� reference
I k Y /wit li�.�i�✓t i vth.r • -..1 �/- '
I� v�Y!''� ii �l ' y
C o
„ (�t✓ LzL i �k)tJJ U,� 6[-,('1 Y?t!c�E
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _Site _Drainage Report Other
Utility _Redline Utility Landscape
Q "M
!;�114100)40
City of Fort Collins
VUco
Vt'�tvcd ,
ry EnC-5
will be incorporated into the design for all storm water run-off.
10. Refer to civil engineering drawings in response to this comment.
11. Refer to civil engineering, utility drawings in response to this comment.
12. The building will include a sprinkler system. Refer to Utility drawings for
additionalrequirements for water services. Further coordination with Poudre Fire
Authority will be arranged.'
13. The parking structure will include a solid wall on the west edge of the structure,
where the: building is 5-0" from the property line. The parking structure will
provide adequate ventilation, and fire protection.
14. Comments acknowledged.
15. A transportation Impact study will not be submitted at the initial submittal. The
applicant requests that this study be waived, as the actual impact from the
current conditions to proposed project will be equal to or a reduction in traffic
generated from this site. Currently there are 104 residents and 22 full time
employees, who travel from this site now, and future parking allows for 28 on -site _
parking spaces. The future conditions would amount to a reduction in trips per
day. If additional information is required, please contact Don Brookshire of
Eastpoint Studio, 207-1973.
16. Less than 350 trips per day is expected from the Sherwood St. driveway. .
17. The driveway on Sherwood St will exceed 175'-0" from Laurel street center line
to drive way center line.
18. All drive aisles will be minimum of 24'-0" in width.
19. Comments acknowledged..
20. Comments acknowledged.
21. Refer to Utility drawings, for utility locations.
22. Comments acknowledged.
23. No trees on site are expected to be removed, at this time. A trash enclosure is
planned to be located adjacent to the rear Alley, and will contain recycle bins.
24. Utility Plans are included as a part of this submittal
25. Additional 1'-0" of right of way to be dedicated with a 15'-0" utility easement is
planned for. Refer to site plan drawings.
26. A plat is included with this submittal
27. The applicant requests that a neighborhood meeting be scheduled. APO lists
have been included with this submittal.
If there are any further questions, please contact me.
Don Brookshire, Eastpoint Studio.
- Project Comments Sheet 02
� a&i
City ofFort Collins Selected Departments
--
Department: Engineering
Date: August 2, 2004
Project:
ATRIUM SUITES, 502 W. LAUREL - MODIFICATION OF STANDARD -
TYPE I
All comments must be received by Ted Shepard in Current Planning, no later than
the staff review meeting:
August 11, 2004
Note - Please identify your redlines for future reference
Issue Contact: Katie Moore
Topic: General
Number: 1 Created: 8/2/2004
[8/2/04] Where is the data? There is nothing provided to back up the assertion that, if the
project provides the! standard number of parking spaces, a number of them will be left empty
and unused. Additional information should be provided so that it can be seen whether this
assertion is true.
fI 2-M
Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _ Site Drainage Report Other_
Utility _ Redline Utility Landscape
Page 1
Project Comments Sheet
C
Selected Departments
itv of Fort Collins
nmmwmww®�
Department: Transportation Planning
Date: August 5, 2004
Project:
ATRIUM SUITES, 502 W. LAUREL - MODIFICATION OF STANDARD -
TYPE I
All comments must be received by Ted Shepard in Current Planning, no later than
the staff review meeting:
August 11, 2004
Note - Please identify your redlines for future reference
Issue Contact: David Averill
Topic: Transportation
Number: 3 Created: 8/5/2004
[8/5/04] 1 think it would be a good idea for the applicant to provide a summary report of the
"research" that was undertaken and is cited as supporting evidence for this request.
Signature
8S v
Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _ Site Drainage Report Other
Utility _ Redline Utility r Landscape
Page I
FINAL .PLAN
ift�
...• COMMENT SHEET
City of Fort Collins.
icC.a'H11011
Current Planning
DATE: October 28, 2004 TO: Technical Services
PROJECT: #7-04C Atrium Suites, 502 W. Laurel PDP -
'FINAL COMPLIANCE
F
All comments must be received by Ted Shepard no later than the staff
review meeting:
November 17, 2004
Note - Please identify your redlines for future reference
2'Y, L 5 G- tt (.., !rs o' PJ 0 T E {_ e n: � �' n171 lam>: o. � T �� ! i'1"; -% •
/ '
J �
OF LA UiZicc-
��i �i ��� /� �1� �� 11416'<1
Name (pleasb print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat Site Drainage Report _Other
_Utility _Redline Utility _Landscape city of Fort Collins
Project Comments Sheet
Selected Departments
City of fort Collins.
Department: Transportation Planning
Date: November 16, 2004
Project:
ATRIUM SUITES, 502 W. LAUREL PDP - TYPE II AND FINAL
COMPLIANCE
All comments must be received by Ted Shepard in Current Planning, no later than
the staff review meeting:
November 17, 2004
Note - Please identify your redlines for future reference
Issue Contact: David Averill
Topic: Transportation
Number: 57 Created: 11/16/2004
[11/16/04] The walkway that leads from Sherwood St into the parking area is 4 feet in width
as it passes in front of a couple of parking stalls. It widens to 6' past the envelope of the
ground floor. This walk needs to be 6' in width along any portion that passes in front of a
parking stall, unless wheel stops are to be used. If this is the case, the applicant should
double check the required dimensions of the parking stalls to make sure that what they are
proposing is acceptable.
DUL, riv -11
Signature Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _�te Drainage Report Other
Utility _ -Redline Utility � Landscape
Page 1
6 Ilk
l Selected Issues Report
N NEARCity of Fort Collins
Date:
11/19/2004
ATRIUM SUITES, 502 W. LAUREL PDP - TYPE II AND FINAL
COMPLIANCE
SELECTION CRITERIA: Department = Engineering; Status = Unresolved
ISSUES:
Department: Engineering Issue Contact: Katie Moore
Topic: General
Number: ? Created: 3/2/2004 Pending
[11 /16/041
[5/4/04] Repeat:
[3/2104] Please see redlines for any additional comments.
Topic: Utility Plans
Number:51 Created:11/16/2004 Pending
(11/16/04] The 2ndl Benchmark in Note 40 lists an incorrect reference elevation.
Number:52 Created:11/16/2004 Pending
[11/16/04] Further clarification is still needed regarding the ramps at the corner- are they
staying or being rebuilt? If they're being rebuilt, they need to be constructed using the City's
new ADA truncated dome details. Let me know if you need copies.
Number:53 Created:11/16/2004 Pending
[11/16/04] Please shift the sidewalk transition to the south to be on this project's frontage -
the small wedge of concrete shown to be added to the sidewalk to the north as a transition
would not be allowed (min 4' when adding concrete to a walk) - but the transition could be
accommodated on the property's frontage in a much more maintanable way.
Number:54 Created:11/16/2004 Pending
[11/16/041 By the end of Friday, Nov 19th, I should know whether any of the utilities have
concerns regarding the proposed wall/fence and planters proposed within the utility
easement. If there are concerns, these items may have to be removed. If they are allowed,
then the DA will include language stating that, should any of the utilities need to work within
the easement and damage or remove any of these items, then it would be the responsibility
of the Developer to replace/repair them.
As of 3:00pm Friday, I still have not heard from Qwest. I will call Jade Monday to let him
know definitively.
Number:55 Created:11/16/2004 Pending
[11/16/04] There ,are some scanability concerns with the plans. Please review appendix E-
6 of LCUASS for the requirements and revise the plans as necessary.
a.
Page I �� C�IULW3
k 7Wm0r+-n
PROJECT
(0WKWNi3ffird)ACOMMENT SHEET
City of Fort Collins r'rC,G
Current Planning
DATE: February 25, 2004 TO: Technical Services
PROJECT: 47-04A ATRIUM SUITES, 502 W. LAUREL PDP —
'TYPE II (LUC)
A11 comments must be received by Ted Shepard no later than the staff
review meeting:
March 17, 2004
Note - PFEAsE identify your redlines for future reference
�z.
mot. SEC rI tN Sv.3 -iT .=
S M C= c u r tf- j cJ�� t 2 ��;
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
plat _Site _Drainage Report _Other
Utility _Redline Utility _Landscape
City of Fort Collins
PROJECT
6 a COMMENT SHEET
City of IDII Collins
Current Plannin�
DATF: February 25, 2004 TO: Building Inspection
PROJF( "h: 147-04A ATRIUM SUITES, 502 W. LAUREL PDP —
TYPE ll (LtJQ
All comments must be received by Ted Shepard no later than the staff
review meeting: R
E( ED
A, t •.
March 17, 2004 CURRENT N ANNING
Note - PLEASE identify rrorcr redlines for fidure reference
Please find attached the various codes that the Fort Collins
Building Department will enforce. The information submitted
suggests that multi -family housing will be provided. We want to
inform you that we are currently enforcing the 1998 ANSI for
accessibility and a State statute, which uses a point system to satisfy
compliant accessibility. We recommend that the designer becomes
familiar with this new method of satisfying accessibility.
Another more commonly missed component is the required fire
rated separation between units and in attic spaces. The project
designer shot.ild become aware of the benefits of sprinkling this
structure to satisfy separation requirements and that for residences
on the third floor one -hour construction may be required.
Date 03/02/04
F_ 1cr-L tt:
Plans Analyst Rick Lee
CIII:CK 11rR ? IF YOU «'IS11 TO RECEIVE, COPI[ S OF REVISIONS
Plal Site Drain ILL Repoit Other-
( )ti I ity Rc'ilinc UtilitN __Landscape c� of Port con3ns
Cite of I oil Collins
CUnl nl a It itN, Planning; and Environmental Seri'ices
13uildin and Zonia Flcpartmcnt
Codes and Standards
Amendal S/1219"
Amended 6/28/01
Ammadcd I2/I9/01(UN
Amended ft/11/117(NkC)C)
Anicudcd 10/ I 1/01 PROD Line, pre-submieal meeting
All ( onstrucl ion within the City of Fort Collins shall comply with current adopted editions of the Uniform Codes:
1997 Uniform Building. Code w/Local Amendments
1991 Uniform Mechanical Code
2000 Uniform Plumbing Code
2002 National Electrical Code
1995 Model Energy Code with amendments for residential.
Fort Collins Nonresidential Energy Code, an amended version of ASHRAE/IES 90.1-1989.
Accessible and Usable Buildings and Facilities, lCC/ANSI Al17.1-199& State Law IIB1221
Wind Load: design for 100-MPH Exposure B or 90-MPH Exposure C. If building site has flat open terrain
extending outward for mile in any full quadrant, use 100-MPHExposure C.
Dead Load: 15 PSF min.
Snow Load Live Load: 30 PSF
Seismic Zone 1
Frost Depth 30 inches
Submittals
With the exception of Single Family Dwellings.
All Projects require a
Pre -submittal Code Review Meeting
With The
City of Fort Collins Building Department.
Call 416-2747 to schedule
All submittals for review of construction documents and release of building pennit shall include:
• (I ) Completed huilding permit application per building.
• (I ) Completed application checklist for commercial and/or residential.
• (2) Complete sets of Colorado professional "Wet Stamped" plans, include site plans, engineered
foundations, architectural, structural, mechanical, electrical, and plumbing drawings.
• Completed Energy Code compliance forms.
For questions pertaining to Plan Review, please call 416-2747
For questions pertaining to /oning, please call 4162745
For questions pertaining to required Contractor licensing, please contact Delynn Coldiron at 221-6767.
t,0 • 1 `\ (970)
PROJECT
i••r� COMMENT SHEET
City of Fort Collins
Current Planning
DATE: February 25, 2004 TO: Post Office
PROJECT: 47-04A ATRIUM SUITES, 502 W. LAUREL PDP—
TYPE If (LUC)
All comments must be received by Ted Shepard no later than the staff
review meeting:
March 17, 2004
Note - PCF,ASE identif`y/ your redlines for qfi titre reference
av e c D!e C///-q/ryc c
RECEIVED
M.r.
CURRENT PLANNING
coh �C ('o1S—C
Name (please print)
CHECK IIERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
k'lat Sitc llrainagc Report __Other_
Utility - Redline Utility Landscape
FJ <
City of root Collins
Cft,
M
;�N PROJECT
�j COMMENT SHEET
City of Font Collins
Current Planning
DATE: February 25, 2004 TO: Zoning
PROJECT: #7-04A ATRIUNI SUITES, 502 W. LAUREL PDP—
TYPE II (LUC)
All comments must be received by Ted Shepard no later than the staff
review meeting:
March 17, 2004
Note - P.GEfISE Uentifyyour redlines for future reference
5ce e �UChP(Q
RE(
Ct1RIIEN7 FLANNING
P4v, 6 Q V vi aS l�, 0
it (please print)
CIIECK HERE IF YOU WISH TO RECEIVE COPIES OF Rb:VISIONS
xPlat Site Drainaoc Report _ Other
_utility Redlinc Utility /KLnndscape
6a
City of Fort Collins
PROJECT
i...� COMMENT SHEET
City of tort Collins
Current Planning
DATE: February 25, 2004 TO: Comcast
PROJECT: 47-04A ATRIUM SUITES, 502 W. LAUREL PDP —
TYPE, II (LUC)
All comments must be received by Ted Shepard no later than the staff
review meeting:
March 17, 2004
Note - 17,GfISE identify your redlines for fixture reference
Comcast Cable would like to see Utility Easements on the Plat Map for this project.
We would like at least 13 feet out side of the Road Right of Way on both Sherwood St
and Laurel St.
We would also like to have a utility easement along the alleyway.
RECEIV;cD
CURRENT F_P.NNING
Name (please print)
CIIh:CK I FIZE IF N OF WISH TO RECEIVE COPIES OF REVISIONS
Vlat �Sitc Drainage Report Other__4=)
Utility Rcdline Utility �handscape City of Fort Colons
Project Comments Sheet
Selected Departments
Department: Engineering
Date: March 2, 2004
Project: ATRIUM SUITES, 502 W. LAUREL PDP - TYPE II
All comments must be received by Ted Shepard in Current Planning, no later than
the staff review meeting:
March 17, 2004
Note - Please identify your redlines for future reference
Issue Contact: Katie Moore
Topic: General
Number: 7 Created: 3/2/2004
[3/2/04] Please see redlines for any additional comments.
Number: 23 Created: 3/2/2004
(3/2104] The sidewalk on Laurel is required to be a minimum of 6' wide. It is shown as 4' on the plans, so there are two
options for widening the walk: remove the walk and replace it with a U walk, or add 4' of concrete to the additional walk
per LCUASS (4' is the minimum width of concrete that is allowed to be added to widen a sidewalk).
Topic: Landscape Plan
Number: 8 Created: 3/2/2004
(3/2/04) Please show the utilities on the landscape plan, so that the separation requirements can be verified.
Topic: Plat
Number: 2 Created: 3/2/2004
[3/2/04] Please use the current standard plat language. (See attached.)
Number: 3 Created: 3/2/2004
[3/2/04] According to City records I found, the ROW for Sherwood should be 100', not 80'.
Number: 4 Created: 3/2/2004
(3/2/04] Please list the reception number or book and page number for the Laurel Street ROW vacation shown and
provide a width for it.
Number: 5
[3/2/04] Please fill in the title block.
Created: 3/2/2004
Number: 6 Created: 3/2/2004
[3/2/04] Please show the 15' utility easement along Laurel. It should match the utility plans.
r
SiInatare Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _-(VzSitc Drainage Report Other
Utility _Redline Utility _\,/' Landscape