DATE: =vSep e7 DEPARTMENT: �r�
ITEM: 209-79P COLLINDALE AT THE FIRST TEE PUD - Final
No Problems
L ..Problems or Concerns (see below)
h
Date,/��/'y Signature
CITY OF FORT COLLINS
COMMUNITY DEVELOPMENT DEPARTMENT, PLANNING DIVISION
M E 11 0 R A N D U M
Bob Snow
Mountain Bell -Engineering
124 W. Magnolia
Fort Collins, CO 80521
TO:
FROM: Mike Herzig, Development Coordinator
RE: Subdivision Utility Plans
DATE: September 29, 1987
Submitted for your review and comment are utility plans for:
Please respond by:
Collindale at the First Tee
Friday, October 9, 1987
1 Y ti+
OFFICE OF COMMUNITY
DEVELOPMENT, PLANNING DIVISION
N_ 1987
300 LaPorte Ave. • P.O. Box 580 • Fort Collins, Colorado 80522 • (303) 221 6750
t
i
a. /�Z
!
CITY OF FORT COLLINS
OFFICE OF DEVELOPMENT SERVICES, PLANNING DEPARTMENT
October 13, 1987
Mr. Merl Haworth
c/o Robb, Brenner, and Brelig
125 South Howes, Suite 880
P.O. Box 251
Fort Collins, CO. 80522
Dear Mr. Haworth:
The staff has reviewed the request for final PUD approval for Collindale
First Tee and offers the following comments:
1. The following note should be added to the landscape plan:
"A free (no charge) permit must be obtained from the City Forester
before any trees or shrubs as noted on this plan are planted, pruned
or removed on the public right-of-way."
2. The following comments refer to the Grading Plan of the Drainage
Report„
a. Show the proposed contours.
b. Show the proposed building footprints with F.G. and F.F. eleva-
tions.
c. Show the lot corner elevations.
d. Show the street names.
e. The backlot drainage problem has still not been addressed. How
will this issue be resolved?
3. The following comments refer to the Drainage Report:
a. Please provide drainage calculations, inlet sizing calculations,
and check the calculations on the curb capacity.
b. Provide schematic drawing of final outfall. How will flows get to
the outfall?
OFFICE OF DEVELOPMENT
SERVICES. PLANNING
300 LaPorte Ave. • P.O. Box 580 • Fort Collins, Colorado 80522 • (303) 221-6750
Page 2
c. Please show the location of the Collindale Filings that are refer-
enced in the Drainage Report.
d. Verify the capacity of all existing facilities which will carry_ the
First Tee drainage to the pond.
e. Please provide the P.E. stamp.
4. The site plan should be amended to show the sidewalk running across the
parking spaces. Also, the site plan should show the access ramps.
5. The Poudre Valley Fire Authority requests that the fire hydrant located
on Faraday Circle be moved further to the west to approximately the middle
of the block. Also, a fire hydrant should be added at the eastern corner
(near Carlton) of Faraday Circle and Alcott Street. These locations would
put a hydrant at each end to the Circle and one in the middle.
This concludes staff comments at this time. Please note that because of the
Thanksgiving holiday, the Planning and Zoning Board hearing will be on
November 16, 19,87. In order to stay on schedule for this hearing, the fol-
lowing deadlines will apply:
Plan revisions are due October 28, 1987.
PMT's, colored renderings, and 10 prints are due November 9, 1987.
Final documents are due November 12, 1987.
If there are any questions or concerns, please feel free to call.
Sincerely,
Ted Shepard
cc: Joe Frank, Assistant Planning Director
Mike Herzig, Development Coordinator
Start of Item 1.
Message. Dated: 11/06/87 at 1236.
Subject: Collindale 1st Tee
Sender: Doug MARTINE / CFC52/01 Contents: 2.
TO: Mike HERZIG / CFC52/01
Part 1.
TO: Mike HERZIB / CFC52/01
Part 2.
Upon review of the utility plans for this project, I have no comments.
What do you think of our comments to you coming via hpdesk (as long as
there are no notes we need to show on the plans)? I can do whatever works
for you - let me know. Thanks.
End of Item 1.
09:31:47
Intray >
CITY OF FORT COLLINS
COMMUNITY DEVELOPMENT DEPARTMENT, PLANNING DIVISION
MEMORANDUM
TO: Mr. Bob Snow
FROM: Mike Herzig, Development Coordinator
RE: Collindale First Tee PUD
DATE: 11.4.87
Submitted for your review and comment= The Collindale First Tee PUD
plat has been revised to eliminate the green belt on the north side.
The remaining tracts will be drainage and utility easements deeded to
the Off Site properties in the Collindale Fifth Filing. Please review
this ASAP and return comments by November loth.
Thank you for your quick response.
MDIINTAM .BELL REaUEST'S A (,n' EASEMENT -
IN THE REAZ OF LOTS /I TIf,U /7.
-
-1. ,, ,ti •re
OFFICE OF COMMUNITY