Loading...
HomeMy WebLinkAbout2114 BLUE YONDER WAY - DISCLOSURES - 9/16/2015BUILDING LEAKAGE TEST Date of Test: 9/16/2015 Test File: 2114 Blue Yonder Way Multi Point Tectite Customer: DR Horton Technician: Brad Smith - EnergyLogic Project Number: 37505 Test Results 1. Airflow at 50 Pascals: (50 Pa = 0.2 w.c.) 2. Leakage Area: 3. Building Leakage Curve: Building Address: 2114 Blue Yonder Way Fort Collins, CO 80525 1604 CFM50 (+/- 1.2 %) 2.35 ACH50 88.2 in2 LBL ELA @ 4 Pa Flow Coefficient (C) = 109.1 (+/- 27.1 %) Exponent (n) = 0.687 ( +/- 0.068 ) Correlation Coefficient = 0.99518 4. Test Settings: Test Standard: RESNET Multi -Point Test Test Mode: Depressurization 5. Accuracy Level Standard Level of Accuracy Test Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 2. Estimated Design Infiltration Rate: Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: 76.0 CFM 0.11 ACH 25.3 CFM per person Winter: 107.5 CFM Summer: 78.9 CFM 0.16 ACH 0.12 ACH Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010) Recommended Whole Bldg Rate: 55.5 CFM Base Rate: 58.0 CFM Infiltration Credit: <2.5 CFM> No Text No Text No Text