HomeMy WebLinkAbout2114 BLUE YONDER WAY - DISCLOSURES - 9/16/2015BUILDING LEAKAGE TEST
Date of Test: 9/16/2015 Test File: 2114 Blue Yonder Way Multi Point Tectite
Customer: DR Horton Technician: Brad Smith - EnergyLogic
Project Number: 37505
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building Leakage Curve:
Building Address: 2114 Blue Yonder Way
Fort Collins, CO 80525
1604 CFM50 (+/- 1.2 %)
2.35 ACH50
88.2 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 109.1 (+/- 27.1 %)
Exponent (n) = 0.687 ( +/- 0.068 )
Correlation Coefficient = 0.99518
4. Test Settings: Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
76.0 CFM
0.11 ACH
25.3 CFM per person
Winter: 107.5 CFM Summer: 78.9 CFM
0.16 ACH 0.12 ACH
Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010)
Recommended Whole Bldg Rate: 55.5 CFM
Base Rate: 58.0 CFM
Infiltration Credit: <2.5 CFM>