HomeMy WebLinkAbout2145 BLUE YONDER WAY - DISCLOSURES - 5/12/2015BUILDING LEAKAGE TEST
Date of Test: 05/12/15 Test File: 2145 Blue Yonder Wy-Multi Point Tectite
Customer: DR Horton Technician: Justin Heldenbrand
Project Number: EnergyLogic (35149)
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Area:
3. Building Leakage Curve:
Building Address: 2145 Blue Yonder Way
Fort Collins, CO 80525
1685 CFM50 (+/- 0.3 %)
2.91 ACH50
92.7 in2 LBL ELA @ 4 Pa
Flow Coefficient (C) = 111.1 (+/- 4.5 %)
Exponent (n) = 0.695 ( +/- 0.012 )
Correlation Coefficient = 0.99985
4. Test Settings: Test Standard: RESNET Multi -Point Test
Test Mode: Depressurization
5. Accuracy Level Standard Level of Accuracy Test
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
98.3 CFM
0.17 ACH
19.7 CFM per person
Winter: 184.8 CFM Summer: 116.0 CFM
0.32 ACH 0.20 ACH
Mechanical Ventilation Guideline (based on ASHRAE 62.2-2010)
Recommended Whole Bldg Rate: 72.3 CFM
Base Rate: 72.3 CFM
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 05/12/15 Test File: 2145 Blue Yonder Wy-Multi Point Tectite
Building Information Location Climate Information
Volume
34761
Surface Area
7382
Floor Area
3483
Height
20
# of Bedrooms
4
# of Occupants
5
Year of Construction
2015
Wind Shield
M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Ventilation Weather Factor
0.87
Energy Climate Factor
17.00
Heating Degree Days
6128
Cooling Degree Days
297
Design Winter Wind Speed
7.3 mph
Design Summer Wind Speed
9.4 mph
Design Winter Temp Diff
73 deg F
Design Summer Temp Diff
15 deg F
Equipment Information
Type
Manufacturer
Model
Serial Number
Custom Calibration Date
Fan
Energy Conservatory
Model 3 (110V)
-
Micromanometer
Energy Conservatory
DG700
275-7
10/31/2014
No Text
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 05/12/15 Test File: 2145 Blue Yonder Wy-Multi Point Tectite
Comments
Connection to:
Mechanicals-50pa
Garage-45pa