HomeMy WebLinkAbout4700 LADY MOON DR - DISCLOSURES - 2/20/2015City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT … D4195.01 City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 2 Architectural Testing, Inc. Building Address: 4700 Lady Moon Drive, Fort Collins Performed for: Whole Building Air Leakage Enclosure Test (Excluding Sections L,M,N,Q, & R...See Layout Appendix) Performed by: Stevens Test date: 2015-02-20 Associated Test file: ASTM 2015-02-20 1311 Building and Test Information Test file name: ASTM 2015-02-20 1311 Customer: Whole Building Air Leakage Enclosure Test (Excluding Sections L,M,N,Q, & R...See Layout Appendix) Building volume: 2,000,000 cu. Ft. Building Height (from ground to top): 32 ft. Floor Area: 125,843 sq. ft. Envelope Area: 217,962 sq. ft. Results CFM at 75 Pa: 24350 Leakage Area (EqLA) [sq. in]: 2610 Air Changes per hour ACH50: .7 Combined Test Data Results Uncertainty Air flow at STP, [CFM at 50] 24350 +/-0.7% Air change rate at 50 Pa [/h] 0.7300 +/-0.7% Flow per unit floor area at 50 [CFM/sq. ft.] 0.193 +/-0.7% Flow per unit envelope area at 50 [CFM/sq. ft.] 0.112 +/-0.7% Equivalent leakage area at 75 Pa [sq. in] 2610 +/-0.7% LBL Effective leakage area at 4 Pa [sq. in] 1520 +/-9.4% LEED Permeability at 4 Pa [sq in/ 100 sq. ft.] 0.6975 +/-9.4% City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 3 Depressurize Data Set Test Dataset Date and Time: 2015-02-20-20:25 Environmental Conditions Wind speed: 5-10 from the West Operator Location: Inside the building Initial Bias Pressure: -1.19 Pa Final Bias Pressure: -2.03 Pa Initial Temperature: indoors: 68.0 °F outdoors: 53.0 °F. Final Temperature: indoors: 65.0 °F outdoors: 52.0 °F. Test Analysis Results Uncertainty Height x Temperature difference: 448 ft °F Air leakage coefficient, Cp: 2040.9 +/- 3.9% Exponent, np: 0.58693 CFM/Paⁿ +/- 1.5963% Correlation coefficient, r 2 : 0.9998 Air flow at STP, [CFM]: 24194 CFM at 75Pa +/-0.2% Air change rate, ACH: 0.7258 air changes per hour at 50 Pa +/-0.2% Flow per unit floor area: 0.1923 CFM per sq. ft. +/-0.2% Flow per unit envelope area: 0.111 CFM per sq. ft. +/-0.2% Induced pressure [Pa] -47.7 -51.7 -55.4 -59.3 -62.6 -66.3 -70.6 -73.6 -77.4 -81.3 Total Flow [CFM] 18200 19100 19900 20800 21400 22200 23100 23700 24300 25100 Corrected Flow [CFM] 19370 20300 21130 22070 22700 23560 24530 25170 25850 26700 Error [%] 0.3% 0.0% -0.2% 0.1% -0.4% -0.1% 0.2% 0.2% -0.2% 0.2% 12 baseline pressures each taken for 10 of required 10 seconds. Static Pressure Averages: initial [Pa] ∆P01 -1.19 ∆P01- -1.19 ∆P01+ 0.00 final [Pa] ∆P02 -2.03 ∆P02- -2.03 ∆P02+ 0.00 Baseline, initial [Pa] - 1.39 - 1.39 - 1.22 - 1.20 - 0.81 - 0.83 - 1.18 - 1.19 - 1.10 City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 4 Pressurize Data Set Test Dataset Date and Time: 2015-02-20-20:53 Environmental Conditions Wind speed: 5-10 from the West Operator Location: Inside the building Initial Bias Pressure: -1.97 Pa Final Bias Pressure: -0.65 Pa Initial Temperature: indoors: 65.0 °F outdoors: 52.0 °F. Final Temperature: indoors: 63.0 °F outdoors: 51.0 °F. Test Analysis Results Uncertainty Test Date and Time: 2015-02-20-20:53 Height x Temperature difference: 400 ft °F Air leakage coefficient, Cp: 3719.6 +/- 25.3% Exponent, np: 0.45775 CFM/Paⁿ +/- 11.7902% Correlation coefficient, r 2 : 0.9897 Air flow at STP: 24468 CFM at 75 Pa +/-1.2% Air change rate: 0.7340 air changes / hour at 50 Pa +/-1.2% Flow per unit floor area: 0.1944 CFM per sq ft +/-1.2% Flow per unit envelope area: 0.112 CFM per sq ft +/-1.2% Induced pressure [Pa] 47.1 51.7 55.5 58.2 63.0 65.6 71.3 73.3 77.0 81.2 Total Flow [CFM] 20300 20700 21400 21600 22500 22900 23800 24200 24900 26000 Corrected Flow [CFM] 22400 22850 23620 23830 24750 25280 26290 26670 27460 28620 Error [%] 2.0% -0.2% -0.1% -1.3% -1.0% -0.8% -0.6% -0.4% 0.3% 2.1% Static Pressure Averages: initial [Pa] ∆P01 -1.97 ∆P01- -1.97 ∆P01+ 0.00 final [Pa] ∆P02 -0.65 ∆P02- -1.28 ∆P02+ 0.60 Baseline, initial [Pa] - 2.21 - 1.89 - 1.89 - 2.16 - 1.77 - 1.65 - 1.84 - 1.97 City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 5 Baseline, final [Pa] - 0.49 - 0.35 0.63 0.76 0.91 - 5.78 0.10 - 0.09 - 0.70 - 1.22 - 0.89 - 0.70 NOTE: ASTM E779 is often utilized with modifications to section 8.9 and 8.10 of the standard as these sections discuss the induced pressure range (10 Pa to 60 Pa) and what increments (5 Pa to 10 Pa) between induced pressure points are required for compliance. Through our testing experience, it has been determined that the lower pressures within the specified range in ASTM E779 are more susceptible to error, due to wind and stack pressure effects that commonly occur in larger structures. Additionally, project specifications typically include whole building air testing performance criteria of a measured air leakage rate at a 75 Pa (not 60 Pa) pressure differential. When testing is limited to higher pressure ranges, induced pressure increments may be less than the increments specified in ASTM E779. The lowest pressure within the induced pressure range may be constrained by weather conditions where the highest pressure within the induced pressure range is typically limited by the fan capacity brought to the site. Ideal weather conditions are difficult to achieve when testing is scheduled weeks in advance. Thus, to achieve the most accurate data and meet the required performance criteria outlined in the project specification, testing is generally limited to smaller induced pressure ranges at higher pressures both above and below the required pressure differential (75 Pa). APPENDIX A Photographs (17 Pages) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 6 Photo No. 1 Building from North West Photo No. 2 Building from North East Photo No. 3 Building from South East City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 7 Photo No. 4 Building from South West Photo No. 5 Sealed Exhausts – LEF-3 and KIT for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 6 Sealed SEF-3 Smoke Relief Vent for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 8 Photo No. 7 Sealed KEF-2 Kitchen Dishwasher Vent for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 8 HU-3 Sealed Supply Damper “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 9 Photo No. 9 HU-3 Sealed Exhaust Damper for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 10 Sealed Exhausts – LEF-6 and LEF-1 for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 10 Photo No. 11 Sealed Exhausts – LEF-6 and LEF-1 for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 12 Sealed EF-4 for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 11 Photo No. 13 AHU-2 Sealed Intake Dampers for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 14 AHU-2 Sealed Exhaust Dampers for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 12 Photo No. 15 Sealed SEF-2 Smoke Relief Vent for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 16 Sealed SEF-1 Smoke Relief Vent for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 13 Photo No. 17 Sealed MEF-1 Vent for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 18 Sealed EF-1 Vent for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 14 Photo No. 19 Sealed Exhausts – LEF-3 and LEF-2 for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 20 Sealed Exhausts – EF-3 for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 15 Photo No. 21 Sealed Exhausts – EF-4 for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 22 AHU-4 Sealed Exhaust Dampers for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 16 Photo No. 23 AHU-4 Sealed Intake Dampers for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 24 Sealed MUA-1 and KDF -1 Kitchen Hood Fan System (Side 1) for “HVAC Excluded” Default Preparation Test Condition (Main Floor) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 17 Photo No. 25 Sealed MUA-1 and KDF -1 Kitchen Hood Fan System (Side 2) for “HVAC Excluded” Default Preparation Test Condition (Main Floor) Photo No. 23 AHU-1 Sealed Intake Dampers for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 18 Photo No. 24 AHU-1 Sealed Exhaust Damper for “HVAC Excluded” Default Preparation Test Condition (Roof Top) Photo No. 25 Sealed Exhausts – EF-5 for “HVAC Excluded” Default Preparation Test Condition (Roof Top) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 19 Photo No. 26 Lower Level ER Entrance North Elevation Fan Setup at Exit Photo No. 27 Lower Level Corridor Inside Corner West Elevation Fan Setup at Exit City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 20 Photo No. 28 Lower Level West Wing West Elevation Fan Setup at Exit Photo No. 29 Lower Level Corridor South Elevation Fan Setup at Exit City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 21 Photo No. 30 Lower Level Corridor Inside Corner East Elevation Fan Setup at Exit Photo No. 31 Lower Level Corridor (Adjacent to Courtyard) Computer System Setup and APT 10% Monitoring System Setups. City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 22 APPENDIX B “HVAC EXCLUDED” Default Preparation (3 Pages) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 23 TABLE 1 Default Conditions for Building Preparation Intentional Openings Air barrier systems enclosure test (HVAC- related openings excluded) Operational enclosure test (air barrier systems and HVAC-related openings included) Doors, hatches and operable windows inside the test enclosure Open Open Fire Dampers Remain as found Remain as found Windows, doors, skylights and hatches in the bounding enclosure Closed and latched Closed and latched Windows, doors, hatches and operable windows in ancillary spaces as identified in section 10.6.3 Treat in accordance with 10.6.3 Treat in accordance with 10.6.3 Dryer doors and air handler access panels Closed and latched Closed and latched Vented combustion appliance Off, unable to fire Off, unable to fire Pilot light As found As found Chimney or outlet for vented combustion device in a separate mechanical room As found As found B-vent or other insulated chimney serving a vented combustion appliance located within the test enclosure Sealed*, ** As found Solid fuel appliances (fireplaces, wood burning stoves, pellet stoves) No fires; dampers closed; chimney sealed*, ** No fires; dampers closed Exhaust, outdoor air, make-up air fans, air handlers that serve areas inside and outside the test enclosure Off Off Clothes dryers Off Off Air intake inlet with motorized dampers Dampers closed and sealed*, ** Dampers closed City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 24 Air intake inlet with gravity dampers Sealed*, ** As found Air intake inlet with no dampers Sealed*, ** Open unless fan(s) serving inlet is operated >8000 hours per year, then sealed*, ** Exhaust or relief air outlet with motorized dampers Dampers closed and sealed*, ** Dampers closed Exhaust or relief air outlet with gravity dampers Sealed*, ** As found Exhaust or relief air outlet with no damper Sealed*, ** Open unless fan serving outlet is operated >8000 hours per year, then sealed*, ** Active or passive smoke control systems - air reliefs and intakes Sealed*, ** As found Intended powered or non-powered openings for vented shafts/stairwells Sealed*, ** As found Waste or linen handling systems and equipment Sealed*, **at rooftop chute vent opening. Rooftop chute vent – open, chute intake doors – closed, chute intake room and chute discharge room doors – closed and latched, fire dampers - left as found Clothes dryer outlets Sealed*, ** As found; sealed*, ** if dryers are not yet installed Exhaust, outdoor air or make-up air fan that runs >8000 hours per year Sealed*, ** Sealed*, ** Ductwork that serves areas inside and outside the test enclosure Sealed*, ** at supply and return Sealed*, ** at supply and return Floor drains and plumbing Traps filled Traps filled *Sealed means that an opening has been temporarily masked airtight (e.g. covered with self- adhering plastic film, taped polyethylene film or rigid board stock). **If the test result meets the passing criteria for the method used then the building is deemed to pass even if not all of the HVAC related openings were sealed during the test. City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 25 APPENDIX C Location Plans (3 Pages) City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 26 Main Floor Equipment Setup DRAFT City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 27 2 nd Floor Equipment Setup DRAFT City Of Fort Collins Certification of Compliance Building Air Leakage Test Results … EXPEDITED DRAFT …D4195.01 28 - 2.20 - 2.35 - 1.96 - 1.76 -1.25 -1.36 -1.35 Baseline, final [Pa] - 1.62 - 1.75 - 1.90 - 1.90 - 2.09 - 2.10 - 2.04 - 2.20 - 2.24 -2.21 -2.18 -2.09