HomeMy WebLinkAbout418 LINDEN ST - SPECIAL INSPECTIONS - 1/6/201514JAM 15 10100AM
AM
TESTING, ADJUSTING AND BALANCING BUREAU
THE PROFESSIONAL19 CHOICE-
NEBB Certification # 3235 JEDI Balancing, Inc. Certification#BB009025C
568 Briggs Street
P.O. Box 525
Erie, CO. 80516
Phone (720) 839-5333
Website: www.jedibalancing.co
Certified Test; Adjust; & Balance Report
Project
Address
Architect
Mechanical Engineer
Contractor
Balancing Supervisors
Date
Job Number
SB009003C
0e
SUPa I nor N0720
Not VaNd UnL r S4Pl d
o )Z bH
Block One & Encompass
418 Linden St. Fort Collins, CO 80521
AU Workshop
Integrated Mechanical
Air Comfort
Don Pittser & Greg Barnes
January 6, 2015
2014-4947
jHund N
BBDOWo3C
7� e
supervlaw 6072e
Not Va Ed UnleS Slgna
?Z:
e><o--W31/16
TABB Technician TABB Technician TABB Ii•chniciaa
N:mtr. C-rcgorY UZ rnr Name' ltahcn Romeo TARZI n asnn 0494
TABB M BB105792 rr TABB Mt BB1059S06T TABa me 6n10i9dffiT
c_....._....... tr,r.•. t�/at/2ntS $anlruion Da 12/32/2015 I EXAtrationDiOME. AW31/201
DONALD W. PrrrSER
ATION IC j
Exp.313tne
Vo 0
r�o.��ae� �esm,cau.ml
TABB Technician
N=ns Ethan Smith
T 138 ID: BB977727T
rsnLm lon Date- 12/31/201•
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 4-FCU-S-01
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
24CDX0
Unit Serial Number
X068737226
Total CFM Design
845 CFM
Design SP
0.35 in, we
Outside Air CFM Design
- CFM
Total Connected CFM
845 CFM
Starter Data
4-FCU-B-01 1 Supply Fan
Starter Manufacturer
THERMALLY PROTECED
Test Data
Total CFM Actual
925
Return Air CFM Actual
925
4-FCU-B-01 / Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
124
Motor Amps 1
2.4
4-FCU-B-01 Supply Outlet Summary
' 1•
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
4-FCU-B-01 I Supply Fan
Motor Manufacturer
U.S. ELECTRIC
Motor HP
1/5
Motor RPM
1650
Motor Frame
42Y
Motor Type
-
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
2.7
Sheave Data
4-FCU-8-01 I Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.10 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
215
156
335
109
235
Outlet-02
SD
265
121
320
109
290
Outlet-03
SD
265
100
265
109
290
Outlet-04
SD
100
70
70
110
110
Totals:
845
117 %
990
109 %
925
' NOteS 4-FCU-S-01 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE
JEDI Balancing, Inc.
0 k •', _ u
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 20144947
SYSTEM/UNIT., 4-FCU-B-02
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
24CDXO
Unit Serial Number
X06B637227
Total CFM Design
845 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
845 CFM
Starter Data
4-FCU•13-021 Supply Fan
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
895
Return Air CFM Actual
895
4-FCU-B-02 I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
119
Motor Amps 1
2.0
4-FCU-B-02 Supply Outlet Summary
•C:11 1
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Barely
Test Date: December 16, 2014
Motor Data
4-FCU-B-021 Supply Fan
Motor Manufacturer
U.S. ELECTRIC
Motor HP
115
Motor RPM
1650/
Motor Frame
42Y
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
2.7
Sheave Data
4-FCU-B-p21 Supp V Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.09 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading,
% Final
Deviatie
Final
Reading
Outlet-01
SD
365
67
245
110
400
Outlet-02
SD
240
135
325
102
245
Outlet-03
SD
240
83
200
104
250
Totals:
- 845
91 %
770
106 01
* Notes 4-FCU-B-02 16-Dec-14 Brian Birely FINALTESTING ON MED SPEED
✓EDI Balancing, Inc.
Air Dandling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 4-FCU-C-01
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
24CDXO
Unit Serial Number
X068737228
Total CFM Design
1050 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
1050 CFM
Starter Data
4-FCU-C-01 I Supply Fan
Starter Manufacturer
THERMALLY PROTECED
Test Data
Total CFM Actual
1005
Return Air CFM Actual
1005
4-FCU-C-01 I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
123
Motor Amps 1
2.5
4-FCU-C-01 Supply Outlet Summary
#3235 #BB009026C
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
4-FCU-C-01 I Supply Fan
Motor Manufacturer
U.S. ELECTRIC
Motor HP
1/5
Motor RPM
1650
Motor Frame
42Y
Motor Type
-
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
2.7
Sheave Data
4-FCU-C-01 I Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Fllter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.09 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
80
138
110
94
75
Outlet-02
SO
365
60
220
97
355
Outlet-03
SO
255
106
270
96
245
Outlet-04
SD
255
112
285
94
240
Outlet-05
SD
95
147
140
95
90
Totals:
1'050
98 %
1,025
96 %
1,D05
* Notes
4-FCU-C-01 5-Dec-14 Brian Birely FINAL TESTING ON HIGH SPEED
4-FCU-C-01 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE
✓EDI Balancing, Inc.
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 20144947
SYSTEM/UNIT., 4-FCU-C-02
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
24CDXO
Unit Serial Number
X06B737225
Total CFM Design
1050 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
1050 CFM
Starter Data
4-FCU-C-02 / SupplV Fan
Starter Manufacturer
THERMALLY PROTECED
Test Data
Total CFM Actual
1095
Return Air CFM Actual
1095
4-FCU-C-021 Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
123
Motor Amps 1
2.3
4-FCU-C-02 Supply Outlet Summary
' d r k A� p
Y"'. . Y i ram'
i
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Barely
Test Date: December 05, 2014
Motor Data
4-FCU-C-021 Supply Fan
Motor Manufacturer
U.S. ELECTRIC
Motor HP
115
Motor RPM
1650
Motor Frame
42Y
Motor Type
-
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
2.7
Sheave Data
4-FCU-C-021 Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.09 in. we
System I Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatlo
Final
Reading
Outlet-01
SD
330
79
260
109
360
Ouflet-02
SD
310
131
405
102
315
OuOet-03
SD
310
124
385
100
310
Outlet-04
SD
100
175
175
110
110
Totals :
I -
-
11050
1 117 %
1 1,225 y"
104 %
i° Notes 4-17CU-C-02 5-Dec-14 Brian Birely FINAL TESTING ON HIGH SPEED
JEDI Balancing, Inc.
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 4-FCU-D-01
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
36CDXQ
Unit Serial Number
X06B637304
Total CFM Design
1000 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
1000 CFM
Starter Data
4-FCU-D-01 I Suppiv Fan
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
1095
Return Air CFM Actual
1095
4-FCU-D-01 I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
124
MotorAmps 1
2.3
4-FCU-D-01 Supply Outlet Summary
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
4-FCU-D-01 1 Supply Fan
Motor Manufacturer
NAN-FENG
Motor HP
115
Motor RPM
1650
Motor Rated Volts
120
Motor Phase
1
Motor FL Amps
2.75
Sheave Data
4-FCU-D-01 1 Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.18 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
225
216
485
109
245
Outlet-02
SD
200
28
55
110
220
Outlet-03
SD
200
230
460
110
220
Outlet-04
SD
200
ISO
360
108
215
Outlet-05
SD
175
37
65
Ill
195
Totals :
11000
143 %
1,425
110%
1,095
* Notes
4-FCU-D-01 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED
4-FCU-D-01 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE
JEDI Balancing, Inc.
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 20144947
SYSTEAWNIT: 4-FCU-D-02
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
36CDXO
Unit Serial Number
X068637303
Total CFM Design
1000 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
1000 CFM
Starter Data
4-FCU-D-021 Supply Fan
Starter Manufacturer
THERMALLY PROTECTED
4-FCU-D-02 / Supply Fan
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
1055
Return Air CFM Actual
1055
4-FCU-D-021 Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
123
Motor Amps 1
2.5
4-FCU-D-021 Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
123
Motor Amps 1
2.5
4-FCU-D-02 Supply Outlet Summary
�C tk 1' fi s -FgE
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 16, 2014
Motor Data
4FCU-113-02 I Supply Fan
Motor Manufacturer
NAN-FENG
Motor HP
115
Motor RPM
1650
Motor Rated Volts
120
Motor Phase
1
Motor FL Amps
2.75
4-FCU-D-021 Supply Fan
Motor Manufacturer
NAN-FENG
Motor HP
1/5
Motor RPM
1650
Motor Rated Volts
120
Motor Phase
1
Motor FL Amps
2.75
Sheave Data
4-FCU-D-02 / Supply Fan
Motor Sheave Model
DIRECT DRIVE
4-FCU-D-02 I SupplV Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.23 in. we
System i Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SO
105
133
140
105
110
Outlet-02
SO
330
85
280
109
360
Outlet-03
SD
280
109
305
102
285
Outlet-04
SD
285
121
345
105
300
Totals:
I -
1,000
107 %
1,070
1 106 % ;t
1,055
* Notes 4-FCU-D-02 16-Dec-14 Brian Birely FINAL TESTING ON MED SPEED
JEDI Balancing, Inc.
3
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT M 2014-4947
SYSTEM/UNIT: 4-FCU-E-HALLWAY
AREA:
Unit Data
Unit Manufacturer
NO TAG
Unit Model Number
Unit Serial Number
-
Total CFM Design
600 CFM
Design SP
0.3 in. we
Outside Air CFM Design
75 CFM
Total Connected CFM
600 CFM
Test Data
Total CFM Actual
625
Outside Air CFM Actual
105
Return Air CFM Actual
520
OA Damper Pos
100 %
4-FCU-E-HALLWAY I4-FCU-E-HALLWAY I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
209
Motor Amps 1
0.76
4-FCU-E-HALLWAY Supply Outlet Summary
�s
l
#3235 #BB009025C
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 16, 2014
Motor Data
4-FCU-E-HALLWAY I Suooly Fan
Motor Manufacturer NAC TO MOTOR
Sheave Data
4-FCU-E-HALLWAY / Supply Fan
Motor Sheave Model DIRECT DRIVE
Test Pressures
Filter SP In NO ACCESS in. we
Filter SP Out -0.10 in. we
Fan SP In NO ACCESS in. we
Fan SP Out 0.24 in. we
System I Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
220
100
220
100
220
Outlet-02
SD
190
145
275
108
205
Outlet-03
SD
190
147
280
105
200
Totals:
I
600
129 %
775
104 a/a
I t 625
* Notes
4-FCU-E-HALLWAY / 16-Dec-14 Brian Birely NAC TO MOTOR TAG, NO INFO TAG
Supply Fan
JED/ Balancing, Inc.
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014A947
SYSTEM/UNIT: M-FCU-C
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
30CDXQ
Unit Serial Number
X068637325
Total CFM Design
1050 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
1050 CFM
Starter Data
M-FCU-C / Supply Fan
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
905
Return Air CFM Actual
905
M-FCU-C I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
118
Motor Amps 1
3.2
M-FCU-C Supply Outlet Summary
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 16, 2014
Motor Data
M-FCU-C / Supply Fan
Motor Manufacturer GENTEQ
Motor HP 1/4
Motor RPM 1625
Motor Rated Volts 115
Motor Phase 1
Motor FL Amps 3.30
Sheave Data
M-FCU-C / Supply Fan
Motor Sheave Model DIRECT DRIVE
Test Pressures
Filter SP Out ATMOSPHERE in. we
Fan SP Out 0.24 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outfet-02
SD
210
98
205
110
230
Outlet-03
SD
300
103
310
110
330
Outlet-04
SD
215
128
275
107
230
Outlet-05
SD
105
86
90
110
115
Totals :
-
-
-
830
1106 %
1 880
1 109 %
906
* Notes I M-FCU-C 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED
JED/ Balancing, Inc.
l W-
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014A947
SYSTEM/UNIT: RTU-01
AREA:
Unit Data
Total CFM Design 23000
Design SP 2.2 in. we
Outside Air CFM Design 3505
* Notes
SYSTEM/UNIT: RTU-01 /VAV-01-02
AREA:
Unit Data
VAV Address
FV1-02
Box Inlet Size
12 in
K Factor
.7
Test Data
Max Design CFM
1425 CFM
Max Actual CFM
1390 CFM
Min Design CFM
430 CFM
Min Actual CFM
435 CFM
Reheat Design CFM
930 CFM
Reheat Actual CFM
1000 CFM
RTU-01 / VAV-01-02 Supply Outlet Summary
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 16, 2014
Tested By: Brian Birely
Test Date: December 03, 2014
System I Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Devlatlo
Final
Reading
Outlet-01
SD
11.25x5.25
0.41
285
35
100
100
285
Outlet-02
SD
11.25x5.25
0.41
285
70
200
98
280
Outlet-03
SD
11.25x5.25
0.41
285
65
185
98
280
Outlet-04
SD
11.25x5.25
0.41
1 285
67
190
1 95
270
Outlet-05
sb-1
11.25x5.25
0.41
285
35
100
96
275
Totals :
-
-
1,425
54 %
775
98 %
1,390
* Notes
JEDI Balancing, Inc.
ILDI
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT M 2014-4947
SYSTEM/UNIT: RTU-01 /VAV-01-04
AREA:
Unit Data
VAV Address
VAV-1-04
Box Inlet Size
10 in
K Factor
0.8
Test Data
Max Design CFM
1020 CFM
Max Actual CFM
1030 CFM
Min Design CFM
305 CFM
Min Actual CFM
310 CFM
Reheat Design CFM
- CFM
RTU-01 / VAV-01-04 Supply Outlet Summary
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 16, 2014
System I Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
9.25x5.25
0.33
375
60
225
97
365
Outlet-02
SD
9.25x5.25
0.33
215
88
190
105
225
Outlet-03
SD
9.25x5.25
0.33
215
58
125
102
220
Outlet-04
SD
9.25x5.25
0.33
215
93
200
102
220
Totals :
1,020
73 %
740
i01 %
' 1,030
* Notes
JEDI Balancing, Inc.
O 49
'.P
W&U df^.' [J�� R �T
'g L
Date: January 19, 2015
Re: Block One Mixed Use exhaust fan airflows
It has recently come to our attention that the City of Fort Collins has taken exception with the results of
the Test and Balance report for the above mentioned project. Specifically with regards to bathroom
exhaust fans in the apartment units with final airflows that exceed the design amount.
After review of the Test and Balance report, our office takes no exception to the airflow values. Test data
indicates that all final airflows meet the requirements of the Mechanical Code for restroom exhaust and
the Fort Collins Green Code for whole dwelling unit ventilation. Additionally, power consumption of each
fan does not exceed drawing specifications. It is not anticipated that these increased airflows will create
an air balance issue within the building, nor cause an increase in energy usage based on the fact that
these are residential bathroom fans that will likely see intermittent usage.
Thank you and if you have any questions, please call our office.
Respectfully,
Aaron Uoy, P.E.
Page 1 of 1 19-Jan-2015
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 /VAV-02-02
AREA:
Unit Data
VAV Address
FV2-02
Box Inlet Size
8 in
K Factor
0.6
Test Data
Max Design CFM
560 CFM
Max Actual CFM
525 CFM
Min Design CFM
170 CFM
Min Actual CFM
180 CFM
Reheat Design CFM
370 CFM
Reheat Actual CFM
390 CFM
RTU-01 / VAV-02-02 Supply Outlet Summary
J—
M.
.l, .
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 03, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SO
9x5.25
0.32
280
57
160
95
265
Outlet-02
SO
9x5.25
0.32
280
68
190
93
260
Totals :
560
63 %
350
94 %
525
* Notes
JEDI Balancing, Inc.
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 / VAV-02-04
AREA:
Unit Data
VAV Address
VR2-04
Box Inlet Size
12 in
K Factor
.9
Test Data
Max Design CFM
1460 CFM
Max Actual CFM
1320 CFM
Min Design CFM
445 CFM
Min Actual CFM
450 CFM
Reheat Design CFM
- CFM
RTU-01 / VAV-02-04 Supply Outlet Summary
r s•
#3236 #BB009025C
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 03, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
260
92
240
110
285
Outlet-02
SD
200
63
125
75
150
Oudet-03
SD
200
80
160
93
185
Outlet-04
SD
200
70
140
78
155
Outlet-05
9x5.25
0.32
200
113
225
88
175
Outlet-06
9x5.25
0.32
200
118
235
93
185
Outlet-07
9x5.25
0.32
200
108
216
93
185
Totals :
1,460
92 %
1,340
90 %
1,320
' Notes I RTU-01 / VAV-02-04 3-Dec-14 Brian Birely NO DAMPERS ON OUTLETS 1-4
JEDI Balancing, Inc.
ROOF Top (Unit
PROJECT: BLOCK ONE & ENCOMPASS Ti
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 / VAV-02-05
AREA:
Unit Data
VAV Address
FV2-05
Box Inlet Size
10 in
K Factor
.9
Test Data
Max Design CFM
1200 CFM
Max Actual CFM
1275 CFM
Min Design CFM
360 CFM
Min Actual CFM
370 CFM
Reheat Design CFM
690 CFM
Reheat Actual CFM
690 CFM
RTU-01 / VAV-02-05 Supply Outlet Summary
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 03, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
9x5.25
0.32
240
54
130
106
255
Outlet-02
SD
9x5.25
0.32
240
63
150
108
260
Outlet-03
SD
9x5.25
0.32
240
42
100
108
260
Outlet-04
SD
9x5.25
0.32
240
56
135
104
250
Outlet-05
SD
9x5.25
0.32
240
63
150
104
250
Totals:
I-
-
-
1,200
55 %
665
106 %
1,275
* Notes
.IEDI Balancing, Inc.
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 /VAV-02-06
AREA:
Unit Data
VAV Address
VR2-06
Box Inlet Size
10 in
K Factor
.8
Test Data
Max Design CFM
1050 CFM
Max Actual CFM
990 CFM
Min Design CFM
315 CFM
Min Actual CFM
310 CFM
Reheat Design CFM
- CFM
RTU-01 / VAV-02-06 Supply Outlet Summary
10" MA
Pic
WE
#3235 #BB009026C
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 02, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
9x5.25
0.32
210
60
125
95
200
Outlet-02
SO
9x5.25
0.32
210
69
145
90
190
Outlet-03
SD
9x5.25
0.32
210
95
200
93
195
Outlet-04
SD
9x5.25
0.32
210
88
185
98
205
Outlet-05
SD
9x5.25
0.32
210
1 90
190
95
200
Totals:
I-
-
1,050
1 80 %
845
94 %
990
* Notes
JEDI Balancing, Inc.
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 20144947
SYSTEM/UNIT: RTU-01 /VAV-02-07
AREA:
Unit Data
VAV Address
FV2-07
Box Inlet Size
10 in
K Factor
.9
Test Data
Max Design CFM
920 CFM
Max Actual CFM
950 CFM
Min Design CFM
275 CFM
Min Actual CFM
280 CFM
Reheat Design CFM
475 CFM
Reheat Actual CFM
465 CFM
RTU-01 / VAV-02-07 Supply Outlet Summary
r`
#3236 #BB009025C
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 01, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
9x5.25
0.32
230
85
195
100
230
Outlet-02
SD
9x5.25
0.32
230
89
205
102
235
Outlet-03
SD
9x5.25
0.32
230
93
215
104
240
Outlet-04
SD
9x5.25
0.32
230
74
170
107
245
Totals :
-
920
85 %
785
1 103 N,
950
* Notes
JEDI Balancing, Inc.
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECTM 2014-4947
SYSTEM/UNIT: RTU-01 /VAV-02-08
AREA:
Unit Data
VAV Address
FV2-08
Box Inlet Size
12 in
K Factor
.7
Test Data
Max Design CFM
1405 CFM
Max Actual CFM
1325 CFM
Min Design CFM
420 CFM
Min Actual CFM
425 CFM
Reheat Design CFM
720 CFM
Reheat Actual CFM
740 CFM
RTU-01 / VAV-02-08 Supply Outlet Summary
�s
#3235 #BB009025C
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 01, 2014
System /Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
%Final
Deviatio
Final
Reading
Outlet-01
SD
305
98
300
98
300
Outlet-02
SD
250
14
35
92
230
Outlet-03
SD
250
22
55
90
225
Outlet- 04
SD
300
100
300
95
285
Outlet-05
SD
300
93
280
95
285
Totals:
1,405
69 %
970
94 %
1,325
Notes
JEDI Balancing, Inc.
F =i
.
t. Wn A ti
t-
R®Of Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 /VAV-02-11
AREA:
Unit Data
VAV Address
FV2-11
Box Inlet Size
10 in
K Factor
.7
Test Data
Max Design CFM
1170 CFM
Max Actual CFM
1145 CFM
Min Design CFM
350 CFM
Min Actual CFM
360 CFM
Reheat Design CFM
650 CFM
Reheat Actual CFM
675 CFM
RTU-01 / VAV-02-11 Supply Outlet Summary
i s ■ ". :ern p` ='
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 01, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
350
56
195
97
340
Outlet-02
SD
350
47
165
96
335
Outlet-03
SD
470
96
450
100
470
Totals:
I -
-
1,170
89 %
810
1 98 % .
1,145
* Notes
JEDI Balancing, Inc.
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 /VAV-02-12
AREA:
Unit Data
VAV Address
FV2-12
Box Inlet Size
12 in
K Factor
.7
Test Data
Max Design CFM
1475 CFM
Max Actual CFM
1430 CFM
Min Design CFM
445 CFM
Min Actual CFM
450 CFM
Reheat Design CFM
745 CFM
Reheat Actual CFM
755 CFM
RTU-01 / VAV-02-12 Supply Outlet Summary
ir '
#3236 #BB009025C
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 01, 2014
System I Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
295
29
85
90
265
Outlet-02
SD
295
100
295
98
290
Outlet-03
SD
295
105
310
100
295
Outlet-04
SD
295
20
60
97
285
Outlet-05
SD
295
1 115
1 340
1 100
295
Totals :
1,475
74 %
1,090
97 %
1,430
* Notes
JEDI Balancing, Inc.
ROOF Top (Unit
PROJECT: BLOCK ONE & ENCOMPASS Ti
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 / VAV-02-13
AREA:
Unit Data
VAV Address
FV2-13
Box Inlet Size
12 in
K Factor
.7
Test Data
Max Design CFM
1550 CFM
Max Actual CFM
1615 CFM
Min Design CFM
465 CFM
Min Actual CFM
475 CFM
Reheat Design CFM
915 CFM
Reheat Actual CFM
900 CFM
RTU-01 / VAV-02-13 Supply Outlet Summary
#3235 #BB009025C
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 03, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SO
275
64
175
85
235
Outlet-02
SO
275
44
120
89
245
Outlet-03
SD
250
236
590
88
220
Outlet-04
SO
250
16
40
86
215
Outlet-05
SD
250
1 22
1 55
196
490
Outlet-06
SO
250
32
80
84
210
Totals:
1,550
68 %
1,060
104 %
1,615
* Notes
RTU-01 / VAV-02-13 3-Dec-14 Brian Birely OUTLET 5 CABLE DAMPER WILL NOT CLOSE
LEFT 100%OPEN
JEDI Balancing, Inc.
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 /VAV-02-14
AREA:
Unit Data
VAV Address
FV2-14
Box Inlet Size
12 in
K Factor
.5
Test Data
Max Design CFM
865 CFM
Max Actual CFM
780 CFM
Min Design CFM
260 CFM
Min Actual CFM
270 CFM
Reheat Design CFM
460 CFM
Reheat Actual CFM
465 CFM
RTU-01 / VAV-02-14 Supply Outlet Summary
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 03, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
290
114
330
88
255
Outlet-02
SD
290
12
35
90
260
Outlet-03
SD
290
53
155
91
265
Totals:
I
870
60 %
520
90 %
780
* Notes
JEDI Balancing, Inc.
i10
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 3-FCU-A-01
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
24CDXQ
Unit Serial Number
X0613637233
Total CFM Design
700 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
700 CFM
Starter Data
3-FCU-A-01 I Supply Fan
Starter Manufacturer
THERMALLY PROTECED
Test
Data
Total CFM Actual
760
Return Air CFM Actual
760
3-FCU-A-01 I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
122
MotorAmps 1
2.2
3-FCU-A-01 Supply Outlet Summary
•SS11
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
3-FCU-A-01 I Supply Fan
Motor Manufacturer
U.S. ELECTRIC
Motor HP
115
Motor RPM
1650
Motor Frame
42Y
Motor Type
-
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
2.7
Sheave Data
3-FCU-A-01 I Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.12 in. we
System I Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatlo
Final
Reading
Outlet-01
SD
185
200
370
108
200
Oullet-02
SD
210
107
225
110
230
Outlet-03
SD
210
95
200
110
230
Outlet-04
SD
95
89
85
105
100
Totals:
700
1 126 %
1 880
109 %
780
Notes
JEDI Balancing, Inc.
N
Roof Top Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: RTU-01 /VAV-02-15
AREA:
Unit Data
VAV Address
FV2-15
Box Inlet Size
12 in
K Factor
.9
Test Data
Max Design CFM
1555 CFM
Max Actual CFM
1445 CFM
Min Design CFM
465 CFM
Min Actual CFM
470 CFM
Reheat Design CFM
765 CFM
Reheat Actual CFM
755 CFM
RTU-01 / VAV-02-15 Supply Outlet Summary
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 03, 2014
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatia
Final
Reading
Outlet-01
SD
305
38
115
90
275
Outlet-02
SD
305
ill
340
90
275
Outlet-03
SD
305
13
40
93
285
Outlet-04
SD
215
102
220
95
205
Outlet-05
SD
215
93
200
95
205
Outlet-06
SD
215
63
135
93
200
Totals :
1,560
67 %
1,050
93 %
1,445
* Notes
JEDI Balancing, Inc.
iA v .T
3
r
y
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS Ti
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 3-EF-04-01
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
165
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
Motor Amps 1 Actual
.44
* Notes
SYSTEM/UNIT: 3-EF-04-02
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
125
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
122
Motor Amps 1 Actual
.42
* Notes
rs
r
#3235 #BB009025C
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
JEDI Balancing, Inc.
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 3-EF-04-03
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
170
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
123
Motor Amps 1 Actual
.42
* Notes
SYSTEM/UNIT: 3-EF-04-04
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
180
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
Motor Amps 1 Actual
.44
* Notes
j
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
JEDI Balancing, Inc.
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014A947
SYSTEM/UNIT: 3-EF-04-05
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
180
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
122
Motor Amps 1 Actual
.40
* Notes
SYSTEM/UNIT: 3-EF-04-06
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
160
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
123
MotorAmps 1 Actual
.42
* Notes
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
JED/ Balancing, Inc.
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT. 3-EF-05-01
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
GBR80
Fan Serial Number
-
Rated CFM
69
Total SP Design
0.25 in. we
Total Connected CFM
69
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
60
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
Motor Amps 1 Actual
.17
* Notes
SYSTEM/UNIT: 3-EF-05-02
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
GBR80
Fan Serial Number
-
Rated CFM
69
Total SP Design
0.25 in. we
Total Connected CFM
69
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
90
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
MotorAmps 1 Actual
.19
* Notes
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO OFF NAME PLAT
Motor Rated Volts 120
Motor FL Amps .21
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO OFF NAME PLAT
Motor Rated Volts 120
Motor FL Amps .21
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
JEDI Balancing, Inc.
I
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 4-EF-04-01
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
170
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
Motor Amps 1 Actual
.41
* Notes
SYSTEM/UNIT: 4-EF-04-02
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
130
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
MotorAmps 1 Actual
.39
* Notes
•SCIt
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
JED/ Balancing, Inc.
c n y
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 4-EF-04-03
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
GBR80
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
100
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
Motor Amps 1 Actual
.19
* Notes
SYSTEM/UNIT: 4-EF-04-04
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
140
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
MotorAmps 1 Actual
.40
* Notes
5 ,
—.ram t
#3235 #BB009025C
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO OFF NAME PLAT
Motor Rated Volts 120
Motor FL Amps .21
Sheave Data
Motor Sheave Model DIRECT DRIVE
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO FROM NAME PL
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
JEDI Balancing, Inc.
�I��i �Y 1 � �• �: 4
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 4-EF-04-05
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
170
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
123
Motor Amps 1 Actual
.44
* Notes
SYSTEM/UNIT: 4-EF-04-06
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
124
Total SP Design
0.25 in. we
Total Connected CFM
124
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
155
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
122
MotorAmps 1 Actual
.39
* Notes
1 a •� �
- r til
#3235 #BB009025C
DATE: 1 /612015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 16, 2014
Motor Data
Motor Manufacturer ALL INFO TAKEN FROM UN
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
Tested By: Brian Birely
Test Date: December 16, 2014
Motor Data
Motor Manufacturer ALL INFO TAKEN FROM LIN
Motor Rated Volts 120
Motor Phase 1
Motor FL Amps .44
Sheave Data
Motor Sheave Model DIRECT DRIVE
✓ED1 Balancing, Inc.
> w p
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 4-EF-05-01
AREA:
Unit Data
Fan Manufacturer
DELTA
Fan Model Number
SMT130
Fan Serial Number
-
Rated CFM
69
Total SP Design
0.25 in. we
Total Connected CFM
69
Starter Data
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
175
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1 Actual
121
Motor Amps 1 Actual
.42
* Notes
�x
#3235 #BB009025C
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
Motor Manufacturer ALL INFO OFF NAME PLAT
Motor Rated Volts 120
Motor FL Amps .21
Sheave Data
Motor Sheave Model DIRECT DRIVE
JEDI Balancing, Inc.
1g p 9
aO�elgl
Fan Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 20144947
SYSTEM/UNIT: EF-03
AREA:
Unit Data
Rated CFM 840
Total SP Design 0.75 in. we
Total Connected CFM 840
Test Data
Total CFM Actual 827
EF-03 Exhaust Inlet Summary
q ,' m
-.._�--
#3235 #1313009025C
DATE: 1 /612015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 16, 2014
System / Unit
Outlet
Type
Type of
Reading
Face Area
AK
Factor
Design
Reading
Prelim
Reading
% Prelim
Deviation
Final
Reading
% Final
Deviatio
Inlet-01
ER
140
185
132
150
107
Inlet-02
ER
140
155
111
150
107
Inlet-03
ER
70
55
79
77
110
Inlet-05
ER
210
270
129
225
107
Inlet-06
ER
210
265
126
225
107
Totals :
770
930
121 %
827
107 %
* Notes I EF-03 16-Dec-14 Brian Birely OUTLET FOUR NOT INSTALLED
SYSTEM/UNIT: M-EF-05
AREA:
Unit Data
Fan Manufacturer PAINTED OVER
Rated CFM 69
Total SP Design 0.25 in. we
Total Connected CFM 69
Starter Data
Starter Manufacturer THERMALLY PROTECTED
Test Data
Total CFM Actual 90
Fan RPM Actual DIRECT DRIVE
Motor Volts 1 Actual 122
Motor Amps 1 Actual .39
* Notes
Tested By: Brian Birely
Test Date: December 16, 2014
Motor Data
Motor Manufacturer PAINTED OVER
Sheave Data
Motor Sheave Model DIRECT DRIVE
Test Pressures
Fan SP In Actual ATMOSPHERE in. we
Fan SP Out Actual NO ACCESS in. we
JEDI Balancing, Inc.
A F.� .y a
6alanong ,� 4 �`` t
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 3-FCU-A-02
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
24CDXQ
Unit Serial Number
X0613637224
Total CFM Design
700 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
700 CFM
Starter Data
3-FCU-A-021 Supply Fan
Starter Manufacturer
THERMALLY PROTECED
Test Data
Total CFM Actual
760
Return Air CFM Actual
760
3-FCU-A-021 Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
124
Motor Amps 1
2.0
3-FCU-A-02 Supply Outlet Summary
:}+
4r e4
CSI II
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
3-FCU-A-021 Supply Fan
Motor Manufacturer
U.S. ELECTRIC
Motor HP
1/5
Motor RPM
1650
Motor Frame
42Y
Motor Type
-
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
2.7
Sheave Data
3-FCU-A-021 Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.10 in. we
System / Unit
Outlet
Type
Pace Area
AK Factor
Design
Reeding
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
210
157
330
110
230
Oullet-02
SD
200
133
265
108
215
Outlet-03
SD
200
125
250
110
220
Outlet-04
SD
90
106
95
106
95
Totals :
700
1 134 %
1 940
109 %
760
* Notes
3-FCU-A-02 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED
3-FCU-A-02 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE
JEDI Balancing, Inc.
6alaiia� � -
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 20144947
SYSTEM/UNIT: 3-FCU-B-01
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
24CDXO
Unit Serlal Number
X0613637225
Total CFM Design
845 CFM
Design SP
0.35 in, we
Outside Air CFM Design
- CFM
Total Connected CFM
845 CFM
Starter Data
3-FCU-B-01 I Supply Fan
Starter Manufacturer
THERMALLY PROTECED
Test Data
Total CFM Actual
930
Return Air CFM Actual
930
3-FCU-B-01 1 Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
124
Motor Amps 1
2.4
3-FCU-B-01 Supply Outlet Summary
DATE: 1 /6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
3-FCU-B-01 I Supply Fan
Motor Manufacturer
US MOTORS
Motor HP
115
Motor RPM
1650
Motor Frame
42Y
Motor Type
-
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
2.7
Sheave Data
3-FCU-B-01 I Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.15 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SO
35
286
100
100
35
Outlet-02
SO
290
124
360
112
325
Outlet-03
SD
210
129
270
110
230
Outlet-04
SD
210
145
305
110
230
Outlet-05
SD
100
75
75
110
110
Totals,
845
131 %
1,110
110 %
930
* Notes I 3-FCU-B-01 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED
JEDI Balancing, Inc.
y
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 3-FCU-B-02
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
30CDXQ
Unit Serial Number
X06B637324
Total CFM Design
845 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
845 CFM
Starter Data
3-FCU-B-021 Supply Fan
Starter Manufacturer
THERMALLY PROTECED
Test Data
Total CFM Actual
915
Return Air CFM Actual
915
3-FCU-13-021 Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
123
Motor Amps 1
2.3
3-FCU-B-02 Supply Outlet Summary
ems)
P zM
+'
#3235 #BB009025C
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
3-FCU-13-021 Supply Fan
Motor Manufacturer
U.S. ELECTRIC
Motor HP
1/5
Motor RPM
1650
Motor Frame
42Y
Motor Type
-
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
2.7
Sheave Data
3-FCU-B-021 Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.12 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
195
115
225
110
215
Outlet-02
SD
275
125
345
109
300
Outlet-03
SD
275
82
225
107
295
Outlet-04
SD
100
200
200
105
105
Totals:
I -
845
1 118 %
1 995
1 - 108 %
915
* Notes
3-FCU-B-02 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED
3-FCU-B-02 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE
JEDI Balancing, Inc.
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 3-FCU-C-01
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
30CDXQ
Unit Serial Number
X0613637323
Total CFM Design
1050 CFM
Design SP
0.35 In. we
Outside Air CFM Design
- CFM
Total Connected CFM
1050 CFM
Starter Data
3-FCU-C-01 I Supply Fan
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
1130
Return Air CFM Actual
1130
3-FCU-C-01 I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
118
Motor Amps 1
3.2
3-FCU-C-01 Supply Outlet Summary
"T
43235 #BB009025C
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
3-FCU-C-01 I Supply Fan
Motor Manufacturer
GENTEQ
Motor HP
1/4
Motor RPM
1625
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
3.30
Sheave Data
3-FCU-C-01 I Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.12 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SO
165
109
180
109
180
Outlet-02
SD
230
96
220
109
250
Outlet-03
SD
230
146
335
107
245
Outlet-04
SD
235
128
300
106
250
Outlet-05
SO
190
124
235
108
205
Totals:
-
1,050
121 %
1,270
108 °/°
1,130
* Notes
JEDI Balancing, Inc.
Air Handling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 2014-4947
SYSTEM/UNIT: 3-FCU-C-02
AREA:
Unit Data
Unit Manufacturer
FIRST -CO
Unit Model Number
30CDXQ
Unit Serial Number
X06B637322
Total CFM Design
1050 CFM
Design SP
0.35 in. we
Outside Air CFM Design
- CFM
Total Connected CFM
1050 CFM
Starter Data
3-FCU-C-021 Supply Fan
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
1100
Return Air CFM Actual
1100
3-FCU-C-02 I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
119
Motor Amps 1
3.2
3-FCU-C-02 Supply Outlet Summary
4ir
#3235 #BB009025C
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 05, 2014
Motor Data
3-FCU-C-021 Supply Fan
Motor Manufacturer
GENTEQ
Motor HP
1/4
Motor RPM
1625
Motor Rated Volts
115
Motor Phase
1
Motor FL Amps
3.30
Sheave Data
3-FCU-C-02 / Supply Fan
Motor Sheave Model
DIRECT DRIVE
Test Pressures
Filter SP Out
ATMOSPHERE in. we
Fan SP In
NO ACCESS in. we
Fan SP Out
0.09 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SD
130
119
155
108
140
Ouflet-02
SD
400
105
420
109
435
Outlet-03
SD
260
94
245
102
265
Outlet-04
SD
260
115
300
100
260
Totals :
1,050
1 107 %
1 1,120
1 105 %
1 1,100
* (dotes
3-FCU-C-02 5-Dec-14 Brian Birely FINAL TESTING ON HIGH SPEED
3-FCU-C-02 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE
✓EDI Balancing, Inc.
Air dandling Unit
PROJECT: BLOCK ONE & ENCOMPASS TI
LOCATION: FT COLLINS, CO
PROJECT #: 20144947
SYSTEM/UNIT: 3-FCU-E-HALLWAY
AREA:
Unit Data
Unit Manufacturer
NO TAG
Total CFM Design
600 CFM
Design SP
0.3 in. we
Outside Air CFM Design
75 CFM
Total Connected CFM
600 CFM
Starter Data
3-FCU-E-HALLWAY / Supply Fan
Starter Manufacturer
THERMALLY PROTECTED
Test Data
Total CFM Actual
650
Outside Air CFM Actual
120
Return Air CFM Actual
530
OA Damper Pos
100 %
3-FCU-E-HALLWAY I Supply Fan
Fan RPM Actual
DIRECT DRIVE
Motor Volts 1
210
Motor Amps 1
.77
3-FCU-E-HALLWAY Supply Outlet Summary
.►-, r
`lA
#3235 #138009026C
DATE: 1/6/2015
CONTACT: Trevor Quain
AUTHOR:
Tested By: Brian Birely
Test Date: December 16, 2014
Motor Data
3-FCU-E-HALLWAY I Supply Fan
Motor Manufacturer NAG TO MOTOR
Sheave Data
3-FCU-E-HALLWAY I Supply Fan
Motor Sheave Model DIRECT DRIVE
Test Pressures
Filter SP In -0.10 in. we
Cool. Coll SP In NO ACCESS in. we
Cool. Coil SP Out NO ACCESS in. we
Fan SP In NO ACCESS in. we
Fan SP Out 0.21 in. we
System / Unit
Outlet
Type
Face Area
AK Factor
Design
Reading
%
Prelim
Prelim
Reading
% Final
Deviatio
Final
Reading
Outlet-01
SO
220
118
260
109
240
Outlet-02
SO
190
168
320
108
205
Outlet-03
SO
190
116
220
108
205
Totals:
-
-
-
600
133 %
600
108 % '"
650
* Notes
✓EDI Balancing, Inc.