Loading...
HomeMy WebLinkAbout418 LINDEN ST - SPECIAL INSPECTIONS - 1/6/201514JAM 15 10100AM AM TESTING, ADJUSTING AND BALANCING BUREAU THE PROFESSIONAL19 CHOICE- NEBB Certification # 3235 JEDI Balancing, Inc. Certification#BB009025C 568 Briggs Street P.O. Box 525 Erie, CO. 80516 Phone (720) 839-5333 Website: www.jedibalancing.co Certified Test; Adjust; & Balance Report Project Address Architect Mechanical Engineer Contractor Balancing Supervisors Date Job Number SB009003C 0e SUPa I nor N0720 Not VaNd UnL r S4Pl d o )Z bH Block One & Encompass 418 Linden St. Fort Collins, CO 80521 AU Workshop Integrated Mechanical Air Comfort Don Pittser & Greg Barnes January 6, 2015 2014-4947 jHund N BBDOWo3C 7� e supervlaw 6072e Not Va Ed UnleS Slgna ?Z: e><o--W31/16 TABB Technician TABB Technician TABB Ii•chniciaa N:mtr. C-rcgorY UZ rnr Name' ltahcn Romeo TARZI n asnn 0494 TABB M BB105792 rr TABB Mt BB1059S06T TABa me 6n10i9dffiT c_....._....... tr,r.•. t�/at/2ntS $anlruion Da 12/32/2015 I EXAtrationDiOME. AW31/201 DONALD W. PrrrSER ATION IC j Exp.313tne Vo 0 r�o.��ae� �esm,cau.ml TABB Technician N=ns Ethan Smith T 138 ID: BB977727T rsnLm lon Date- 12/31/201• Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 4-FCU-S-01 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 24CDX0 Unit Serial Number X068737226 Total CFM Design 845 CFM Design SP 0.35 in, we Outside Air CFM Design - CFM Total Connected CFM 845 CFM Starter Data 4-FCU-B-01 1 Supply Fan Starter Manufacturer THERMALLY PROTECED Test Data Total CFM Actual 925 Return Air CFM Actual 925 4-FCU-B-01 / Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 124 Motor Amps 1 2.4 4-FCU-B-01 Supply Outlet Summary ' 1• DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 4-FCU-B-01 I Supply Fan Motor Manufacturer U.S. ELECTRIC Motor HP 1/5 Motor RPM 1650 Motor Frame 42Y Motor Type - Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 2.7 Sheave Data 4-FCU-8-01 I Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.10 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 215 156 335 109 235 Outlet-02 SD 265 121 320 109 290 Outlet-03 SD 265 100 265 109 290 Outlet-04 SD 100 70 70 110 110 Totals: 845 117 % 990 109 % 925 ' NOteS 4-FCU-S-01 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE JEDI Balancing, Inc. 0 k •', _ u Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 20144947 SYSTEM/UNIT., 4-FCU-B-02 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 24CDXO Unit Serial Number X06B637227 Total CFM Design 845 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 845 CFM Starter Data 4-FCU•13-021 Supply Fan Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 895 Return Air CFM Actual 895 4-FCU-B-02 I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 119 Motor Amps 1 2.0 4-FCU-B-02 Supply Outlet Summary •C:11 1 DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Barely Test Date: December 16, 2014 Motor Data 4-FCU-B-021 Supply Fan Motor Manufacturer U.S. ELECTRIC Motor HP 115 Motor RPM 1650/ Motor Frame 42Y Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 2.7 Sheave Data 4-FCU-B-p21 Supp V Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.09 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading, % Final Deviatie Final Reading Outlet-01 SD 365 67 245 110 400 Outlet-02 SD 240 135 325 102 245 Outlet-03 SD 240 83 200 104 250 Totals: - 845 91 % 770 106 01 * Notes 4-FCU-B-02 16-Dec-14 Brian Birely FINALTESTING ON MED SPEED ✓EDI Balancing, Inc. Air Dandling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 4-FCU-C-01 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 24CDXO Unit Serial Number X068737228 Total CFM Design 1050 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 1050 CFM Starter Data 4-FCU-C-01 I Supply Fan Starter Manufacturer THERMALLY PROTECED Test Data Total CFM Actual 1005 Return Air CFM Actual 1005 4-FCU-C-01 I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 123 Motor Amps 1 2.5 4-FCU-C-01 Supply Outlet Summary #3235 #BB009026C DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 4-FCU-C-01 I Supply Fan Motor Manufacturer U.S. ELECTRIC Motor HP 1/5 Motor RPM 1650 Motor Frame 42Y Motor Type - Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 2.7 Sheave Data 4-FCU-C-01 I Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Fllter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.09 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 80 138 110 94 75 Outlet-02 SO 365 60 220 97 355 Outlet-03 SO 255 106 270 96 245 Outlet-04 SD 255 112 285 94 240 Outlet-05 SD 95 147 140 95 90 Totals: 1'050 98 % 1,025 96 % 1,D05 * Notes 4-FCU-C-01 5-Dec-14 Brian Birely FINAL TESTING ON HIGH SPEED 4-FCU-C-01 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE ✓EDI Balancing, Inc. Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 20144947 SYSTEM/UNIT., 4-FCU-C-02 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 24CDXO Unit Serial Number X06B737225 Total CFM Design 1050 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 1050 CFM Starter Data 4-FCU-C-02 / SupplV Fan Starter Manufacturer THERMALLY PROTECED Test Data Total CFM Actual 1095 Return Air CFM Actual 1095 4-FCU-C-021 Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 123 Motor Amps 1 2.3 4-FCU-C-02 Supply Outlet Summary ' d r k A� p Y"'. . Y i ram' i DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Barely Test Date: December 05, 2014 Motor Data 4-FCU-C-021 Supply Fan Motor Manufacturer U.S. ELECTRIC Motor HP 115 Motor RPM 1650 Motor Frame 42Y Motor Type - Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 2.7 Sheave Data 4-FCU-C-021 Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.09 in. we System I Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatlo Final Reading Outlet-01 SD 330 79 260 109 360 Ouflet-02 SD 310 131 405 102 315 OuOet-03 SD 310 124 385 100 310 Outlet-04 SD 100 175 175 110 110 Totals : I - - 11050 1 117 % 1 1,225 y" 104 % i° Notes 4-17CU-C-02 5-Dec-14 Brian Birely FINAL TESTING ON HIGH SPEED JEDI Balancing, Inc. Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 4-FCU-D-01 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 36CDXQ Unit Serial Number X06B637304 Total CFM Design 1000 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 1000 CFM Starter Data 4-FCU-D-01 I Suppiv Fan Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 1095 Return Air CFM Actual 1095 4-FCU-D-01 I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 124 MotorAmps 1 2.3 4-FCU-D-01 Supply Outlet Summary DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 4-FCU-D-01 1 Supply Fan Motor Manufacturer NAN-FENG Motor HP 115 Motor RPM 1650 Motor Rated Volts 120 Motor Phase 1 Motor FL Amps 2.75 Sheave Data 4-FCU-D-01 1 Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.18 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 225 216 485 109 245 Outlet-02 SD 200 28 55 110 220 Outlet-03 SD 200 230 460 110 220 Outlet-04 SD 200 ISO 360 108 215 Outlet-05 SD 175 37 65 Ill 195 Totals : 11000 143 % 1,425 110% 1,095 * Notes 4-FCU-D-01 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED 4-FCU-D-01 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE JEDI Balancing, Inc. Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 20144947 SYSTEAWNIT: 4-FCU-D-02 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 36CDXO Unit Serial Number X068637303 Total CFM Design 1000 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 1000 CFM Starter Data 4-FCU-D-021 Supply Fan Starter Manufacturer THERMALLY PROTECTED 4-FCU-D-02 / Supply Fan Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 1055 Return Air CFM Actual 1055 4-FCU-D-021 Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 123 Motor Amps 1 2.5 4-FCU-D-021 Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 123 Motor Amps 1 2.5 4-FCU-D-02 Supply Outlet Summary �C tk 1' fi s -FgE DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 16, 2014 Motor Data 4FCU-113-02 I Supply Fan Motor Manufacturer NAN-FENG Motor HP 115 Motor RPM 1650 Motor Rated Volts 120 Motor Phase 1 Motor FL Amps 2.75 4-FCU-D-021 Supply Fan Motor Manufacturer NAN-FENG Motor HP 1/5 Motor RPM 1650 Motor Rated Volts 120 Motor Phase 1 Motor FL Amps 2.75 Sheave Data 4-FCU-D-02 / Supply Fan Motor Sheave Model DIRECT DRIVE 4-FCU-D-02 I SupplV Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.23 in. we System i Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SO 105 133 140 105 110 Outlet-02 SO 330 85 280 109 360 Outlet-03 SD 280 109 305 102 285 Outlet-04 SD 285 121 345 105 300 Totals: I - 1,000 107 % 1,070 1 106 % ;t 1,055 * Notes 4-FCU-D-02 16-Dec-14 Brian Birely FINAL TESTING ON MED SPEED JEDI Balancing, Inc. 3 Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT M 2014-4947 SYSTEM/UNIT: 4-FCU-E-HALLWAY AREA: Unit Data Unit Manufacturer NO TAG Unit Model Number Unit Serial Number - Total CFM Design 600 CFM Design SP 0.3 in. we Outside Air CFM Design 75 CFM Total Connected CFM 600 CFM Test Data Total CFM Actual 625 Outside Air CFM Actual 105 Return Air CFM Actual 520 OA Damper Pos 100 % 4-FCU-E-HALLWAY I4-FCU-E-HALLWAY I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 209 Motor Amps 1 0.76 4-FCU-E-HALLWAY Supply Outlet Summary �s l #3235 #BB009025C DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 16, 2014 Motor Data 4-FCU-E-HALLWAY I Suooly Fan Motor Manufacturer NAC TO MOTOR Sheave Data 4-FCU-E-HALLWAY / Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP In NO ACCESS in. we Filter SP Out -0.10 in. we Fan SP In NO ACCESS in. we Fan SP Out 0.24 in. we System I Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 220 100 220 100 220 Outlet-02 SD 190 145 275 108 205 Outlet-03 SD 190 147 280 105 200 Totals: I 600 129 % 775 104 a/a I t 625 * Notes 4-FCU-E-HALLWAY / 16-Dec-14 Brian Birely NAC TO MOTOR TAG, NO INFO TAG Supply Fan JED/ Balancing, Inc. Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014A947 SYSTEM/UNIT: M-FCU-C AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 30CDXQ Unit Serial Number X068637325 Total CFM Design 1050 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 1050 CFM Starter Data M-FCU-C / Supply Fan Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 905 Return Air CFM Actual 905 M-FCU-C I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 118 Motor Amps 1 3.2 M-FCU-C Supply Outlet Summary DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 16, 2014 Motor Data M-FCU-C / Supply Fan Motor Manufacturer GENTEQ Motor HP 1/4 Motor RPM 1625 Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 3.30 Sheave Data M-FCU-C / Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP Out 0.24 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outfet-02 SD 210 98 205 110 230 Outlet-03 SD 300 103 310 110 330 Outlet-04 SD 215 128 275 107 230 Outlet-05 SD 105 86 90 110 115 Totals : - - - 830 1106 % 1 880 1 109 % 906 * Notes I M-FCU-C 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED JED/ Balancing, Inc. l W- Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014A947 SYSTEM/UNIT: RTU-01 AREA: Unit Data Total CFM Design 23000 Design SP 2.2 in. we Outside Air CFM Design 3505 * Notes SYSTEM/UNIT: RTU-01 /VAV-01-02 AREA: Unit Data VAV Address FV1-02 Box Inlet Size 12 in K Factor .7 Test Data Max Design CFM 1425 CFM Max Actual CFM 1390 CFM Min Design CFM 430 CFM Min Actual CFM 435 CFM Reheat Design CFM 930 CFM Reheat Actual CFM 1000 CFM RTU-01 / VAV-01-02 Supply Outlet Summary DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 16, 2014 Tested By: Brian Birely Test Date: December 03, 2014 System I Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Devlatlo Final Reading Outlet-01 SD 11.25x5.25 0.41 285 35 100 100 285 Outlet-02 SD 11.25x5.25 0.41 285 70 200 98 280 Outlet-03 SD 11.25x5.25 0.41 285 65 185 98 280 Outlet-04 SD 11.25x5.25 0.41 1 285 67 190 1 95 270 Outlet-05 sb-1 11.25x5.25 0.41 285 35 100 96 275 Totals : - - 1,425 54 % 775 98 % 1,390 * Notes JEDI Balancing, Inc. ILDI Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT M 2014-4947 SYSTEM/UNIT: RTU-01 /VAV-01-04 AREA: Unit Data VAV Address VAV-1-04 Box Inlet Size 10 in K Factor 0.8 Test Data Max Design CFM 1020 CFM Max Actual CFM 1030 CFM Min Design CFM 305 CFM Min Actual CFM 310 CFM Reheat Design CFM - CFM RTU-01 / VAV-01-04 Supply Outlet Summary DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 16, 2014 System I Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 9.25x5.25 0.33 375 60 225 97 365 Outlet-02 SD 9.25x5.25 0.33 215 88 190 105 225 Outlet-03 SD 9.25x5.25 0.33 215 58 125 102 220 Outlet-04 SD 9.25x5.25 0.33 215 93 200 102 220 Totals : 1,020 73 % 740 i01 % ' 1,030 * Notes JEDI Balancing, Inc. O 49 '.P W&U df^.' [J�� R �T 'g L Date: January 19, 2015 Re: Block One Mixed Use exhaust fan airflows It has recently come to our attention that the City of Fort Collins has taken exception with the results of the Test and Balance report for the above mentioned project. Specifically with regards to bathroom exhaust fans in the apartment units with final airflows that exceed the design amount. After review of the Test and Balance report, our office takes no exception to the airflow values. Test data indicates that all final airflows meet the requirements of the Mechanical Code for restroom exhaust and the Fort Collins Green Code for whole dwelling unit ventilation. Additionally, power consumption of each fan does not exceed drawing specifications. It is not anticipated that these increased airflows will create an air balance issue within the building, nor cause an increase in energy usage based on the fact that these are residential bathroom fans that will likely see intermittent usage. Thank you and if you have any questions, please call our office. Respectfully, Aaron Uoy, P.E. Page 1 of 1 19-Jan-2015 Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 /VAV-02-02 AREA: Unit Data VAV Address FV2-02 Box Inlet Size 8 in K Factor 0.6 Test Data Max Design CFM 560 CFM Max Actual CFM 525 CFM Min Design CFM 170 CFM Min Actual CFM 180 CFM Reheat Design CFM 370 CFM Reheat Actual CFM 390 CFM RTU-01 / VAV-02-02 Supply Outlet Summary J— M. .l, . DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 03, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SO 9x5.25 0.32 280 57 160 95 265 Outlet-02 SO 9x5.25 0.32 280 68 190 93 260 Totals : 560 63 % 350 94 % 525 * Notes JEDI Balancing, Inc. Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 / VAV-02-04 AREA: Unit Data VAV Address VR2-04 Box Inlet Size 12 in K Factor .9 Test Data Max Design CFM 1460 CFM Max Actual CFM 1320 CFM Min Design CFM 445 CFM Min Actual CFM 450 CFM Reheat Design CFM - CFM RTU-01 / VAV-02-04 Supply Outlet Summary r s• #3236 #BB009025C DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 03, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 260 92 240 110 285 Outlet-02 SD 200 63 125 75 150 Oudet-03 SD 200 80 160 93 185 Outlet-04 SD 200 70 140 78 155 Outlet-05 9x5.25 0.32 200 113 225 88 175 Outlet-06 9x5.25 0.32 200 118 235 93 185 Outlet-07 9x5.25 0.32 200 108 216 93 185 Totals : 1,460 92 % 1,340 90 % 1,320 ' Notes I RTU-01 / VAV-02-04 3-Dec-14 Brian Birely NO DAMPERS ON OUTLETS 1-4 JEDI Balancing, Inc. ROOF Top (Unit PROJECT: BLOCK ONE & ENCOMPASS Ti LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 / VAV-02-05 AREA: Unit Data VAV Address FV2-05 Box Inlet Size 10 in K Factor .9 Test Data Max Design CFM 1200 CFM Max Actual CFM 1275 CFM Min Design CFM 360 CFM Min Actual CFM 370 CFM Reheat Design CFM 690 CFM Reheat Actual CFM 690 CFM RTU-01 / VAV-02-05 Supply Outlet Summary DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 03, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 9x5.25 0.32 240 54 130 106 255 Outlet-02 SD 9x5.25 0.32 240 63 150 108 260 Outlet-03 SD 9x5.25 0.32 240 42 100 108 260 Outlet-04 SD 9x5.25 0.32 240 56 135 104 250 Outlet-05 SD 9x5.25 0.32 240 63 150 104 250 Totals: I- - - 1,200 55 % 665 106 % 1,275 * Notes .IEDI Balancing, Inc. Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 /VAV-02-06 AREA: Unit Data VAV Address VR2-06 Box Inlet Size 10 in K Factor .8 Test Data Max Design CFM 1050 CFM Max Actual CFM 990 CFM Min Design CFM 315 CFM Min Actual CFM 310 CFM Reheat Design CFM - CFM RTU-01 / VAV-02-06 Supply Outlet Summary 10" MA Pic WE #3235 #BB009026C DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 02, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 9x5.25 0.32 210 60 125 95 200 Outlet-02 SO 9x5.25 0.32 210 69 145 90 190 Outlet-03 SD 9x5.25 0.32 210 95 200 93 195 Outlet-04 SD 9x5.25 0.32 210 88 185 98 205 Outlet-05 SD 9x5.25 0.32 210 1 90 190 95 200 Totals: I- - 1,050 1 80 % 845 94 % 990 * Notes JEDI Balancing, Inc. Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 20144947 SYSTEM/UNIT: RTU-01 /VAV-02-07 AREA: Unit Data VAV Address FV2-07 Box Inlet Size 10 in K Factor .9 Test Data Max Design CFM 920 CFM Max Actual CFM 950 CFM Min Design CFM 275 CFM Min Actual CFM 280 CFM Reheat Design CFM 475 CFM Reheat Actual CFM 465 CFM RTU-01 / VAV-02-07 Supply Outlet Summary r` #3236 #BB009025C DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 01, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 9x5.25 0.32 230 85 195 100 230 Outlet-02 SD 9x5.25 0.32 230 89 205 102 235 Outlet-03 SD 9x5.25 0.32 230 93 215 104 240 Outlet-04 SD 9x5.25 0.32 230 74 170 107 245 Totals : - 920 85 % 785 1 103 N, 950 * Notes JEDI Balancing, Inc. Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECTM 2014-4947 SYSTEM/UNIT: RTU-01 /VAV-02-08 AREA: Unit Data VAV Address FV2-08 Box Inlet Size 12 in K Factor .7 Test Data Max Design CFM 1405 CFM Max Actual CFM 1325 CFM Min Design CFM 420 CFM Min Actual CFM 425 CFM Reheat Design CFM 720 CFM Reheat Actual CFM 740 CFM RTU-01 / VAV-02-08 Supply Outlet Summary �s #3235 #BB009025C DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 01, 2014 System /Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading %Final Deviatio Final Reading Outlet-01 SD 305 98 300 98 300 Outlet-02 SD 250 14 35 92 230 Outlet-03 SD 250 22 55 90 225 Outlet- 04 SD 300 100 300 95 285 Outlet-05 SD 300 93 280 95 285 Totals: 1,405 69 % 970 94 % 1,325 Notes JEDI Balancing, Inc. F =i . t. Wn A ti t- R®Of Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 /VAV-02-11 AREA: Unit Data VAV Address FV2-11 Box Inlet Size 10 in K Factor .7 Test Data Max Design CFM 1170 CFM Max Actual CFM 1145 CFM Min Design CFM 350 CFM Min Actual CFM 360 CFM Reheat Design CFM 650 CFM Reheat Actual CFM 675 CFM RTU-01 / VAV-02-11 Supply Outlet Summary i s ■ ". :ern p` =' DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 01, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 350 56 195 97 340 Outlet-02 SD 350 47 165 96 335 Outlet-03 SD 470 96 450 100 470 Totals: I - - 1,170 89 % 810 1 98 % . 1,145 * Notes JEDI Balancing, Inc. Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 /VAV-02-12 AREA: Unit Data VAV Address FV2-12 Box Inlet Size 12 in K Factor .7 Test Data Max Design CFM 1475 CFM Max Actual CFM 1430 CFM Min Design CFM 445 CFM Min Actual CFM 450 CFM Reheat Design CFM 745 CFM Reheat Actual CFM 755 CFM RTU-01 / VAV-02-12 Supply Outlet Summary ir ' #3236 #BB009025C DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 01, 2014 System I Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 295 29 85 90 265 Outlet-02 SD 295 100 295 98 290 Outlet-03 SD 295 105 310 100 295 Outlet-04 SD 295 20 60 97 285 Outlet-05 SD 295 1 115 1 340 1 100 295 Totals : 1,475 74 % 1,090 97 % 1,430 * Notes JEDI Balancing, Inc. ROOF Top (Unit PROJECT: BLOCK ONE & ENCOMPASS Ti LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 / VAV-02-13 AREA: Unit Data VAV Address FV2-13 Box Inlet Size 12 in K Factor .7 Test Data Max Design CFM 1550 CFM Max Actual CFM 1615 CFM Min Design CFM 465 CFM Min Actual CFM 475 CFM Reheat Design CFM 915 CFM Reheat Actual CFM 900 CFM RTU-01 / VAV-02-13 Supply Outlet Summary #3235 #BB009025C DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 03, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SO 275 64 175 85 235 Outlet-02 SO 275 44 120 89 245 Outlet-03 SD 250 236 590 88 220 Outlet-04 SO 250 16 40 86 215 Outlet-05 SD 250 1 22 1 55 196 490 Outlet-06 SO 250 32 80 84 210 Totals: 1,550 68 % 1,060 104 % 1,615 * Notes RTU-01 / VAV-02-13 3-Dec-14 Brian Birely OUTLET 5 CABLE DAMPER WILL NOT CLOSE LEFT 100%OPEN JEDI Balancing, Inc. Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 /VAV-02-14 AREA: Unit Data VAV Address FV2-14 Box Inlet Size 12 in K Factor .5 Test Data Max Design CFM 865 CFM Max Actual CFM 780 CFM Min Design CFM 260 CFM Min Actual CFM 270 CFM Reheat Design CFM 460 CFM Reheat Actual CFM 465 CFM RTU-01 / VAV-02-14 Supply Outlet Summary DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 03, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 290 114 330 88 255 Outlet-02 SD 290 12 35 90 260 Outlet-03 SD 290 53 155 91 265 Totals: I 870 60 % 520 90 % 780 * Notes JEDI Balancing, Inc. i10 Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 3-FCU-A-01 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 24CDXQ Unit Serial Number X0613637233 Total CFM Design 700 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 700 CFM Starter Data 3-FCU-A-01 I Supply Fan Starter Manufacturer THERMALLY PROTECED Test Data Total CFM Actual 760 Return Air CFM Actual 760 3-FCU-A-01 I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 122 MotorAmps 1 2.2 3-FCU-A-01 Supply Outlet Summary •SS11 DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 3-FCU-A-01 I Supply Fan Motor Manufacturer U.S. ELECTRIC Motor HP 115 Motor RPM 1650 Motor Frame 42Y Motor Type - Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 2.7 Sheave Data 3-FCU-A-01 I Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.12 in. we System I Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatlo Final Reading Outlet-01 SD 185 200 370 108 200 Oullet-02 SD 210 107 225 110 230 Outlet-03 SD 210 95 200 110 230 Outlet-04 SD 95 89 85 105 100 Totals: 700 1 126 % 1 880 109 % 780 Notes JEDI Balancing, Inc. N Roof Top Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: RTU-01 /VAV-02-15 AREA: Unit Data VAV Address FV2-15 Box Inlet Size 12 in K Factor .9 Test Data Max Design CFM 1555 CFM Max Actual CFM 1445 CFM Min Design CFM 465 CFM Min Actual CFM 470 CFM Reheat Design CFM 765 CFM Reheat Actual CFM 755 CFM RTU-01 / VAV-02-15 Supply Outlet Summary DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 03, 2014 System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatia Final Reading Outlet-01 SD 305 38 115 90 275 Outlet-02 SD 305 ill 340 90 275 Outlet-03 SD 305 13 40 93 285 Outlet-04 SD 215 102 220 95 205 Outlet-05 SD 215 93 200 95 205 Outlet-06 SD 215 63 135 93 200 Totals : 1,560 67 % 1,050 93 % 1,445 * Notes JEDI Balancing, Inc. iA v .T 3 r y Fan Unit PROJECT: BLOCK ONE & ENCOMPASS Ti LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 3-EF-04-01 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 165 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 Motor Amps 1 Actual .44 * Notes SYSTEM/UNIT: 3-EF-04-02 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 125 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 122 Motor Amps 1 Actual .42 * Notes rs r #3235 #BB009025C DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we JEDI Balancing, Inc. Fan Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 3-EF-04-03 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 170 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 123 Motor Amps 1 Actual .42 * Notes SYSTEM/UNIT: 3-EF-04-04 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 180 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 Motor Amps 1 Actual .44 * Notes j DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we JEDI Balancing, Inc. Fan Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014A947 SYSTEM/UNIT: 3-EF-04-05 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 180 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 122 Motor Amps 1 Actual .40 * Notes SYSTEM/UNIT: 3-EF-04-06 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 160 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 123 MotorAmps 1 Actual .42 * Notes DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we JED/ Balancing, Inc. Fan Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT. 3-EF-05-01 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number GBR80 Fan Serial Number - Rated CFM 69 Total SP Design 0.25 in. we Total Connected CFM 69 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 60 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 Motor Amps 1 Actual .17 * Notes SYSTEM/UNIT: 3-EF-05-02 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number GBR80 Fan Serial Number - Rated CFM 69 Total SP Design 0.25 in. we Total Connected CFM 69 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 90 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 MotorAmps 1 Actual .19 * Notes DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO OFF NAME PLAT Motor Rated Volts 120 Motor FL Amps .21 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO OFF NAME PLAT Motor Rated Volts 120 Motor FL Amps .21 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we JEDI Balancing, Inc. I Fan Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 4-EF-04-01 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 170 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 Motor Amps 1 Actual .41 * Notes SYSTEM/UNIT: 4-EF-04-02 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 130 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 MotorAmps 1 Actual .39 * Notes •SCIt DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we JED/ Balancing, Inc. c n y Fan Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 4-EF-04-03 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number GBR80 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 100 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 Motor Amps 1 Actual .19 * Notes SYSTEM/UNIT: 4-EF-04-04 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 140 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 MotorAmps 1 Actual .40 * Notes 5 , —.ram t #3235 #BB009025C DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO OFF NAME PLAT Motor Rated Volts 120 Motor FL Amps .21 Sheave Data Motor Sheave Model DIRECT DRIVE Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO FROM NAME PL Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we JEDI Balancing, Inc. �I��i �Y 1 � �• �: 4 Fan Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 4-EF-04-05 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 170 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 123 Motor Amps 1 Actual .44 * Notes SYSTEM/UNIT: 4-EF-04-06 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 124 Total SP Design 0.25 in. we Total Connected CFM 124 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 155 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 122 MotorAmps 1 Actual .39 * Notes 1 a •� � - r til #3235 #BB009025C DATE: 1 /612015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 16, 2014 Motor Data Motor Manufacturer ALL INFO TAKEN FROM UN Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we Tested By: Brian Birely Test Date: December 16, 2014 Motor Data Motor Manufacturer ALL INFO TAKEN FROM LIN Motor Rated Volts 120 Motor Phase 1 Motor FL Amps .44 Sheave Data Motor Sheave Model DIRECT DRIVE ✓ED1 Balancing, Inc. > w p Fan Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 4-EF-05-01 AREA: Unit Data Fan Manufacturer DELTA Fan Model Number SMT130 Fan Serial Number - Rated CFM 69 Total SP Design 0.25 in. we Total Connected CFM 69 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 175 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 121 Motor Amps 1 Actual .42 * Notes �x #3235 #BB009025C DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data Motor Manufacturer ALL INFO OFF NAME PLAT Motor Rated Volts 120 Motor FL Amps .21 Sheave Data Motor Sheave Model DIRECT DRIVE JEDI Balancing, Inc. 1g p 9 aO�elgl Fan Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 20144947 SYSTEM/UNIT: EF-03 AREA: Unit Data Rated CFM 840 Total SP Design 0.75 in. we Total Connected CFM 840 Test Data Total CFM Actual 827 EF-03 Exhaust Inlet Summary q ,' m -.._�-- #3235 #1313009025C DATE: 1 /612015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 16, 2014 System / Unit Outlet Type Type of Reading Face Area AK Factor Design Reading Prelim Reading % Prelim Deviation Final Reading % Final Deviatio Inlet-01 ER 140 185 132 150 107 Inlet-02 ER 140 155 111 150 107 Inlet-03 ER 70 55 79 77 110 Inlet-05 ER 210 270 129 225 107 Inlet-06 ER 210 265 126 225 107 Totals : 770 930 121 % 827 107 % * Notes I EF-03 16-Dec-14 Brian Birely OUTLET FOUR NOT INSTALLED SYSTEM/UNIT: M-EF-05 AREA: Unit Data Fan Manufacturer PAINTED OVER Rated CFM 69 Total SP Design 0.25 in. we Total Connected CFM 69 Starter Data Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 90 Fan RPM Actual DIRECT DRIVE Motor Volts 1 Actual 122 Motor Amps 1 Actual .39 * Notes Tested By: Brian Birely Test Date: December 16, 2014 Motor Data Motor Manufacturer PAINTED OVER Sheave Data Motor Sheave Model DIRECT DRIVE Test Pressures Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we JEDI Balancing, Inc. A F.� .y a 6alanong ,� 4 �`` t Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 3-FCU-A-02 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 24CDXQ Unit Serial Number X0613637224 Total CFM Design 700 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 700 CFM Starter Data 3-FCU-A-021 Supply Fan Starter Manufacturer THERMALLY PROTECED Test Data Total CFM Actual 760 Return Air CFM Actual 760 3-FCU-A-021 Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 124 Motor Amps 1 2.0 3-FCU-A-02 Supply Outlet Summary :}+ 4r e4 CSI II DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 3-FCU-A-021 Supply Fan Motor Manufacturer U.S. ELECTRIC Motor HP 1/5 Motor RPM 1650 Motor Frame 42Y Motor Type - Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 2.7 Sheave Data 3-FCU-A-021 Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.10 in. we System / Unit Outlet Type Pace Area AK Factor Design Reeding % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 210 157 330 110 230 Oullet-02 SD 200 133 265 108 215 Outlet-03 SD 200 125 250 110 220 Outlet-04 SD 90 106 95 106 95 Totals : 700 1 134 % 1 940 109 % 760 * Notes 3-FCU-A-02 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED 3-FCU-A-02 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE JEDI Balancing, Inc. 6alaiia� � - Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 20144947 SYSTEM/UNIT: 3-FCU-B-01 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 24CDXO Unit Serlal Number X0613637225 Total CFM Design 845 CFM Design SP 0.35 in, we Outside Air CFM Design - CFM Total Connected CFM 845 CFM Starter Data 3-FCU-B-01 I Supply Fan Starter Manufacturer THERMALLY PROTECED Test Data Total CFM Actual 930 Return Air CFM Actual 930 3-FCU-B-01 1 Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 124 Motor Amps 1 2.4 3-FCU-B-01 Supply Outlet Summary DATE: 1 /6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 3-FCU-B-01 I Supply Fan Motor Manufacturer US MOTORS Motor HP 115 Motor RPM 1650 Motor Frame 42Y Motor Type - Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 2.7 Sheave Data 3-FCU-B-01 I Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.15 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SO 35 286 100 100 35 Outlet-02 SO 290 124 360 112 325 Outlet-03 SD 210 129 270 110 230 Outlet-04 SD 210 145 305 110 230 Outlet-05 SD 100 75 75 110 110 Totals, 845 131 % 1,110 110 % 930 * Notes I 3-FCU-B-01 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED JEDI Balancing, Inc. y Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 3-FCU-B-02 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 30CDXQ Unit Serial Number X06B637324 Total CFM Design 845 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 845 CFM Starter Data 3-FCU-B-021 Supply Fan Starter Manufacturer THERMALLY PROTECED Test Data Total CFM Actual 915 Return Air CFM Actual 915 3-FCU-13-021 Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 123 Motor Amps 1 2.3 3-FCU-B-02 Supply Outlet Summary ems) P zM +' #3235 #BB009025C DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 3-FCU-13-021 Supply Fan Motor Manufacturer U.S. ELECTRIC Motor HP 1/5 Motor RPM 1650 Motor Frame 42Y Motor Type - Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 2.7 Sheave Data 3-FCU-B-021 Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.12 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 195 115 225 110 215 Outlet-02 SD 275 125 345 109 300 Outlet-03 SD 275 82 225 107 295 Outlet-04 SD 100 200 200 105 105 Totals: I - 845 1 118 % 1 995 1 - 108 % 915 * Notes 3-FCU-B-02 5-Dec-14 Brian Birely FINAL TESTING ON MED SPEED 3-FCU-B-02 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE JEDI Balancing, Inc. Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 3-FCU-C-01 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 30CDXQ Unit Serial Number X0613637323 Total CFM Design 1050 CFM Design SP 0.35 In. we Outside Air CFM Design - CFM Total Connected CFM 1050 CFM Starter Data 3-FCU-C-01 I Supply Fan Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 1130 Return Air CFM Actual 1130 3-FCU-C-01 I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 118 Motor Amps 1 3.2 3-FCU-C-01 Supply Outlet Summary "T 43235 #BB009025C DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 3-FCU-C-01 I Supply Fan Motor Manufacturer GENTEQ Motor HP 1/4 Motor RPM 1625 Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 3.30 Sheave Data 3-FCU-C-01 I Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.12 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SO 165 109 180 109 180 Outlet-02 SD 230 96 220 109 250 Outlet-03 SD 230 146 335 107 245 Outlet-04 SD 235 128 300 106 250 Outlet-05 SO 190 124 235 108 205 Totals: - 1,050 121 % 1,270 108 °/° 1,130 * Notes JEDI Balancing, Inc. Air Handling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 2014-4947 SYSTEM/UNIT: 3-FCU-C-02 AREA: Unit Data Unit Manufacturer FIRST -CO Unit Model Number 30CDXQ Unit Serial Number X06B637322 Total CFM Design 1050 CFM Design SP 0.35 in. we Outside Air CFM Design - CFM Total Connected CFM 1050 CFM Starter Data 3-FCU-C-021 Supply Fan Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 1100 Return Air CFM Actual 1100 3-FCU-C-02 I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 119 Motor Amps 1 3.2 3-FCU-C-02 Supply Outlet Summary 4ir #3235 #BB009025C DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 05, 2014 Motor Data 3-FCU-C-021 Supply Fan Motor Manufacturer GENTEQ Motor HP 1/4 Motor RPM 1625 Motor Rated Volts 115 Motor Phase 1 Motor FL Amps 3.30 Sheave Data 3-FCU-C-02 / Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP Out ATMOSPHERE in. we Fan SP In NO ACCESS in. we Fan SP Out 0.09 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SD 130 119 155 108 140 Ouflet-02 SD 400 105 420 109 435 Outlet-03 SD 260 94 245 102 265 Outlet-04 SD 260 115 300 100 260 Totals : 1,050 1 107 % 1 1,120 1 105 % 1 1,100 * (dotes 3-FCU-C-02 5-Dec-14 Brian Birely FINAL TESTING ON HIGH SPEED 3-FCU-C-02 / Supply Fan 5-Dec-14 Brian Birely MOTOR IS DIRECT DRIVE ✓EDI Balancing, Inc. Air dandling Unit PROJECT: BLOCK ONE & ENCOMPASS TI LOCATION: FT COLLINS, CO PROJECT #: 20144947 SYSTEM/UNIT: 3-FCU-E-HALLWAY AREA: Unit Data Unit Manufacturer NO TAG Total CFM Design 600 CFM Design SP 0.3 in. we Outside Air CFM Design 75 CFM Total Connected CFM 600 CFM Starter Data 3-FCU-E-HALLWAY / Supply Fan Starter Manufacturer THERMALLY PROTECTED Test Data Total CFM Actual 650 Outside Air CFM Actual 120 Return Air CFM Actual 530 OA Damper Pos 100 % 3-FCU-E-HALLWAY I Supply Fan Fan RPM Actual DIRECT DRIVE Motor Volts 1 210 Motor Amps 1 .77 3-FCU-E-HALLWAY Supply Outlet Summary .►-, r `lA #3235 #138009026C DATE: 1/6/2015 CONTACT: Trevor Quain AUTHOR: Tested By: Brian Birely Test Date: December 16, 2014 Motor Data 3-FCU-E-HALLWAY I Supply Fan Motor Manufacturer NAG TO MOTOR Sheave Data 3-FCU-E-HALLWAY I Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP In -0.10 in. we Cool. Coll SP In NO ACCESS in. we Cool. Coil SP Out NO ACCESS in. we Fan SP In NO ACCESS in. we Fan SP Out 0.21 in. we System / Unit Outlet Type Face Area AK Factor Design Reading % Prelim Prelim Reading % Final Deviatio Final Reading Outlet-01 SO 220 118 260 109 240 Outlet-02 SO 190 168 320 108 205 Outlet-03 SO 190 116 220 108 205 Totals: - - - 600 133 % 600 108 % '" 650 * Notes ✓EDI Balancing, Inc.