HomeMy WebLinkAbout4702 PRAIRIE VISTA DR - SPECIAL INSPECTIONS - 1/16/2012[.,E7E-_C;. EARTH ENGINEERING COMPANY, INC. January 16, 2012 The Pauls Corporation 270 St. Paul Street Denver, Colorado 80206 Attn: Mr. Landon Williams Re: Foundation Footing Observation Lot 45 — Harmony Ridge Fort Collins, Colorado EEC Project No. l 1-01-288 Mr. Williams: Earth Engineering Company, Inc. (EEC) personnel have completed the construction observation services you requested for the referenced project. Those services included an observation of the foundation footing dimensions placed for the referenced address. The results of the site observations completed by EEC personnel are included with this report. On December 27, 2011, EEC personnel observed footing foundation widths for the foundation footings for the above referenced single-family residence. The garage and crawlspace footings were approximately 16 and 36 inches wide by 10 inches thick at various locations. The basement footings were approximately 16, 22 and 36 inches wide by 10 thick at various locations. Two #4 bars were placed horizontally and continuous throughout the length of the footings. The basement pads observed were approximately 34 inches by 34 inches by 12 inches thick and 39 inches by 39 inches by 12 inches thick. Four #4 bars were in position to be placed horizontally each way in the pads. At the time of our observations, it appeared that the foundation footing dimensions and observed reinforcing steel had been placed in general accordance with the construction plans prepared by Dossey/Sudik Structural Engineers (Plan No. 6) dated October 21, 2011. F,0,_BQX 271. ,4Z8 COLOF+ADO $PRI P asg66L'o 2. FORT;GO•L.LINS GOLORADO'6Q52Z 1 �}�$; RRDO Soea9.9322 t9705' 224 I',5'2Z tFpX) 661.025,2 f7„19);442'$8-t3 (FAX) 447-9635. January 1'6, 201:1 EARTH ENGINEERING COMPANY, Ii4c. The Pauls Corporation 270 St. Paul.Street Denver, Colorado 80206 ,Attn: Mr. Landon.Williams Re: Foundation Drain and Damp Proofing;Observation Lot 45 —Harmony Ridge ,Fort Collins, Colorado EEC .Project No. I 1-01-288 Mr. Williams As requested, .Earth Engineering Company, Inc. (EEC) personnel -have completed the, construction. observation.servicesyou requested for the referenced project. Those services includedobservations of the foundation. -drain, Pplacement and: damp proofing at the referenced' address. Tlie results of those observations are; included with -this report: On January 10, 2012, EEC personnel observed :the ;foundation drain for the :referenced. project. The foundation;drain consisted of 4-inch perforated pipe overlying,a plastic liner and+bedded,in gravel around the below ,grade exterior perimeter of the: structure: The gravel was covered with filter fabric.. Various locations were spot.checked and-measured.from the top of the footing to determine(slope and the drain, appeared to slope.toward the basementsump pit. The damp proofing consisted ofa grey: spray -on ,coating that appeared wcover all exterior below,grade-living areas, of.the basement• walls. We appreciateAbe opportunity to be: of service to you on this project, If you have,'any questions regarding this report, or if we can:be of further service to:you in anyway; please do not hesitate to contact us. Very truly yours,, Earth, Engineering Company, Inc. MichaelJ. Coley, P.E. Principal Engineer cc:, IvIr.,Landon Williams '{Iandon:willianigno raulscorp coif ) P.O. BOX 27 1 428 p0. BOx, 49322: FORT COLLINS, COLORADO 80527• 1 428 COLORADO SPRINGS.;' COLORA00'80949-9322 (9.70). 224-:1522' (FAX) 663-0282' (719). 442-.6&13 (FAX) 447-9535 ,E-E,C Project4o. i i-0-11918 .January 16, 2012 Page 2 Eqvh Enginming.Copmpany, Inc. We appreciate the opportunity. to be of s6rvice.46 you on this project. If you 'have any questions .regarding 'this, rcp6il, or, it, we .can be of fnrtlietservice ,to you :in any -way",: ,please do not he§itate to'contkfus: Very truly Yours, apany, Inc. .Principal Engineer MX/41'a -cc: jL6hdbn December 19, 2011 The Pauls Corporation 270 St. Paul Street Denver, Colorado 80206 Attn: Mr. Landon Williams Re: Foundation Bearing Observation Lot 45 — Harmony Ridge Fort Collins, Colorado EEC Project No. 11-01-288 Mr. Williams: EARTH ENGINEERING COMPANY, INC. As requested, Earth Engineering Company, Inc. (EEC) personnel have completed an observation of the foundation bearing materials for footing foundations for the referenced project. The results of those observations along with site photos are included with this report. On December 16, 2011, EEC personnel observed foundation bearing materials for the foundation footings for the referenced residence. We understand the residence will be a lightly loaded wood frame structure constructed on a partial basement. At the time of our field observations, part of the building area had been excavated to approximate foundation -bearing elevation. The garage footing foundation bearing level was at a depth of approximately 4'/z feet below original grade. Reddish brown clayey sand and gravel materials with cobbles were observed at foundation bearing level at that location. The crawlspace footing foundation bearing level was at a depth of approximately 4 to 4%2feet below original grade. Reddish brown sandy to very sandy clay soils with gravel were observed at foundation bearing level at that location. The materials observed in the basement excavation area exposed generally consisted of reddish brown sandy clay soils. Calibrated hand penetrometer tests indicated that the in -situ sandy clay soils were very stiff in consistency and the sand and gravel materials were generally dense in consistency. P.O;: 6'0x;27:1.428 P.'O., Boz=4B3222 FORT COLUfNS. 'GOLORAD,O. 8052=,7- 1 428': (;OLORA00 JPt31NGS,,.L'OL6RAD0.80949r9322 t97,07 224- I,52Z (FAx) 663-0282 &T19) .442 68 1;3 tWO44;7z9635 EEC"Troject'NoA I'M-, , 288 December 19,2011 ,Page 2. '8iW.6111consolidatidii ;tests v,dree performed, on representative;,sairy.' samples o A I f I tI . i ,foundation , - bearing: -materials in .the crawioate,- and baterhent,foiindatidn beari*nW'elevations; "to deteftrihie �s*,elV-pdtpn wi th` Varidtion",in moisture content, tb,v4*- S** clay. soils .arthe cramilsp bearing 161�e'ls,showe�(t'lli*,PotdhtidI aqe anct basement for sw.ell"miz:at:Dresent:moisturciand,density conditions. The materials dbserve&iff the excavation.were genera .. 1 . ly consistent with thoseputlined. in the soils rep ar E rffi,Engi pg Cqrnp n pqeri py.j..4 c datedjulylO &,Based ng onthe nresults offhe outlined field. fesfi ':andobservations; servatibm A is ourop inion, the ui-situ' , materials; co.ul-'a'.,be, ,usqdtfor 'support ,ofibe'kpt g1rundationsafib. design 1., net allowable tofal` load soil; bearing .pressure ;of 1500" psf Care, e t should. �iikpn,110 :4vqtq , . pla6in A4yjQu4O4tionIfqoi' 6lementsajid.floor�slabs�on,areasof:fiozens ipg� ,. oil priorio i;..Onc.ret.6,v..Iacle.menit,.,, We: appreciate, , the opportunity to U of serv` � to ;you; on ibis: project; I 'hkyq- any, tqq— 'You, q 'further iservice, y in lagy, way, 4pifions regarding itW,,reppf( or i f.'we:,qan 'be, o iplease, ,do; ,not hesiiAieto,cqnt PTiqcipaj Fmgilipe.F. cc: Mr eLandon wil I Mr;Joe Willson (ioexiilson(a) aW'scorD.CO'M) LOT 45 — HARMONY RIDGE FORT COLLINS, COLORADO EEC PROJECT No. 1 1-01-288 DECEMBER2011 SWELL / CONSOLIDATION TEST RESULTS Material Description: Reddish Brown Sandy to Very Sandy Clay Sample Location: S-1 @ 4'(Crawlspace Foundation Bearing Level) Liquid Limit: -- IPlasticity Index: -- I % Passing #200: -- Beginning Moisture: 14.5% JDry Density: 98.2 pcf Ending Moisture: Swell Pressure: 800 psf 1% Swell @ 500 psf: 0.3% 10 8 6 U) 4 2 E 2 0 rdded � Idded IL -2 -4 0 0 'n -6 0 -8 -10 0.01 0.1 1 10 Load(TSF) Project: Lot 45 - Harmony Ridge Fort Collins, Colorado Project No.: 11-01-288 Date: December 2011 SWELL / CONSOLIDATION TEST RESULTS Material Description: Reddish Brown Sandy Clay Sample Location: S-2 @ 9' (Basement Foundation Bearing Level) Liquid Limit: -- IPlasticity Index: -- I % Passing #200: -- Beginning Moisture: 12.9% Dry Density: 112.0 pcf JEnding Moisture: -- Swell Pressure: < 500 psf % Swell @ 500 psf: None 10 I 8 I i cn 6 I 4 I 2 j o 2 0 c I � a r dded i IL _2 c -4 0 m a c -6 o � U ; j -10 - 0.01 0.1 1 10 Load(TSF) Project: Lot 45 - Harmony Ridge - Fort Collins, Colorado In Project No.: 11-01-288 Date: December 2011 January 16, 2012 The Pauls Corporation 270 St. Paul Street Denver, Colorado 80206 Attn: Mr. Landon Williams Re: Wall Steel Reinforcement Observation Lot 45 — Harmony Ridge 4702 Prairie Vista Drive Fort Collins, Colorado EEC Project No. 11-01-288 Mr. Williams: 2 EARTH ENGINEERING COMPANY, INC. Earth Engineering Company, Inc. (EEC) personnel have completed the construction observation services you requested for the referenced project. Those services included an observation of foundation wall reinforcement steel for the referenced residence. The results of the observations completed by EEC personnel are included with this report. On January 5, 2012, EEC personnel observed the reinforcing steel for the foundation walls for the referenced residence. The reinforcing steel observed at the garage foundation walls consisted of two 45 bars placed horizontally at the top and bottom of the walls. The reinforcing steel observed at the basement foundation walls consisted of two #5 bars placed horizontally at the top and bottom of the foundation walls. One #4 bar was placed vertically and horizontally at approximately 12 inches on -center throughout the length and height of the basement walls. Lap lengths observed were checked and appeared to meet the minimum required lengths. In addition to the reinforcing steel observed, the Uffer ground (a.k.a. concrete encased electrode) was also observed. The Uffer grounding rod consisted of a single piece of #4 rebar tied to the bottom horizontal reinforcement within the forms and extended approximately 1 foot above the foundation wall at the northwest corner area of the garage. R.Q :Box 271-.,42a R01, BPx--49322 FORT COLLINS. CpIpRADp. 6052Z"' (428; COLOFi:BAOp'^.9piijN68 ,6000RA00 80949-932!2 't970) '224-1 522 (FAX) 663,-0282' 'i719) 4'42:=68:k3 (FAX), 447>9635; EEC Project :-N6 11-01-288 wry - . I ,, 1 JaPy, 16,2012 Page 2 EiA Eu&6&ribg:Comp.any,jric, At. the,fime of our observations, it appeared, that the wall reinforcing --ing steel.had, been placed' -in general accordance with the; consiructim,planp prepared by Oosse Y.ISudik Structural, . Engineers (Plan N6,.'6)Aaied.,'O.c06beT 11, 2011 'We appreciate the oDt)o.rbj,ni.tY 19 be of service to ;you on. this project. If you have an y. questions .regarding thjsjqp 'r if 'if we.can'bepf fiuther;service t . oypu in any w4y.j please do not hesitate to contacltv.s, Very truly Yours; Earth Engi eeri, " hg Co p , _MP,44yilw: Nflchael.J. Coley,"'P.E., Principal Engineer `Mjt/iva ce: Mr., Landon Williams:(Iand6n.viilliamsO ,I)aulscom:com