Fort Collins Residential Energy Code
AIR SEALING DISCLOSURE FORM
aMWc2xm —mass
(Not applicable to E-STAR or ENERGY SCORE rated homes)
Neighborhood & Building Services
281 N. College Ave., P.O. Box 580, Fort Collins, CO 80522
Phone: 970 2216760 FAX: 970 224 6134
Job address: Unit 161, 603 Quaking Aspen, Fort Collins, CO
General contractor: Drahota
Air sealing contractor:
INSTRUCTIONS
Complete either Part A or Part B
Part A is to be signed by the air sealing contractor or representative of the general contractor.
Part B is to be signed by the blower door testing contractor or representative of the general contractor.
The "Blower Door Test Report" or equivalent documentation must be attached.
Please type or print, except for the signature.
If components vary, make multiple entries to describe them.
One copy of this form must be provided to the Building and Zoning Department prior to C. O.
One copy of this form must be provided to the original home buyer.
A. Prescriptive path (Air Sealing Checklist)
l/We certify that the air sealing requirements specified in the current City of Fort Collins Residential Energy Code
have been completed in this building, in accordance with the "Air Sealing Checklist" published by the City of Fort Collins.
Person Certifying Job:
Signature: Date:
Business Firm:
Address:
Phone:
B. Performance path (Blower Door Test)
I/We certify that this building has met the air leakage performance threshold specified in the current Fort Collins
Residential Energy Code, in accordance with the "Blower Door Test Procedures" published by the City of Fort Collins.
Testing contractor: Colorado Professional Inspections
Date of test: 08/12/2011
CFM50: Air flow through the blower door at 50 Pascals pressure difference (cfm)
Volume: 6 Volume of home (cu. ft)
ACH50: i % Air change rate per hour at 50 Pascals pressure difference
ACH50 = (CFM50 x 60) / Volume
The performance threshold for code compliance is ACH50
not exceeding 5.0 acth
Person Certifyin b: Bruce Czech
Signature: Date: 8-12-11
Business Firm: Colorado Professional Inspections
Address: 50 Weber Drive, Loveland, CO 80537
Phone: 970-430-1819
)3 s� s y
Fort Collins Residential Energy Code Neighborhood & Building Services
AIR SEALING DISCLOSURE FORM 281 N. College Ave., P.O. Box 580, Fort Collins, CO 80522.
simisaift-anew Phone: 970 2216760 FAX: 970 224 6134
(Not applicable to E-STAR or ENERGY SCORE rated homes)
Job address: Unit JOA 603 Quaking. Aspen, Fort Collins, CO
General contractor: Drahota
Air sealing contractor:
INSTRUCTIONS
Complete either Part A or Part B
Part A is to be signed by the air sealing contractor or representative of the general contractor.
Part B is to be signed, by the blower door testing contractor or representative of the general contractor
The 'Blower Door Test Report" or equivalent documentation must be attached.
Please type or print, except for the signature.
If components vary, make multiple entries to describe them.
One copy of this form must be 'provided to the Building and Zoning Department prior -to C. O.
One copy of this form must be provided to the original home buyer.
A.Prescriptive path (Air;Sealing Checklist)
Me certify that the air sealing requirements specified in the current City of Fort Collins Residential Energy Code
have been completed in this building, in accordance with the "Air Sealing, Checklist' published by the City of Fort Collins:
Person Certifying Job:
Signature:. - - Date'
Business Firm:
Address•
Phone'
$. Performance path (Blower Door Test)
[Me certify that this building has met the air leakage performance threshold specified in. the current Fort Collins
Residential Energy Code, in accordance with the "Blower Door Test Procedures" published by the City of Fort Collins.
Testing contractor:
Date of test:
CFIV150:
Volume:
ACH56:
Person
Colorado Professional Inspections
08/12/2011
-.Air flow through the blower door at 50 Pascals pressure difference (cfm)
Volume of home (cu. ft.)
Air change rate,per hour at 50 Pascals pressure difference
ACH50 = (CFM50 x 60) /Volume
The performance threshold for code compliance is ACH50
not exceeding 5.0 acth
Brace Czech
Dom;: 8-12-11
Business _Firm- _ Colorado Professional_ Inspections_ _
Address: 50 Weber Drive, Loveland, CO 80537
__ Phone: 970-430A819 -
Fort Collins Residential Energy Code
AIR SEALING DISCLOSURE FORM
aumsa2.wa — 7n0ree - -
(Not applicable to &STAR or ENERGY SCORE, rated homes)
Neighborhood &Building Services
281 N. College Ave., P.O. Box 680, Fort Collins, CO 80522
Phone: 970 2216760 FAX: 970 224 6134
Job address: Unit 103 603 Quaking Aspen, Fort Collins, CO
General contractor: Drahota
Airsealing contractor:
INSTRUCTIONS
Complete either Part A or Part B
Part A is to be signed by the air -sealing contractor or representative of the general contractor.
Part B is to be signed by the blower door testing contractor or representative lof the general contractor.
The "Blower Door Test Report" or equivalent documentation must be attached.
Please type or print; except for the signature.
If components vary, make multiple entries to describe them.
One copy of this form must be provided to the Building and Zoning Department prior to C. O.
One copy of this form must be provided to the original home buyer.
A PrescriptiveP path;iSealAir°n Checklist =
9
I/We certify that the air sealing requirements specified in the current City of Fort. Collins Residential Energy Code
have been completed in this building, in accordance with the "Air Sealing Checklist' published by the City of Fort Collins.
Person Certifying'Job:
6. Performance path (Blower Door Test
I/We certify that this building has met the air leakage performance threshold specified in the current Fort Collins
Residential Energy Code, in accordance with the "Blower Door Test Procedures" published bythe City of Fort Collins.
Testing contractor: Colorado Professional Inspections
Date of test_: 08/.12/2011
CFM50: Air flow through the blower door at 50 Pascals pressure difference (ifm)
Volume: _ _ __ Volume of home (cu. ft.)
ACH50: Air change rate per hour at 50 Pascals pressure difference
ACH50 = (CFM50 x 60) / Volume
The performance threshold for code compliance is ACH50
not exceeding 5.0 ac/h
Person Certifying Job: Bruce Czech
Signature: _ _ _ _ _ _ - - _-_ _ - _ - _ - - _ Date: 8-12-11,
Business_ Firm:Colorado Professional Inspections
Address: 50 Weber Drive, Loveland, CO 80537
Phone: 970430-1819 -
-- - - -- --- -
Fort Collins Residential Energy Code Neighborhood & Building Services
AIR SEALING DISCLOSURE_ FORM _ 281 N. College Ave.., P.O. Box 580, Fort Collins, CO 80522
8Jm -7/1Me - _ _ . Phone: 910 2216760 FAX: 970 224 6134
(Not applicable to E-STAR or ENERGY SCORE rated homes)
Job address: UnitOy , 603 Quaking Aspen, FortCollins, CO
General contractor: Drahota
Air sealing contractor:
INSTRUCTIONS
Complete either Part, A or Part B
Part A is to be signed by the air sealing Contractor or representative of the general contractor.
Part B is to be signed by the blower door testing contractor or representative of the general contractor.
The 4tlower Door Test Report" or equivalent documentation must be attached.
Please type or print, except for the signature.
If components vary, make multiple entries to describe them.
One copy of this form must be provided to the Building and Zoning Department prior to C. O.
One copy of this form must be provided to the original home buyer.
A ;Prescriptive path (Air.Sealmg Checklist).-
Me certify that the air sealing requirements specified in the current City of Fort Collins Residential Energy Code
have been completed in this building, in.6ccordance with the "Air Sealing Checklist" published by the City of Fort Collins.
Person Certifying Job:
B.Performance path Blower Door Test)
I/We certify that this building has met the air leakage performance threshold• specified in the current Fort Collins
Residential Energy Code;. in accordance with the "Blower Door Test Procedures" published by the City of Fort Collins.
Testing contractor.
Date of test:
CFMSo .
Volume:
ACH50:
Person Certifying Job:
Colorado Professional Inspections
08/12/2011
Air flow through the blower door at 50 Pascals pressure difference (cfm)
Volume of home (cu. ft.)
Air change rate per hour at 50 Pascals pressure difference
ACH50 = (CFM50 x 60) / Volume
The performance threshold for code compliance is ACH50
not exceeding 5.0 acth
8-12-1`1
Business Firm: 61orado Professional Inspections
Address: 50 Weber Drive, Loveland, CO 80537
Phone: 970-430-1819
6
Fort Collins Residential Energy Code
AIR SEALING DISCLOSURE FORM
alydISCZAs — mope
(Not applicable to E-STAR or ENERGY SCORE rated homes)
Neighborhood & Building Services
281 N. College Ave., P.O. Box 580, Fort Collins, CO 80522
Phone: 970 2216760 FAX: 970 224 6134
Job address: Unit I'05'-,603 Quaking Aspen, Fort Collins, CO
General contractor: Drahota
Air sealing contractor:
INSTRUCTIONS
Complete either Part A or Part B
Part A is to be signed by the air sealing contractor or representative of the general contractor.
Part B is to be signed by the blower door testing contractor or representative of the general contractor.
The "Blower Door Test Report" or equivalent documentation must be attached.
Please type or print, except for the signature.
If components vary, make multiple entries to describe them.
One copy of this form must be provided to the Building and Zoning Department prior to C. O.
One copy of this form must be provided to the original home buyer.
A. Prescriptive path (Air Sealing Checklist)
Me certify that the air sealing requirements specified in the current City of Fort Collins Residential Energy Code
have been completed in this building, in accordance with the "Air Sealing Checklist" published by the City of Fort Collins.
Person Certifying Job:
Signature: Date:
Business Firm:
Address:
Phone:
B. Performance path (Blower Door Test)
I/We certify that this building has met the air leakage performance threshold specified in the current Fort Collins
Residential Energy Code, in accordance with the "Blower Door Test Procedures" published by the City of Fort Collins.
Testing contractor: Colorado Professional Inspections
Date of test: 08/12/2011
CFM50: 47 S y Air flow through the blower door at 50 Pascals pressure difference (cfm)
Volume: 6 el 01 Volume of home (cu. ft.)
—T
ACH50: y, g� S Air change rate per hour at 50 Pascals pressure difference
ACH50 = (CFM50 x 60) / Volume
The performance threshold for code compliance is ACH50
not exceeding 5.0 acth
Person Certifying Job: Bruce Lech
Signature: Date: 8-12-11
Business Firm: olorado Professional Inspections
Address: 50 Weber Drive, Loveland, CO 80537
Phone: 970-430-1819
Fort Collins Residential Energy Code Neighborhood & Building Services
AIR SEALING DISCLOSURE_ FORM 281 N. College Ave., P.O. Box 580, Fort Collins, Co 80522
e1miW2.w -?M01 a Phone: 970 2216760 FAK 970 224 6134
(Not applicable to E-STAR or ENERGY SCORE rated homes)
Job address: Unit /06, 603 Quaking Aspen, Fort Collins, CO
General contractor: Drahota
Air sealing contractor,
INSTRUCTIONS
Complete either Part A or Part B
Part A is to be signed by the air sealing contractor or representative of the general contractor.
Part B is to be signed by the blower door testing contractor or representative of the general contractor.
The "Blower Door Test Report" or equivalent documentation must be attached.
Please type or print, except for the signature.
If components vary, make multiple entries to describe them.
One copy of this form must be provided to the .Building and Zoning Department prior to C. O.
One copy of this form must be provided to the original home buyer.
A.Prescriptive path ;(Air Sealing :Checklist)
Me certify that the air sealing requirements specified in the current City of Fort Collins Residentia[ Energy Code
have been completed in this. building, in accordance with the "Air Sealing Checklist" published by the City of Fort Collins.
Person Certifying Job:
B. Performance path (blower Door Test)
IMe certify that this building has met the air leakage performance threshold specified in the current Fort Collins
Residential Energy Code, in accordance with the "Blower Door Test Procedures" published by the City of Fort Collins.
Testing contractor: Colorado Professional Inspections
Date of test: 08/12/2011
t
CFM50: Airflow through the blower door at 50 Pascals pressure difference (dm)
Volume: Volume of home (cu. ft.)
ACH50 Yr �.Z— Air change rate per hour at 50 Pascals pressure difference
- - ACH50 = (CFM50 x 60) / Volume
The performance threshold for code compliance is ACH50
not exceeding 5.0 adh
Person Certifying Job: Bruce Czech
Signature: _ - _ _ _ _ Date: 8-12-11
Address- 50 Weber Drive, Loveland, CO 80537
Phone: 970-430-1819
Fort Collins Residential Energy Code
AIR SEALING: DISCLOSURE FORM
aud1W2-* - 7n 0=
(Not applicable to E-STAR or ENERGY SCORE rated homes)
�/00�6 sy
Neighborhood & Building Services
281 N. College Ave., P.O. Box 580, Fort Collins, CO 80522
Phone: 970 2216760 FAX: 970,224 6134
Doti address: Unit /07, 603 Quaking Aspen, Fort Collins, CO
General contractor: Drahota
Air sealing contractor:
INSTRUCTIONS
Complete either Part A or Part B
Part A is to be signed by the air sealing contractor or representative of the general contractor.
Part B is to be signed by the blower door testing contractor or representative of the general contractor.
The "Blower Door Test Reportor equivalent documentation must be attached.
Please type or print, except for the signature..
If components vary, make multiple entries to describe them.
One copy of this form must be provided to the Building and Zoning Department prior to C. O.
One copy of this form must be provided to the original home buyer.
A. Prescriptive path (Air Sealing :Checklist)
Me certify that the air sealing requirements specified in the current City of Fort Collins Residential Energy Code
have been completed in this building, in accordance with the "Air Sealing Checklist",published by the City of Fort Collins.
Person Certifying Job:
B..Peforrnance path (Blower Door Test) - -
I/We certify that this building has met the air leakage performance threshold specified in the current Fort Collins
Residential Energy Code, in accordance with the "Blower Door Test Procedures" published by the City of Fort Collins.
Testing contractor: Colorado Professional Inspections
Date of test 08/12/2011
CFM50 Air flow through the blower door at 50 Pascals pressure difference (cfm)
Volume: Volume of home (cu. ft.)
ACH50: yr �% Air change rate per hour at 50 Pascals pressure difference
ACH50 = (CFM50 x 60) / Volume
The performance threshold for code compliance.is ACH50
not exceeding 5.0 acth
Person Certifying Job: race Czech
Si nature: Date: 8-12=11
Business Firm: Colorado Professional Inspections
Address:50 Weber -Drive, Loveland, CO 80537
Phone: 970-430-1819
Fort Collins Residential Energy Code Neighborhood & Building Services
AIR SEALING DISCLOSURE FORM 281 N. College Ave., P.O. Box 580, Fort Collins, CO 80522.
ellduzbs-7/1aMS Phone: 970 2216760 FAX`.- 970 224 6134
(Not applicable to E-STAR or ENERGY SCORE rated homes)
Job address: Unit /0A03 Quaking Aspen, Fort Collins, CO
General contractor: Drahota
Air sealing contractor:
INSTRUCTIONS
Complete either Part A or Part B
Part A is to be signed by the air sealing contractor or representative of the general contractor.
Part B is to be signed by the blower door testing contractor or representative of the general contractor..
The "Blower Door Test Report" or equivalent documentation must be attached.
Please type or print, except for the signature.
If components vary, make multiple entries to describe them.
One copy of this form must be provided to the Building and Zoning Department prior to C. O:.
One copy of this form must be provided to the original home buyer.
A. Prescci tive path Air Sealing Checklist
INVe certify that the air sealing requirements specified in the current City of Fort Collins Residential Energy Code
have been completed in this building, in accordance with the "Air Sealing Checklist" published by the City of Fort Collins.
Person Certifying Job:
Signature: Date:
Business Firm,
Address:
Phone:
6. Performance ormance pa (BlowerDoor Test
IMe certify that this building has met the air leakage performance threshold specified in the current Fort Collins
Residential Energy Code, in accordance with the "Blower Door Test Procedures" published by the City of Fort Collins.
Testing contractor: Colorado Professional Inspections
Date of test: 08/12/2011
C1FM50:Air flow through the blower door at 50 Pascals pressure difference (cfm)
Volume: 9
--
_ Volume of home (cu. ft.)
ACH50: Air change rate per hour at 50 Pascals pressure difference
ACH50 = (CFM50 x 60) / Volume
The performance threshold for code compliance is ACH50
not exceeding 5.0 ac/h
Person Certifying Job: Bruce Czech
Signature: Date: 8-12-11
Business Firm: Colorado Professional Inspections
Address: 50 Weber Drive, Loveland, CO 80537
Phone: 970-430-1819