HomeMy WebLinkAbout626 QUAKING ASPEN DR - SPECIAL INSPECTIONS - 6/28/2011tili"A��' P yam/ pa°°aJq 3"h TEP t �a 11 r = n l i i;h4* CA , iLC To: Marc Rohloff Air Comfort, Inc. Date: June 17, 2011 Re: Provincetowne Care Housing/oos39� Air Balance Report — FUR-CC1 We have reviewed the test and balance report for the building dated 6-14-2011. Our understanding is that the airflow on furnace FUR-CC1 is approximately 87% of the value scheduled on the drawings. We have reviewed our load calculations further as well as re-evaluated equipment supply air leaving air temperatures, and it appears that the current actual supply airflow rate of 1400 cfm will be acceptable for conditioning of these spaces. Thank you and if you have any questions, please call our office. Respectfully, Shannon Campbell Professional Engineer L-09-046-Letter-Air Balance 11-06-17 Page 1 of 1 6/17/2011 uivilrN Sl', SUI )T 2O4, F0.13; Cli.0 INQ ^ , 24 To: Marc Rohloff Air Comfort, Inc. �/ao 539� Date:. June IT 2011 N Re: Provincetowne Care Housing Air Balance Report — FUR-CC1 I r We have reviewed the test and balance report for the building dated 6-,14-N11. Our understanding is " that the airflow on furnace FUR-CC1 is approximately 87% of the value scheduled on the drawings. We. have reviewed our load calculations further as well as re-evaluated equipment. supply air leaving air temperatures, and it appears that the current actual supply airflow rate of 1400 cfm will be acceptable for conditioning of these spaces. Thank you and if you have any questions, please call our office.. Respectfully, J p Shannon Campbellp✓ G Professional Engineer I L49-046-Letter-Air Balance 11-06-17 Page 1 of 1 6/17/2011 P. �"� �� . • �.�-�� as � � , � � . _ _ : d � i r%%ii* 3"4. SCiIT204, 13140011 iVIE� rrx rl_724 P Unii `Data UnitManufaetwer Payne :unit Model Number PG9MM0600080ABSA..; Untt Serial Number 4808A02222 -CC. i Fan" an Type `Forward Curve 'Fan.3tze 11,1/2" rD Fan Arrangement DWDI, , Fan Qlsoharge Hori ontaI FUR-CC1 l SF Enter Bank Fliter, Manufacturer ." , AAF FllterType, Pleated 911ter Cuantity 1 Filter Size,20x25x1 . Stariel Dad'_ -. FUR-CC1 I SU61310 Fan installedTheniat; internal. Test Da Total'CFM Design 1600 CFM Cool. Coll SP In 0.24 in..wc -Cool. Coil SP Out 0.12 in. we Fan SP In -0.8 in: we Fan SP Out 0.24-Im we Fin. Filter'SP In -0.54 in. we Fin. Filter SP Out -0.8 in: we OA Damper Poo 50 % . RA DamperPos 100'% Actual E.S.P. 0.60 in. we Total t:FM Actual, . .1399 CAM „ OA CFM Design,,. 70 / OA CFIH'Actual 180 CFM /V FUR=CC1 / Suooly Fan ;: ,. 'Fan RPM Aotual HIGH RPM MotorYoJta 1 -122 Volts MatdeAniog 1. 10.4 Amps FUR-CC9 Supply uddt'Summary 01orri i Unit ; - ' Served Outlet Size L*W / R _ AK tAaxlmum Prolht► Maidmuip "7oPrellm %Final{ TYP@ `Factor Resign Reading. Final DeYiation` -Deviation' Outlet-01 Lobby D-7-144 6x14 250 272 211 109 84 0utlet-02 ,,, Lobby. D-7-14x6 6x14 250 261 228 1`64 91 Outlet-03 Computer D-5-12 24x24 470 378 421 80 : 90 Lab . ' _ Outlet-04 , . Kitchen.," D-5 12 24x24 400 277 341 69 85 Outlet-05 Office 1 D-8-10 24x24.: 230 222 198 97 86 8814 87 %a NO10+S 2-Juni1 KeithFinn.. . Maximum obtained airflow. Unit is direct drive on high speed. F..UR-CC1 2- tun=11, Keith Finn Motor access not svdable:due to installation. LH Finn ahjAa, dates kRNN - w • UtiifData . Uhlt.Manufaeturer Payne - Unit"MOdel Number. ' ' . ,.: OWMAt IJ600080ACSA Unit Serial Num6er "3110A03326 FUR-CC21 Suooly Fan Pan Type Forward Curve Fan Size 11 1/2" ID Fan Class • 1 Fan Arrangement DV11DI . „Fan.Dlseharge Horizontal Y. FEUR-CC2:/_SF(F(Iter Bank .,,FilterManufactur"er Filter Type Pleated - f i erQuarrtlty :. .• 1 Filter Stze 20x25x1. $tarter -Data . . 77 jFU&9C21SunIvFan Installed Thermal Intemal I • '%sf Qata' �" Total CFM Design 1600 CFM Total CFM Actual. 1610 CFM OA CFM Design,' 320 CFM OA CFM Actual : _ 300 CFM FUR-CC2 ► Subbly Fan RPM Actual ' HIGH RP1VI Motor Volts 1 122 Volts . Motor 1 10.7 Am s p FUR-CC2 Supply 6110ft Summary System/unit ; An3eSeryed O.utlat. SIza,L►ctN1D AK °: Maximum i'relim._. Maxifrrium °W14611m- °k,Flnal. - . Type Fectpr , Design .AR Tdtno Final-. R`eyiatipn, . D_eWatio-ri Outlet-01. - Conference D-6-10 24x24 255 348 232 136 91 Room . Outlet-02. Conference. , D-6-10 24x24 255 350 246 137 96 - _ .Room _ - Outlet-0.3, C:onfererice' D-6-10' 24x24 295 250 278, 85 94 Room Outlet-04 Conference D-6-10 24x24 295 213 .274' 72 93 OuOet-05_ Office3: ;' ': D-6.12 24x24 330 246 317 75 86 Outlet-06 . Office 2- D-6-8 24x24 170 181 163 -- - 106 96 717 Totals , •; - 1,6110 .: 1,588 too99` - 14 °Ie *' NOtBS FUR-CC2: 2-Jun-11 Keith Finn Motor access not available due to installation. • '` LH. Finn aridAssgciaies LHFINN -- ... Unit -Data' . FanManufacturer Penn - Fan Model Number. Z6H Fao'Serial Number -- 611V&63242 Fan:Type Forward Curve Fan Size .. 5.. Fan Gass 1 _. Fan -Arrangement DWDI :Fan Dlschaige Horizontal , ;: Starter Data Installed Thermal Internal -' .. Tsst'Data Total`CFM Design 15Q CFM Total CFM Actual ::=,186 CFM Motor'Votta 1, . _ I2 62 lts Amps 1'. In 1.5AMps , SPo Actual .. 0.0 In. we 0 Out Actual - NM in. we ' NOtes EF-CC1 .. 3-Jun-11 Keith Finn Lowest Obtainable Airflow. Unit Is direct drive with no speed control. p. LH..A' andAssacfates . LHRAIN � ,._. J ' J� lSe �J 2. Lawrence H Finn, & .Associates,' Inc. Ngl R 2389 Fan Unit PROJECT Provincetowne Cane Housing DATE 6114/2011. . LOCATION Fdit'Cpllins, CO CONTACT:. SYSTEIOU M i! -CC2 - Teste d By: Keith AREA` Test Date. Jun e 03, 2011 -t. Unit n 'pate Motor Data s Fan Manufacturer MPenn� _ Motor Manufacturer A.0 Smith, Fan'Model Number Z6H 'Motor HP 0.027 HP ` Fenserlal Numlier B114%11Z63256 Motor RPM 105N1550 RPM - Fan;Type Forward Curve Motor Rated Volts 115 Vohs Fan size 5 Motor Phase 1 Fan Class 1 Motor Hertz 60 Hz . Fan Arrangement DINDI Motor FL Amps 0.6/1.4 Amps Fan Discharge Horizontal �tattesData �: ; � . _ "...�____: _ _•. _ . _ _. _- . _ _ � _ -- .:: - � .Motor Sheave Make — Direct Drive Installed Thermal Internal Tea#;Data ' Total CFM.Dealgn 150 CFM Tota4CFM Actual` 198 CFM . Motor Volg 1 123 Volts Motor Amps 1 1.5 Amps SPi t Actual" 0.0 in. we, SP Out Actual. NM in. wo " NOteS, EF-CC2 3,Jun-11 Keith Finn Lowest Obtainable Airflow. Unit is direct drive with no speed control . . L.H. Finn andAsso ales _.....: LHF/NN Fan•Manufactu►er Penn Fan Model Number- ZT Fan Serial Numtier B11XZ14816 Fan Type . , . Forward Curve Fan Size" 5 Fan Class 1 Fan �langenient SIN51. Fan Discharge. VerticalNp x Starter Data. Installed Thermal internal Total CFM Design 75 CFM Total CFM Actual 112 CFM Motor Volts 1 . 1201/olts Moto'Ainps 1 0:7 Amps ' .. SP Ie Actual 0.01n. we §P OuE Actoal NM in, we Notes 3-Jun-11 Keith Finn Lowest Obtalnabte-Airflow. Unit is direct drive with .. no speed control. lq : LH. Finn andAssociates _ LHFIAIN Unit Data. Fan Manufacturer .. Penn Fen,Number ' Z6H `- Fan Serlal Number 1 811WZ63252 Fan Type Fo►wartl Cuwe. -, F Size 5 Fan Class , 1 fan Arrangement s, DWDI ` Fan Discharge Horizontal ' -• `':'' Starter Data, '. - Installed Thermal — intemal