HomeMy WebLinkAbout909 CENTRE AVE - SPECIAL INSPECTIONS - 9/13/2005Sep 13 05 07:43a PPRBD 7193272988 p.2
THOMAS EVANCICH III
ELEVATOR INSPECTIONS
N.A.E.S.A. Q.E.I. # C-1696
1935 WINSTON RD.
COLORADO SPRINGS, CO.80909
719-63 4-1016---719-650-8700
Sept.13-2005
To: Ft. Collins Bldg. Dept.
281 College Ave.
Ft. Collins CO 80522-0580
Attn: Mike Gebo
Re: Acceptance inspection Sept 12-2005 for the Schindler passenger -hydro
Elevator # 6402—Center Car # 1 located at:
Winslow Independent Living
909 Centre Ave.
Ft. Collins CO 80526
Inspection performed under guidelines of ASME A17.1-2004 / NFPA 70 (NEC)
The following items are non -compliant:
1) Working programmed phone A17.1 Rule 2.27.1.1
2) Fire seal hoistway penetrations A17.1 Rule 2.1.1.1.1
3) Sump requirements in pit A17.1 Rule 2.2.2.4 (Not required per Bldg. Dept.)
Phase I & II Fire Service key operation tested & approved.
(Smoke & Heat test by Fire Dept.)
Thank You
Thomas Evancich III
Sep 13 05 07:43a PPRHD 7193272988 p.3
THOMAS EVANCICH III
ELEVATOR INSPECTIONS
N.A.E.S.A. Q.E.I. # C-1696
1935 WINSTON RD.
COLORADO SPRINGS, CO.80909
719-634-1016---719-650-8700
Sept.13-2005
To: Ft. Collins Bldg. Dept.
281 College Ave.
Ft. Collins CO 80522-0580
Attn: Mike Gebo
13,9,0110
9�i3�a5
Re: Acceptance inspection Sept 12-2005 for the Schindler passenger -hydro
Elevator # 6404—South Car # 2 located at:
Winslow Independent Living
909 Centre Ave.
Ft. Collins CO 80526
Inspection performed under guidelines of A SMF A 17 1-2004 / NFPA 70 (NEC)
The following items are non -compliant:
1) Fire seal hoistway penetrations A 17.1 Rule 2.1.1.1.1
2) Sump requirements in pit A 17.1 Rule 2.2.2.4 (Not required per Bldg. Inept.)
Phase I & II Fire Service key operation tested & approved.
(Smoke & Heat test by Fire Dept.)
Thank You
k�
Thomas Evancich III
Sep 13 05 07:43a PPRHD 7193272988 p.5
ELEVATOR
CERTIFICATE OF INSPECTION
Date: Sept 12-2005ylo 3i/D
Name of
Building: Winslow Independent Living — South Car # 2
Address: 909 Centre Ave
Ft. Collins CO 80526
Elevator Manufacturer: Schindler
Elevator I.D. HGB 6404 Rated Load: 2500lbs.
This elevator was inspected on the above date. A report on the results
thereof is on file with the authority having jurisdiction.
Inspector:-14
N.A.E.S.A. Certification # C1696
Thomas Evancich III
Sep 13 05 07:44a PPRBD 7193272988 p.6
ELEVATOR
CERTIFICATE OF INSPECTION
Date: Sent 12-2005
le 111-151,s
Name of
Building: Winslow Independent Living North Car # 3
Address: 909 Centre Ave
Ft. Collins CO 80526
Elevator Manufacturer: Schindler
Elevator I.D. HGB 6403 Rated Load: 2500lbs.
This elevator was inspected on the above date. A report on the results
thereof is on file with the authority having jurisdiction.
i
N.A.E.S.A. Certification # C1696
Thomas Evancich III
Sep 13 05 07:43a PPRBD 7193272998 p.4
ELEVATOR
CERTIFICATE OF INSPECTION
Date: Sept 12-2005
Name of
Building: Winslow Independent Living —Center Car # 1
Address: 909 Centre Ave
Ft. Collins CO 80526
Elevator Manufacturer: Schindler
Elevator I.D. HGB 6402 Rated Load: 2500lbs.
� //,, 1/1 �, -
This elevator was inspected on the above date. A report on the results
thereof is on file with the authority having jurisdiction.
N.A.E.S.A. Certification # C1696
Thomas Evancich III