HomeMy WebLinkAbout909 CENTRE AVE - SPECIAL INSPECTIONS - 9/6/2005Date: Sept 2-2005
Name of
Building: Winslow Independent Living
Address: 909 Centre Ave.
Ft. Collins CO 80526
Elevator Manufacturer: Schindler Elevator Co.
Elevator I.D. HGB 6403 Rated Load: 2500 lb.
This elevator was inspected on the above date. A report on the results
thereof is on file with the authority having jurisdiction.
Inspector: —Yoak�.
N.A.E.S.A. Certification # C1696
Thomas Evancich III
Sep 06 05 07:55a PPRBD 7193272988 p.2
THOMAS EVANCICH III
ELEVATOR INSPECTIONS
N.A.E.S.A. Q.E.I. # C-1696
1935 WINSTON RD.
COLORADO SPRINGS, CO.80909
719-634-1016--- 719-650-8700
■......••rr.•r..••r••............■•.......■■r.■■■......r...............r......1
Sept. 2-2005
To: Ft. Collins Bldg. Dept.
281 N. College Ave.
Ft. Collins Co. 84522-0580
Attn: Mike Gebo
Re: Acceptance inspection Sept. 1-2005 for the Schindler Pass -Hydro elevator
# HGB 6403 located at:
Winslow Independent Living
909 Centre Ave.
Ft. Collins CO 80526
Inspection performed under guidelines of ASME A 17.1-2004 / NFPA 70 (NEC)
The following items are non -compliant:
1) Fire seal machine room penetrations -A 17.1 Rule 2. L 1.1.1
2) Provide fire extinguisher at door to machine room-A17.1 Rule 8.6.1.6.5
3) Pit sump requirements-A17.1 Rule 2.2.2.4 (Not required per Bldg. Dept.)
Phase I & II fire service key operation tested & approved
( Smoke & Heat test by Fire Dept. )
Thank You
Thomas Evancich III
-MOW400 zaW410c: