Loading...
HomeMy WebLinkAbout4926 NORTHERN LIGHTS DR - SPECIAL INSPECTIONS - 1/14/2005Utilities City of Fort Collins January 14, 2005 electric • stormwater • wastewater • water Cross -Connection Control Required Permit Application # B0407463. 4926 Northern Lights Dr. SINGLE STORY NEW CONSTRUCTION FOR POOL HOUSE. A backflow prevention assembly is required on the water service and the pool supply line. These must be an approved Reduced Pressure Backflow Assembly installed horizontally and accessible for testing. This assembly is designed to discharge water under a backpressure situation when the second check is fouled. It is also capable of a full discharge if the first check is fouled. Because of the possibility of this occurring, the assembly must be installed in a location where there is adequate drainage for the size of the service. In addition an approved, listed expansion tank or other device designed for thermal expansion control is required. If there is a lawn irrigation system, an approved backflow preventer is required. A separate permit is required for a lawn irrigation system. Call for an inspection when assemblies are installed and tested. All backflow preventer installations must provide adequate clearances on all sides of the backflow preventer. If there are any questions concerning these backflow preventers please contact this office. John Nelson Cross -Connection Control Administrator 970-221-6677 700 Wood St. • P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6700 • FAX (970) 221-6619 • TDD (970) 224-6003 e-mail: utilities(a fcgov.com . www.fcgov.com/utilities