HomeMy WebLinkAbout468 PEYTON DR - SPECIAL INSPECTIONS - 6/10/2004June 10, 2004
DR Horton, Melody Series
11031 Sheridan Blvd.
Westminster, Colorado 80020
Attn: Mr. Corey Weaver
Re: Exterior Perimeter Drain Observation
Ridgewood Hills 3rd Filing
468 Peyton Drive - Lot 182
Fort Collins, Colorado
Terracon Project No. 20005162
Dear Mr. Weaver:
Irerracon
301 N. Howes • P.O. Box 503
Fort Collins, Colorado 80521-0503
(970) 484-0359 Fax: (970) 484-0454
A representative of Terracon observed the perimeter drain at the above referenced June 3, 2004, as
requested. A four -inch diameter perforated PVC pipe had been placed around the exterior
perimeter of the basement and crawl -space foundations with an impervious PVC membrane
beneath the drainage system. The drainage pipe appeared to exhibit positive drainage toward the
sump pit located within the basement area. We also observed 1 %2 inch washed gravel placed above
and below the pipe and drainage filter fabric above the gravel. The waterproof dampening was also
observed and in our opinion was uniformly applied to the exterior foundations.
In our opinion the exterior perimeter drain was constructed in general accordance with the plans and
specifications for this project.
Tnpal Engineer
Reviewed By:
David A. Richer, P.E.
Geotechnical Engineer/Department Manager
Copies to: (2) Addressee
(1) Brian Kelly — DR Horton, Melody Series