Loading...
HomeMy WebLinkAbout414 PLOWMAN WAY - DISCLOSURES - 10/1/20025ara`s Energy Scoring 813 Oxford LN DATE FT. COLLINS, CO 80525 10/01/02 (970)377-1056 CUSTOMER: Kaufman and $road 414 Plowman '"Af Fort Collins ,CO1 BUILDING CONDITIONS: Interior Temp = 68 F Exterior Temp = 50 F Volume = 16565 Cu. Ft. Above Grade Surface Area = 0 Sq. Ft. Number of Stories = 2 Number of Occupants = 2 Wind Shield Factor = .9 HOUSE TEST : Depressurized Fan Model = 3 Performed By SARA Data Points: House Pressure Fan Pressure CFM %Error Fan Configuration 54 50 1230 —0.8 Ring A 45 43 1142 0.9 Ring A 39 37 1060 0.6 Ring A 29 27 907 —0.1 Ring A 20 18 742 —1.5 Ring A 16 15 678 0.7 Ring A Correlation Coefficient Flow Coefficient Exponent r = .9991 C = 167.04 n = 0.503 Results: Air Flow @ 50 Pascals : = 1194 CFM50 +/— 0.5E 4.32 ACH50 (Air Changes Per Hour) Effective Leakage Area (LBL) = 95.07 Square Inches +!— 2.4E Equivalent Leakage Area (CANADA) = 156.11 Square Inches +/— 1.4E Estimated Natural Infiltration (50 Pascal Flow Divided By 12.2) 98 CFM = 48.9 CFM/OCCUPANT = 0.35 AIR CHANGES PER HOUR