HomeMy WebLinkAbout903 BUCKINGHAM ST - CORRESPONDENCE - 4/8/1998Water Utilities Stormwater • Water • Wastewater City of Fort Collins Cross -Connection Control Required April 8, 1998 Permit Application # 37379 Address To Be Announced, Warehouse Metal Building System A backflow prevention assembly is required on the service connection at this address. This must be an approved Reduced Pressure Backflow Assembly installed horizontally and accessible for testing. This assembly is designed to discharge water under a backpressure situation when the second check is fouled. It is also capable of a full discharge if the first check is fouled. Because of the possibility of this occurring the assembly must be installed in a location where there is adequate drainage for the size of the service. If this facility cannot have the water service interrupted during testing or repair, a bypass may be installed with the same degree of protection. A backflow prevention assembly is required on the fire line riser at this address. This must be an approved Double Check Backflow Assembly installed horizontally and accessible for testing. If there is antifreeze in the system, an approved Reduced Pressure Backflow Assembly is required. This also must be installed horizontally and accessible for testing. Adequate drainage must be available for water spillage during annual testing and maintenance. This office must approve a vertical installation. If there is a lawn irrigation system, an approved backflow preventer is required. A separate permit is required for a lawn irrigation system. Call for an inspection when assemblies are installed and tested. All backflow preventer installations must provide adequate clearances on all sides of the backflow preventer. If there are any questions concerning these backflow prevcmers please contact this office. John Nelson Cross -Connection Control Administrator 970-221-6677 P.O. Box 580 • Fort Collins, CO 80522-0580 • (970) 221-6681