Loading...
HomeMy WebLinkAbout613 S COLLEGE AVE - CORRESPONDENCE - 9/30/1977Mr. Bill Waldo September 30, 1977 S=f or m = 1200 psi x 22:56 in.3 m allowable = 27,075 in. lbs. 2 m=WB or w = 8x27,075 in-lbs 12 in x 14.17 ft2 w allowable = 90 lbs.Js.f. Dead load attributable joists 4 psf plaster 8 psf flooring 4 psf total D.L. 16 psf This leaves a total load reserve to live load of 74 p.s.f. page 2 We approve the floor at the upper level for a live load of 75 p.s.f. at the maximum span condition. This letter shall not be construed to be approval for the exterior concrete deck at the upper level. As we understand the deck area will not be added until the kitchen addition is added. At that time structural modifications as may be required will be made if the deck is to be added. Additionally, it is our understanding that the main floor level has previously been okayed with past remodeling and this letter shall not serve as approval for the main floor for structural requirements. It is hoped that these calculations will serve to answer the questions of loading and that with its submittal and approval will allow the remodeling of the interior of the restaurant to take place. Thank you, Bill, for taking the time to speak with me about this matter and to review this letter. Please call if you have any questions. RAS:sfj CC: Mr. Clyde Canino, III Cordially, ?// Robert A. Sutter, A.I.A. 6j--<ff. w - -z7-7z