HomeMy WebLinkAbout4306 S COLLEGE AVE - SPECIAL INSPECTIONS - 12/10/1991 (2)aAPPLEBZE'S RESTAURANT FORT COLLINS COLORADO ENERGY ANALYSIS 12/10/91 1. HEATING ANALYSIS FOR WALLS WALL 1 WALL 2 WALL 3 WALL 3A GLASS GLASS DOOR N.M. DOOR (0.078 X 144 SF) + (0.119 X 176.8 SF) + (0.102 X 1053 SF) + (0.79 X 1315.9 SF) + (0.49 X 538.3 SF) + (1.13 X 98 SF) + (0.513 X 67 9F) p= -------------------------------------------------------------------------------------------------------------------------------------- 0 3396.8 GSF 652.83 U=------------- 0 3396.8 U = 0.192 0 U0 REQUIRED = 0.25 2. HEATING ANALYSIS FOR ROOF/CEILING FLAT ROOF SLOPED ROOF (0.05 X 4009.5 SF) + (0.043 X 352 SF) Uc -------------------------------------- 0 4361.5 GSF 215.6 Uo ------------- 0 4361.5 Uo = 0.049 U. REQUIRED = 0.07 " 3. HEATING ANALYSIS FOR SLAB -ON -GRADE FLOORS PERIMETER INSULATION = 2" THICK POLYSTYRENE HIGH DENSITY EXTRUDED FOAM BOARD (R-10). R-10 PROVIDED R-5.4 REQUIRED r�C 1R.�►�.SN pwS �'�u5 � '4.-COOL"ING•ANALYSYS FOR WALLS WALL 1 AT 45 LBS/SF = 33.5 TOEQ SOLAR FACTOR = 120 BTUH/FT2 WALL 2 AT 45 LBS/SF = 38.0 TOEQ GLASS SHADING COEFFICIENCT = 0.82 WALL 3/3A AT 45 LBS/SF = 30.0 TDEQ GLASS DOOR SHADING COEFFICIENT = 0.95 HM DOOR AT 5 LBS/SF = 46.5-TOEQ WALL 1 WALL 2 WALL 3 WALL 3A GLASS (0.078 X 144 SF X 33.5) + (0.119 X 176.8 SF X 380) + (0.102 X 1053 SF X 30) + (0.79 X 1318.9 SF X 30) + (0.49 X 538.3 SF X 120) + OTT% ____________________________________________________________________________________________________________________________________ 3396.8 GSF OTTVW = GLASS DOOR H.M. DOOR GLASS TRANSMISSION GLASS DOOR TRANSMISSION + (1.13 X 98 SF X 120) + (0.513 X 67 SF X 46.5) + (0.57 X 538.3 SF X 200 DT) + (0.513 X 67 SF X 20' DT) __________________________________________________________________________________________________________ 3396.8 GSF 81,440 3396.8 OTTVW = 23.98 BTU/FT2 OTTVW REQUIRED = 33.4 BTU/FT2 5. COOLING ANALYSIS FOR ROOF/CEILING FLAT ROOF AT 45 LBS/SF = 0.005 TOEa SLOPED ROOF AT 45 LBS/SF = 0.0043 OTDEQ FLAT ROOF SLOPED ROOF (0.04 X 4009.5 SF X 76) + (0.043 X 352 SF X 75) OTTVR____________________________________________________ 4361.5 GSF 16,371 OTTVR _ ____________ 4361. 5 OTTVR = 3.05 BTUIFT2 OTTVR REQUIRED = 8.5 BTU/FT2 6^ SI4UL`TAHEOUS-HEATING AND COOLING IS NOT POSSIBLE USING THE SPECIFIED THERMOSTATS FOR THE ROOFTOP UNITS. 7. NVAC SYSTEM COMBUSTION EQUIPMENT RTU-1,2,3,4 S 5 ARE RATED AT 79 % STEADY STATE EFFICIENCY ON GAS -FIRED HEATING (CARRIER DATA). e. MECHANICAL VENTILATION OF OUTSIDE AIR INTAKE IS PROVIDED BY MANUAL DAMPERS ON EACH ROOFTOP UNIT FOR YEAR-ROUND USE. EACH FAN SYSTEM IS LESS THAN 5000 CFM. 9. HVAC SYSTEM COOLING MODE. 71,200 STUN RTU-1,2 8 4:----------------- = 10.0 EER (2.9 COP) 7100 WATTS 87,900 BTUH RTU-3 8 5:----------------- = 9.7 EER (2.8 COP) 9000 WATTS EER REQUIRED = 8.2 (COP 2.4) 10. TRANSPORT ENERGY, AIR TRANSPORT FACTOR 56,100 BTUH SENSIBLE RTU-1,2 d 4:------------------------- = 14.7 ATF 1-1/2 HP X 2545 BTUH/HP 68,200 BTUH SENSIBLE RTU-3 8 5:------------------------- = 17.9 ATF 1-1/2 HP X 2545 BTUH/HP MINIMUM ATF = 5.5 ATF COMPLIES 11. SUPPLY AIR DIFFUSERS ARE SPECIFIED"WITH OPPOSED BLADE DAMPERS. 12. OUTDOOR AIR IS LIMITED BY A MANUAL DAMPER TO PROVIDE AN AVERAGE OF APPROXIMATELY 15 CFM PER PERSON. THIS AIR IS SUBSEQUENTLY EXHAUSTED BY THE TOILET EXHAUST SYSTEM AND CONTRIBUTES TO MAKE-UP AIR FOR KITCHEN EXHAUST HOODS. EACH UNIT IS LESS THAN 5000 CFM AND LESS THAN 134,000 BTUH COOLING CAPACITY. 13. EACH ROOFTOP UNIT IS SPECIFIED WITH DUAL SET -POINT TYPE THERMOSTAT AND LOCKING COVER. 14. DUCT INSULATION IS RATED AT R-7 FOR THE THICKNESS SPECIFIED. 75.. DUCT CO1STRUC7I014 SHALL BE IN ACCORDANCE WITH SMACNA STANDARDS. 16. DOMESTIC WATER HEATER COMPLES WITH ASHRAE STANDARD 90A-1980. 17. DOMESTIC WATER PIPING IS SCHEDULED WITH 1/2" THICK FIBERGLASS. 18. LAVATORIES IN GUEST RESTROOMS ARE SERVED WITH 1100 HOT WATER TO FAUCETS WITH 0.5 GPM FLOW CONTROLS. HANOWASH LAVATORIES IN THE KITCHEN ARE SERVED WITH 1400 HOT WATER. HANDICAPPED LAVATORIES ARE EQUIPPED WITH WRIST BLADES.