January 31, 1992
SA .Grove_ _
Applebee's Neighbo"rhood—Grill—and`Bar-----------__Y `-_
400 Interstate North Parkway, Suite 970
Atlanta, GA 30339
Dear Mr. Grove:
The additional information and specifications submitted for the construction
of Applebee's, to be located at the Pavillion in Fort Collins, Colorado, have been
reviewed by,this department. The items listed below correspond to the Department's
review letter of January 7, 1992.
1. Review fee received.
2. Equipment:
b. No information submitted for the drink tower and ice bin (#23). Please
submit.
d. Approved.
e_ Approved.
8. Approved.
16 b. Approved.
21. Approved.
22. Approved.
Submit information for item #2b. The written plans submitted are approved at
this time. Be advised approval of plans, including the modifications listed in the
January 7, 1992 letter does not constitute acceptance of the completed structure.
An inspection of the premises must be conducted by this department prior to
approval for operation and licensure of the establishment. Failure to follow the
recommended changes may prevent or delay the licensure of this establishment. .Any
approval of the plans will be null and void if construction is not commenced within
120 days.
BOARD OF COUNTY COMMISSIONERS
Courtlyn W. Hotchkiss M. J.'Moo" Mekelburg Darylo W. Kloarun
District I District 11 District III
SA Grove
January 31, 1992
Page 2
A state food service license and this department's written approval is
necessary prior to opening.
Please feel free to contact this department if questions arise, or if I can be
of further service at 498-6775.
Sincer 1 ,
Jim Devore
Sanitarian
JDjhy
cc: `Fort Col--li:ns_Bu-i_l_ding-Department__
TJ Fitzpatrick - - -
Paul Scott
4-3c,6 SoDtdi
CcMeje_ Aueque
BOARD OF HEALTH
Kent N. Campbell, JD, Fort Collins
President
Pamela Howard, Loveland
Vice President
Kenneth W. Curds, Jr., MD, MPH, Fort Collins
Eldon Savage, PhD, MPH, Fort Collins
Glenn W. Wellman, OD, MPH, Estes Park
r✓
LARIMER COUNTY DEPARTMENT OF HEALTH AND ENVIRONMENT 1525 Blue Spruce Drive
Fort Collins, Colorado 80524
Adrienne LeBailly, MD, MPH, Director General Health 498-6700
Environmental Health 498-6775
A Commitment To Progrcts
January 10, 1992
SA Grove
Appl-eb"ee` s`Nei ghborhbod ' Gril I- and -Bar
400 Interstate North Parkway, Suite 970
Atlanta, Ga 30339
Dear Mr. Grove:
The additional information and specifications submitted for the construction
of Applebee's, to be located at the Pavillion in Fort Collins, Colorado have been
reviewed by this department. The following items were not clearly specified in the
plans or were not in compliance with the Rules and Regulations Governing the
Sanitation of Food Service Establishments 5 the State of Colorado. These items
must be clearly specified in writing or be modified. to be in compliance with the
above regulations prior to approval of the submitted plans. The items listed below
correspond to the Department's.review letter of January 7, 1992.
1. Required $75.00 plan review fee is not submitted.
2. Equipment:
a. Submitted information reviewed and approved.
-- — - b. - No-information-submitted-for--the-drink-tower-and ice -bin (#23). -Please -
submit.
c. Chef's table (#8) will require visual inspection for final approval.
d. Countertop holding cabinet (#57) and toaster (#69) should be on 4 inch
legs.
e. Be advised, if countertop griddle (#13) is to be used for any grease
cooking or browning of meats, an exhaust hood will be,required over it.
Provide information detailing the use for this griddle. ppBR�E4IES
I �D
3. Approved. �l .�? hl,���l
5. Approved.
J A N 1 5 1.992
BOARD OF COUNTY COMMISSIONERS
Courtlyn W. Hotchkiss M. J. "Moe" Mekelburg Daryle W. Klassen
District I District 11 District ill
SA Gro e
January 10, 1992
Page 2
6. Approved.
7. Acknowledged.
8. Locations of required additional hand sinks not submitted.
12. Approved.
13. Approved, again be advised of requirement for gas line installation behind
cooking equipment.
16. a. Approved.
b. Accoustical board for ceiling above bar is not approved. ,
21. No information submitted.
22. No location information submitted.
23. Approved.
The plans cannot be approved at this time. Once items #1, 2e, 8, 16b, 21 and
22 have been submitted in writing, the plans will be reviewed for final approval.
Be advised your plans will not be reviewed until all of these items are resubmitted
to this department. After the last item is resubmitted, this department will
review the plans and resubmittals within 10 days.
Be advised that Colorado Revised Statutes (1973) 12-44-206 require plans and
specifications be submitted to the local health department and approved prior to
beginning construction.
Sincerely,
-1D-.4,
Jim Devore
- - --- --- Sanitarian - — - -
JD/hy
cc: Fort Collins Building Department
TJ Fitzpatrick
Paul Scott
—' 3306 S,0441 C(>lleje A0e-V)0e
A Commitment To Progras
BOARD OF HEALTH
Kent N. Campbell, JD, Fort Collins
President
Pamela Howard, Loveland
Vice President
Kenneth W. Curtis, Jr., MD, MPH, Fort Collins
Eldon Savage, PhD, MPH, Fort Collins
Glenn W. Wellman, OD, MPH, Estes Park
LARIMER COUNTY DEPARTMENT OF HEALTH AND ENVIRONMENT
Adrienne LeBallly, MD, MPH, Director
January 7, 1991
im
Paul J. Scott
Bevan's Enterprises, Inc.
187 North 85 Parkway
Fayetteville, GA 30214
Dear Mr. Scott:
1525 Blue Spruce Drive
Fort Collins, Colorado 80524
General Health 498-6700
Environmental Health 498-6775
The plans and specifications submitted for the construction of Applebee's, to
be located at the Pavillion in Fort Collins, Colorado, have been reviewed.by this
department., The following items were not clearly specified in the plans or were;.
not in compliance with the Rules and Regulations Governithe Sanitation of Food
Service Establishments in the State of Colorado. These ing tems must be clearly
specified in writing or be modified to be in compliance with the above"regulations
prior to approval of the submitted plans. All plans must be approved prior to
commencement of construction.
The required plan review fee ($75.00) was not paid at the time of the plan
submittal. Please submit the plan review fee.
All food service equipment must be NSF (National Sanitation Foundation)
approved or its equivalent-. --Custom made -equipment and used equipment cannot be
approved until it is visually inspected. Submit make and model numbers and
specification sheets for all the equipment.
All gas cooking equipment (e.g., fryers, grill, and broiler) must be installed
in such a way as to permit easy cleaning around this equipment. It is
recommended that castors be provided on the equipment and that gas lines be
long enough to allow the equipment to be pulled far away from the wall for
cleaning. Also the oven (#59) and hot plate (#1) must be installed on legs and
in a manner that facilitates cleaning. Note how this gas equipment will. be
installed.
Be advised; -that no appurtenances, such as; syrup lines, carbonators, drop -in
cold plates, drain lines or bottle,holders are permitted in potable ice bins or
ice machines or any unit used to store potable ice.
BOARD OF COUNTY COMMISSIONERS
Courtlyn W. Hotchkiss M" J.'Moo' Mekelburg Daryle W. Klassen
District I District 11 District 01
Paul J. Scott
:January 7, 1992
Page 2
5. Submit cut sheets for exhaust hoods N1 and N2 and the dishwasher exhaust hood.
Include UL classified air flows for hoods 1 & 2. Also submit exhasut CFM's for
the dishwasher exhaust hood. Be advised, the kitchen exhaust hoods must be
constructed of stainless steel when located over grease cooking equipment and
must overhang cooking equipment not less than 6 inches beyond the edge of the
cooking surface on all open sides. Make up air must be filtered mechanically
introduced into the establishment at a volume equal to or greater .than what is
being exhausted and must be distributed to establish necessary air patterns so
as not to short circuit the exhaust hoods.
6. Submit make, model number and recovery rate of the proposed commercial water
heater. Also, submit the size dimensions of the 3-compartment sink basins
including the width, length and depth.
7. Submit a proposed menu.
8. Hand sinks must be easily accessible in all rooms and areas where food is
prepared or utensils are washed. Additional hand sinks must be provided in the
service and dishwashing areas. Provide information on the proposed locations
for these hand sinks.
9. Be advised that all hand sinks must be provided with hot and cold running water
under pressure through a mixing valve; single service hand towels from a
dispenser and soap.
10. All drain lines from equipment such as; ice machines, ice bins, drink
dispensers, drink overflow drains, liquor gun overflow drains, prep sinks,
refrigeration/freezer units, steam kettles, walk-in compressors and cold tables
holding ice must be directed to a floor drain or floor sink and be properly air
gapped.
11. Be advised, floor sinks must not be installed under equipment where they cannot
be cleaned. All floor sinks and floor drains must be installed so that they
are flush with the finished floor.
12. Subimt the make and model number of the dishwasher booster heater.
13. All plumbing and electrical conduit are to be installed within and behind walls
or below floors. Exposed water pipes, sewer lines, or electrical conduit
running along walls or floors are not approved. The gas line located behind
the cooking equipmentmust be enclosed within the wall behind the cook's line.
14. Be advised that all exit and restroom doors must be fitted with self -closures.
15. Be advised, 30 foot candles of light are required on all working surfaces and
20 foot-candles of light on all other surfaces and equipment in the kitchen,
storage areas, service counter, waitress stations, restrooms, bar, utensil
washing area, and all food prep areas. At least 10 foot candles of light must
be provided in all areas of the walk-in cooler and freezer. All lights in the
above areas, excluding the restrooms, must be shielded in an approved manner.
Paul 4. Scott
January 7, 1992
Page 3
16. Floors, walls, ceilings, counter tops, storage shelves, cabinets and all work
surfaces located within the kitchen, storage areas, restrooms, waitress
station, serving area, bar, dishwashing area, walk-ins, and all food prep areas
must be of an approved material that is smooth, easily cleanable, nonabsorbent,
and of a light color.
a. Provide information on the finishes to be used on the inside of the bar
partition walls. SD-8.1 not included in submitted plans.
b. 4ccoustical Board (AB) is not approved above bar.
17. All floor/wall and stationary equipment floor junctures in the kitchen, storage
areas, restrooms, waitress -,station, -serving area, bar, dishwashing area,
walk-ins, and all food prep areas must be provided with approved concave
coving.
18. All equipment, cabinets, and counters that are not easily moveable must be: a)
spaced so that floors, walls, and exterior surfaces of equipment can be easily
cleaned; or b) be sealed to adjoining walls, equipment, cabinets, or counters.
Hard to clean areas, spaces or gaps are not approved.
19. Be advised that the lowest shelf of all storage shelves located in all kitchen
areas, storage areas, and the walk-in(s) must be situated at least six inches
up off the floor.
20. Solid metal shelving in the walk-in cooler and freezer is not approved, unless
NSF approved for use in walk-ins. Wooden shelves, pallets, or any wooden
interior finishes is not permitted in walk-in coolers or freezers. Metal
shelves in the walk-in cooler and freezer must be of an approved metal wire
construction.
21. Submit information detailing what the shed located on the pad behind the
building will be utilized for. Be advised, if food and or single service
articles are stored in the shed the interior must be finished as outlined in
item 16 above.
22. Provide an approved area away from food operations, food storage and utensil
washing facilities for the storage of toxic materials and surplus cleaning
items. Submit a proposed location.
23. Provide an approved area for the proper storage of employee's personal items;
coats, clothing, etc. Submit a proposed location.
24. Please be advised that the following items are required in the establishment at
the time of the opening inspection and thereafter:
a) stab food thermometer (0' to 220°F)
b) food grade plastic gloves
c) approved sanitizer
d) test strips for your sanitizer
The plans are not approved at this time. Once items #1, 2, 3, 5, 6, 7, 8, 12,
13, 16 a&b, 21, 22, and 23 have been submitted in writing, the plans will be
Paul.-J. Scott
'January 7, 1992
Page 4
reviewed for final approval. Be advised, your plans will not be reviewed until all
of these items are resubmitted to this department. After the last item is
resubmitted, this department will review the plans and resubmittals within 10 days.
Be advised that Colorado Revised Statutes (1973) 12-44-206 require plans and
specifications be submitted to the local health department and approved prior to
beginning construction.
Please feel free to contact this department if questions arise, or if I can be
of further service at 498-6775.