HomeMy WebLinkAbout411 LINDEN ST - SPECIAL INSPECTIONS - 1/9/2014Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 — Eaton, CO 80615 • Phone (970) 454-5351 — Fax (970) 454-5391 2389 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 1i9i14 PROJECT Legacy Senior Residences f411 Linden Street Ft. Collins, CO *** Pre -final Report*** ARCHITECT Robert W. Engel and Assoc. 2110 South 156th Circle Omaha, NE ENGINEER RDH Engineering 13504 Stevens Street, Suite D Omaha, NE CONTRACTOR Air Comfort, Inc. 150 Rome Court Ft. Collins, CO t fob f 5f r 0Ve� A6, j Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEWUNIT: F-1-107 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 1813A46774 Filter Manufacturer AirHandler Filter Type Pleated Filter Qty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 830 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.09 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.07 In. wc. F-1-107 Supply Outlet Summary DATE: 1/9/2014 CONTACT: Emerson Moore Ni�) BIB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-2B R-1 12x6 100 136 136 136 136 Outlet-02 Unit-2B R-1 12x6 100 146 139 146 139 Outlet-03 Unit-2B R-1 12x6 100 125 142 125 142 Outlet-04 Unit-2B R-1 12x6 100 151 138 151 138 Outlet-05 Unit-2B R-1 12x6 100 147 141 147 141 Outlet-06 Unit-2B R-1 8x4 50 58 67 116 134 Outlet-07 Unit-2B R-1 8x4 50 74 67 148 134 Totals : - - - 600 837 830 140 % 138 % Notes L.H. Finn and Associates Pre -final Repoli Page 12 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEWUNIT. F-1-108 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC213040S141110 Unit Serial Number 2113A50174 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 882 CFM Motor Volts Tt-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.08 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.06 In. wc. F-1-108 Supply Outlet Summary DATE: 1 /9/2014 CONTACT: Emerson Moore N E� BIB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-11-12 R-1 12x6 100 149 146 149 146 Outlet-02 Unit-11-12 R-1 12x6 100 150 148 150 148 Outlet-03 Unit-11-12 R-1 12x6 100 166 151 166 151 Outlet-04 Unit-11-12 R-1 12x6 100 141 145 141 145 Outlet-05 Unit-1H2 R-1 12x6 100 129 144 129 144 Outlet-06 Unit-11-12 R-1 8x4 50 73 73 146 146 Outlet-07 Unit-11-12 R-1 8x4 50 76 1 75 152 1 150 Totals : - - 600 884 882 147 % 1 147 % * Notes L.H. Finn and Associates Pre -final Report Page 13 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEWUNIT: F-1-109 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 2113A50184 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x20x2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 704 CFM Motor Volts Tt-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.15 In. wc. E.S.P. In -0.03 In. wc. E.S.P. Out 0.12 In. wc. F-1-109 Sunnly Outlet Summary DATE: 1/9/2014 CONTACT: Emerson Moore NE� BB . 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-1A R-1 12x6 200 197 229 99 115 Outlet-02 Unit-1A R-1 12x6 150 187 174 125 116 Outiet-03 Unit-1A R-1 8x4 50 79 60 158 120 Outlet-04 Unit-1A R-1 8x4 50 81 60 162 120 Outlet-05 Unit-1A R-1 12x6 150 165 181 110 121 Totals : - - 600 709 704 118 % 1 117 % * Notes L.H. Finn and Associates Pre -final Report Page 14 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fart Collins, CO SYSTEM/UNIT: F-1-110 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 1813A46776 Filter Manufacturer AirHandler Filter Type Pleated Filter Qty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 780 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.12 In. wc. E.S.P. In -0.03 In. wc. E.S.P. Out 0.09 In. wc. F-1-110 Supply Outlet Summary DATE: 1/9/2014 CONTACT: Emerson Moore N E { BiB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-11­11 R-1 12x6 200 259 263 130 132 Outlet-02 Unit-11-17 R-1 12x6 150 194 191 129 127 Outlet-03 Unit-11-11 R-1 8x4 50 54 64 108 128 Outlet-04 Unit-11-11 R-1 8x4 50 54 64 108 128 Outlet-05 Unh-11-11 R-1 12x6 150 226 198 151 132 Totals : - - - 600 787 780 131 % 130 . Notes L.H. Finn and Associates Pre-finalRepoa Page 15 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTENUUNIT: F-1-111 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC26040S141110 Unit Serial Number 2113A50197 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 904 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.09 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.07 In. wc. F-1-111 Supply Outlet Summary DATE: 1 /9/2014 CONTACT: Emerson Moore NE� 1. i. 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 113 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-1D R-1 12x6 100 151 149 151 149 Outlet-02 Unit-113 R-1 12x6 100 161 153 161 153 Outlet-03 Unit-113 R-1 12x6 100 159 151 159 151 Outlet-04 Unit-1D R-1 12x6 100 139 147 139 147 Outlet-05 Unit-11) R-1 12x6 100 160 154 160 154 Outlet-06 Unit-1D R-1 8x4 50 64 74 128 148 Outlet-07 Unit -ID R-1 8x4 50 78 76 156 152 Totals : - - 600 912 904 152 % 151 % Notes L.H. Finn and Associates Pre-fina/Report Page 16 of 102 Inc Lawrence H. Finn & Associates, . N'E� se 2389 Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTENUUNIT. F-1-112 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC28040S141110 Unit Serial Number 2113A50203 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 840 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.10 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.08 In. wc. F-1-112 SUDDIV Outlet Summary DATE: 1/9/2014 CONTACT: Emerson Moore Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-1D R-1 12x6 100 136 139 136 139 Outlet-02 Unit -ID R-1 12x6 100 155 139 155 139 Outlet-03 Unit-11) R-1 12x6 100 161 144 161 144 Outlet-04 Unit-1D R-1 12x6 100 149 142 149 142 Outlet-05 Un8-11) R-1 12x6 100 177 138 177 138 Outlet-06 Unit-11) R-1 8x4 50 65 68 130 136 Outlet-07 Unit -ID R-1 8x4 50 65 70 130 140 Totals : - - - 600 908 840 151 % 140 % . Notes L.H. Finn and Associates Pre -final Report Page 17 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEWUNIT. F-1-113 AREA: Unit Data Unit Manufacturer Cartier Unit Model Number 59SC2B040S141110 Unit Serial Number 1813A46792 Filter Manufacturer AirHandier Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 738 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.10 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.08 In. wc. F-1-113 Supply Outlet Summary DATE: 1 /9/2014 CONTACT: Emerson Moore N E� BIB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data —� Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-tA R-1 12x6 200 222 246 111 123 Outlet-02 Unit -IA R-1 12x6 150 211 181 141 121 Outlet-03 Unit -IA R-1 8x4 50 53 64 106 128 Outlet-04 Unit -IA R-1 8x4 50 66 63 132 126 Outlet-05 Unit-lA R-1 12x6 150 207 184 1138 123 Totals : - - - 600 759 1 736 1 127 % 1 123 * Notes L.H. Finn and Associates Pre -final Report Page 18 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEM/UNIT: F-1-114 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 1813A46780 Filter Manufacturer AirHandler Filter Type Pleated Filter Qty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 771 CFM Motor Volts Tt-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.10 In. wc. E.S.P. In -0.03 In. wc. E.S.P. Out 0.07 In. wc. F-1-114 Supply Outlet Summary DATE: 1 /9/2014 CONTACT: Emerson Moore N,E P!B�!B 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System I Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-1A R-1 12x6 200 258 258 129 129 Outlet-02 Unit-1A R-1 12x6 150 194 194 129 129 Outlet-03 Unit-1A R-1 8x4 50 73 64 146 128 Outlet-04 Unit-1A R-1 8x4 50 71 62 142 124 Outlet-05 Unit-1A R-1 12x6 150 179 193 1119 129 Totals : - - - 600 776 1 771 1 129 % 129 % * Notes L.H. Finn and Associates Pre -final Report Page 19 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEM/UNIT. F-1-115 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC28040S141110 Unit Serial Number 2113A50201 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 857 CFM Motor Volts T7-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.08 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.06 In. wc. F-1-115 Supply Outlet Summary DATE: 1 /9/2014 CONTACT: Emerson Moore N E SB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-2A R-1 12x6 100 161 141 161 141 Outlet-02 Unit-2A R-1 12x6 100 156 146 156 146 Outlet-03 Unit-2A R-1 12x6 100 147 144 147 144 Outlet-04 Unit-2A R-1 12x6 100 110 143 110 143 Outlet-05 Unit-2A R-1 12x6 100 170 143 170 143 Outlet-06 Unit-2A R-1 8x4 50 58 71 116 142 Outlet-07 Unit-2A R-1 8x4 50 58 69 116 138 Totals: - - - 600 860 857 143 % 143 % * Notes L.H. Finn and Associates Pre-finalRepoR Page 20 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEM/UNIT: F-1-116 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 2113A50186 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 878 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.07 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.05 In. wc. F-1-116 Supply Outlet Summary DATE: 1 /9/2014 CONTACT: Emerson Moore TB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System I Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-2A R-1 12x6 100 140 144 140 144 Outlet-02 Unit-2A R-1 12x6 100 150 149 150 149 Outlet-03 Unit-2A R-1 12x6 100 156 145 156 145 Outlet-04 Unit-2A R-1 12x6 100 151 146 151 146 Outlet-05 Unit-2A R-1 12x6 100 159 151 159 151 Outlet-06 Unit-2A R-1 8x4 50 71 71 142 142 Outlet-07 Unit-2A R-1 8x4 50 55 72 110 144 Totals: - - 600 882 878 147 % 146 % * Notes L.H. Finn and Associates Pre-finaiReport Page 21 Of 102 Lawrence H. Finn & Associates, Inc. Energy Recovery Unit PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEWUNIT: ERV-01 AREA: Unit Data Unit Manufacturer RenewAire Unit Model Number EV300 Unit Serial Number E134605R ERV-01 / Exhaust Fan Fan Type Forward Curve Fan Size 6'ID Fan Class 1 Fan Arrangement OWDI ERV-01 / Supply Fan Fan Type Forward Curve Fan Size 6'ID Fan Class 1 Fan Arrangement DWDI Starter Data ERV-01 / Exhaust Fan Installed Thermal Internal ERV-01 / Supply Fan Installed Thermal Internal Test Data SF Total CFM Design 300 CFM SF Total CFM Actual 312 CFM SF OA CFM Design 300 CFM SF OA CFM Actual 312 CFM EF Total CFM Design 300 CFM EF Total CFM Actual 311 CFM EF OA CFM Design 300 CFM EF OA CFM Actual 311 CFM ERV-01 / Exhaust Fan Fan RPM Actual Direct Drive RPM Motor Volts 1 122 Volts Motor Amps 1 3.1 Amps ERV-01 / Supply Fan Fan RPM Actual Direct Drive RPM Motor Volts 1 122 Volts Motor Amps 1 3.1 Amps DATE: 1/9/2014 CONTACT: Emerson Moore N E� BIB 2389 Tested By: Emerson Moore Test Date: December 31, 2013 Motor Data ERV-01 / Exhaust Fan Motor HP 0.2 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.3 Amps ERV-01 / Supply Fan Motor HP 0.2 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.3 Amps Sheave Data ERV-01 I Exhaust Fan Motor Sheave Make Direct Drive ERV-01 / Supply Fan Motor Sheave Make Direct Drive Test Pressures SF Fan SP In -0.29 in. we SF Fan SP Out 0.09 in. we EF Fan SP In -0.31 in. we EF Fan SP Out 0.08 in. we * Notes ERV-01 31-Dec-13 Emerson Moore Unit contains 1 motor and 2 blowers. L.H. Finn and Associates Pre -final Report Page 4 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEM/UNIT. F-1-201 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 2113A50185 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 735 CFM Motor Volts Ti-T2 122 Volts Amps Tt 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.09 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.07 In. wc. F-1-201 Suooly Outlet Summary DATE: 1 /912014 CONTACT: Emerson Moore N J rB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outtet-01 Unit-1 B R-1 12x6 200 248 242 124 121 Outlet-02 Unit-1B R-1 12x6 150 222 188 148 125 Outlet-03 Unit-1B R-1 8x4 50 40 62 80 124 Outlet-04 Unit-1B R-1 8x4 50 62 60 124 120 Outlet-05 Unit-16 R-1 12x6 150 187 183 125 122 Totals : - - - 600 759 735 127 % 123 % * Notes L. H. Finn and Associates Pre -final Report Page 22 of 102 Lawrence H. Finn & Associates, Inc. Energy Recovery Unit PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEM(UNIT: ERV-02 AREA: Unit Data Unit Manufacturer RenewAire Unit Model Number EV300 Unit Serial Number E134605R Test Data SF Total CFM Design 300 CFM SF Total CFM Actual 312 CFM SF OA CFM Design 300 CFM SF OA CFM Actual 312 CFM EF Total CFM Design 300 CFM EF Total CFM Actual 311 CFM EF OA CFM Design 300 CFM EF OA CFM Actual 311 CFM * Notes SYSTEM/UNIT: ERV-03 AREA: Unit Data Unit Manufacturer RenewAire Unit Model Number EV300 Unit Serial Number E134605R Test Data SF Total CFM Design 300 CFM SF Total CFM Actual 312 CFM SF OA CFM Design 300 CFM SF OA CFM Actual 312 CFM EF Total CFM Design 300 CFM EF Total CFM Actual 311 CFM EF OA CFM Design 300 CFM EF OA CFM Actual 311 CFM * Notes DATE: 1 /9/2014 CONTACT: Emerson Moore NE BB e- . 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Test Pressures SF Fan SP In -0.29 in. we SF Fan SP Out 0.09 in. we EF Fan SP In -0.31 in. we EF Fan SP Out 0.08 in. we Tested By: Emerson Moore Test Date: January 09, 2014 Test Pressures SF Fan SP in -0.29 in. we SF Fan SP Out 0.09 in. we EF Fan SP in -0.31 in. we EF Fan SP Out 0.08 in. we L.H. Finn and Associates Pie -final Report Page 5 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEWUNIT: F-1-101 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 2113A50176 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 806 CFM Motor Volts T1-T2 122 Volts Amps Tt 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.08 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.06 In, wc. F-1-101 Supply Outlet Summary DATE: 1 /9/2014 CONTACT: Emerson Moore NTEB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-1B R-1 12x6 200 258 266 129 133 Outlet-02 Unit-1B R-1 12x6 150 195 197 130 131 Outlet-03 Unit-16 R-1 8x4 50 78 66 156 132 Outlet-04 Unit-1B R-1 8x4 50 71 69 142 138 Outlet-05 Unit-1 B R-1 12x6 150 219 208 146 139 Totals : - - - 600 821 $06 137 % 1 134 % * Notes L.H. Finn and Associates Pre-Ana/Report Page 6 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEMVNIT. F-1-102 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 2113A50190 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 730 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.091n. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.07 In. wc. F-1-102 Supply Outlet Summary DATE: 1/9/2014 CONTACT: Emerson Moore r' N E� BB I.2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-1B R-1 12x6 200 246 237 123 119 Outlet-02 Unit-1B R-1 12x6 150 189 183 126 122 Outlet-03 Unit-1B R-1 8x4 50 47 63 94 126 Outlet-04 Unft-1B R-1 8x4 50 58 61 116 122 Outlet-05 Unit-1B R-1 12x6 150 195 186 130 124 Totals: I - - - 600 735 730 123 % 1 122 % * Notes L. H. Finn and Associates Pre-line/Report Page 7 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEWUNIT: F-1-103 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 1813A46760 Filter Manufacturer AirHandier Filter Type Pleated Filter ay 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 783 CFM Motor Volts T1-T2 122 Volts Amps Tt 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.14 In. we. E.S.P. In -0.03 In. we. E.S.P. Out 0.11 In. we. F-1-103 Supply Outlet Summary DATE: 1/9/2014 CONTACT: Emerson Moore r� N Ej BB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-1A R-1 12x6 200 257 257 129 129 Outlet-02 Unit-1A R-1 12x6 150 205 202 137 135 Outlet-03 Unit-1A R-1 8x4 50 63 64 126 128 Outlet-04 Unit-1A R-1 8x4 50 64 65 128 130 Outlet-05 Unit-1A R-1 12x6 150 195 195 130 130 Totals : - - - 600 784 783 131 % 1 131 °k * Notes L.H. Finn and Associates Pre -final Report Page 8 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTENdUNIT. F-1-104 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 2113A50189 Filter Manufacturer AirHandier Filter Type Pleated Filter Qty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 744 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.12 In. wc. E.S.P. in -0.02 In. wc. E.S.P. Out 0.10 In. wc. F-1_10d Sunniv Outlet Summary DATE: 1 /9/2014 CONTACT: Emerson Moore NEj 11 BB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 52 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-11-11 R-1 12x6 200 239 247 120 124 Outlet-02 Unit-11-11 R-1 12x6 150 195 187 130 125 Outlet-03 Unit-11-11 R-1 8x4 50 73 65 146 130 Outlet-04 Unit-11-11 R-1 8x4 50 54 61 108 122 Outtet-05 Unit-11-11 R-1 12x6 150 197 184 131 123:] Totals : I - - - 600 758 7" 126 % 12401, Notes L.H. Finn and Associates Pie -final Report Page 9 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTEWUNIT: F-1-105 AREA: Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2804OS141110 Unit Serial Number 2113A50188 Filter Manufacturer AirHandler Filter Type Pleated Filter Oty 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 842 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.10 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.08 In. we. F-1-105 Supply Outlet Summary DATE: 1/9/2014 CONTACT: Emerson Moore NE BB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 1/3 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-2B R-1 12x6 100 142 140 142 140 Outlet-02 Unit-2B R-1 12x6 100 152 143 152 143 Outlet-03 Unit-2B R-1 12x6 100 127 145 127 145 Outlet-04 Unit-2B R-1 12x6 100 144 137 144 137 Outlet-05 Unit-2B R-1 12x6 100 142 137 142 137 Outlet-06 Unit-2B R-1 8x4 50 72 71 144 142 Outlet-07 Unit-2B R-1 8x4 50 69 69 138 138 Totals: - - 600 848 842 141 % 140 % ' Notes L.H. Finn and Associates Pre -final Report Page 10 of 102 Lawrence H. Finn & Associates, Inc. Fan Coil PROJECT: Legacy Senior Residences LOCATION: Fort Collins, CO SYSTENUUNIT. F-1-106 AREA: ' Unit Data Unit Manufacturer Carrier Unit Model Number 59SC2B040S141110 Unit Serial Number 1813A46777 Filter Manufacturer AirHandler Filter Type Pleated Filter City 1 Filter Size 20x2Ox2 Unit Location Closet Test Data Total CFM Design 600 CFM Total CFM Actual 780 CFM Motor Volts T1-T2 122 Volts Amps T1 2.7 Amps Fan RPM Actual Low Speed RPM Unit E.S.P. Actual 0.13 In. wc. E.S.P. In -0.02 In. wc. E.S.P. Out 0.11 In. wc. F-1-106 Supply Outlet Summary DATE: 1/9/2014 CONTACT: Emerson Moore NTEB 2389 Tested By: Emerson Moore Test Date: January 09, 2014 Motor Data Motor Manufacturer ANA Motor HP 113 Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 5.2 Amps Sheave Data Motor Sheave Make Direct Drive System / Unit Area Served Outlet Type Size L.xW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 Unit-11-12 R-1 12x6 100 129 129 129 129 Outlet-02 Unit-11-12 R-1 12x6 100 137 132 137 132 Outlet-03 Unit-1H2 R-1 12x6 100 139 133 139 133 Outlet-04 Unit-11-12 R-1 12x6 100 128 129 128 129 Outlet-05 Unit-11-12 R-1 12x6 100 131 130 131 130 Outlet-06 Unit-11-12 R-1 8x4 50 56 63 112 126 Outlet-07 Unit-11-12 R-1 8x4 50 60 64 120 128 Totals : - - - 600 780 780 130 % 130 % * Notes L.H. Finn and Associates Pre -final Report Page 11 of 102