HomeMy WebLinkAbout411 LINDEN ST - SPECIAL INSPECTIONS - 1/9/2014Lawrence H. Finn & Associates, Inc.
55 S. Elm Ave., Suite 220 — Eaton, CO 80615
• Phone (970) 454-5351 — Fax (970) 454-5391
2389
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
DATE
1i9i14
PROJECT
Legacy Senior Residences
f411 Linden Street
Ft. Collins, CO
*** Pre -final Report***
ARCHITECT
Robert W. Engel and Assoc.
2110 South 156th Circle
Omaha, NE
ENGINEER
RDH Engineering
13504 Stevens Street, Suite D
Omaha, NE
CONTRACTOR
Air Comfort, Inc.
150 Rome Court
Ft. Collins, CO
t
fob
f 5f
r 0Ve�
A6, j
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEWUNIT: F-1-107
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
1813A46774
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Qty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
830 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.09 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.07 In. wc.
F-1-107 Supply Outlet Summary
DATE: 1/9/2014
CONTACT: Emerson Moore
Ni�) BIB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-2B
R-1
12x6
100
136
136
136
136
Outlet-02
Unit-2B
R-1
12x6
100
146
139
146
139
Outlet-03
Unit-2B
R-1
12x6
100
125
142
125
142
Outlet-04
Unit-2B
R-1
12x6
100
151
138
151
138
Outlet-05
Unit-2B
R-1
12x6
100
147
141
147
141
Outlet-06
Unit-2B
R-1
8x4
50
58
67
116
134
Outlet-07
Unit-2B
R-1
8x4
50
74
67
148
134
Totals :
-
-
-
600
837
830
140 %
138 %
Notes
L.H. Finn and Associates
Pre -final Repoli Page 12 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEWUNIT. F-1-108
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC213040S141110
Unit Serial Number
2113A50174
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
882 CFM
Motor Volts Tt-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.08 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.06 In. wc.
F-1-108 Supply Outlet Summary
DATE: 1 /9/2014
CONTACT: Emerson Moore
N E� BIB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-11-12
R-1
12x6
100
149
146
149
146
Outlet-02
Unit-11-12
R-1
12x6
100
150
148
150
148
Outlet-03
Unit-11-12
R-1
12x6
100
166
151
166
151
Outlet-04
Unit-11-12
R-1
12x6
100
141
145
141
145
Outlet-05
Unit-1H2
R-1
12x6
100
129
144
129
144
Outlet-06
Unit-11-12
R-1
8x4
50
73
73
146
146
Outlet-07
Unit-11-12
R-1
8x4
50
76
1 75
152
1 150
Totals :
-
-
600
884
882
147 %
1 147 %
* Notes
L.H. Finn and Associates
Pre -final Report Page 13 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEWUNIT: F-1-109
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
2113A50184
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x20x2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
704 CFM
Motor Volts Tt-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.15 In. wc.
E.S.P. In
-0.03 In. wc.
E.S.P. Out
0.12 In. wc.
F-1-109 Sunnly Outlet Summary
DATE: 1/9/2014
CONTACT: Emerson Moore
NE� BB
.
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-1A
R-1
12x6
200
197
229
99
115
Outlet-02
Unit-1A
R-1
12x6
150
187
174
125
116
Outiet-03
Unit-1A
R-1
8x4
50
79
60
158
120
Outlet-04
Unit-1A
R-1
8x4
50
81
60
162
120
Outlet-05
Unit-1A
R-1
12x6
150
165
181
110
121
Totals :
-
-
600
709
704
118 %
1 117 %
* Notes
L.H. Finn and Associates
Pre -final Report Page 14 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fart Collins, CO
SYSTEM/UNIT: F-1-110
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
1813A46776
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Qty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
780 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.12 In. wc.
E.S.P. In
-0.03 In. wc.
E.S.P. Out
0.09 In. wc.
F-1-110 Supply Outlet Summary
DATE: 1/9/2014
CONTACT: Emerson Moore
N E { BiB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-1111
R-1
12x6
200
259
263
130
132
Outlet-02
Unit-11-17
R-1
12x6
150
194
191
129
127
Outlet-03
Unit-11-11
R-1
8x4
50
54
64
108
128
Outlet-04
Unit-11-11
R-1
8x4
50
54
64
108
128
Outlet-05
Unh-11-11
R-1
12x6
150
226
198
151
132
Totals :
-
-
-
600
787
780
131 %
130
. Notes
L.H. Finn and Associates
Pre-finalRepoa Page 15 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTENUUNIT: F-1-111
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC26040S141110
Unit Serial Number
2113A50197
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
904 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.09 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.07 In. wc.
F-1-111 Supply Outlet Summary
DATE: 1 /9/2014
CONTACT: Emerson Moore
NE� 1.
i.
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 113
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-1D
R-1
12x6
100
151
149
151
149
Outlet-02
Unit-113
R-1
12x6
100
161
153
161
153
Outlet-03
Unit-113
R-1
12x6
100
159
151
159
151
Outlet-04
Unit-1D
R-1
12x6
100
139
147
139
147
Outlet-05
Unit-11)
R-1
12x6
100
160
154
160
154
Outlet-06
Unit-1D
R-1
8x4
50
64
74
128
148
Outlet-07
Unit -ID
R-1
8x4
50
78
76
156
152
Totals :
-
-
600
912
904
152 %
151 %
Notes
L.H. Finn and Associates
Pre-fina/Report Page 16 of 102
Inc
Lawrence H. Finn & Associates, . N'E� se
2389
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTENUUNIT. F-1-112
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC28040S141110
Unit Serial Number
2113A50203
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
840 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.10 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.08 In. wc.
F-1-112 SUDDIV Outlet Summary
DATE: 1/9/2014
CONTACT: Emerson Moore
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-1D
R-1
12x6
100
136
139
136
139
Outlet-02
Unit -ID
R-1
12x6
100
155
139
155
139
Outlet-03
Unit-11)
R-1
12x6
100
161
144
161
144
Outlet-04
Unit-1D
R-1
12x6
100
149
142
149
142
Outlet-05
Un8-11)
R-1
12x6
100
177
138
177
138
Outlet-06
Unit-11)
R-1
8x4
50
65
68
130
136
Outlet-07
Unit -ID
R-1
8x4
50
65
70
130
140
Totals :
-
-
-
600
908
840
151 %
140 %
. Notes
L.H. Finn and Associates
Pre -final Report Page 17 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEWUNIT. F-1-113
AREA:
Unit Data
Unit Manufacturer
Cartier
Unit Model Number
59SC2B040S141110
Unit Serial Number
1813A46792
Filter Manufacturer
AirHandier
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
738 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.10 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.08 In. wc.
F-1-113 Supply Outlet Summary
DATE: 1 /9/2014
CONTACT: Emerson Moore
N E� BIB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data —�
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-tA
R-1
12x6
200
222
246
111
123
Outlet-02
Unit -IA
R-1
12x6
150
211
181
141
121
Outlet-03
Unit -IA
R-1
8x4
50
53
64
106
128
Outlet-04
Unit -IA
R-1
8x4
50
66
63
132
126
Outlet-05
Unit-lA
R-1
12x6
150
207
184
1138
123
Totals :
-
-
-
600
759
1 736
1 127 %
1 123
* Notes
L.H. Finn and Associates
Pre -final Report Page 18 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEM/UNIT: F-1-114
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
1813A46780
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Qty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
771 CFM
Motor Volts Tt-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.10 In. wc.
E.S.P. In
-0.03 In. wc.
E.S.P. Out
0.07 In. wc.
F-1-114 Supply Outlet Summary
DATE: 1 /9/2014
CONTACT: Emerson Moore
N,E P!B�!B
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System I Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-1A
R-1
12x6
200
258
258
129
129
Outlet-02
Unit-1A
R-1
12x6
150
194
194
129
129
Outlet-03
Unit-1A
R-1
8x4
50
73
64
146
128
Outlet-04
Unit-1A
R-1
8x4
50
71
62
142
124
Outlet-05
Unit-1A
R-1
12x6
150
179
193
1119
129
Totals :
-
-
-
600
776
1 771
1 129 %
129 %
* Notes
L.H. Finn and Associates
Pre -final Report Page 19 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEM/UNIT. F-1-115
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC28040S141110
Unit Serial Number
2113A50201
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
857 CFM
Motor Volts T7-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.08 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.06 In. wc.
F-1-115 Supply Outlet Summary
DATE: 1 /9/2014
CONTACT: Emerson Moore
N E SB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-2A
R-1
12x6
100
161
141
161
141
Outlet-02
Unit-2A
R-1
12x6
100
156
146
156
146
Outlet-03
Unit-2A
R-1
12x6
100
147
144
147
144
Outlet-04
Unit-2A
R-1
12x6
100
110
143
110
143
Outlet-05
Unit-2A
R-1
12x6
100
170
143
170
143
Outlet-06
Unit-2A
R-1
8x4
50
58
71
116
142
Outlet-07
Unit-2A
R-1
8x4
50
58
69
116
138
Totals:
-
-
-
600
860
857
143 %
143 %
* Notes
L.H. Finn and Associates
Pre-finalRepoR Page 20 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEM/UNIT: F-1-116
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
2113A50186
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
878 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.07 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.05 In. wc.
F-1-116 Supply Outlet Summary
DATE: 1 /9/2014
CONTACT: Emerson Moore
TB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System I Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-2A
R-1
12x6
100
140
144
140
144
Outlet-02
Unit-2A
R-1
12x6
100
150
149
150
149
Outlet-03
Unit-2A
R-1
12x6
100
156
145
156
145
Outlet-04
Unit-2A
R-1
12x6
100
151
146
151
146
Outlet-05
Unit-2A
R-1
12x6
100
159
151
159
151
Outlet-06
Unit-2A
R-1
8x4
50
71
71
142
142
Outlet-07
Unit-2A
R-1
8x4
50
55
72
110
144
Totals:
-
-
600
882
878
147 %
146 %
* Notes
L.H. Finn and Associates
Pre-finaiReport Page 21 Of 102
Lawrence H. Finn & Associates, Inc.
Energy Recovery Unit
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEWUNIT: ERV-01
AREA:
Unit Data
Unit Manufacturer
RenewAire
Unit Model Number
EV300
Unit Serial Number
E134605R
ERV-01 / Exhaust Fan
Fan Type
Forward Curve
Fan Size
6'ID
Fan Class
1
Fan Arrangement
OWDI
ERV-01 / Supply Fan
Fan Type
Forward Curve
Fan Size
6'ID
Fan Class
1
Fan Arrangement
DWDI
Starter Data
ERV-01 / Exhaust Fan
Installed Thermal
Internal
ERV-01 / Supply Fan
Installed Thermal
Internal
Test Data
SF Total CFM Design
300 CFM
SF Total CFM Actual
312 CFM
SF OA CFM Design
300 CFM
SF OA CFM Actual
312 CFM
EF Total CFM Design
300 CFM
EF Total CFM Actual
311 CFM
EF OA CFM Design
300 CFM
EF OA CFM Actual
311 CFM
ERV-01 / Exhaust Fan
Fan RPM Actual
Direct Drive RPM
Motor Volts 1
122 Volts
Motor Amps 1
3.1 Amps
ERV-01 / Supply Fan
Fan RPM Actual
Direct Drive RPM
Motor Volts 1
122 Volts
Motor Amps 1
3.1 Amps
DATE: 1/9/2014
CONTACT: Emerson Moore
N E� BIB
2389
Tested By: Emerson Moore
Test Date: December 31, 2013
Motor Data
ERV-01 / Exhaust Fan
Motor HP
0.2 HP
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor FL Amps
3.3 Amps
ERV-01 / Supply Fan
Motor HP
0.2 HP
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor FL Amps
3.3 Amps
Sheave Data
ERV-01 I Exhaust Fan
Motor Sheave Make
Direct Drive
ERV-01 / Supply Fan
Motor Sheave Make
Direct Drive
Test Pressures
SF Fan SP In
-0.29 in. we
SF Fan SP Out
0.09 in. we
EF Fan SP In
-0.31 in. we
EF Fan SP Out
0.08 in. we
* Notes ERV-01 31-Dec-13 Emerson Moore Unit contains 1 motor and 2 blowers.
L.H. Finn and Associates
Pre -final Report Page 4 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEM/UNIT. F-1-201
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
2113A50185
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
735 CFM
Motor Volts Ti-T2
122 Volts
Amps Tt
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.09 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.07 In. wc.
F-1-201 Suooly Outlet Summary
DATE: 1 /912014
CONTACT: Emerson Moore
N J rB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outtet-01
Unit-1 B
R-1
12x6
200
248
242
124
121
Outlet-02
Unit-1B
R-1
12x6
150
222
188
148
125
Outlet-03
Unit-1B
R-1
8x4
50
40
62
80
124
Outlet-04
Unit-1B
R-1
8x4
50
62
60
124
120
Outlet-05
Unit-16
R-1
12x6
150
187
183
125
122
Totals :
-
-
-
600
759
735
127 %
123 %
* Notes
L. H. Finn and Associates
Pre -final Report Page 22 of 102
Lawrence H. Finn & Associates, Inc.
Energy Recovery Unit
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEM(UNIT: ERV-02
AREA:
Unit Data
Unit Manufacturer
RenewAire
Unit Model Number
EV300
Unit Serial Number
E134605R
Test Data
SF Total CFM Design
300 CFM
SF Total CFM Actual
312 CFM
SF OA CFM Design
300 CFM
SF OA CFM Actual
312 CFM
EF Total CFM Design
300 CFM
EF Total CFM Actual
311 CFM
EF OA CFM Design
300 CFM
EF OA CFM Actual
311 CFM
* Notes
SYSTEM/UNIT: ERV-03
AREA:
Unit Data
Unit Manufacturer
RenewAire
Unit Model Number
EV300
Unit Serial Number
E134605R
Test Data
SF Total CFM Design
300 CFM
SF Total CFM Actual
312 CFM
SF OA CFM Design
300 CFM
SF OA CFM Actual
312 CFM
EF Total CFM Design
300 CFM
EF Total CFM Actual
311 CFM
EF OA CFM Design
300 CFM
EF OA CFM Actual
311 CFM
* Notes
DATE: 1 /9/2014
CONTACT: Emerson Moore
NE BB
e- .
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Test Pressures
SF Fan SP In
-0.29 in. we
SF Fan SP Out
0.09 in. we
EF Fan SP In
-0.31 in. we
EF Fan SP Out
0.08 in. we
Tested By: Emerson Moore
Test Date: January 09, 2014
Test Pressures
SF Fan SP in
-0.29 in. we
SF Fan SP Out
0.09 in. we
EF Fan SP in
-0.31 in. we
EF Fan SP Out
0.08 in. we
L.H. Finn and Associates
Pie -final Report Page 5 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEWUNIT: F-1-101
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
2113A50176
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
806 CFM
Motor Volts T1-T2
122 Volts
Amps Tt
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.08 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.06 In, wc.
F-1-101 Supply Outlet Summary
DATE: 1 /9/2014
CONTACT: Emerson Moore
NTEB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-1B
R-1
12x6
200
258
266
129
133
Outlet-02
Unit-1B
R-1
12x6
150
195
197
130
131
Outlet-03
Unit-16
R-1
8x4
50
78
66
156
132
Outlet-04
Unit-1B
R-1
8x4
50
71
69
142
138
Outlet-05
Unit-1 B
R-1
12x6
150
219
208
146
139
Totals :
-
-
-
600
821
$06
137 %
1 134 %
* Notes
L.H. Finn and Associates
Pre-Ana/Report Page 6 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEMVNIT. F-1-102
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
2113A50190
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
730 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.091n. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.07 In. wc.
F-1-102 Supply Outlet Summary
DATE: 1/9/2014
CONTACT: Emerson Moore
r'
N E� BB
I.2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-1B
R-1
12x6
200
246
237
123
119
Outlet-02
Unit-1B
R-1
12x6
150
189
183
126
122
Outlet-03
Unit-1B
R-1
8x4
50
47
63
94
126
Outlet-04
Unft-1B
R-1
8x4
50
58
61
116
122
Outlet-05
Unit-1B
R-1
12x6
150
195
186
130
124
Totals:
I -
-
-
600
735
730
123 %
1 122 %
* Notes
L. H. Finn and Associates
Pre-line/Report Page 7 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEWUNIT: F-1-103
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
1813A46760
Filter Manufacturer
AirHandier
Filter Type
Pleated
Filter ay
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
783 CFM
Motor Volts T1-T2
122 Volts
Amps Tt
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.14 In. we.
E.S.P. In
-0.03 In. we.
E.S.P. Out
0.11 In. we.
F-1-103 Supply Outlet Summary
DATE: 1/9/2014
CONTACT: Emerson Moore
r�
N Ej BB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-1A
R-1
12x6
200
257
257
129
129
Outlet-02
Unit-1A
R-1
12x6
150
205
202
137
135
Outlet-03
Unit-1A
R-1
8x4
50
63
64
126
128
Outlet-04
Unit-1A
R-1
8x4
50
64
65
128
130
Outlet-05
Unit-1A
R-1
12x6
150
195
195
130
130
Totals :
-
-
-
600
784
783
131 %
1 131 °k
* Notes
L.H. Finn and Associates
Pre -final Report Page 8 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTENdUNIT. F-1-104
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
2113A50189
Filter Manufacturer
AirHandier
Filter Type
Pleated
Filter Qty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
744 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.12 In. wc.
E.S.P. in
-0.02 In. wc.
E.S.P. Out
0.10 In. wc.
F-1_10d Sunniv Outlet Summary
DATE: 1 /9/2014
CONTACT: Emerson Moore
NEj 11
BB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 52 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-11-11
R-1
12x6
200
239
247
120
124
Outlet-02
Unit-11-11
R-1
12x6
150
195
187
130
125
Outlet-03
Unit-11-11
R-1
8x4
50
73
65
146
130
Outlet-04
Unit-11-11
R-1
8x4
50
54
61
108
122
Outtet-05
Unit-11-11
R-1
12x6
150
197
184
131
123:]
Totals :
I -
-
-
600
758
7"
126 %
12401,
Notes
L.H. Finn and Associates
Pie -final Report Page 9 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTEWUNIT: F-1-105
AREA:
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2804OS141110
Unit Serial Number
2113A50188
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter Oty
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
842 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.10 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.08 In. we.
F-1-105 Supply Outlet Summary
DATE: 1/9/2014
CONTACT: Emerson Moore
NE BB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 1/3
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size LxW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-2B
R-1
12x6
100
142
140
142
140
Outlet-02
Unit-2B
R-1
12x6
100
152
143
152
143
Outlet-03
Unit-2B
R-1
12x6
100
127
145
127
145
Outlet-04
Unit-2B
R-1
12x6
100
144
137
144
137
Outlet-05
Unit-2B
R-1
12x6
100
142
137
142
137
Outlet-06
Unit-2B
R-1
8x4
50
72
71
144
142
Outlet-07
Unit-2B
R-1
8x4
50
69
69
138
138
Totals:
-
-
600
848
842
141 %
140 %
' Notes
L.H. Finn and Associates
Pre -final Report Page 10 of 102
Lawrence H. Finn & Associates, Inc.
Fan Coil
PROJECT: Legacy Senior Residences
LOCATION: Fort Collins, CO
SYSTENUUNIT. F-1-106
AREA:
'
Unit Data
Unit Manufacturer
Carrier
Unit Model Number
59SC2B040S141110
Unit Serial Number
1813A46777
Filter Manufacturer
AirHandler
Filter Type
Pleated
Filter City
1
Filter Size
20x2Ox2
Unit Location
Closet
Test Data
Total CFM Design
600 CFM
Total CFM Actual
780 CFM
Motor Volts T1-T2
122 Volts
Amps T1
2.7 Amps
Fan RPM Actual
Low Speed RPM
Unit E.S.P. Actual
0.13 In. wc.
E.S.P. In
-0.02 In. wc.
E.S.P. Out
0.11 In. wc.
F-1-106 Supply Outlet Summary
DATE: 1/9/2014
CONTACT: Emerson Moore
NTEB
2389
Tested By: Emerson Moore
Test Date: January 09, 2014
Motor Data
Motor Manufacturer ANA
Motor HP 113
Motor Phase 1
Motor Hertz 60 Hz
Motor Rated Volts 115
Motor FL Amps 5.2 Amps
Sheave Data
Motor Sheave Make Direct Drive
System / Unit
Area Served
Outlet
Type
Size L.xW / D
AK
Factor
Maximum
Design
Prelim
Reading
Maximum
Final
% Prelim
Deviation
% Final
Deviation
Outlet-01
Unit-11-12
R-1
12x6
100
129
129
129
129
Outlet-02
Unit-11-12
R-1
12x6
100
137
132
137
132
Outlet-03
Unit-1H2
R-1
12x6
100
139
133
139
133
Outlet-04
Unit-11-12
R-1
12x6
100
128
129
128
129
Outlet-05
Unit-11-12
R-1
12x6
100
131
130
131
130
Outlet-06
Unit-11-12
R-1
8x4
50
56
63
112
126
Outlet-07
Unit-11-12
R-1
8x4
50
60
64
120
128
Totals :
-
-
-
600
780
780
130 %
130 %
* Notes
L.H. Finn and Associates