HomeMy WebLinkAbout4703 PRAIRIE VISTA DR - DISCLOSURES - 9/12/2013BUILDING LEAKAGE TEST
Date of Test: 9/12/2013 Test File: Paradise Homes 4703 Praire Vista Dr- BD
Customer: Paradise Homes Technician: Paul Higman
Project Number:
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Areas:
Building Address: 4703 Prairie Vista Dr
Fort Collins, CO 80526
1655 CFM50 (+/- 0.4 %)
3.17 ACH50
0.4736 CFM501ft2 floor area
156.2 in2 ( +/- 1.7 %) Canadian EgLA @ 10 Pa
79.1 in2 (+/- 2.8 %) LBL ELA @ 4 Pa
0
3. Building Leakage Curve:
Flow Coefficient (C) = 104.8 ( +/- 4.4 %)
Exponent (n) = 0.705 ( +/- 0.012)
Correlation Coefficient = 0.99902
4. Test Settings: Test Standard: CGSB
Test Mode: Depressurization
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 81.2 CFM
0.16 ACH
2. Estimated Design Infiltration Rate: Winter: 130.8 CFM Summer: 86.8 CFM
0.25 ACH 0.17 ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 9/12/2013 Test File: Paradise Homes 4703 Praire Vista Dr- BD
Building Information Location Climate Information
Volume
31353
Surface Area
_
Floor Area
3495
Height
18
# of Bedrooms
2
# of Occupants
Year of Construction
2013
Wind Shield
M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Ventilation Weather Factor
0.87
Energy Climate Factor
17.00
Heating Degree Days
6128
Cooling Degree Days
297
Design Winter Wind Speed
7.3 mph
Design Summer Wind Speed
1 9.4 mph
Design Winter Temp Diff
73 deg F
Design Summer Temp Diff
15 deg F
Equipment Information
Type
Manufacturer
Model
Serial Number
Custom Calibration Date
Fan
Energy Conservatory
Model 3 (110V)
Default
Micromanometer
Energy Conservatory
DG700
You created this PDF from an application that is not licensed to print to novaPDF printer (hfp://www.novapdf.com)
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 9/12/2013 Test File: Paradise Homes 4703 Praire Vista Dr- BD
Depressurization Test:
Environmental Data
Indoor Temperature (OF) Outdoor Temperature (OF)
72.0 85.0
Data Points - Data Entered Manually
Nominal Baseline Adjusted Fan
Building Pressure Building Pressure Pressure
(Pa) (Pa) (Pa)
Nominal Adjusted
Flow Flow Fan
(cfm) (cfm) % Error Configuration
-2.7
n/a
n/a
-61.4
-59.0
105.0
1839
1861
0.1
Ring A
-54.9
-52.5
88.4
1691
1712
-0.1
Ring A
-49.3
-46.9
75.0
1561
1580
-0.1
RingA
-45.4
-43.0
68.0
1488
1506
1.2
Ring A
-40.4
-38.0
53.8
1327
1343
-1.5
Ring A
-35.3
-32.9
44.1
1205
1220
-1.0
Ring A
-30.3
-27.9
36.1
1092
1105
0.8
Ring A
-25.5
-23.1
28.2
969
981
2.2
RingA
-21.0
-18.6
182.2
800
810
-1.7
Ring B
-2.1
n/a
n/a
Deviations from Standard CGSB - Test Parameters
None
You created this PDF from an application that is not licensed to print to novaPDF printer (hftp://www.novapdf.com)
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 9/12/2013 Test File: Paradise Homes 4703 Praire Vista Dr- BD
Comments
House WRT Garage =-48.7pa
You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)
Date of Test: 9/12/2013
Customer: Paradise Homes
Test Results
1. Airflow at 50 Pascals:
(50 Pa = 0.2 w.c.)
2. Leakage Areas:
3. Building Leakage Curve:
4. Test Settings:
BUILDING LEAKAGE TEST
Test File: Paradise Homes 4703 Praire Vista Dr- BD
Technician: Paul Higman
Project Number:
Building Address: 4703 Prairie Vista Dr
Fort Collins, CO 80526
1655 CFM50 (+/- 0.4 %)
3.17 ACH50
0.4736 CFM50/ft2 floor area
156.2 in2 ( +/- 1.7 %) Canadian EgLA @ 10 Pa
79.1 in2 (+/- 2.8 %) LBL ELA @ 4 Pa
Flow Coefficient (C) = 104.8 ( +/- 4.4 %)
Exponent (n) = 0.705 ( +/- 0.012 )
Correlation Coefficient = 0.99902
Test Standard: CGSB
Test Mode: Depressurization
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate:
2. Estimated Design Infiltration Rate:
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
81.2 CFM
0.16 ACH
Winter: 130.8 CFM Summer: 86.8 CFM
0.25 ACH 0.171ACH
You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 9/12/2013 Test File: Paradise Homes 4703 Praire Vista Dr- BD
Building Information Location Climate Information
Volume
31353
Surface Area
Floor Area
3495
Height
18
# of Bedrooms
2
# of Occupants
Year of Construction
2013
Wind Shield
M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Ventilation Weather Factor
0.87
Energy Climate Factor
17.00
Heating Degree Days
6128
Cooling Degree Days
297
Design Winter Wind Speed
7.3 mph
Design Summer Wind Speed
9.4 mph
Design Winter Temp Diff
73 deg F
Design Summer Temp Diff
15 deg F
Equipment Information
Type
Manufacturer
Model
Serial Number
Custom Calibration Date
Fan
Energy Conservatory
Model 3 (110V)
Default
Micromanometer
Energy Conservatory
DG700
You created this PDF from an application that is not licensed to print to novaPDF printer (hftp://www.novapdf.com)
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 9/12/2013 Test File: Paradise Homes 4703 Praire Vista Dr- BD
Depressurization Test:
Environmental Data
Indoor Temperature (OF) Outdoor Temperature (OF)
72.0 85.0
Data Points - Data Entered Manually
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration
-2.7
n/a
n/a
-61.4
-59.0
105.0
1839
1861
0.1
Ring A
-54.9
-52.5
88.4
1691
1712
-0.1
Ring A
-49.3
-46.9
75.0
1561
1580
-0.1
Ring A
-45.4
-43.0
68.0
1488
1506
1.2
Ring A
40.4
-38.0
53.8
1327
1343
-1.5
Ring,A
-35.3
-32.9
44.1
1205
1220
-1.0
Ring A
-30.3
-27.9
36.1
1092
1105
0.8
Ring A
-25.5
-23.1
28.2
969
981
2.2
Ring A
-21.0
-18.6
182.2
800
810
-1.7
Ring B
-2.1
n/a
n/a
Deviations from Standard CGSB - Test Parameters
None
i
You created this PDF from an application that is not licensed to print to novaPDF printer (hftp://www.novapdf.com)
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 9/12/2013 Test File: Paradise Homes 4703 Praire Vista Dr- BD
Comments
House WRT Garage =-48.7pa
You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)
$13011sb
City of
FOit C011inS Planning, Development & Transportation Services
Community Development & Neighborhood Services
Simulated Performance Alternative (SPA) Cover Sheet
Submittal and Rating Type
Stock Plan Permit — Projected Worst -Case Rating Builder Model: Importe
Lot -specific Permit - Projected Rating Address:
x❑completed Home — Confirmed Rating Address: 4703 Prairie vista Dr
Data Required for All SPA Ratings
Builder: Paradise Homes Rating Firm: Thermal Concepts
Energy rater:
Paul Higman Date: 9-12-13
Duct Location Inputs
Location
Su ply
Return
% Area
R-Value
% Area
R-Value
Inside conditioned space
100
100
Utility Rates
Energy Source
I Service charge
Rate
Electricity
5 $/month
0.09 $/kWh
Natural gas
10 $/month
0.65 $/therm
Spaces considered outside the thermal boundary:
Additional Information for Stock Plan Permit — Projected Worst -Case Rating
"Worst -case" configuration:
Foundation type(s)
Options included
Orientation of front elevation
Attach REM/Rate Fort Collins 2012 Annual Energy Cost Compliance report
Attach REM/Rate Energy Code Inspection Checklist
Additional Information for Lot -Specific Permit — Projected Rating
Attach REM/Rate Fort Collins 2012 Annual Energy Cost Compliance report
Attach REM/Rate Energy Code Inspection Checklist
Additional Information for Completed Home — Confirmed Rating
Attach REM/Rate Fort Collins 2012 Annual Energy Cost Compliance report
(Utility rates reflected in this report must be City -approved rates on lot -specific permit application date.)
Attach Home Energy Rating Certificate
Updated 11109/2012