HomeMy WebLinkAbout415 NOQUET CT - DISCLOSURES - 6/6/2013 (4)Date of Test: 6-6-13
Customer: Encore Homes
Windsor, CO 80550
Test Results
1. Airflow at 50 Pascals
(50 Pa = 0.2 w.c.)
2. Leakage Areas:
3. Building Leakage Curve:
BUILDING LEAKAGE TEST
Thermal Concepts
6617 S. College Ave
Fort Collins, CO 80525
Test File: Encore Homes 415 Noquet-BD
Technician: Paul Higman
Project Number:
Building Address: 415 Noquet
Fort Collins, CO 80524
1045 CFM50 (+/- 1.2 %)
3.81 ACH50
0.6663 CFM50/ft2 floor area
61.9 in2 (+/- 4.4 %) Canadian EgLA @ 10 Pa
24.0in2(+/-7.3%)LBLELA@4Pa
Flow Coefficient (C) = 21.3 (+/- 11.7 %)
Exponent (n) = 0.995 ( +/- 0.032 )
Correlation Coefficient = 0.99742
4. Test Settings: Test Standard: CGSB
Test Mode: Depressurization
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 23.8 CFM
0.09 ACH
2. Estimated Design Infiltration Rate: Winter: 40.6 CFM
0.15ACH
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
Summer: 22.8 CFM
0.08 ACH
BUILDING LEAKAGE TEST Page 2 of 4
Date of Test: 6-6-13 Test File: Encore Homes 415 Noquet-BD
Building Information Location Climate Information
Volume
16474
Surface Area
Floor Area
1569
Height
16
# of Bedrooms
3
# of Occupants
Year of Construction
2013
Wind Shield
M
Heating and Cooling Cost and Efficiency Information
Heating Fuel Gas
Heating Fuel Cost
Heating Efficiency %
Cooling Fuel Cost
Cooling SEER
Ventilation Weather Factor
0.87
Energy Climate Factor
17.00
Heating Degree Days
6020
Cooling Degree Days
287
Design Winter Wind Speed
9.0 mph
Design Summer Wind Speed
7.0 mph
Design Winter Temp Diff
69 deg F
Design Summer Temp Diff
16 deg F
Equipment Information
Type
Manufacturer
Model
Serial Number
Custom Calibration Date
Fan
Energy Conservatory
Model 3 (110V)
Default
Micromanometer
Energy Conservatory
DG700
BUILDING LEAKAGE TEST Page 3 of 4
Date of Test: 6-6-13 Test File: Encore Homes 415 Noquet-BD
Depressurization Test:
Environmental Data
Indoor Temperature (OF) Outdoor Temperature (OF)
67.0 68.0
Data Points - Data Entered Manually
Nominal Baseline Adjusted Fan Nominal Adjusted
Building Pressure Building Pressure Pressure Flow Flow Fan
(Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration
-1.3
n/a
n/a
-50.3
-48.9
30.0
999
1000
-2.2
Ring A
-45.0
-43.6
25.5
922
923
1.2
Ring A
-40.7
-39.3
201.6
841
842
2.3
Ring B
-35.6
-34.2
149.4
725
726
1.3
Ring B
-30.1
-28.7
98.9
591
592
-1.7
Ring B
-25.0
-23.6
67.8
490
490
-1.0
Ring B
-20.9
-19.5
45.7
403
403
-1.5
Ring B
-1.5
n/a
n/a
Deviations from Standard CGSB - Test Parameters
- Test data was not collected at all 8 recommended target building pressures.
a
BUILDING LEAKAGE TEST Page 4 of 4
Date of Test: 6-6-13 Test File: Encore Homes 415 Noquet-BD
Comments
House wrt Garage =-47.3pa
House wrt Mach Rm= outside conditioned spa