Loading...
HomeMy WebLinkAbout438 BANNOCK ST - DISCLOSURES - 3/20/2013BUILDING LEAKAGE TEST Thermal Concepts 6617 S. College Ave Fort Collins, CO 80528 Date of Test: 3-20-13 Test File: Encore Homes 438 Bannock -BD Customer: Encore Homes Technician: Paul Higman Project Number: Windsor, CO 80550 Building Address: 438 Bannock Fort Collins, CO 80524 Test Results 1. Airflow at 50 Pascals: 1213 CFM50 (+/- 0.5 %) (50 Pa = 0.2 w.c.) 4,00 ACH50 0.7651 CFM50/ft2 floor area 2. Leakage Areas: 86.3 in2 (+/- 2.4 %) Canadian EgLA @ 10 Pa 37.2 in2 (+/_ 3.9 %) LBL ELA @ 4 Pa 3. Building Leakage Curve: Flow Coefficient (C) = 38.6 ( +/- 6.2 %) Exponent (n) = 0.881 ( +/- 0.016 ) Correlation Coefficient = 0,99896 4. Test Settings: Test Standard: CGSB Test Mode: Depressurization Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 36.8CFM 0.12 ACH 2. Estimated Design Infiltration Rate: Winter: 62.7 CFM Summer: 35.2 CFM 0.21 ACH 0.12 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 3-20-13 Test File: Encore Homes 438 Bannock -BD Building Information Location Climate Information Volume 18207 Surface Area Floor Area 1585 Height 16 # of Bedrooms 3 # of Occupants Year of Construction 2013 Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6020 Cooling Degree Days 287 Design Winter Wind Speed 9.0 mph Design Summer Wind Speed 7.0 mph Design Winter Temp Diff 69 deg F Design Summer Temp Diff 16 deg F Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 3-20-13 Test File: Encore Homes 438 Bannock -BD Depressurization Test: Environmental Data Indoor Temperature (OF) Outdoor Temperature (OF) 68.0 27.0 Data Points - Data Entered Manually Nominal Baseline Adjusted Fan Nominal Adjusted Building Pressure Building Pressure Pressure Flow Flow Fan (Pa) (Pa) (Pa) (cfm) (cfm) % Error Configuration 3.1 n/a n/a -55.4 -55.8 59.4 1393 1338 0.2 Ring A -50.3 -50.6 48.4 1261 1211 -1.3 Ring A -45.2 -45.6 41.6 1171 1125 0.7 Ring A -40.3 -40.6 33.3 1050 1008 -0.2 Ring A -34.2 -34.6 238.4 914 878 0.3 Ring B -31.2 -31.6 210.8 860 826 2.2 Ring B -25.3 -25.7 139.6 701 673 -0.0 Ring B -20.2 -20.6 88.7 560 538 -2.9 Ring B -2.4 n/a n/a Deviations from Standard CGSB - Test Parameters None BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 3-20-13 Test File: Encore Homes 438 Bannock -BD Comments House WRT Garage =-45.2pa house WRT mech room = outside conditioned space