Residential Mechanical Systems Performance Testing Submittal Form
This form is a record of testing targets and results, with Pass/Fail outcomes. For information on measurement tools and testing techniques, see the "Residential New
Construction Mechanical Systems Testing Guide." The guide and this form may be periodically updated; check the Building Services web site for the current version.
This form must be completed and signed by an "Approved Agency," and submitted to Building Services as a requirement for receiving a C.O.
Color key
Measured value to
Target or limit
compare with target o
Pass
Fail
Caution
Other data
Address 438 Bannock
Builder
HVACcontractoi Northern Colorado Air
Testing date(s) 7 3
Local2. ••Ventilation
Bath exhaust
Flow box _ Flow collar
Airflow measurement meth passive flow hood Pitot tube traverse
Temperature of air throng Indicated flow to Volumetric flow multipli it 098
measurement too 68 F @ 5000', air temperature
:1
Measured Exhaust Airflow
Minimum
Operation
Airflow
Indicated
Volumetric Flow
Exhaust Pickup location
Intermittent or
Requirement
Flow
(CFM 5,000')
PassFail
Continuous
(CFM)
(CFM 5000')
masterBath
rmit _ Contin
50 cfm
56
161.488
❑
U.LBath
termit _Contin
50 cfm
59
64.78
❑
Pwdr
ntermit _ Contin
50 cfm
67
73.56—
❑
Intermit Contin
❑
❑
Intermit Contin
❑
❑
Intermit Contin
❑
❑
Intermit Contin
❑
❑
Intermit Contin
❑
❑
Kitchen exhaust
Oven fuel as y> v
lectric 1 �
Exhaust airflow Minimum exhaust LowequirementCFM 5"'
operatioril Intermittent Continuous
Measured airflow
Airflow measurement method Flow box _ Flow collar
Passive flow hood Pitot tube traverse
Temperature of air through Indicated flow to Volumetric flow multiplier
measurement tool F @ 5000% air temperature
Indicated flow FM Volumetric flowCFM 5000' ❑ Pass ❑ Fail
Testing notes (fan speed, maskini
flow out of range, .. .
Mechanical Systems Performance Testing Submittal FormV20120321
1 of 6
Systems other than sub -structural floor exhaust
Minimum exhaust airflow requirement
45
FM 5000'
Indicated to
Measured Airflow
Volumetric
Design Airflow
Measurement
Measurement Location +
Flow
Indicated Flow Volumetric
(CFM 5000')
Method
Air Temperature (F)
Multiplier
(CFM) Flow
Pass/Fail
(CFM 5000')
w box
Total exhaust airflow
— Passive flow hood
_ Flow collar
Pilot tube traverse
pwdr
1.098
67
73.56
_ Flow collar
Total
_ Pitot tube traverse
supply airflow
Flow box
Passive flow hood
For systems in which supply airflow is circulatedohe air handler fan, fan speed for measuremen Heat Cooling Continuous fan
Balanced airflow in balanced systems
Average of measured suppl
and exhaust flow CFM 5000'
i I
Sub -structural floor exhaust
Design airflow
❑ Pass
CFM 5000'
Target flow rang to CFM 5000'
(average +/- 15 % )
❑ Fail
Measured airflow
_ Flow box Flow collar
Airflow measurement meth Passive flow hood Pitot tube traverse
Temperature of air through F Indicated flow to Volumetric flow multiplier
measurement tool @ 5000', air temperature
Indicated flow CFM Volumetric flow CFM 5000' Pass Fail
Cooling Duct Leakage
Temperature of air throug F Indicated flow to Volumetric flow multiplier
measurement too 68 @ 5000', air temperature 1.098
House conditioned floor area 1 585 sf
Maximum Allowed Duct Leakage I Measured Duct Leakage
Test Parameter and Conditions
Normalized Leakage
(CFM25/ 100 sf)
Absolute
Leakage
(CFM25)
Indicated Flow
(CFM25)
Volumetric
Flow
(CFM25 5000')
Measurement
Timing
Air Handler
Pass/Fail
Total leakage
Rough -in
Excluded
4
❑
❑
Total leakage
Rough -in
Included
6
❑
❑
tal leakage
[Leakage
Complete
Included
12
❑
❑
to outdoorsC
mplete
Included
8
127
1 27
29.64
❑
Mechanical Systems Performance Testing Submitui fo V20120321 2 0! 6
Filter type
Br_koch Type / styl Dis osable I Thici. 1 " Inches MERV (optionen�
Static pressures (OPTIONAL)
Mode: Heating
Cooling
I
Continuous Fan
Fan speed tap
,
Humidifier bypass Open _Closed
GP AC coil=
X—All registers open
'
Zone dampers open
�
-
P=-
1
1p filter
jOP Total ESP =
P=-
Cooling: Measured air flow through indoor coil using flow grid
Design cooling airflo A652 ICFM 5000' Target airflow limits (design +/- 15%) 1554 to 750 JCFM 5000'
Measured airflow
Cooling fan speed tap Med-High
Temperature of air throug
measurement too 68 _J
NSOP 38 Pa TFSOP Pa
Measured airflow, no adjustments or correction CFM
Volumetric flo 712 CFM 5000' Pass
Flow grid plate siz 14 20
Indicated flow to Vo umetric flow multipli r
@ 5000', air temperature 1.098
Flow Resistance Correction Facto DIG 7W
Adjusted (indicated) airflo 64t8 FM
❑ Fail
Heating: Gas manifold pressure
OEM manifold pressu 5 IWC Target manifold pressure limits (spec +/- 5%) �J to �t� IWC
specification, 5000
Measured manifold pressur IWC N6 Pass El Fail
Heating: Temperature rise
OEM temperature rise limit to�D F
Measured temperature rise
Return air 68 IF
Temp rise 48 IF
Supply air 1116 ::::IF
Pass Fail
❑ Caution: Temp rise within
10 F of top of range
Mechanical Systems Performance Testing SubmittaiWo V20120321 3 of 6
(This section under development, not yet being enforced)
Supply air flows (This section under development, not yet being enforced)
Pressure balance
Pressure differenoe limit, room -to -core -$ to Pa
Room
Measured pressure
drop (Pa)
Pass
Fail
Master Bed room
+2.1
P6-
❑
Bedroom 2 front
+1.6
Ar-
❑
Bedroom 3 Back
+1.7
6iZL-
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
Mechanical Systems Perfonnance'lesting SubmittrAl-o V20120321 4 of 6
8. Combustion Safety
Outdoor temperature F
Worst -case depressurization testing A,121
House setup
Tested appliances
_ # of bath fans on These doors are closed:
_ Vented range hood on
Clothes dryer on ---
Air handler on
Other fans on
Appiiana
Type
Locatioi
CAZ pressure
BPI depressurization limit Pa wrt outside
Measured net CAZ depressurizationPa wrt outside
OK (less negative) I Caution (more negative)
Spillage
BPI maximum limit seconds
Measured spillage duration seconds
Pass = duration not exceeding limit
Draft pressure
BPI limit Pa wrt CAZ
Measured Pa wrt CAZ
Pass = pressure more negative than limit
CO concentration in undiluted flue gas
BPI maximum limit ppm
Measured CO ppm
Pass = CO level not exceeding limit
Caution = CO level 25 to 100 ppm
_ Draft -hood
Induced -draft
_ Draft -hood
Induced -draft
Draft -hood
Induced -draft
■
60
60
60
❑
Vass
❑ ail
❑
Pass
I Ej�il
❑
ass
I ❑ ail
❑ Pass ❑ ail ❑ Pass I Lflail ❑ ass I ❑ Vail
100
100
100
❑
ass
I ❑ Vail
❑
Pass
I 01iii
❑ fass
❑ ail
❑
Kaution
❑
Caution
1 ❑ aution
Mechanical Systems Performance Testing Submittakfo V20120321 _ _.
System controls operating per design intent
Fail
Local exhaust
❑
Whole -house ventilation
❑
Sub -structural floor exhaust
❑
❑
Heating
❑
Cooling
`� ,--,,�r
lL9�
❑
Approved Agency (technician perfor
Name (print) Paul Higman
Title Energy Rater
Company I Thermal
Signature and Date
HVAC contractor
Name (print)
Title
Company
Signature and Date
Ins license
Allied
ad testino documented on this
03/20/201
Thomas
Northern Colorado A
03/20/201
Mechanical Systems Performance Testing SubmittaWo V20120321 6 of 6