AIR LEAKAGE REPORT
Date: January 28, 2013 Rating No.: Worst Case Scenario DE
Building Name:
2015
Rating Org.:
Burgess Inc.
Owners Name:
DR Horton
Phone No.:
303-3004527
Property:
839 Campfire Drive
Rater's Name:
Robert Hutchinson
Address:
Fort Collins, CO80524
Raises No.:
7470933
Builders Name:
DR Horton
Weather Site:
Ft. Collins, CO
Rating Type:
Confirmed
File Name:
839 Campfire Drive.blg
Rating Date:
1/28/2013
Whole House Infiltration
Duct Leakage
Ventilation
Blower door test
Heating
Cooling
NaturalACH:
0.17
0.13
ACH @ 50 Pascals:
2.69
2.69
CFM @ 25 Pascals:
726
726
CFM @ 50 Pascals:
1140
1140
Eff. Leakage Area: [sq.in]
62.6
62.6
Specific Leakage Area:
0.00014
0.00014
ELAM 00 sf shell: [sq.in]
0.85
0.85
Leakage to Outside Units
Hvac
CFM @ 25 Pascals:
0
CFM25 / CFMfan:
0.0000
CFM25 / CFA:
0.0000
CFM per Std 152:
N/A
CFM per Std 152 / CFA:
N/A
CFM @ 50 Pascals:
0
Eff. Leakage Area: [sq.in]
0.00
Thermal Efficiency:
N/A
Total Duct Leakage Units
CFM251CFA
Total Duct Leakage:
0.0477
Mechanical:
Exhaust Only
Sensible Recovery Eff. (%):
0.0
Total Recovery Eff. (%):
0.0
Rate (cfm):
60
Hours/Day:
24.0 j
Fan Watts:
11.3
Cooling Ventilation:
Natural Ventilation
ASHRAE 62.2 - 2010 Ventilation Requirements
For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable IndoorAir Quality in
Low -Rise Residential Buildings, a minimum of60 cfm of mechanical ventilation must be provided continuously,
24 hours per day. Alternatively, an intermittently operating mechanical ventilation system may be used if the
ventilation rate is adjusted accordingly. For example, a 121 cfin mechanical ventilation system would need to
operate 12 hours per day, as long as the system operates to provide required average ventilation once each
hour.
REM/Rate - Residential Energy Analysis and Rating Software v13.0
This information does not constitute any warranty of energy cost or savings.
0 1985-2012 Architectural Energy Corporation, Boulder, Colorado.
BUILDING LEAKAGE TEST
Date of Test: 1/28/2013 Technician: Doug Groff
Test File: DR Horton Blower door
Customer: DR Horton Building Address: 839 Campfire Drive
7600 E Orchard Rd #350-S Fort Collins, Colorado 80524
Greenwood Village, Colorado 80111
Phone
Test Results
1. Airflow at 50 Pascals: 1107 CFM (+/ 0.1 %)
(50 Pa = 0.2 w.c.) 2.61 ACH
0.36 CFM per ft2 floor area
2. Leakage Areas: 261.0 in2 (+/ 0.6 %) Canadian EgLA @ 10 Pa
222.1 in2 (+/ 1.0 %) LBL ELA @ 4 Pa
3. Minneapolis Leakage Ratio: 0.15 CFM50 per ft2 surface area
4. Building Leakage Curve: Flow Coefficient (C) = 647.9 ( +/- 1.5 %)
Exponent (n) = 0.137 ( +/- 0.004 )
Correlation Coefficient = 0.99883
5. Test Settings: Test Standard: = CGSB
Test Mode: = Depressurization
Equipment = Model 3 Minneapolis Blower Door
Infiltration Estimates
1. Estimated Average Annual Infiltration Rate: 230.1 CFM
0.54 ACH
2. Estimated Design Infiltration Rate: Winter: 375.3 CFM
0.89 ACH
Summer: 213.3 CFM
0.50 ACH
3. Recommended Whole Building Mechanical 0.0 CFM
Ventilation Rate: (based on ASHRAE 62.2)
Cost Estimates
1. Estimated Cost of Air Leakage for Heating:
2. Estimated Cost of Air Leakage for Cooling:
BUILDING LEAKAGE TEST Page 2
Date of Test: 1/28/2013 Test File: DR Horton Blower door
Building Conditions
Inside Temperature:
67 deg F
Heating Fuel:
Gas
Outside Temperature:
32 deg F
Heating Fuel Cost:
# of Stories
2.0
Heating Efficiency:
Heating Degree Days:
6020
Wind Shield:
M
Cooling Fuel Cost:
# of Occupants
Cooling SEER:
Cooling Degree Days:
287
# of Bedrooms:
3.0
Volume:
25437 ft3
Ventilation Weather Factor:
0.87
Surface Area:
7323 11:2
Energy Climate Factor:
17.0
Floor Area:
3043 112
Design Winter Wind Speed:
9.0 mph
Design Winter Temp Diff:
69 deg F
Design Summer Wind Speed:
7.0 mph
Design Summer Temp Diff:
16 deg F
Comments
Garage WRT House: 45.0 Pa @ 50 Pa
M
BUILDING LEAKAGE TEST Page 3
Date of Test: 1 /28/2013 Test File: DR Horton Blower door
Data Points: Data Entered Manually
Nominal
Temperature
Building
Fan Pressure
Nominal
Adjusted
Fan Baseline
Pressure (Pa)
(Pa)
Flow
Flow
% Error
Configuration Std Dev (Pa)
-1.7
n/a
+/ 0.00
-65.0
42.6
1185
1145
0.1
Ring A
-60.0
41.5
1170
1130
-0.0
Ring A
-55.0
40.5
1155
1116 .
-0.1
Ring A
-50.0
39.4
1140
1101
-0.1
Ring A
-45.0
38.3
1125
1087
0.1
Ring A