Loading...
HomeMy WebLinkAbout421 BANNOCK ST - DISCLOSURES - 1/19/2013 (2)Date of Test: 1-19-13 Customer: Encore Homes Windsor, CO 80550 BUILDING LEAKAGE TEST Thermal Concepts 6617 S. College Ave Fort Collins, CO 80525 Test File: Encore Homes 421 Bannock BD Technician: Paul Higman Project Number: Building Address: 421 Bannock Fort Collins, CO 80524 Test Results 1. Airflow at 50 Pascals: 1002 CFM50 (+/- 1.2 %) (50 Pa = 0.2 w.c.) 3.65 ACH50 0.6387 CFM50/ft2 floor area . 2. Leakage Areas: 60.8 in2 (+/- 4.4 %) Canadian EgLA @ 10 Pa 23.9in2(+/-7.3%)LBLELA@4Pa 3. Building Leakage Curve: Flow Coefficient (C) = 21.7 ( +/- 11.7 %) Exponent (n) = 0.980 ( +/- 0.032 ) Correlation Coefficient = 0.99733 4. Test Settings: Test Standard: CGSB Test Mode: Depressurization Infiltration Estimates 1. Estimated Average Annual Infiltration Rate: 23.7 CFM 0.09 ACH 2. Estimated Design Infiltration Rate: Winter: 40.4 CFM Summer: 22.7 CFM 0.15 ACH 0.08 ACH Cost Estimates 1. Estimated Cost of Air Leakage for Heating: 2. Estimated Cost of Air Leakage for Cooling: BUILDING LEAKAGE TEST Page 2 of 4 Date of Test: 1-19-13 Test File: Encore Homes 421 Bannock BD Building Information Location Climate Information Volume 16474 Surface Area Floor Area 1669 Height 16 # of Bedrooms 3 # of Occupants Year of Construction Wind Shield M Heating and Cooling Cost and Efficiency Information Heating Fuel Gas Heating Fuel Cost Heating Efficiency % Cooling Fuel Cost Cooling SEER Ventilation Weather Factor 0.87 Energy Climate Factor 17.00 Heating Degree Days 6020 Cooling Degree Days 287 Design Winter Wind Speed 9.0 mph Design Summer Wind Speed 7.0 mph Design Winter Temp Diff 69 deg F Design Summer Temp Diff 16 deg F Equipment Information Type Manufacturer Model Serial Number Custom Calibration Date Fan Energy Conservatory Model 3 (110V) Default Micromanometer Energy Conservatory DG700 BUILDING LEAKAGE TEST Page 3 of 4 Date of Test: 1-19-13 Test File: Encore Homes 421 Bannock BD Depressurization Test: Environmental Data Indoor Temperature (OF) Outdoor Temperature (OF) 62.0 29.0 Data Points - Data Entered Manually Nominal Baseline Adjusted Building Pressure Building Pressure (Pa) (Pa) Fan Pressure (Pa) Nominal Flow (cfm) Adjusted Flow (cfm) % Error Fan Configuration -1.1 n/a n/a -50.3 -49.1 285.3 999 967 -1.9 Ring B -45.0 -43.9 242.6 922 892 1.3 Ring B -40.7 -39.6 201.6 841 814 2.2 Ring B -35.6 -34.5 149.4 725 702 0.9 Ring B -30.1 -29.0 98.9 591 572 -2.5 Ring B -25.0 -23.9 67.8 490 474 -2.3 Ring B -20.9 -19.8 50.4 423 409 1.5 Ring B -1.2 n/a n/a Deviations from Standard CGSB - Test Parameters - Test data was not collected at all 8 recommended target building pressures. BUILDING LEAKAGE TEST Page 4 of 4 Date of Test: 1-19-13 Test File: Encore Homes 421 Bannock BD Comments House wrt Garage =-47.4pa House wrt Mech Rm=outside conditioned space