HomeMy WebLinkAbout4700 BOARDWALK DR - SPECIAL INSPECTIONS - 11/14/2012BALANCE REPORT
PROJECT:
SAM'S `CLUB #6633
FORT COLLINS, CO
&-q-700 6oarc4�a 1 k Dr -
PREPARED FOR: ' \
HEATH CONSTRUCTION
REPORT ISSUE DATE:
NOVEMBER 14, 2012
AR/ PROJECT NO.:
12
PREPARED Y.-
O=AIR- RIGHT, INC. _-
REM
-
- i -
=AIR- RIGHT, INC. _-
TEST, ADJUST, AND BALANCE REPORT
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND
WAS OBTAINED IN COMPLIANCE WITH NEBB PROCEDURAL STANDARDS. ANY VARIANCES FROM THE
DESIGN REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT.
THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS REPORT IS CERTIFIED TO BE
ACCURATE AND COMPLETE, TO THE EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED
THROUGHOUT THIS SURVEY.
THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NEBB
"PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS"
AND THE PROJECT SPECIFICATIONS.
CERTIFIED BY: DATE., NOVEMBER 14,201
THE FINAL HYDRONIC DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NEBB
"PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS"
AND THE PROJECT SPECIFICATIONS.
CERTIFIED BY:
DATE:
AIR -RIGHT WARRANTS THAT THE AIR AND HYORONIC SYSTEM EVALUATED DURING THIS SURVEY
IS OPERATING AT THE SPECIFIED LEVELS AS SHOWN WITHIN THIS REPORT, AT AND ONLYAT THIS TIME.
AIR -RIGHT MAKES NO OTHER WARRANTIES, STATED OR IMPLIED, CONCERNING THE CONTINUED
PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS EQUIPMENT PAST THIS TIME.
AR/ TECHNICIAN(S):
AR/NEBB TAB SUPERVISOR: TIMOTHY A. TOPPING REG. NO.2589 CERTIFICATION EXPIRATION. 03131114
TIMOTHY A. TOPPING
B CERTIFICATION
2589
3/31/14 /
747 SHERIDAN BLVD UNIT 8B, LAKEWOOD, COLORADO 80214, PHONE: (303) 232 5145 FAX:(303) 232-1238
AlR- RIGHT, INC.
TABLE OF CONTENTS
DOCUMENT
COVER PAGE .
TAB CERTIFICATION
TABLE OF CONTENTS.
AIR APPARATUS TEST REPORT RTU-24
AIR APPARATUS TEST REPORT RTU-25
AIR TERMINAL TEST REPORT.
FAN TEST REPORT EF-11
PAGE
5
6-8
v
AIR- RIC,HT, INC.
PROJECT: SAWS CLUB
AIR HANDLER UNIT DATA
MANUFACTURER
LENNOX
MODEL
SCC060H4BMG
SERIAL
5612005695
FAN TYPE
FC
DESIGN CFM
1,650 CFM @ 0.50' ESP
MIN OSA
165 CFM
STARTER DATA
MANUFACTURER
FACTORY PACKAGE
MODEL
SIZEITHERMAL NO.
RANGE
SET AT (AMPS)
REQ. THERMAL
RATING (AMPS)
AIRFLOW DATA
SUPPLY CFM
1,685
OSA CFM
170
RETURN CFM
1,515
FILTER
-0.13" -0.33"
COIL
AIR APPARATUS
TEST REPORT
UNIT: RTU-24
MOTOR NAMEPLATE DATA
MANUFACTURER
INTERLINK
HP
R.P.M.
1.5
1745
PHASE
FRAME
3
56HZ
S.F.
TYPE
1.15
N/G
VOLTS
AMPS
460
2
THERMALLY PROTECTED
DRIVE DATA
MOTOR DRIVE
1VL40
MOTOR BORE
7/8"
FAN DRIVE
MA68
FAN BORE
V
NO. BELTS & SIZE
ONE AX44
ROTATION
CORRECT
DRIVE CHANGE I
N/A
TEST DATA
INITIAL
FINAL
FAN R.P.M.
940
VOLTAGE
482/481/483
AMPERAGE
1.5/1.5/1.5
rJ NAC
PAGE: 04
O=AIR -RIGHT, INC.
PROJECT: SAM'S CLUB
AIR HANDLER UNIT DATA
MANUFACTURER
LENNOX
MODEL
SGC036H4BT1 G
SERIAL
5612CO3001
FAN TYPE
FC
DESIGN CFM
1,200 CFM @ 0.50" ESP
MIN OSA
120 CFM
STARTER DATA
MANUFACTURER
FACTORY PACKAGE
MODEL
SIZE/THERMAL NO.
RANGE
SET AT (AMPS)
REQ. THERMAL
RATING (AMPS)
AIRFLOW DATA
SUPPLY CFM
1,230
OSA CFM
125
RETURN CFM
1,105
-0.10' FILTER-0.20"
COIL
AIR APPARATUS
TEST REPORT
UNIT: RTU-25
MOTOR NAMEPLATE DATA
MANUFACTURER
INTERLINK
HP
R.P.M.
1.5
1745
PHASE
FRAME
3
56HZ
S.F.
TYPE
1.15
N/G
VOLTS
AMPS
460
2
THERMALLY PROTECTED
DRIVE DATA
MOTOR DRIVE
1VL34
MOTOR BORE
7/8"
FAN DRIVE
MA60
FAN BORE
1"
NO. BELTS & SIZE
ONE AX44
ROTATION
CORRECT
DRIVE CHANGE
I N/A
TEST DATA
INITIAL
FINAL
FAN R.P.M.
780
VOLTAGE
483/484/483
AMPERAGE
1.All .All .4
4�7 NAC
PAGE: 05
O=AIR- RIGHT, INC.
PROJECT: SAM'S CLUB
AIR TERMINAL
TEST REPORT
SYSTEM: RTU'S
mmm
PAGE: 06
PAGE: 06
O=AIR- R/GHT, INC.
PROJECT: SAWS CLUB
AIR TERMINAL
TEST REPORT
SYSTEM: RTU'S
'1 NO DAMPERS. UNITSET FORTOTAL
PAGE: 07
O=AIR- RIGHT, INC. _-
PROJECT: SAM'S CLUB
AIR TERMINAL
TEST REPORT
SYSTEM: RTU'S & EXHAUST
mmm
��
®®®®®®
PAGE: 08
(g7 AIR- RIGHT, INC.
PROJECT: SAM'S CLUB
FAN TEST
REPORT
FAN NUMBER
EF-11
UNIT DATA
UNIT DATA
UNIT DATA
MANUFACTURER
PENNBARRY
MODEL
FXI6RFT
SERIAL
D12HZ69725
DESIGN CFM
900 CFM @ 0.89" ESP
MOTOR DATA
MOTOR DATA
MOTOR DATA
MANUFACTURER
FASCO
MOTOR HP
RPM
1/3
1550/1300/1050
PHASE
TYPE
1
N/G
S.F.
FRAME
1
U24131
VOLTS
AMPS
115
4
DRIVE DATA
DRIVE DATA
DRIVE DATA
MOTOR DRIVE
BORE
DIRECT DRIVE
FAN DRIVE
BORE
NO. BELTS
SIZE
DRIVE CHANGE
ROTATION
STARTER DATA
STARTER DATA
STARTER DATA
MFG.
MODEL
NONE
SIZE
RANGE
SET AT(AMPS)
REQTHERM
THERMAL PROTECTION
TEST DATA
TEST DATA
TEST DATA
CFM
VOLTS
920
120
RPM
AMPS
DIRECT DRIVE
4
-0.42" rJ ATMOS
PAGE: 09