HomeMy WebLinkAboutSite Certifications - 02/02/2007NORTHERN
ENGINEERING
February 2, 2007
Mr. Jay Barber
Stormwater Utilities
City of Fort Collins
700 Wood Street
Fort Collins, CC 80524
ADDRESS: PHONE: 970.221.4158
200 S. College Ave. Suite 100 WEBSITE:
Fort Collins, C080524 FAX:970.221.4159 www•northernengineering.com
RE: Plantation Manor Site Drainage Certification
Dear Mr. Barber,
STORMWATER
RECEIVED
FH 0 2 2007
This letter is in regards to Plantation Manor at Big Ben Drive and West Horsetooth Road, and in
particular, to provide a final certification of the drainage facilities. A partial certification was submitted
to your office November 3, 2006; the certification stated that the spillway of the pond needed to be
raised 3" to provide the required volume. The pond spillway elevation was raised on or about November
17, 2006 by approximately 3", verified by a site visit in late November 2006. The raised spillway
increased the capacity by approximately 5,400 cf to a total volume of 63,600 cf; 63,500 cf is the required
detention volume for Plantation Manor. Drainage facilities were examined during the site investigation;
all inlets, pans, and storm sewer appear to be in good working condition. The pond outfall near Seneca
was also examined, the pipes and inlet also appear to be in good working condition.
In conclusion, the site drainage is complete and; all facilities are anticipated to perform as designed. The
overlot grading does essentially follow the proposed grading plan.
Please feel free to call should you have any questions regarding this certification.
Sincerely,
ENG
Roger A, Curtiss, P.E'
Project Manager .
cc: Brett Latimer
0? 14A`07
As -Built volume south 02-02-07.txt
PLANTATION MANOR
Elev
Area
Avgg Vol
Cumml Avg
ft
ac
ft3
ft3
5109.70
0.598
2528
61018
5109.60
0.563
2315
58490
5109.58
0.550
2275
58100
5109.50
0.500
2116
56175
5109.40
0.471
2004
54059
5109
0.4
1
52055
�-5I'69-20
0
0.43030 ,
1830830
'STl1�
5109.10
0.411
1752
48311
5109.00
0.394
1691
46559
5108.90
0.383
1651
44868
5108.80
0.376
1622
43217
5108.70
0.369
1594
41595
5108.60
0.363
1571
40001
5108.50
0.358
1551
38430
5108.40
0.354
1536
36879
5108.30
0.351
1522
35343
5108.20
0.348
1508
33821
5108.10
0.345
1494
32313
5108.00
0.341
1480
30820
5107.90
0.338
1466
29340
5107.80
0.335
1452
27874
5107.70
0.332
1438
26422
5107.60
0.329
1424
24984
5107.50
0.325
1410
23560
5107.40
0.322
1397
22149
5107.30
0.319
1383
20753
5107.20
0.316
1369
19370
5107.10
0.313
1355
18001
5107.00
0.309
1341
16646
5106.90
0.306
1326
15305
5106.80
0.303
1311
13979
5106.70
0.299
1294
12669
5106.60
0.295
1274
11375
5106.50
0.290
1250
10101
5106.40
0.284
1226
8851
5106.30
0.279
1201
7626
5106.20
0.273
1176
6424
5106.10
0.267
1146
5249
5106.00
0.259
1054
4103
5105.90
0.225
848.
3049
5105.80
0.165
642
2201
5105.70
0.130
503
1559
5105.60
0.101
384
1055
5105.50
0.075
286
671
5105.40
0.056
208
386
5105.30
0.040
132
177
5105.20
0.021
46
46
5105.10
0.000
0
0
Page 1
As -Built volume north 02-02-07.txt
PLANTATION MANOR
Elev
Area
Avg Vol
gt3
Cumml'Avg
ft
ac
ft3
5109.70
0.077
319
2552
5109.60
0.070
296
2233
5109.50
0.066
277
1937
5109.40
0.062
259
1660
5109.30
0.057
241
1401
5109.20
0.053
223
1160
5109.10
0.049
199
937
5109.00
0.042
166
737
5108.90
0.034
133
571
5108.80
0.027
109
438
5108.70
0.023
91
329
5108.60
0.019
73
238
5108.50
0.015
58
165
5108.40
0.012
44
107
5108.30
0.009
31
63
5108.20
0.006
19
32
5108.10
0.003
10
13
5108.00
0.001
3
3
5107.90
0.000
0
0
Page 1
n� INORTHERN
ENGINEERING
ADDRESS: PHONE: 970.221 .4158 WEBSITE:
200 S. College Ave. Suite 100 www.northernengineering.com
Fort Collins, CO 80524 FAX: 970.221.4159
November 27, 2006 STORMWATER
Mr. Jay Barber RECEIVE®
Stormwater Utilities
City of Fort Collins NOV 2 8 2006
700 Wood Street
Fort Collins, CO 80524
RE: Plantation Manor Site Drainage Certification
Dear Mr. Barber,
1
This letter is in regards to Plantation Manor at Big Ben Drive and West Horsetooth Road, and in
particular, to provide a partial certification of the drainage facilities. A survey conducted in July of 2006
provided the topography for this certification; a site visit November 3, 2006 confirmed drainage patterns
and facility conditions. From the topography, the combined pond volume is calculated to be 58,100 cf.
The design pond volume totaled 63,500 cf, or 5,400 cf short of storage. The pond spillway elevation was
raised on or about November 17, 2006 by approximately 3", which increased capacity to 63,600 cf,
slightly more than required. Drainage facilities were examined during the site investigation; all inlets,
pans, and storm sewer appear to be in good working condition. The pond outfall near Seneca was also
examined, the pipes and inlet also appear to be in good working condition
In conclusion, the site drainage is complete and; all facilities are anticipated to perform as designed. The
overlot grading does essentially follow the proposed grading plan.
Please feel free to call should you have any questions regarding this certification.
Sincerely,
NORTHERN ENGINEERING
oveooiN
Roger A, Curtiss, RE 27362
Project Manager
cc: Brett Larimer ���iiij�FSSION
I . - PLANTATION MANOR PARTIAL DRAINAGE CERTIFICATION
200 South College Avenue, Suite 100
Fort Collins, Colorado 80524
NORTHERN
ENGINEERING
PHONE: 970.221.4158 FAX: 970.221.4159
v .northernengineedngxotn
ILT POND CONTOURS
NO UTILITY FEATURES ARE
V FOR REFERENCE ONLY
PLANTATION MANOR
AS -BUILT PONDS
DRAWN BY: K. Dail SHEET NO:
SCALE: 1 "=60'
ISSUED:11-06-06 1 of 1
w.
R
O
O
Ot
A
i
late
fa
g
.t
0
Q
0
I
H
0
0
w