HomeMy WebLinkAboutSite Certifications - 04/30/2025 NORTHERNENGINEERING.COM | 970.221.4158 DRAINAGE SITE CERTIFICATION LETTER: COUNTRY CLUB RESERVE FORT COLLINS | GREELEY 1 | 2 March 25, 2025 City of Fort Collins Stormwater Utility 700 Wood Street Fort Collins, Colorado 80521 RE: FINAL OVERALL SITE AND DRAINAGE CERTIFICATION COUNTRY CLUB RESERVE Dear Staff, Northern Engineering (aka, EPS Group, Inc.) is pleased to submit this drainage certification letter to verify as- constructed conditions for Country Club Reserve. Northern Engineering has performed survey work starting on (06.27.2022) and completed on (03.26.2024) to verify general compliance with the Final Utility Plans for Country Club Reserve, dated 02.25.2021. Included in this drainage certification submittal are the following: Appendix A – City of Fort Collins Overall Site and Drainage Certification Form Appendix B – City of Fort Collins During Construction Inspection Checklist and Photographs Appendix C – As-constructed rain garden and detention pond calculations Appendix D – As-constructed record drawings for Grading and Storm Drain Plan & Profile sheets. Appendix E – Documents provided to the Colorado State Drain Time website. Based on the calculations shown in Appendix C, the as-built detention and water quality volumes are listed in Table 1. The as-built volumes for each detention facility is consistent with the approved drainage report. TABLE 1: POND RECORD VOLUMES Pond Required Volume (ac-ft) Design Volume (ac-ft) Constructed Volume (ac-ft) Constructed Flat Area (sq-ft) Detention Pond 1 18.72 44.91 34.38 n/a Detention Pond 2 1.70 1.70 1.87 n/a Rain Garden 1 0.124 0.131 0.274 8,560 Rain Garden 2 0.190 0.243 0.257 17,587 Rain Garden 3 0.088 0.089 0.107 10,512 Grading/Stormwater Certification Accepted (Certificate of Occupancy Released) Accepted by: Date: ☐ Escrow was held for CO and is now released we Dan Mogen 04/30/2025 NORTHERNENGINEERING.COM | 970.221.4158 DRAINAGE SITE CERTIFICATION LETTER: COUNTRY CLUB RESERVE FORT COLLINS | GREELEY 2 | 2 We have concluded, based on the attached information and personal site inspection, that the drainage features for the project site have been constructed in substantial compliance with the above referenced Final Utility Plans, with the following exceptions: Item I.B.3.b – There is no traditional spillway used for the detention pond. Instead, an emergency overflow inlet on the pond outlet pipe between the Pond 1 outlet structure and the west ROW of Turnberry is provided. This will ensure that flows will continue to reach the pond outfall pipe in the event of a clogged outlet structure. Item III.B.2 – Northern Engineering did not observe construction. Northern Engineering was unable to verify if encasements and clearances are per the approved construction drawings. See the ‘during construction’ checklist for storm drain installation and inspection information for public storm sewer. Item XIII – LID and Water Quality Features are generally compliant and documentation for all three rain gardens are contained herein. However, Rain Garden 2 is currently under the purview of Prospect Energy (PE). PE has Remediation Project Number 33171 through Colorado Energy & Carbon Management Commission as well as an erosion control and remediation plan with the City of Fort Collins Environmental Regulatory Affairs. Per a site meeting with City of Fort Collins, Prospect Energy, their consultants, Northern Engineering/EPS Group Inc., Coyote Ridge, and Jensen LaPlante it was agreed upon that Prospect Energy would repair the damaged area per the as-builts attached to this certification. Prospect Energy and their consultants are responsible for providing that documentation to the City. As of 1/28/2025 Northern Engineering/EPS Group Inc. have not received a response from Prospect Energy or their consultants on whether or not they have fixed the swale and berm on the southwest side of Rain Garden 2. On February 28, 2025 the development team was notified by the City of Fort Collins that Prospect Energy had abandoned the site, stopped work, and their consultant that was going to complete the recertifcation (Apex) had communicated they are not stamping/re-certifying any re-work of the area impacted by Prospect Energy’s remediation efforts. On September 27, 2024 the City of Fort Collins inspected the reinstallation of Rain Garden 2 and verified it was built per the correct specification. Both the email correspondence from 2/28/25 and the LID Inspection Form are included at the end of Appendix B. On March 19, 2025 the development team remobilized to correct the issues caused by Prospect Energy’s negligence. EPS Group restaked the impacted area (south of Block 6 Lots 1-3), Coyote Ridge then regraded the area, and finally EPS Group went back onto site to collect as-builts for the impacted swale. These changes are shown in blue in Appendix D sheet G5. The regrading corrected the inadequate swale and it now functions as designed. Photos of this correction are located at the end of Appendix B. Please feel free to contact us with any questions. Sincerely, NORTHERN ENGINEERING | EPS GROUP, INC. Blaine Mathisen, PE Project Manager .ORTHER.ENGINEERING.COM | 970.221.4158 DRAI.AGE SITE CERTIFICATIO. LETTER: COUNTRY CLUB RESERVE FORT COLLI.S | GREELEY APPE.DIX Appendix A OVERALL SITE AND DRAINAGE CERTIFICATION FORM Page 1 OVERALL SITE and DRAINAGE CERTIFICATION Commercial, Multi-Family and Subdivision Certification Form and Checklist Project Name: Date: Building Permit Numbers: (Commercial or multi-family) Per the requirement in Fort Collins Stormwater Criteria Manual (FCSCM) Chapter 3, Section 3.0 to certify as- built construction to the approved drainage and grading plans, please fill in all applicable items in this Certification Form for Commercial, Multi-Family and Overall Single Family sites. NOTE: several items must be verified during construction. A copy of the approved grading plan must be submitted with the as-built grading plan. (As-built elevations must be written in red next to the approved elevations.) •Use “Yes” for items completed as described. •Use “N/A” for items that are not applicable to the site being certified. •If any blanks are “No,” attach an explanation referencing the item number below. Attach an explanation or description of the as-built condition for any items listed or for anything not listed but shown on the approved construction plans. Provide an as-built redline or Mylar drawing with the following: I.Water Quality and Quantity Detention Basin - FCSCM Ch. 6 and 7 For multiple detention basins on a site, provide the following for each basin separately: A. Volume: As-built topographic verification is attached at 1-foot (or less) contour intervals and volume verification calculations for the water quality capture volume and the 100-year detention storage volume. 1. Detention basin topography was prepared by a professional land surveyor registered in the state of Colorado. 2.Both proposed and as-built contours are shown on the same plan sheet (dashed lines for proposed and solid lines for as-built). 3.All critical spot elevations as shown on the approved construction plans have been verified and the as-built elevations are shown on the plan sheet. 4.Stage-storage-discharge tables are provided on a separate document. 5.Verification that designed drain time is in compliance with Colorado Revised Statute § 37-92- 602(8) is attached and has been uploaded to the Statewide Compliance Portal (tinyurl.com/COCompliancePortal) for approval. Uploaded documents must include: a.The cover sheet from the approved drainage report b.The stamped certification page from the approved drainage report c.As-built topographic survey d.Stamped certification page from the Overall Site & Drainage Certification e.PDF output from the Stormwater Detention and Infiltration Design Data Speadsheet 11/19 Country Club Reserve 05/05/2023 Yes Yes Yes Yes Yes Yes Page 2 B.Water Quality and Quantity Detention Basin Grading: Attached is as-built verification that there is a minimum 2% positive fall into the concrete trickle pans or flow-line(s) from all areas in the bottom of the detention pond. If there is a “soft pan” in the flow-line, all areas still must meet the minimum 2% grade requirement. 1.Low Flow: Choose one of the following detention basin low flow options as applicable: a. Turf swale for low flow path in detention basin. There is a minimum 2% grade in the flow-line(s) of the detention basin. The flattest as-built grade is . b.Concrete pan for low flow in detention basin. There is a concrete pan installed that meets the grades as shown on the approved construction plans. (Show as-built spot elevations.) c.Soft pan for low flow in detention basin. •Verify and document the soft pan material gradation, trench width and depth - to be verified during construction by engineer. Picture documentation is preferred or engineer’s statement of visual inspection and compliance. (Choose one below.) o There is a soft pan with an underdrain installed that meets the design on the approved construction plans. (Show the underdrain grades, bedding material, geotextile, spot elevations, bends, cleanouts, etc.) o There is soft pan installed without an underdrain but there is a type A or B soil. The soil type must be documented by supplying verification from a registered professional geotechnical engineer. NOTE: Spot elevations are to be within 0.2 ft. +/-. 2. Side Slopes: The as-built side slopes of the detention basin have been calculated and are shown. Indicate the side slope with an arrow and a numerical value (e.g., 6.25:1). The maximum slope allowed is 4:1. Small areas of 3:1 may be acceptable, but slopes steeper than 3:1 must be stabilized or re- graded. Provide documentation if a variance was granted for steeper slopes during the design process. 3.Spillway: The following items must be field verified: a.The location of the spillway is indicated on the as-built plan. b.The width of the spillway is indicated on the as-built plan. c.The elevation(s) of the spillway is shown on the as-built plan. d.A concrete ribbon defines the location and grade of the spillway. e.There is downstream scour protection in the spillway as per the construction plans. Indicate type: (riprap size “D50” gradation and bedding type, geotextile, buried riprap with inches of bury, etc.). f.There are no obstructions in the spillway, such as trees, bushes, sidewalks, landscape features, rocks, etc. 11/19 Yes N/A Yes N/A N/A N/A Yes Yes N/A N/A N/A N/A N/A Page 3 4.Outlet Structure: a.The orifice plate for the approved release rate is installed with the correct size and location of the orifice. b.The orifice plate for the water quality outlet is installed with the correct hole size, number of rows and columns of holes. c.The bottom hole on both the water quality and quantity outlets are at the bottom of the plate so no water ponds in front of the plate. d.The well screen is the correct material and is installed as shown on the construction plans. e.100-year overflow grate elevation is . (Elev. A on detail D-46) f.The top elevation of the water quality capture volume is . (Elev. B on detail D-46) g.Overflow grate is made of the correct material, has the correct bar spacing, is hinged at the top and bolted at the bottom. h.The bottom of the outlet box has no obstructions or misalignments that will cause it to retain runoff water and is sloped at 2% towards outlet. II.Channels/Swales - FCSCM Ch. 8, Sec. 2.0 and Ch. 9, Sec. 5.0 A. Capacity: The as-built capacity of all the major channels and swales has been verified. They meet or exceed capacity requirements shown in the approved drainage study for this project. 1.All swales are located within the drainage easements as shown on the construction plans. 2.Longitudinal slopes and side-slopes (cross-sections) have been verified. Design criteria requires longitudinal slopes of 2% min. (on vegetated swales) and side-slopes no steeper than 4:1. If these criteria are not met, the certification engineer will write a justification and propose mitigation for each instance or have the issues corrected. If variances to these criteria have previously been approved and are shown on the construction plans, no justification is needed. 3.As-built spot elevations on channels/swales are shown that correspond to spot elevations shown on the approved construction plans. 4.All permanent erosion control measures are installed as shown on the approved construction plans (e.g., drop structures, riprap, TRMs, etc.). (Include pictures and verification of the materials used as part of this verification.) 5.All pans, curbs, storm pipes or other appurtenances appropriately tie into each other in the system. (Pictures at tie-in points suggested.) 6.The minimum freeboard is provided for all channels and swales as shown on the approved construction plans or as identified in the approved drainage study. (Show the freeboard provided on the cross-sections as on the construction plan set or attached as separate documentation.) 7.The low flow portion of all channels or swales is clear of obstructions. (No landscaping, trees, shrubs, sod, etc. infringe on the low flow portion of channels or swales.) 11/19 Yes Yes Yes Yes Yes 5054.69 Yes 5057.09 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Page 4 III.Storm Pipes (aka storm drains) - FCSCM Ch. 9, Sec. 4.0 A. Storm Drain Pipe Capacity: The as-built capacity of all pipes installed on this project has been verified and meets or exceeds the capacity requirements shown in the approved drainage study for this project. 1.All storm drain pipe sizes and materials have been verified and are in conformance with the approved construction plans. (Indicate on the plan and profile sheets that they have been verified.) Material and size substitutions must be approved prior to installation. If a pipe size or material was changed during construction, the certification engineer must attach the approval documents or supply them with this certification. Approval documents must include a calculation documenting the capacity equivalency (equal or greater) of the substituted size. 2.The longitudinal slope of the pipe is as shown on the approved construction plans. The acceptable minimum slope is 0.4%. All slopes flatter than the designed slope on the construction plans must be justified with capacity calculations on an attached sheet. 3.The as-built invert elevations have been verified and are shown on the plan and profile sheets of the approved construction plans. B.Storm Drain Pipe Installation Requirements: All pipes are installed in accordance with the approved construction plans and construction specifications. 1.The minimum cover requirements for all pipes have been met as shown on the approved construction plans. These will be called out in critical locations. 2.All encasements and clearances as specified on the approved construction plans have been met. 3.Any specific joint types or construction methods specified on the approved construction plans have been met. (List on a separate sheet and attach to this certification.) IV.Concrete Pans - FCSCM Ch. 8, Sec. 2.0 A. Construction/Installation: All concrete pans have been constructed in accordance with the approved construction plans. 1.The concrete pans are the correct size/width as shown on the approved construction plans. 2.The longitudinal slopes of the pans are as shown on the approved construction plans. The certification engineer must justify or mitigate longitudinal slopes less than the minimum of 0.4% unless a flatter slope was approved and is shown on the approved construction plans. Provide mitigation or justification by separate document. 3.The cross-section of the pan is as shown on the construction plans. (Specifically, the pan cross- section is “V” shaped and meets the side slope shown on the detail.) 4.The concrete pans are a minimum of 6 inches thick without reinforcement and a minimum of 4 inches thick with a minimum of 6X6-W14xW14 reinforcement per detail D20B and D20C. (Provide documentation of the reinforcement used if different than shown on the details or on the approved construction plans.) 5.The spot elevations shown on the concrete pan(s) have been verified and are shown on the as- built drawings. 11/19 Yes Yes Yes Yes Yes Yes N/A N/A Yes Yes Yes Yes Yes Yes Page 5 V. Storm Drain Inlets - FCSCM Ch. 9, Sec. 3.0 A. Construction/Installation: All storm drain inlets have been constructed in accordance with the approved construction plans and construction specifications. 1.The size and type of inlets are consistent with the inlets shown on the approved construction plan. Indicate by writing “Verified” on each inlet on the plan sheet or list on a separate document the inlet number(s), type and size (length). If the inlet installed is other than the one on the approved construction plan detail sheet, provide the name and source of the detail with justification for equal or better capacity. 2.The size of the inlet opening is consistent with the approved detail. (Check height and width.) 3.The elevation of the grate (if applicable) is at the elevation shown on the street profile or as indicated by a spot elevation on the construction plans. 4.The as-built invert elevations of all pipes entering and leaving the inlet are shown on the plan and profile sheets within construction tolerance of 0.2 feet. If substantially different, provide justification and capacity calculations to show the capacity is not affected or propose mitigation. 5.The as-built size of the inlet box is as shown on the construction plans or an explanation or justification is attached. 6.All Type C, R, 13 and 16 inlet covers are stenciled or stamped with the following designation (or an equivalent): NO DUMPING – DRAINS TO POUDRE RIVER. VI.Culverts - FCSCM Ch. 9, Sec. 4.0 A. Construction/Installation: All culverts have been constructed and/or installed in accordance with the approved construction plans and construction specifications. 1.All culvert sizes have been verified as indicated on the as-built construction plans as correct. 2.The culvert material type for all culverts installed is as on the approved construction plans and is indicated on the as-built plans. 3.The as-built invert “in and out” elevations have been verified and are indicated on the as-built construction plans. 4.The culvert headwalls or wing walls have been installed as shown on the approved construction plans. Headwalls or wing walls may be needed in the as-built conditions onsite if the slopes adjacent to the culvert are greater than 4:1. Please note areas needing stabilization in the certification narrative. An alternative to consider is a turf reinforcement mat (TRM). VII.Sub-Drains A. Construction/Installation: All sub-drains shown on the construction plans have been installed in accordance with those plans and the construction specifications. Sub-drains installed with the sanitary sewer are to be verified on the sanitary sewer plan and profile sheets of the construction plans. (NOTE: Indicate any sub-drains installed after the plans were approved on the as-built plans.) 1.The size of the sub-drains are as approved on the construction plans and are indicated on the as- built plans. 2.The type of sub-drain, in particular the perforated and non-perforated sections of the drain, are as indicated on the approved construction plans. 11/19 Yes Yes Yes N/A Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Page 6 3.The cover requirements per the construction plans are provided. 4.The cleanouts have been installed at the locations shown on the construction plans and are accessible for cleaning. (Cleanouts can be buried a maximum of 6 inches deep with their locations marked.) 5.The backfill materials for sub-drains are as shown on the approved construction plans. (This includes the type, depth and width.) 6.The geo-textile liner completely wraps the sub-drain and the permeable backfill material unless shown otherwise on the approved construction plans. (Sub-drain pipe wrapped in a sock filter material is accepted only if approved prior to installation.) VIII.Curb Cuts A. Construction: All curb cut openings are constructed in accordance with the approved construction plans and construction specifications. 1.The size (width) of the curb cut opening is as shown on the approved construction plans. 2.The curb cut openings tie into a downstream swale, pipe, or other appurtenances with a smooth transition and there no obstructions such as riprap or sod impeding the flow downstream of the curb cut. IX.Sidewalk Culverts & Chases A. Construction/Installation: All sidewalk culverts have been installed at the locations shown on the approved construction plans. 1.The size (width and length) of the culverts are as shown on the approved construction plans. 2.The cover plate is a minimum 5/8-inch galvanized plate bolted to a galvanized angle iron per the detail shown on the approved construction plans or per the City’s detail. 3.The sidewalk culvert invert “in and out” elevations have been verified and are indicated on the as-built plans. 4.The sidewalk culvert opening is as shown on the approved construction plans or per the City’s detail. 5.There is a smooth transition both on the inlet and outlet ends of the sidewalk culvert with no obstructions such as riprap or sod impeding the flow into or out of the sidewalk culvert. X. Site Grading - FCSCM Ch. 8 A. Construction: All common open spaces have been graded in accordance with the approved construction plans. 1.The grading on all common open spaces bordering private lots has been verified as correct and the as-built rear lot corner elevations have been shown on the as-built plans. 11/19 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Page 7 2.The as-built contours for “overlot grading” are shown on the as-built construction plans for all common open spaces, tracts, outlots, etc. If not in compliance, please attach a narrative describing the situation for noncompliance and when it may be corrected. An escrow for overlot grading may be required. (NOTE: Residential Lot Grading Certification is a separate process from this Overall Site Certification. It is understood that residential lots will be brought to final grade once the foundation is backfilled so they may be lower than the plan shows at this Overall Site Certification stage.) 3.All turf reinforcement mats (TRMs) have been installed as shown on the approved construction plans and the slopes are stabilized. XI.Permanent Erosion Control BMPs - FCSCM Ch. 9, Sec. 7.0 A. Construction: All permanent erosion control BMPs have been installed per the approved construction plans. 1.All riprap has been installed in the locations and sizes indicated on the approved construction plans. 2.All fabric has been installed in the locations and sizes indicated on the approved construction plans. a.All fabric was installed per the details on the approved construction plans. XII.Post-Construction Site Cleanup - FCSCM Ch. 3, Sec. 2.0 A. Construction: All construction debris and obstructions of any kind have been removed from drainage paths. 1.All construction debris has been removed except in staging area(s). 2.All ruts have been smoothed out in all construction areas. 3.All areas needing reseeding have been identified and future stabilization goals have been coordinated with the Erosion Control Inspector and in accordance with FCSCM Vol.2 Chapter 12. Note the area needing stabilization in the narrative. XIII.Certification of LID and Water Quality Facilities - FCSCM Ch. 7 A.Attached are the During Construction Inspection Checklist for Low Impact Development (LID) and other items to be verified during construction, along with pictures and other required documentation. B.Attached is verification of the rain garden and/or sand filter flat surface area(s) and ponding volume(s). This verification includes survey of critical elevations. C.Attached is verification of the underground infiltration required volume(s), weir elevations, orifices, inspection ports and filtering fabric. This verification includes survey of critical elevations. D.All visible LID design features were verified as part of the engineer's site visit. 11/19 Yes N/A Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes N/A Yes 11/19 Page 8 XIV.Certification of Other Permanent BMPs A.The construction of other permanent BMPs not specifically addressed in this certification is in accordance with the approved plan. This may include grade control structures, rundowns, bridges, stream access/improvements, etc. Please specify other permanent BMPs included on this site: XV. Certification and Erosion Control Measures - FCSCM Ch. 3 A. All temporary erosion control measures shall be removed upon stabilization. If at the time of preparing this certification there are any erosion control measures still remaining on the site, please note them in the narrative and verify that they need to remain at this time. If in doubt as to the need for any control measure, please consult with the Erosion Control Inspector at erosion@fcgov.com. XVI.Statement of Compliance - FCSCM Ch. 3 A. This certification is signed and stamped. By signing this form, the engineer(s) attests that he/she has visited and observed the site, and to the best of his/her knowledge, the as-built conditions of the drainage facilities are as described in the above form and in the enclosed as-built plans. B.Failure to properly disclose all known information could result in the rejection of this certification and prevent the release of any and all Stormwater Utility permit holds on Building Permits and/or Certificates of Occupancy within this development. XVII. Signature and Stamp by a Colorado-Registered Professional Engineer Engineer’s contact information: Name: Email: Phone: Company: Address: PE Stamp Storm Line A Concrete Rundown Yes Blaine Mathisen blaine.mathisen@epsgroupinc.com 970-488-3901 EPS Group Inc. (aka Northern Engineering) 301 N. Howes Street, Suite 100 Fort Collins, CO 80521 NORTHERNENGINEERING.COM | 970.221.4158 DRAINAGE SITE CERTIFICATION LETTER: COUNTRY CLUB RESERVE FORT COLLINS | GREELEY APPENDIX Appendix B DURING CONSTRUCTION INSPECTION 1/19 Page 1 of 2 DURING CONSTRUCTION INSPECTION CHECKLIST To be completed by Construction Superintendent This checklist is to be completed during construction and included with the Overall Site and Drainage Certification. · Use “Yes” for items completed as described. · Use “N/A” for items that are not applicable to the site being certified. · If any blanks are “No,” attach an explanation referencing the item number below. Project Name: Country Club Reserve Date: 4.3.23 Building Permit Numbers: I. Compaction A. Yes All berms and embankments meet the compaction requirements as specified in the project geotechnical report or comply with the City’s standard, which is “soils should be compacted within a moisture content range of 2% below to 2% above optimum moisture content and compacted to 95% of the Maximum Standard Proctor Density (ASTM D698).” Compaction requires verification during construction. Provide testing log from contractor/engineer. II. Storm Drain Pipe Installation Requirements A. Yes The pipe trenches have been compacted in accordance with Section 02225-3.07.A.1. of the Fort Collins Development Construction Standards for Water, Wastewater, Stormwater (e.g., the trenches in the roadways are to be 95% of maximum density and all other areas are to be at 90%, both in accordance with ASTM D698). III. Energy Dissipation and Erosion Protection - FCSCM Chapter 9, Section 7.0 A. Riprap 1. Yes The riprap bedding is a granular bedding of the gradation and thickness indicated on the approved construction plans. 2. Yes A filter fabric was installed instead of granular bedding and is the material shown on the approved construction plans or was an approved equal. Provide documentation for an approved equal. 3. Yes The riprap is the gradation shown on the approved construction plans with a D50 of 12. 4. Yes The riprap thickness is as shown on the approved construction plans and extends to the horizontal limits shown. 5. Yes The riprap is buried to the depth indicated on the approved construction plans. (A minimum of 6 inches of soil is required.) B. Permanent Erosion Control Fabric - FCSCM Vol.1, Ch.7 1. Yes All fabric was installed per manufacturer’s specifications. 1/19 Page 2 of 2 IV. Other Permanent BMPs A. Yes All cut-off walls have been installed in accordance with the approved construction plans. (Cut-off walls are required for irrigation ditch crossings of storm drain pipes.) V. Extended Detention Basins A. Yes Installation of this facility was verified via inspection by a City-Stormwater Inspector at the point of installation of the water quality control box(es). Provide date of inspection and name of inspector: Adam Camp Included certification sheet(s): Please check the appropriate box(es) for the Low Impact Development (LID) facilities found on this site and complete the corresponding certification sheets. ☐ Permeable Interlocking Concrete Pavers ☒ Bioretention Cells (Rain Gardens) ☐ Sand Filters ☐ Vegetated Buffers ☐ Underground Infiltration ☐ Other LID – For certification of Dry Wells, Tree Filters, Constructed Wetland Channels & Ponds, etc., contact City Staff to determine requirements to exhibit the LID facility has been constructed and functions as intended per the approved drainage report. *Please provide photographic documentation of the installation of all stages of all LID facilities. **Please contact the City Stormwater Inspector at stormwaterinspection@fcgov.com to discuss inspection requirements for each LID facility and request inspections. ***All facilities being certified must be “clean” – free of sediment & construction debris – prior to certification or acceptance of the facility. Completed by: Name: Marcus Steward Title: Project Manager Email: msteward@crc-co.net Phone: 970-829-2488 Company: Coyote Ridge Construction Address: 1/19 Page 1 of 3 Bioretention Cells (Rain Gardens) Item/Activity Yes No N/A Submittal Requirements Submitted?/Response Stormwater Inspection Pre-construction meeting was held with City-Stormwater Inspector to discuss installation, inspection, checklist, and protection from sedimentation ☒ ☐ ☐ Record date, inspector name, meeting location (i.e. DCP, initial erosion control inspection, etc.) Underdrain and basecourse inspection(s): Installation of this facility was verified via inspection by a City-Stormwater Inspector at the point of installation of the outlet, underdrain, geomembrane layer, and base course (per design in Final Plan Documents) ☒ ☐ ☐ Record date(s) of inspection and inspector’s name Pea gravel and BSM inspection(s): Installation of this facility was verified via inspection by a City-Stormwater Inspector at the point of installation of the pea gravel and bioretention sand media ☒ ☐ ☐ Record date(s) of inspection and inspector’s name Excavation Heavy equipment did not encroach into the excavated area (prevents over-compaction) ☒ ☐ ☐ Bottom of cell was “ripped” after excavation ☐ ☐ ☐ Provide photographs before and after “ripping” Bottom surface of cell is flat and level ☒ ☐ ☐ Provide photograph Excavated area is protected/surrounded by sediment/runoff control measures during construction ☒ ☐ ☐ Provide photograph Intake Upstream catchment drains to inlet/bioretention cell per plan and flows are fully captured ☐ ☐ ☐ Forebay Forebay is installed according to design specifications ☒ ☐ ☐ Provide photograph There is a minimum 3” drop at the forebay entrance ☒ ☐ ☐ Provide photograph Forebay will drain fully and not hold standing water ☒ ☐ ☐ Outlet Structure/Overflow Emergency overflow elevation is confirmed ☒ ☐ ☐ Measure and record distance from overflow to top of media filter; provide photograph Overflow inlet elevation is set above bioretention media per plan ☒ ☐ ☐ Provide photograph 9/16/2022 with Adam Camp on site 11/23/2022, 12/1/2022, 12/7/2022 with Adam Camp 11/24/2022,11/25/2022, 12/2/2022,12/8/2022, 12/9/2022 with Adam Camp Provided in pictures Provided in pictures Silt fence was installed around area. Installed Per Plan Provided in pictures All conveyances to Rain Gardens are swales 1/19 Page 2 of 3 Overflow inlet invert elevation is at least 3 inches below containment wall/berm (to direct overflow into inlet) ☒ ☐ ☐ Measure and record distance between inlet and top of containment wall/berm; provide photograph Overflow path and check dams, if used, are armored to protect from erosion and maintain elevations ☒ ☐ ☐ Provide photograph Impermeable Liner Impermeable liner meets design specifications ☒ ☐ ☐ Provide specifications of delivered material Impermeable liner is appropriately anchored ☒ ☐ ☐ Provide photograph Impermeable liner is buried with no exposure ☒ ☐ ☐ Any penetrations of the impermeable liner have been sealed and checked for water-tightness ☒ ☐ ☐ Provide photograph (if necessary) Underdrain System Underdrain pipe meets design specifications ☒ ☐ ☐ Provide photograph At least one cleanout is provided per underdrain lateral ☒ ☐ ☐ Provide photograph Cleanout pipe is solid (not perforated/slotted) ☒ ☐ ☐ Provide photograph Cleanout covers are installed and watertight ☒ ☐ ☐ Provide photograph Verify the underdrain is NOT wrapped in geotextile fabric ☒ ☐ ☐ Provide photograph Verify there is no orifice plate on the underdrain outfall ☒ ☐ ☐ Provide photograph Underdrain integrity tested after backfilling using TV and/or water test ☒ ☐ ☐ Provide documentation of test results Filter Media and Aggregate Reservoir aggregate layer (ASTM #57 or #67): - meets design specifications - is installed to the required design depth ☒ ☐ ☐ Provide load ticket, photographs, and record depth installed Diaphragm aggregate layer (“Pea Gravel” with gradation ASTM #8, #89, or #9): - meets design specifications - is installed to the required design depth ☒ ☐ ☐ Provide load ticket, photographs, and record depth installed Bioretention Sand Media (BSM) composition: - meets design specifications - is installed to the required design depth ☒ ☐ ☐ Provide load ticket, photographs, and record depth installed BSM was “machine mixed” by supplier prior to delivery ☒ ☐ ☐ Provide load ticket BSM is installed flat and level ☒ ☐ ☐ Provide photograph Other Structural Components Containment wall/berm is continuous and level ☒ ☐ ☐ Landscaping Provided in pictures Provided in pictures, truck tickets have been submitted. Installed per the Plans Provided in pictures, truck tickets have been submitted. Installed per the Plans Provided in pictures, truck tickets have been submitted. Installed per the Plans Perform Water Test Provided in pictures Load ticket provided Provided in pictures Provided in pictures Provided in pictures Provided in pictures Provided in pictures Provided in pictures. Refer to As-builts for elevations Provided in pictures Provided in pictures Provided in pictures. Spec of delivered material provided 1/19 Page 3 of 3 Verify final landscaping is free of sod ☒ ☐ ☐ If sod is used, it must be shown to be “sand-grown” Final landscaping (non-floatable mulch) is flat and level ☒ ☐ ☐ Provide photograph Vegetation is planted according to landscape design specifications and final landscaping plan ☒ ☐ ☐ Provide photograph Verify that weed barrier is NOT installed ☒ ☐ ☐ Temporary irrigation installed ☒ ☐ ☐ If N/A, then verify that permanent irrigation is installed to establish/maintain vegetation Close Out Upstream catchment stabilized prior to diverting runoff into bioretention cell ☒ ☐ ☐ Provided in pictures Provided in pictures Soilogic, Inc. 3522 Draft Horse Court • Loveland, CO 80538 • (970) 535-6144 April 4, 2022 Coyote Ridge Construction, LLC 6648 County Road 56 Johnstown, Colorado 80534 Attn: Mr. Ken Baty Re: Construction Materials Testing and Observation Services Report Country Club Reserve Fort Collins, Colorado Soilogic Project # 22-2002 Mr. Baty: During the period of February 8, 2022 through March 25, 2022, Soilogic Inc. (Soilogic) provided construction materials testing and observation services for the referenced project. Our services were provided on a part-time basis and included the observation and testing of overlot fill materials. Results of the observation and testing services completed during the referenced period are included with this report. During the referenced period, Soilogic personnel obtained one (1) representative sample of the excavated site soils and import soils for laboratory evaluation of the moisture density relationship of those materials. The laboratory testing completed on the obtained samples included a standard Proctor (ASTM D-698) test. Results of the completed standard Proctor tests were used to evaluate the percent compaction and moisture variability with reworked soils in the field. During the referenced period, Soilogic personnel performed field moisture/density tests on overlot fill materials that had been placed and compacted prior to and during our site visits. The field moisture/density tests were completed at random locations and elevations within the backfill areas and were performed in general accordance with ASTM Specification D- 2922. Results of the field moisture/density tests completed during the referenced period are included with this report. The field moisture/density test results met the project compaction requirement of at least 95% of the material’s standard Proctor maximum dry density and within -1% to +3% of the materials optimum moisture content. Construction Materials Testing and Observation Services Report Country Club Reserve Fort Collins, Colorado Soilogic # 22-2002 2 We appreciate the opportunity to be of service to you on this project. If you have any questions concerning the enclosed information or if we can be of further assistance to you in any way, please do not hesitate to contact us. Very Truly Yours, Soilogic, Inc. Kreis A Rutledge Jason Horner, P.E. Senior Engineering Technician Senior Project Engineer Description: Lean Clay (CL) Sample Location: Onsite Material ID: 22-2002A 90 95 100 105 110 115 120 125 130 135 140 145 0 5 10 15 20 25 30 35 Dr y De n s i t y (p c f ) . Moisture Content (%) Standard Proctor Test Summary (ASTM D-698) COUNTRY CLUB RESERVE FORT COLLINS, CO Project #22-2002 FEBRUARY 2022 Maximum Dry Density = 110.0 pcf Optimum Moisture Content =16.0% Liquid Limit = 32 Plasticity Index = 15 -200 Wash = 55.4% Saturation Curves @ Specific Gravity Equal to: 2.80 2.70 2.60 Gradation Analysis Test Summary Sieve Size Percent Passing (%) #40 99 #200 55.4 #4 100 #10 100 Material ID: 22-2002A Description: Lean Clay (CL) Sample Location: Onsite 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 0.0010.010.1110100 Pe r c e n t P a s s i n g ( % ) . Sieve Size (mm) COUNTRY CLUB RESERVE Fort Collins, Colorado Project # 22-2002 February 2022 Field Moisture/Density Testing Summary Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Moisture Compaction 1 2/8 1 -3.5'Overlot Fill - 90'N 240'E NE corner Lot 8 Block 3 A 15.8% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 104.5 -0.2%95%Pass Pass 2 2/8 2 Grade Overlot Fill - 20'N 238'E NE corner Lot 8 Block 3 Pass 3 2/8 3 -1.5'Overlot Fill - 38'S 258'E NE corner Lot 8 Block 3 A 15.4%105.1 -0.6% A 16.1%105.0 0.1%95%Pass 96%Pass Pass 4 2/9 1 -3.5'Overlot Fill - 91'N 18'W NE corner Lot 8 Block 3 A 19.0%104.6 3.0%95%Pass Pass 5 2/9 2 -3'Overlot Fill - 94'N 60'E NE corner Lot 8 Block 3 Pass 6 2/9 3 -3'Overlot Fill - 89'N 150'E NE corner Lot 8 Block 3 A 16.3%105.3 0.3% A 19.0%104.8 3.0%95%Pass 96%Pass Pass 96%Pass Pass 8 2/9 5 -1.5'Overlot Fill - 30'S 160'E NE corner Lot 8 Block 3 PassA17.2%105.0 1.2%95%Pass 7 2/9 4 -3'Overlot Fill - 92'N 100'E NE corner Lot 8 Block 3 A 15.9%105.1 -0.1% 97%Pass Pass 10 2/9 7 -3'Overlot Fill - 65'N 64'E NE corner Lot 8 Block 3 A 18.5%106.0 2.5%96%Pass Pass 9 2/9 6 -1.5'Overlot Fill - 68'S 100'E NE corner Lot 8 Block 3 A 18.5%106.4 2.5% 11 2/9 8 -3'Overlot Fill - 87'N 211'E NE corner Lot 8 Block 3 Pass 12 2/10 1 -2.5'Overlot Fill - 150'N NE corner Lot 8 Block 3 A 17.4%105.1 1.4% A 19.0%104.8 3.0%95%Pass 96%Pass Pass 95%Pass Pass 14 2/10 3 -2'Overlot Fill - 152'N 300'E NE corner Lot 8 Block 3 PassA18.3%106.0 2.3%96%Pass 13 2/10 2 -2.5'Overlot Fill - 150'N 100'E NE corner Lot 8 Block 3 A 17.9%104.9 1.9% 95%Pass Pass 16 2/11 1 -3'Overlot Fill - 60'S 36'E NE corner Lot 8 Block 3 A 17.9%105.7 1.9%96%Pass Pass 15 2/10 4 -3'Overlot Fill - 68'S 100'E NE corner Lot 8 Block 3 A 18.2%104.6 2.2% 17 2/11 2 -2'Overlot Fill - 62'S 240'E NE corner Lot 8 Block 3 Pass 18 2/11 3 -3'Overlot Fill - 69'S 352'E NE corner Lot 8 Block 3 A 19.0%104.9 3.0% A 17.5%108.7 1.5%99%Pass 95%Pass Pass 98%Pass Pass 20 2/11 5 -2'Overlot Fill - 128'N 106'E NE corner Lot 8 Block 3 PassA18.3%105.0 2.3%95%Pass 19 2/11 4 -2'Overlot Fill - 90'N 3'W NE corner Lot 8 Block 3 A 17.2%108.2 1.2% 96%Pass Pass 22 2/14 1 -1'Overlot Fill - 120'N NE corner Lot 8 Block 3 A 17.5%104.9 1.5%95%Pass Pass 21 2/11 6 -2'Overlot Fill - 146'N 214'E NE corner Lot 8 Block 3 A 18.1%105.2 2.1% 23 2/14 2 -1'Overlot Fill - 137'N 120'E NE corner Lot 8 Block 3 Pass 24 2/14 3 -1'Overlot Fill - 140'N 197'E NE corner Lot 8 Block 3 A 17.9%105.0 1.9% A 16.8%104.9 0.8%95%Pass 95%Pass Pass 97%Pass Pass 26 2/14 5 -2.5'Overlot Fill - 60'S 311'E NE corner Lot 8 Block 3 PassA18.4%104.9 2.4%95%Pass 25 2/14 4 -1.5'Overlot Fill - 15'S 26'E NE corner Lot 8 Block 3 A 18.2%106.7 2.2% 96%Pass Pass 28 2/14 7 -2'Overlot Fill - 57'S 207'E NE corner Lot 8 Block 3 A 18.5%105.0 2.5%95%Pass Pass 27 2/14 6 -2'Overlot Fill - 100'S 248'E NE corner Lot 8 Block 3 A 18.7%105.2 2.7% 29 2/14 8 -1'Overlot Fill - 68'S 107'E NE corner Lot 8 Block 3 Pass 30 2/14 9 -1'Overlot Fill - 80'S 200'E NE corner Lot 8 Block 3 A 19.0%105.0 3.0% A 17.9%105.2 1.9%96%Pass 95%Pass Pass 95%Pass Pass 32 2/15 2 Grade Overlot Fill - 75'S 140'E NE corner Lot 8 Block 3 PassA18.2%105.3 2.2%96%Pass 31 2/15 1 Grade Overlot Fill - 30'S NE corner Lot 8 Block 3 A 17.6%104.9 1.6% 95%Pass Pass 34 2/15 4 Grade Overlot Fill - 100'N 3'W NE corner Lot 8 Block 3 A 19.0%105.0 3.0%95%Pass Pass 33 2/15 3 Grade Overlot Fill - 90'N 169'E NE corner Lot 8 Block 3 A 18.5%104.9 2.5% 35 2/18 1 -8.5'Overlot Fill - 60'S NE corner Lot 23 Block 6 Pass 36 2/18 2 -3.5'Overlot Fill - 62'S 180'E NE corner Lot 23 Block 6 A 19.0%104.5 3.0% A 18.6%105.2 2.6%96%Pass 95%Pass Pass 96%Pass Pass 38 2/18 4 -3.5'Overlot Fill - 80'S 600'E NE corner Lot 23 Block 6 PassA18.0%104.5 2.0%95%Pass 37 2/18 3 -5.5'Overlot Fill - 68'S 315'E NE corner Lot 23 Block 6 A 18.2%105.9 2.2% 95%Pass Pass 40 2/18 6 -3.5'Overlot Fill - 200'S 503'E NE corner Lot 23 Block 6 A 18.4%104.9 2.4%95%Pass Pass 39 2/18 5 -4'Overlot Fill - 240'S 608'E NE corner Lot 23 Block 6 A 18.2%104.6 2.2% 41 2/18 7 -3.5'Overlot Fill - 162'S 405'E NE corner Lot 23 Block 6 Pass 42 2/18 8 -8'Overlot Fill - 62'S 11'W NE corner Lot 23 Block 6 A 19.0%105.2 3.0% A 18.6%105.4 2.6%96%Pass 96%Pass Pass 95%Pass Pass432/18 9 -3'Overlot Fill - 62'S 173'E NE corner Lot 23 Block 6 A 18.6%105.0 2.6% Compaction Requirement Proctor ID:A Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Procedure D-698 Compaction Requirement 95% Min COUNTRY CLUB RESERVE Fort Collins, Colorado Project # 22-2002 February/March 2022 Field Moisture/Density Testing Summary Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Moisture Compaction 44 2/19 1 -1.5'Overlot Fill - 21'S 100'E NW corner Lot 13 Block 6 A 19.0% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 105.3 3.0%96%Pass Pass 45 2/19 2 -1.5'Overlot Fill - 45'S 19'E NW corner Lot 13 Block 6 Pass 46 2/19 3 -1.5'Overlot Fill - 69'S 300'E NW corner Lot 13 Block 6 A 19.0%105.0 3.0% A 16.9%106.7 0.9%97%Pass 95%Pass Pass 47 2/19 4 -3'Overlot Fill - 50'S 250'W NW corner Lot 13 Block 6 A 17.8%105.8 1.8%96%Pass Pass 48 2/21 1 -2'Overlot Fill - 21'S 200'E NW corner Lot 17 Block 6 Pass 49 2/21 2 -1'Overlot Fill - 60'S 300'E NW corner Lot 17 Block 6 A 18.1%105.1 2.1% A 18.6%104.6 2.6%95%Pass 96%Pass Pass 95%Pass Pass 51 2/21 4 -3'Overlot Fill - 40'S 60'W NW corner Lot 17 Block 6 PassA19.0%104.5 3.0%95%Pass 50 2/21 3 -1'Overlot Fill - 90'S 600'E NW corner Lot 17 Block 6 A 18.9%104.8 2.9% 95%Pass Pass 53 2/21 6 -0.5'Overlot Fill - 38'S 248'E NW corner Lot 17 Block 6 A 18.4%105.2 2.4%96%Pass Pass 52 2/21 5 -2'Overlot Fill - 80'S 115'W NW corner Lot 17 Block 6 A 18.2%105.0 2.2% 54 2/21 7 -0.5'Overlot Fill - 59'S 381'E NW corner Lot 17 Block 6 Pass 55 2/21 8 -0.5'Overlot Fill - 76'S 507'E NW corner Lot 17 Block 6 A 18.9%104.5 2.9% A 19.0%104.5 3.0%95%Pass 95%Pass Pass 95%Pass Pass 57 2/28 2 -0.5'Overlot Fill - 40'S 19'E SE corner Lot 13 Block 6 PassA17.0%105.0 1.0%95%Pass 56 2/28 1 -0.5'Overlot Fill - 20'S 11'W SE corner Lot 15 Block 6 A 17.8%104.7 1.8% 95%Pass Pass 59 2/28 4 -2.5'Overlot Fill - 46'S 120'W NW corner Lot 15 Block 6 A 16.4%104.7 0.4%95%Pass Pass 58 2/28 3 -0.5'Overlot Fill - 60'S 7'W SW corner Lot 11 Block 6 A 18.5%104.9 2.5% 60 2/28 5 -3'Overlot Fill - 6'S 333'W NE corner Lot 7 Block 6 Pass 61 2/28 6 Grade Overlot Fill - 33'S 350'W NE corner Lot 7 Block 6 A 17.0%106.1 1.0% A 17.3%105.9 1.3%96%Pass 96%Pass Pass 95%Pass Pass 63 2/28 8 Grade Overlot Fill - 50'S 69'W NE corner Lot 7 Block 6 PassA17.9%106.0 1.9%96%Pass 62 2/28 7 Grade Overlot Fill - 42'S 218'W NE corner Lot 7 Block 6 A 18.2%104.9 2.2% 95%Pass Pass 65 3/1 2 -2'Overlot Fill - 21'N 2100'W NE corner Lot 7 Block 6 A 13.6%100.3 -2.4%91%*FAIL**FAIL* 64 3/1 1 -2'Overlot Fill - 21'N 120'W NE corner Lot 7 Block 6 A 17.1%104.6 1.1% 66 3/1 3 -2.5'Overlot Fill - 24'N 300'W NE corner Lot 7 Block 6 Pass 67 3/1 4 -3'Overlot Fill - 26'N 510'W NE corner Lot 7 Block 6 A 18.2%105.0 2.2% A 17.3%106.7 1.3%97%Pass 95%Pass Pass 97%Pass Pass 69 3/1 6 -3.5'Overlot Fill - 120'N 45'E NE corner Lot 1 Block 5 PassA18.6%104.5 2.6%95%Pass 68 3/1 5 -2'Retest #65 A 17.9%106.9 1.9% 96%Pass Pass 71 3/1 8 -2.5'Overlot Fill - 240'N 150'W NE corner Lot 1 Block 5 A 16.3%106.7 0.3%97%Pass Pass 70 3/1 7 -3'Overlot Fill - 150'N 69'W NE corner Lot 1 Block 5 A 18.2%105.9 2.2% 72 3/1 9 -2'Overlot Fill - 200'N 240'W NE corner Lot 1 Block 5 Pass 73 3/1 10 -1'Overlot Fill - 25'N 140'W NE corner Lot 7 Block 6 A 17.2%106.3 1.2% A 17.9%104.9 1.9%95%Pass 97%Pass Pass 95%Pass Pass 75 3/1 12 -1.5'Overlot Fill - 22'N 276'W NE corner Lot 7 Block 6 PassA17.8%105.8 1.8%96%Pass 74 3/1 11 -1'Overlot Fill - 23'N 192'W NE corner Lot 7 Block 6 A 19.0%104.9 3.0% 96%Pass Pass 77 3/1 14 -1.5'Overlot Fill - 200'N 169'W NE corner Lot 1 Block 5 A 17.3%105.1 1.3%96%Pass Pass 76 3/1 13 -1'Overlot Fill - 146'N 237'W NE corner Lot 1 Block 5 A 18.7%106.0 2.7% 78 3/1 15 -2'Overlot Fill - 175'N 75'W NE corner Lot 1 Block 5 Pass 79 3/1 16 -2.5'Overlot Fill - 180'N 48'W NE corner Lot 1 Block 5 A 18.7%108.3 2.7% A 15.2%108.5 -0.8%99%Pass 98%Pass Pass Compaction Requirement Proctor ID:A Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Procedure D-698 Compaction Requirement 95% Min COUNTRY CLUB RESERVE Fort Collins, Colorado Project # 22-2002 March 2022 Field Moisture/Density Testing Summary Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Moisture Compaction 80 3/2 1 -1'Overlot Fill - 238'N 75'W NE corner Lot 1 Block 5 A 17.3% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 108.7 1.3%99%Pass Pass 81 3/2 2 -0.5'Overlot Fill - 228'N 169'W NE corner Lot 1 Block 5 Pass 82 3/2 3 -2'Overlot Fill - 215'N 229'W NE corner Lot 1 Block 5 A 18.2%105.9 2.2% A 17.0%105.1 1.0%96%Pass 96%Pass Pass 83 3/2 4 -0.5'Overlot Fill - 148'N 58'W NE corner Lot 1 Block 5 A 17.4%108.9 1.4%99%Pass Pass 84 3/2 5 -2.5'Overlot Fill - 207'N NE corner Lot 1 Block 5 Pass 85 3/2 6 -1'Overlot Fill - 187'N 220'W NE corner Lot 1 Block 5 A 17.0%107.5 1.0% A 16.5%107.4 0.5%98%Pass 98%Pass Pass 99%Pass Pass 87 3/2 8 -1.5'Overlot Fill - 24'N 200'W NE corner Lot 7 Block 6 PassA17.6%105.9 1.6%96%Pass 86 3/2 7 -2'Overlot Fill - 174'N 37'W NE corner Lot 1 Block 5 A 17.9%109.2 1.9% 99%Pass Pass 89 3/2 10 -2'Overlot Fill - 26'N 500'W NE corner Lot 7 Block 6 A 18.3%105.2 2.3%96%Pass Pass 88 3/2 9 -1.5'Overlot Fill - 25'N 400'W NE corner Lot 7 Block 6 A 15.2%108.7 -0.8% 90 3/3 1 -1'Overlot Fill - 15'N 270'W NE corner Lot 7 Block 6 Pass 91 3/3 2 -1.5'Overlot Fill - 18'N 375'W NE corner Lot 7 Block 6 A 18.8%109.1 2.8% A 17.0%105.8 1.0%96%Pass 99%Pass Pass 98%Pass Pass 93 3/3 4 -1.5'Overlot Fill - 150'N 69'W NE corner Lot 1 Block 5 PassA17.9%108.9 1.9%99%Pass 92 3/3 3 -1.5'Overlot Fill - 24'N 420'W NE corner Lot 7 Block 6 A 17.3%108.3 1.3% 98%Pass Pass 95 3/3 6 -2'Overlot Fill - 215'N 6'W NE corner Lot 1 Block 5 A 18.4%106.2 2.4%97%Pass Pass 94 3/3 5 -1.5'Overlot Fill - 108'N 227'W NE corner Lot 1 Block 5 A 16.2%108.1 0.2% 96 3/3 7 -1.5'Overlot Fill - 150'N 120'W NE corner Lot 1 Block 5 Pass 97 3/3 8 -3'Overlot Fill - 158'N 300'W NE corner Lot 1 Block 5 A 18.2%104.7 2.2% A 19.0%104.5 3.0%95%Pass 95%Pass Pass 99%Pass Pass 99 3/3 10 -1'Overlot Fill - 30'S 187'E SW corner Lot 34 Block 9 PassA16.9%108.2 0.9%98%Pass 98 3/3 9 -1'Overlot Fill - 18'S 90'E SW corner Lot 34 Block 9 A 17.7%108.4 1.7% 96%Pass Pass 101 3/3 12 -1'Overlot Fill - 9'S 300'E NW corner Lot 10 Block 1 A 18.5%109.0 2.5%99%Pass Pass 100 3/3 11 -0.5'Overlot Fill - 32'S 12'W SW corner Lot 34 Block 9 A 16.0%106.1 0.0% 102 3/3 13 -1.5'Overlot Fill - 10'S 375'E NW corner Lot 10 Block 1 Pass 103 3/3 14 -1.5'Overlot Fill - 12'S 450'E NW corner Lot 10 Block 1 A 18.2%106.8 2.2% A 18.0%106.8 2.0%97%Pass 97%Pass Pass 96%Pass Pass 105 3/4 2 -1.5'Overlot Fill - 5'S 210'E NW corner Lot 10 Block 1 PassA19.0%104.7 3.0%95%Pass 104 3/4 1 -1.5'Overlot Fill - 3'N 90'E NW corner Lot 10 Block 1 A 18.2%106.1 2.2% 99%Pass Pass 107 3/4 4 -1'Overlot Fill - 8'S 570'E NW corner Lot 10 Block 1 A 17.0%108.5 1.0%99%Pass Pass 106 3/4 3 -1.5'Overlot Fill - 7'S 300'E NW corner Lot 10 Block 1 A 17.6%109.2 1.6% 108 3/4 5 -1'Overlot Fill - 72'N 6000'E NW corner Lot 10 Block 1 Pass 109 3/4 6 Grade Overlot Fill - 20'S 111'E SW corner Lot 34 Block 9 A 16.3%108.8 0.3% A 18.8%104.6 2.8%95%Pass 99%Pass Pass 98%Pass Pass 111 3/4 8 Grade Overlot Fill - 31'S 10'W SW corner Lot 34 Block 9 PassA18.5%107.5 2.5%98%Pass 110 3/4 7 Grade Overlot Fill - 25'S 150'E SW corner Lot 34 Block 9 A 18.8%108.3 2.8% 99%Pass Pass 113 3/4 10 -1'Overlot Fill - 4'N 240'E NW corner Lot 10 Block 1 A 15.9%107.9 -0.1%98%Pass Pass 112 3/4 9 -1'Overlot Fill - 4'S 120'E NW corner Lot 10 Block 1 A 15.7%108.9 -0.3% 114 3/4 11 -1'Overlot Fill - 4'S 420'E NW corner Lot 10 Block 1 Pass 115 3/7 1 -2.5'Overlot Fill - 9'N 10'W SW corner Lot 34 Block 9 A 18.2%105.0 2.2% A 16.0%107.9 0.0%98%Pass 95%Pass Pass 96%Pass Pass 117 3/7 3 -3'Overlot Fill - 60'N 180'E SW corner Lot 34 Block 9 PassA16.3%105.0 0.3%95%Pass 116 3/7 2 -3.5'Overlot Fill - 39'N 90'E SW corner Lot 34 Block 9 A 18.5%105.9 2.5% 95%Pass Pass 119 3/7 5 -3'Overlot Fill - 80'N 58'E SW corner Lot 34 Block 9 A 17.7%108.1 1.7%98%Pass Pass 118 3/7 4 -2.5'Overlot Fill - 72'N 369'E SW corner Lot 34 Block 9 A 19.0%104.8 3.0% 120 3/7 6 -3.5'Overlot Fill - 28'N 120'E SW corner Lot 34 Block 9 Pass 121 3/7 7 -3.5'Overlot Fill - 38'N 225'E SW corner Lot 34 Block 9 A 18.5%108.9 2.5% A 19.0%104.7 3.0%95%Pass 99%Pass Pass 99%Pass Pass1223/7 8 -3'Overlot Fill - 48'N 318'E SW corner Lot 34 Block 9 A 18.8%108.5 2.8% Compaction Requirement Proctor ID:A Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Procedure D-698 Compaction Requirement 95% Min Procedure D-698 Compaction Requirement 95% Min Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Compaction Requirement Proctor ID:A 157 3/14 13 -0.5'Overlot Fill - 58'N 250'E SW corner Lot 34 Block 9 PassA16.2%105.9 0.2%96%Pass 97%Pass Pass 156 3/14 12 -1'Overlot Fill - 27'N 120'E SW corner Lot 34 Block 9 A 17.5%105.8 1.5%96%Pass Pass 155 3/14 11 -1.5'Overlot Fill - 24'N 47'E SW corner Lot 34 Block 9 A 18.1%106.3 2.1% 99%Pass Pass 154 3/14 10 -2'Overlot Fill - 115'S 80'W SE corner Lot 4 Block 7 PassA17.7%105.9 1.7%96%Pass 153 3/14 9 -2'Overlot Fill - 105'S 40'W SE corner Lot 4 Block 7 A 16.3%109.3 0.3% 151 3/14 7 -2.5'Overlot Fill - 100'S 92'W SE corner Lot 4 Block 7 Pass 152 3/14 8 -2'Overlot Fill - 89'S 5'W SE corner Lot 4 Block 7 A 18.2%108.6 2.2% A 17.6%105.0 1.6%95%Pass 99%Pass Pass 95%Pass Pass 150 3/14 6 -2.5'Overlot Fill - 118'S 20'E SE corner Lot 4 Block 7 A 18.7%106.2 2.7%97%Pass Pass 149 3/14 5 -2.5'Overlot Fill - 75'S 10'W SE corner Lot 4 Block 7 A 18.2%104.9 2.2% 95%Pass Pass 148 3/14 4 -0.5'Overlot Fill - 60'N 207'E SW corner Lot 34 Block 9 PassA17.8%105.2 1.8%96%Pass 147 3/14 3 -1'Overlot Fill - 36'N 290'E SW corner Lot 34 Block 9 A 19.0%104.7 3.0% 145 3/14 1 -2'Overlot Fill - 13'N 10'E SW corner Lot 34 Block 9 Pass 146 3/14 2 -1.5'Overlot Fill - 30'N 111'E SW corner Lot 34 Block 9 A 17.0%108.9 1.0% A 16.9%108.7 0.9%99%Pass 99%Pass Pass 98%Pass Pass 144 3/12 7 -3'Overlot Fill - 90'S 90'W SE corner Lot 4 Block 7 A 17.6%106.1 1.6%96%Pass Pass 143 3/12 6 -3'Overlot Fill - 120'S 15'E SE corner Lot 4 Block 7 A 17.0%108.2 1.0% 96%Pass Pass 142 3/12 5 -3'Overlot Fill - 69'S SE corner Lot 4 Block 7 PassA17.1%106.9 1.1%97%Pass 141 3/12 4 -0.5'Overlot Fill - 62'N 250'E SW corner Lot 34 Block 9 A 18.0%105.8 2.0% 139 3/12 2 -2'Overlot Fill - 27'N 100'E SW corner Lot 34 Block 9 Pass 140 3/12 3 -1.5'Overlot Fill - 28'N 300'E SW corner Lot 34 Block 9 A 18.2%106.7 2.2% A 19.0%104.9 3.0%95%Pass 97%Pass Pass 98%Pass Pass 138 3/12 1 -2.5'Overlot Fill - 9'N SW corner Lot 34 Block 9 A 17.3%108.2 1.3%98%Pass Pass 137 3/8 15 -3'Retest #135 A 16.6%107.5 0.6% 95%*FAIL*Pass 136 3/8 14 -4'Overlot Fill - 76'S 189'E SE corner Lot 4 Block 7 PassA16.5%107.9 0.5%98%Pass 135 3/8 13 -3'Overlot Fill - 42'S 12'E SE corner Lot 4 Block 7 A 14.2%104.5 -1.8% 133 3/8 11 -2'Overlot Fill - 69'S 206'E SE corner Lot 4 Block 7 Pass 134 3/8 12 -2'Overlot Fill - 47'S 137'E SE corner Lot 4 Block 7 A 18.1%105.2 2.1% A 17.2%106.8 1.2%97%Pass 96%Pass Pass 95%Pass Pass 132 3/8 10 -1.5'Overlot Fill - 30'N 298'E SW corner Lot 34 Block 9 A 17.7%106.1 1.7%96%Pass Pass 131 3/8 9 -2'Overlot Fill - 40'N 200'E SW corner Lot 34 Block 9 A 18.3%104.9 2.3% 98%Pass Pass 130 3/8 8 -1.5'Overlot Fill - 35'N 87'E SW corner Lot 34 Block 9 PassA17.9%105.3 1.9%96%Pass 129 3/8 7 -2'Overlot Fill - 50'N 300'E SW corner Lot 34 Block 9 A 16.7%108.2 0.7% 127 3/8 5 -2'Overlot Fill - 22'N 69'E SW corner Lot 34 Block 9 Pass 128 3/8 6 -2.5'Overlot Fill - 43'N 187'E SW corner Lot 34 Block 9 A 18.5%104.6 2.5% A 18.3%104.7 2.3%95%Pass 95%Pass Pass Pass 126 3/8 4 -2.5'Overlot Fill - 70'S 210'E SE corner Lot 4 Block 7 A 16.3%106.1 0.3%96%Pass Pass Pass 124 3/8 2 -3.5'Overlot Fill - 60'S SE corner Lot 4 Block 7 Pass 125 3/8 3 -2.5'Overlot Fill - 90'S 120'E SE corner Lot 4 Block 7 A 15.2%105.9 -0.8% A 18.8%105.6 2.8%96%Pass 96%Pass Moisture Compaction 123 3/8 1 -4.5'Overlot Fill - 33'S 36'W SE corner Lot 4 Block 7 A 18.0% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 106.4 2.0%97%Pass Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Fort Collins, Colorado Project # 22-2002 March 2022 Field Moisture/Density Testing Summary COUNTRY CLUB RESERVE Procedure D-698 Compaction Requirement 95% Min Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Compaction Requirement Proctor ID:A 192 3/21 12 -1'Overlot Fill - 100'S 118'W SE corner Lot 6 Block 7 PassA18.5%106.7 2.5%97%Pass 98%Pass Pass 191 3/21 11 -1.5'Overlot Fill - 120'S 94'W SE corner Lot 6 Block 7 A 16.1%109.0 0.1%99%Pass Pass 190 3/21 10 -0.5'Overlot Fill - 69'S 142'W SE corner Lot 6 Block 7 A 16.4%107.3 0.4% 98%Pass Pass 189 3/21 9 Grade Overlot Fill - 40'S 8'W SE corner Lot 6 Block 7 PassA18.8%106.6 2.8%97%Pass 188 3/21 8 -0.5'Overlot Fill - 156'S 299'E center of Lot 34 Block 9 A 16.0%107.5 0.0% 186 3/21 6 -0.5'Overlot Fill - 153'S 120'E center of Lot 34 Block 9 Pass 187 3/21 7 -0.5'Overlot Fill - 153'S 210'E center of Lot 34 Block 9 A 18.3%106.7 2.3% A 19.0%104.8 3.0%95%Pass 97%Pass Pass 97%Pass Pass 185 3/21 5 -0.5'Overlot Fill - 150'S center of Lot 34 Block 9 A 17.7%108.0 1.7%98%Pass Pass 184 3/21 4 -1.5'Overlot Fill - 96'S 120'W SE corner Lot 6 Block 7 A 18.0%106.2 2.0% 95%Pass Pass 183 3/21 3 -2'Overlot Fill - 116'S 100'W SE corner Lot 6 Block 7 PassA18.8%104.9 2.8%95%Pass 182 3/21 2 -1'Overlot Fill - 66'S 150'W SE corner Lot 6 Block 7 A 19.0%104.6 3.0% 180 3/16 9 -2'Overlot Fill - 158'N 248'W SE corner Lot 19 Block 6 Pass 181 3/21 1 -0.5'Overlot Fill - 36'S SE corner Lot 6 Block 7 A 17.8%106.1 1.8% A 19.0%104.8 3.0%95%Pass 96%Pass Pass 99%Pass Pass 179 3/16 8 -3.5'Overlot Fill - 157'N 175'W SE corner Lot 19 Block 6 A 18.7%105.0 2.7%95%Pass Pass 178 3/16 7 -1'Overlot Fill - 43'S 300'E center of Lot 34 Block 9 A 17.2%109.1 1.2% 95%Pass Pass 177 3/16 6 -1'Overlot Fill - 69'S 150'E center of Lot 34 Block 9 PassA18.5%104.9 2.5%95%Pass 176 3/16 5 -1'Overlot Fill - 33'S center of Lot 34 Block 9 A 19.0%104.5 3.0% 174 3/16 3 -1.5'Overlot Fill - 158'N 275'E SE corner Lot 19 Block 6 Pass 175 3/16 4 -1.5'Overlot Fill - 155'N 235'E SE corner Lot 19 Block 6 A 16.9%108.9 0.9% A 18.5%105.6 2.5%96%Pass 99%Pass Pass 98%Pass Pass 173 3/16 2 -4'Overlot Fill - 152'N 169'W SE corner Lot 19 Block 6 A 18.0%105.1 2.0%96%Pass Pass 172 3/16 1 -2.5'Overlot Fill - 169'N 250'W SE corner Lot 19 Block 6 A 16.2%108.0 0.2% 99%Pass Pass 171 3/15 14 -3'Overlot Fill - 152'N 265'W SE corner Lot 19 Block 6 PassA18.2%105.9 2.2%96%Pass 170 3/15 13 -2'Overlot Fill - 151'N 118'W SE corner Lot 19 Block 6 A 16.9%109.4 0.9% 168 3/15 11 -4.5'Overlot Fill - 162'N 175'W SE corner Lot 19 Block 6 Pass 169 3/15 12 -1'Overlot Fill - 155'N 235'W SE corner Lot 19 Block 6 A 17.2%107.3 1.2% A 16.3%108.5 0.3%99%Pass 98%Pass Pass 98%Pass Pass 167 3/15 10 -1.5'Overlot Fill - 160'N 230'E SE corner Lot 19 Block 6 A 19.0%105.0 3.0%95%Pass Pass 166 3/15 9 -0.5'Overlot Fill - 150'N 240'E SE corner Lot 19 Block 6 A 18.0%107.9 2.0% 98%Pass Pass 165 3/15 8 -1.5'Overlot Fill - 60'N 350'E SE corner Lot 19 Block 6 PassA17.6%105.2 1.6%96%Pass 164 3/15 7 -0.5'Overlot Fill - 450'E SE corner Lot 19 Block 6 A 18.2%108.0 2.2% 162 3/15 5 -3.5'Overlot Fill - 150'N 270'W SE corner Lot 19 Block 6 Pass 163 3/15 6 -2'Overlot Fill - 105'N 275'W SE corner Lot 19 Block 6 A 18.5%108.8 2.5% A 19.0%104.6 3.0%95%Pass 99%Pass Pass Pass 161 3/15 4 -3'Overlot Fill - 152'N 210'W SE corner Lot 19 Block 6 A 17.9%105.7 1.9%96%Pass Pass Pass 159 3/15 2 -2.5'Overlot Fill - 150'N 120'W SE corner Lot 19 Block 6 Pass 160 3/15 3 -5'Overlot Fill - 150'N 180'W SE corner Lot 19 Block 6 A 18.2%104.9 2.2% A 16.1%109.2 0.1%99%Pass 95%Pass Moisture Compaction 158 3/15 1 -0.5'Overlot Fill - 90'N SE corner Lot 19 Block 6 A 17.3% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 107.5 1.3%98%Pass Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Fort Collins, Colorado Project # 22-2002 March 2022 Field Moisture/Density Testing Summary COUNTRY CLUB RESERVE Procedure D-698 Compaction Requirement 95% Min Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Compaction Requirement Proctor ID:A PassA17.5%108.6 1.5%99%Pass 105.0 3.0%95%Pass Pass 230 3/24 14 -1'Overlot Fill - 7'N center of Lot 10 Block 10 97%Pass Pass 229 3/24 13 -0.5'Overlot Fill - 8'N center of Lot 6 Block 10 A 19.0% Pass 228 3/24 12 Grade Overlot Fill - 10'N center of Lot 2 Block 10 A 17.2%106.7 1.2% A 17.8%108.3 1.8%98%Pass 104.8 3.0%95%Pass Pass 227 3/24 11 -2'Overlot Fill - Lot 12 Block 10 97%Pass Pass 226 3/24 10 -2'Overlot Fill - Lot 11 Block 10 A 19.0% Pass 225 3/24 9 -2'Overlot Fill - Lot 10 Block 10 A 16.9%106.9 0.9% A 16.3%106.7 0.3%97%Pass 105.9 2.2%96%Pass Pass 224 3/24 8 -2.5'Overlot Fill - Lot 9 Block 10 95%Pass Pass 223 3/24 7 -2'Overlot Fill - Lot 8 Block 10 A 18.2% Pass 222 3/24 6 -2'Overlot Fill - Lot 7 Block 10 A 19.0%104.8 3.0% A 18.7%105.7 2.7%96%Pass 105.2 2.0%96%Pass Pass 221 3/24 5 -1'Overlot Fill - Lot 6 Block 10 95%Pass Pass 220 3/24 4 -1'Overlot Fill - Lot 5 Block 10 A 18.0% Pass 219 3/24 3 -1'Overlot Fill - Lot 4 Block 10 A 19.0%104.9 3.0% A 17.2%106.1 1.2%96%Pass 106.9 -0.1%97%Pass Pass 218 3/24 2 -0.5'Overlot Fill - Lot 3 Block 10 96%Pass Pass 217 3/24 1 -0.5'Overlot Fill - Lot 2 Block 10 A 15.9% Pass 216 3/23 6 -3'Overlot Fill - 7'S 11'W NE corner Lot 12 Block 10 A 18.2%105.5 2.2% A 15.9%109.2 -0.1%99%Pass 104.9 3.0%95%Pass Pass 215 3/23 5 -3.5'Overlot Fill - 26'S 8'E NW corner Lot 10 Block 10 96%Pass Pass 214 3/23 4 -4'Overlot Fill - 10'S 7'E NW corner Lot 8 Block 10 A 19.0% Pass 213 3/23 3 -2.5'Overlot Fill - 10'S 10'E NW corner Lot 5 Block 10 A 18.5%105.5 2.5% A 18.7%107.9 2.7%98%Pass 107.5 1.8%98%Pass Pass 212 3/23 2 -1.5'Overlot Fill - 15'S 11'W NE corner Lot 3 Block 10 95%Pass Pass 211 3/23 1 -1.5'Overlot Fill - 8'S 4'W NE corner Lot 2 Block 10 A 17.8% Pass 210 3/22 18 -4.5'Retest #208 A 15.9%104.7 -0.1% A 16.2%108.6 0.2%99%Pass 96.5 -4.8%88%*FAIL**FAIL* 209 3/22 17 -4.5'Overlot Fill - 12'N 8'E SW corner Lot 12 Block 10 95%Pass Pass 208 3/22 16 -4.5'Overlot Fill - 46'N 15'E SW corner Lot 11 Block 10 A 11.2% Pass 207 3/22 15 -4'Overlot Fill - 40'N 10'E SW corner Lot 10 Block 10 A 17.9%104.9 1.9% A 16.1%108.6 0.1%99%Pass 109.1 0.3%99%Pass Pass 206 3/22 14 -4'Overlot Fill - 42'N 13'E SW corner Lot 9 Block 10 99%Pass Pass 205 3/22 13 -4.5'Overlot Fill - 48'N 5'E SW corner Lot 8 Block 10 A 16.3% Pass 204 3/22 12 -5.5'Overlot Fill - 15'N 15'E SW corner Lot 7 Block 10 A 17.0%109.2 1.0% A 16.9%108.5 0.9%99%Pass 108.3 0.4%98%Pass Pass 203 3/22 11 -5.5'Overlot Fill - 8'N 10'E SW corner Lot 6 Block 10 95%Pass Pass 202 3/22 10 -5.5'Overlot Fill - 13'N 15'E SW corner Lot 5 Block 10 A 16.4% Pass 201 3/22 9 -5.5'Overlot Fill - 4'N 6'E SW corner Lot 4 Block 10 A 19.0%104.7 3.0% A 17.8%106.6 1.8%97%Pass 104.9 2.3%95%Pass Pass 200 3/22 8 -3'Overlot Fill - 10'N 20'E SW corner Lot 3 Block 10 97%Pass Pass 199 3/22 7 -3'Overlot Fill - 46'N 18'E SW corner Lot 2 Block 10 A 18.3% Pass 198 3/22 6 Grade Overlot Fill - 155'S 270'E center of Lot 34 Block 9 A 16.8%106.5 0.8% A 18.5%108.2 2.5%98%Pass 105.8 2.7%96%Pass Pass 197 3/22 5 Grade Overlot Fill - 154'S 190'E center of Lot 34 Block 9 95%Pass Pass 196 3/22 4 Grade Overlot Fill - 152'S 34'E center of Lot 34 Block 9 A 18.7% Pass 195 3/22 3 -0.5'Overlot Fill - 4'S 4'E NW corner Lot 26 Block 6 A 19.0%104.9 3.0% A 16.2%109.1 0.2%99%Pass 108.6 1.4%99%Pass Pass 194 3/22 2 -0.5'Overlot Fill - 27'N 18'W NW corner Lot 25 Block 6 Density Moisture Compaction 193 3/22 1 -0.5'Overlot Fill - 20'S 10'E NW corner Lot 25 Block 6 A 17.4% Number Number ID Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Pe r c e n t Co m p a c t i o n Field Results Dry (Pass/Fail)Material Tested and LocationProjectDateDailyDepth Fort Collins, Colorado Project # 22-2002 March 2022 Field Moisture/Density Testing Summary COUNTRY CLUB RESERVE Procedure D-698 Compaction Requirement 95% Min Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Compaction Requirement Proctor ID:A PassA18.6%105.8 2.6%96%Pass 106.7 2.0%97%Pass Pass 238 3/25 8 -3'Overlot Fill - 20'S 4'W NE corner Lot 2 Block 10 96%Pass Pass 237 3/25 7 -3'Overlot Fill - 3'S 11'E NW corner Lot 4 Block 10 A 18.0% Pass 236 3/25 6 Grade Overlot Fill - 2'S 8'E NW corner Lot 7 Block 10 A 17.8%105.1 1.8% A 18.8%106.9 2.8%97%Pass 105.1 2.8%96%Pass Pass 235 3/25 5 Grade Overlot Fill - 10'S 5'W NE corner Lot 11 Block 10 97%Pass Pass 234 3/25 4 Grade Overlot Fill - 4'N 4'E SW corner Lot 2 Block 10 A 18.8% Pass 233 3/25 3 -0.5'Overlot Fill - 6'N 5'W SE corner Lot 6 Block 10 A 17.2%106.7 1.2% A 19.0%105.9 3.0%96%Pass 108.6 0.4%99%Pass Pass 232 3/25 2 -0.5'Overlot Fill - 5'N 4'E SW corner Lot 8 Block 10 Density Moisture Compaction 231 3/25 1 -0.5'Overlot Fill - 8'N 6'W SE corner Lot 12 Block 10 A 16.4% Number Number ID Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Pe r c e n t Co m p a c t i o n Field Results Dry (Pass/Fail)Material Tested and LocationProjectDateDailyDepth Fort Collins, Colorado Project # 22-2002 March 2022 Field Moisture/Density Testing Summary COUNTRY CLUB RESERVE Soilogic, Inc. 3522 Draft Horse Court • Loveland, CO 80538 • (970) 535-6144 April 26, 2022 Coyote Ridge Construction, LLC 6648 County Road 56 Johnstown, Colorado 80534 Attn: Mr. Ken Baty Re: Construction Materials Testing and Observation Services Report Country Club Reserve Fort Collins, Colorado Soilogic Project # 22-2002 Mr. Baty: During the period of March 28, 2022 through April 22, 2022, Soilogic Inc. (Soilogic) provided construction materials testing and observation services for the referenced project. Our services were provided on a part-time basis and included the observation and testing of overlot fill, utility backfill, reconditioned subgrade and aggregate base course materials, concrete delivered to the site for placement and asphaltic concrete placed during paving of the site roadways. Results of the observation and testing services completed during the referenced period are included with this report. During the referenced period, Soilogic personnel obtained one (1) representative sample of the aggregate base course for laboratory evaluation of the moisture density relationship of that material. The laboratory testing completed on the obtained samples included a standard Proctor (ASTM D-698) test. Results of the completed standard Proctor tests were used to evaluate the percent compaction and moisture variability with reworked soils in the field. During the referenced period, Soilogic personnel performed field moisture/density tests on overlot fill, utility backfill, reconditioned subgrade and aggregate base course materials that had been placed and compacted prior to and during our site visits. The field moisture/density tests were completed at random locations and elevations within the backfill areas and were performed in general accordance with ASTM Specification D- 2922. Results of the field moisture/density tests completed during the referenced period are included with this report. The field moisture/density test results met the project compaction requirement of at least 95% of the material’s standard Proctor maximum dry Construction Materials Testing and Observation Services Report Country Club Reserve Fort Collins, Colorado Soilogic # 22-2002 2 density and within -1% to +3% for native soils and +/-2% for aggregate base course of the materials optimum moisture content. During the referenced period, Soilogic personnel observed and tested cast-in-place concrete delivered to the site for construction of inlets. The testing completed in the field included slump, air content, unit weight, concrete temperature, and ambient air temperature at the time of placement. Test cylinders were molded from representative samples of the plastic concrete for laboratory curing and compressive strength testing. Results of the field and laboratory tests performed during the referenced period are included with this report. Results of laboratory concrete compressive strength tests completed during the referenced period are also included and will be provided as they become available. During the site paving operation, Soilogic personnel obtained two (2) representative samples of the asphaltic concrete being placed for laboratory evaluation. The laboratory testing performed on the obtained samples included Rice value (ASTM D-2041), asphalt content by ignition (ASTM D-6307) and washed sieve analysis/gradation (ASTM C-117 and C-136) tests. Results of the completed Rice value and asphalt content and gradation tests are outlined on the attached summary sheets. The completed laboratory testing performed on the asphaltic concrete samples indicated those materials met the project gradation and asphalt content specifications. During and after compaction of the asphaltic concrete, density tests were completed on the in-place pavement using a portable nuclear density gauge in general accordance with ASTM specification D-2950. The nuclear density tests were completed at random locations across the pavement surface. Results of the completed field density tests are outlined on the attached summary sheet. The final completed asphaltic concrete field density tests met the project compaction requirement of 92 to 96% of the materials Rice value. Construction Materials Testing and Observation Services Report Country Club Reserve Fort Collins, Colorado Soilogic # 22-2002 3 We appreciate the opportunity to be of service to you on this project. If you have any questions concerning the enclosed information or if we can be of further assistance to you in any way, please do not hesitate to contact us. Very Truly Yours, Soilogic, Inc. Kreis A Rutledge Jason Horner, P.E. Senior Engineering Technician Senior Project Engineer Description: Class 5 Road Base Sample Location: Onsite Material ID: 22-2002B 90 95 100 105 110 115 120 125 130 135 140 145 0 5 10 15 20 25 30 35 Dr y De n s i t y (p c f ) . Moisture Content (%) Standard Proctor Test Summary (ASTM D-698) COUNTRY CLUB RESERVE FORT COLLINS, CO Project #22-2002 APRIL 2022 Maximum Dry Density = 137.0 pcf Optimum Moisture Content =7.0% Liquid Limit = NL Plasticity Index = NP -200 Wash = 11.7% Saturation Curves @ Specific Gravity Equal to: 2.80 2.70 2.60 4" 3" 2" 1 1/2" 1" 3/4" 1/2" 3/8" 1/4" No. 4 No. 8 No. 10 No. 16 No. 30 No. 40 No. 50 No. 100 No. 200 Sample Description: Class 5 Road Base 63% 53% 51% 44% 33% 28% 23% 16% 11.7% Sample ID: B 67% 100% 100% 100% 100% 100% 93% 80% 74% 5"100% COUNTRY CLUB RESERVE FORT COLLINS, COLORADO Project # 22-2002 APRIL 2022 SUMMARY OF GRADATION TEST ANALYSIS GRADATION OF AGGREGATE (AASHTO T-11, T-27) SIEVE SIZE PERCENT PASSING 6"100% Pr o j e c t - L a s t C h a n c e A g g r e g a t e E v a l u a t i o n Sa m p l e D e s c r i p t i o n : C l a s s 5 R o a d B a s e CO U N T R Y C L U B R E S E R V E FO R T C O L L I N S , C O L O R A D O Pr o j e c t # 2 2 - 2 0 0 2 AP R I L 2 0 2 2 Sa m p l e I D : B 0% 10 % 20 % 30 % 40 % 50 % 60 % 70 % 80 % 90 % 10 0 % 0. 0 0 1 0. 0 1 0. 1 1 10 10 0 Percent Finer by Weight Gr a i n S i z e i n M i l l i m e t e r s Su m m a r y o f W a s h e d S i e v e A n a l y s i s T e s t 2" 1 . 5 " 1 " 3 / 4 " 1 / 2 " 3 / 8 " N o 4 N o 8 N o 1 6 N o 4 0 N o 1 0 0 N o 2 0 0 No 3 0 N o 5 0 U. S . S t a n d a r d S i e v e O p e n i n g s i n I n c h e s U . S . S t a n d a r d S i e v e N u m b e r s Hy d r o m e t e r Procedure D-698 Compaction Requirement 95% Min Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Compaction Requirement Proctor ID:A 267 3/31 10 -1'Overlot Fill - 15'S 11'E NW corner Lot 19 Block 10 PassA18.5%108.4 2.5%99%Pass 95%Pass Pass 266 3/31 9 -1'Overlot Fill - 24'S 12'W NE corner Lot 17 Block 5 A 18.2%108.7 2.2%99%Pass Pass 265 3/31 8 -1'Overlot Fill - 10'N 10'E SW corner Lot 15 Block 10 A 19.0%105.0 3.0% 98%Pass Pass 264 3/31 7 -1'Overlot Fill - 19'S 27'E NW corner Lot 13 Block 10 PassA17.2%109.2 1.2%99%Pass 263 3/31 6 -6'Storm Line Backfill - Storm Line A STA 11+30 A 17.5%107.3 1.5% 261 3/31 4 Grade Storm Line Backfill - Storm Line A STA 10+85 Pass 262 3/31 5 -4'Storm Line Backfill - Storm Line A STA 11+03 A 16.9%109.1 0.9% A 19.0%104.8 3.0%95%Pass 99%Pass Pass 98%Pass Pass 260 3/31 3 Grade Overlot Fill - 10'S 6'E NW corner Lot 10 Block 5 A 18.2%104.6 2.2%95%Pass Pass 259 3/31 2 Grade Overlot Fill - 12'N 4'E SW corner Lot 9 Block 5 A 17.0%108.0 1.0% 97%Pass Pass 258 3/31 1 Grade Overlot Fill - 6'S 7'E NW corner Lot 8 Block 5 PassA17.2%108.2 1.2%98%Pass 257 3/29 11 -1.5'Overlot Fill - 9'S 8'E NW corner Lot 9 Block 5 A 17.9%107.1 1.9% 255 3/29 9 -1.5'Overlot Fill - 6'N 10'E SW corner Lot 8 Block 5 Pass 256 3/29 10 -1.5'Overlot Fill - 13'N 6'E SW corner Lot 7 Block 5 A 17.3%108.8 1.3% A 18.1%106.9 2.1%97%Pass 99%Pass Pass 99%Pass Pass 254 3/29 8 -1.5'Overlot Fill - 5'S 5'E NW corner Lot 9 Block 5 A 18.2%106.7 2.2%97%Pass Pass 253 3/29 7 -1.5'Overlot Fill - 7'N 6'E SW corner Lot 10 Block 5 A 16.0%108.5 0.0% 99%Pass Pass 252 3/29 6 -1'Storm Line Backfill - Storm Line A STA 10+89 PassA16.4%107.5 0.4%98%Pass 251 3/29 5 -2'Storm Line Backfill - Storm Line A STA 10+87 A 15.8%109.2 -0.2% 249 3/29 3 -4'Storm Line Backfill - Storm Line A STA 10+90 Pass 250 3/29 4 -3'Storm Line Backfill - Storm Line A STA 10+98 A 15.2%105.9 -0.8% A 16.0%105.7 0.0%96%Pass 96%Pass Pass 98%Pass Pass 248 3/29 2 -5'Storm Line Backfill - Storm Line A STA 10+85 A 16.8%105.2 0.8%96%Pass Pass 247 3/29 1 -3'Storm Line Backfill - Storm Line A STA 11+00 A 15.9%108.3 -0.1% 99%Pass Pass 246 3/28 8 Grade Overlot Fill - 7'N 11'E SW corner Lot 11 Block 10 PassA16.2%109.2 0.2%99%Pass 245 3/28 7 Grade Overlot Fill - 12'N 6'W SE corner Lot 9 Block 10 A 16.7%108.8 0.7% 243 3/28 5 Grade Overlot Fill - 6'N 12'W SE corner Lot 3 Block 10 Pass 244 3/28 6 Grade Overlot Fill - 5'N 5'E SW corner Lot 7 Block 10 A 19.0%104.9 3.0% A 18.2%104.6 2.2%95%Pass 95%Pass Pass Pass 242 3/28 4 -1'Overlot Fill - 7'N 11'E SW corner Lot 12 Block 10 A 17.2%105.9 1.2%96%Pass Pass Pass 240 3/28 2 -1'Overlot Fill - 8'N 6'E SW corner Lot 6 Block 10 Pass 241 3/28 3 -1'Overlot Fill - 5'N 5'W SE corner Lot 8 Block 10 A 18.9%106.5 2.9% A 18.5%104.9 2.5%95%Pass 97%Pass Moisture Compaction 239 3/28 1 -1'Overlot Fill - 13'N 8'W SE corner Lot 2 Block 10 A 18.1% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 106.9 2.1%97%Pass Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Fort Collins, Colorado Project # 22-2002 March 2022 Field Moisture/Density Testing Summary COUNTRY CLUB RESERVE Procedure D-698 Compaction Requirement 95% Min Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Compaction Requirement Proctor ID:A 302 4/7 10 -1'Sewer Main Backfill - Turnberry Rd STA 15+05 Pass 303 4/7 11 Grade Sewer Main Backfill - Turnberry Rd STA 15+00 A 15.8%109.2 -0.2% A 15.0%107.8 -1.0%98%Pass 99%Pass Pass 99%Pass Pass 301 4/7 9 -3'Sewer Main Backfill - Turnberry Rd STA 15+10 A 16.4%105.1 0.4%96%Pass Pass 300 4/7 8 -5'Sewer Main Backfill - Turnberry Rd STA 15+15 A 15.2%108.7 -0.8% 98%Pass Pass 299 4/7 7 -7'Sewer Main Backfill - Turnberry Rd STA 15+20 PassA15.9%108.0 -0.1%98%Pass 298 4/7 6 Grade Sewer Main Backfill - Turnberry Rd STA 12+00 A 16.0%108.2 0.0% 296 4/7 4 -2'Sewer Main Backfill - Turnberry Rd STA 14+05 Pass 297 4/7 5 Grade Sewer Main Backfill - Turnberry Rd STA 13+00 A 16.4%106.9 0.4% A 15.8%108.9 -0.2%99%Pass 97%Pass Pass 99%Pass Pass 295 4/7 3 -4'Sewer Main Backfill - Turnberry Rd STA 14+10 A 15.0%105.9 -1.0%96%Pass Pass 294 4/7 2 -6'Sewer Main Backfill - Turnberry Rd STA 14+15 A 15.7%109.0 -0.3% 98%Pass Pass 293 4/7 1 -8'Sewer Main Backfill - Turnberry Rd STA 14+20 PassA15.2%108.7 -0.8%99%Pass 292 4/6 11 Grade Sewer Main Backfill - Turnberry Rd STA 10+00 A 17.8%108.0 1.8% 290 4/6 9 -2'Sewer Main Backfill - Turnberry Rd STA 11+20 Pass 291 4/6 10 Grade Sewer Main Backfill - Turnberry Rd STA 11+00 A 18.0%105.4 2.0% A 17.9%108.2 1.9%98%Pass 96%Pass Pass 98%Pass Pass 289 4/6 8 -4'Sewer Main Backfill - Turnberry Rd STA 11+30 A 18.3%105.0 2.3%95%Pass Pass 288 4/6 7 -6'Sewer Main Backfill - Turnberry Rd STA 11+40 A 17.2%107.5 1.2% 95%Pass Pass 287 4/6 6 -8'Sewer Main Backfill - Turnberry Rd STA 11+50 PassA17.5%107.1 1.5%97%Pass 286 4/6 5 -2.5'Retest #277 A 15.2%105.0 -0.8% 284 4/6 3 -3'Overlot Fill - 270'N 190'E NW corner Lot 15 Block 10 Pass 285 4/6 4 -3.5'Overlot Fill - 138'N 176'E NW corner Lot 15 Block 10 A 17.9%108.9 1.9% A 17.5%108.0 1.5%98%Pass 99%Pass Pass 99%Pass Pass 283 4/6 2 -2.5'Overlot Fill - 150'N 180'E NW corner Lot 15 Block 10 A 13.3%92.2 -2.7%84%*FAIL**FAIL* 282 4/6 1 -2'Overlot Fill - 60'N 150'E NW corner Lot 15 Block 10 A 16.9%108.7 0.9% 99%Pass Pass 281 4/5 6 -6'Sewer Main Backfill - Turnberry Rd STA 10+20 PassA17.0%105.9 1.0%96%Pass 280 4/5 5 -1'Sewer Main Backfill - Turnberry Rd STA 10+02 A 17.2%109.2 1.2% 278 4/5 3 -4'Sewer Main Backfill - Turnberry Rd STA 10+10 Pass 279 4/5 4 -5'Sewer Main Backfill - Turnberry Rd STA 10+15 A 19.0%104.9 3.0% A 18.8%105.7 2.8%96%Pass 95%Pass Pass 97%Pass Pass 277 4/5 2 -3'Sewer Main Backfill - Turnberry Rd STA 10+05 A 18.5%105.6 2.5%96%Pass Pass 276 4/5 1 -2'Sewer Main Backfill - Turnberry Rd STA 10+00 A 18.2%106.9 2.2% 99%Pass Pass 275 4/1 8 -1'Overlot Fill - 3'S 9'W NE corner Lot 13 Block 10 PassA18.9%105.2 2.9%96%Pass 274 4/1 7 -1'Overlot Fill - 4'S 4'E NW corner Lot 14 Block 10 A 16.4%108.9 0.4% 272 4/1 5 -1'Overlot Fill - 7'S 11'E NW corner Lot 16 Block 10 Pass 273 4/1 6 -1'Overlot Fill - 9'S 6'W NE corner Lot 15 Block 10 A 17.9%108.8 1.9% A 17.7%106.7 1.7%97%Pass 99%Pass Pass Pass 271 4/1 4 -0.5'Retest #269 A 18.5%106.7 2.5%97%Pass Pass Pass 269 4/1 2 -0.5'Overlot Fill - Lot 16 Block 10 *FAIL* 270 4/1 3 -0.5'Overlot Fill - Lot 18 Block 10 A 18.2%104.9 2.2% A 12.2%96.6 -3.8%88%*FAIL* 95%Pass Moisture Compaction 268 4/1 1 -0.5'Overlot Fill - Lot 14 Block 10 A 17.3% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 106.1 1.3%96%Pass Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Fort Collins, Colorado Project # 22-2002 April 2022 Field Moisture/Density Testing Summary COUNTRY CLUB RESERVE Procedure D-698 Compaction Requirement 95% Min Moisture Content Requirement -1 to +3% Optimum Moisture Content (%)16.0% Maximum Dry Density (pcf)110.0 Compaction Requirement Proctor ID:A 99%Pass Pass 347 4/13 8 -1'Sewer Main Backfill - Turnberry Rd STA 25+28 PassA17.0%107.0 1.0%97%Pass 346 4/13 7 -2'Sewer Main Backfill - Turnberry Rd STA 25+20 A 15.9%108.9 -0.1% 344 4/13 5 -6'Sewer Main Backfill - Turnberry Rd STA 25+25 Pass 345 4/13 6 -5'Sewer Main Backfill - Turnberry Rd STA 25+30 A 17.9%107.9 1.9% A 17.6%107.5 1.6%98%Pass 98%Pass Pass 99%Pass Pass 343 4/13 4 S.G.Reconditioned Subgrade - Turnberry Rd STA 22+50 A 16.1%106.1 0.1%96%Pass Pass 342 4/13 3 S.G.Reconditioned Subgrade - Turnberry Rd STA 24+50 A 15.0%109.2 -1.0% 97%Pass Pass 341 4/13 2 -3'Sewer Main Backfill - Turnberry Rd STA 24+72 PassA15.5%109.0 -0.5%99%Pass 340 4/13 1 -7'Sewer Main Backfill - Turnberry Rd STA 24+82 A 15.9%106.9 -0.1% 338 4/12 5 S.G.Reconditioned Subgrade - Turnberry Rd STA 26+50 Pass 339 4/12 6 Grade Overlot Fill - 9'W SW corner Lot 1 Block 10 A 16.9%109.2 0.9% A 16.1%106.4 0.1%97%Pass 99%Pass Pass 98%Pass Pass 337 4/12 4 S.G.Reconditioned Subgrade - Turnberry Rd STA 28+50 A 15.2%109.0 -0.8%99%Pass Pass 336 4/12 3 S.G.Reconditioned Subgrade - Turnberry Rd STA 30+50 A 15.0%107.9 -1.0% 98%Pass Pass 335 4/12 2 -3'Sewer Main Backfill - Turnberry Rd STA 22+75 PassA15.5%108.5 -0.5%99%Pass 334 4/12 1 -5'Sewer Main Backfill - Turnberry Rd STA 22+82 A 15.9%108.0 -0.1% 332 4/11 14 -2.5'Overlot Fill - 8'S 4'W SW corner Lot 18 Block 10 Pass 333 4/11 15 -2.5'Overlot Fill - 5'S 9'E SE corner Lot 13 Block 10 A 17.5%107.7 1.5% A 17.1%108.2 1.1%98%Pass 98%Pass Pass 95%Pass Pass 331 4/11 13 Grade Overlot Fill - 8'N NW corner Lot 15 Block 9 A 19.0%104.6 3.0%95%Pass Pass 330 4/11 12 Grade Overlot Fill - 5'N 2'E NW corner Lot 8 Block 9 A 18.7%104.9 2.7% 97%Pass Pass 329 4/11 11 Grade Sewer Main Backfill - Turnberry Rd STA 20+50 PassA16.0%109.0 0.0%99%Pass 328 4/11 10 -8'Sewer Main Backfill - Turnberry Rd STA 21+00 A 17.5%106.3 1.5% 326 4/11 8 -4'Sewer Main Backfill - Turnberry Rd STA 20+87 Pass 327 4/11 9 -6'Sewer Main Backfill - Turnberry Rd STA 20+95 A 16.3%108.1 0.3% A 15.9%105.5 -0.1%96%Pass 98%Pass Pass 97%Pass Pass 325 4/11 7 -2'Sewer Main Backfill - Turnberry Rd STA 20+82 A 17.8%105.9 1.8%96%Pass Pass 324 4/11 6 Grade Sewer Main Backfill - Turnberry Rd STA 19+00 A 17.8%106.2 1.8% 99%Pass Pass 323 4/11 5 -1'Sewer Main Backfill - Turnberry Rd STA 20+05 PassA16.9%106.4 0.9%97%Pass 322 4/11 4 -3'Sewer Main Backfill - Turnberry Rd STA 20+10 A 16.4%109.3 0.4% 320 4/11 2 -7'Sewer Main Backfill - Turnberry Rd STA 20+20 Pass 321 4/11 3 -5'Sewer Main Backfill - Turnberry Rd STA 20+15 A 17.3%105.9 1.3% A 17.1%105.7 1.1%96%Pass 96%Pass Pass 99%Pass Pass 319 4/11 1 -9'Sewer Main Backfill - Turnberry Rd STA 20+25 A 17.3%108.6 1.3%99%Pass Pass 318 4/8 15 -1'Overlot Fill - 26'N 18'E NW corner Lot 15 Block 10 A 16.2%109.3 0.2% 96%Pass Pass 317 4/8 14 -1'Overlot Fill - 20'E NW corner Lot 10 Block 9 PassA17.9%104.9 1.9%95%Pass 316 4/8 13 Grade Overlot Fill - 9'S 10'W NE corner Lot 13 Block 10 A 18.8%105.2 2.8% 314 4/8 11 -0.5'Overlot Fill - 146'N 152'E NW corner Lot 15 Block 10 Pass 315 4/8 12 Grade Overlot Fill - 12'S 8'E NW corner Lot 16 Block 10 A 18.1%104.7 2.1% A 18.6%108.4 2.6%99%Pass 95%Pass Pass 98%Pass Pass 313 4/8 10 -0.5'Overlot Fill - 187'N 169'E NW corner Lot 15 Block 10 A 19.0%104.6 3.0%95%Pass Pass 312 4/8 9 -7'Sewer Main Backfill - Turnberry Rd STA 18+90 A 16.9%107.3 0.9% 97%Pass Pass 311 4/8 8 -4'Sewer Main Backfill - Turnberry Rd STA 18+82 PassA16.3%106.9 0.3%97%Pass 310 4/8 7 -3'Sewer Main Backfill - Turnberry Rd STA 18+75 A 16.5%106.2 0.5% 308 4/8 5 Grade Sewer Main Backfill - Turnberry Rd STA 16+50 Pass 309 4/8 6 -1'Sewer Main Backfill - Turnberry Rd STA 18+72 A 17.7%105.0 1.7% A 16.5%104.8 0.5%95%Pass 95%Pass Pass Pass 307 4/8 4 -8'Sewer Main Backfill - Turnberry Rd STA 17+70 A 18.2%104.6 2.2%95%Pass Pass Pass 305 4/8 2 -4'Sewer Main Backfill - Turnberry Rd STA 17+50 Pass 306 4/8 3 -6'Sewer Main Backfill - Turnberry Rd STA 17+60 A 17.0%108.9 1.0% A 18.2%107.0 2.2%97%Pass 99%Pass Moisture Compaction 304 4/8 1 -2'Sewer Main Backfill - Turnberry Rd STA 17+40 A 17.8% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 108.6 1.8%99%Pass Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Fort Collins, Colorado Project # 22-2002 April 2022 Field Moisture/Density Testing Summary COUNTRY CLUB RESERVE Procedure D-698 D-698 Compaction Requirement 95% Min 95% Min Moisture Content Requirement -1 to +3%±2% Optimum Moisture Content (%)16.0%7.0% Maximum Dry Density (pcf)110.0 137.0 Compaction Requirement Proctor ID:A B 99%Pass Pass3844/22 6 -5'Storm Drain Backfill - Subdrain B STA 12+00 A 16.4%108.8 0.4% 382 4/22 4 -1'Overlot Fill - 15'N 15'W SE corner Lot 5 Block 9 Pass 383 4/22 5 -5'Storm Drain Backfill - Subdrain B STA 10+75 A 15.9%109.3 -0.1% A 19.0%107.2 3.0%97%Pass 99%Pass Pass 97%Pass Pass 381 4/22 3 -1'Overlot Fill - 24'S 18'E NW corner Lot 2 Block 9 A 18.7%109.0 2.7%99%Pass Pass 380 4/22 2 -1'Overlot Fill - 105'S 75'W NE corner Lot 6 Block 7 A 18.5%106.5 2.5% 99%Pass Pass 379 4/22 1 Grade Overlot Fill - 103'S 15'E NE corner Lot 6 Block 7 PassA16.9%106.9 0.9%97%Pass 378 4/21 6 -2'Storm Drain Backfill - Subdrain A STA 13+00 A 16.0%108.7 0.0% 376 4/21 4 -2'Storm Drain Backfill - Subdrain A STA 11+00 Pass 377 4/21 5 -2'Storm Drain Backfill - Subdrain A STA 12+00 A 16.8%106.4 0.8% A 15.6%105.9 -0.4%96%Pass 97%Pass Pass 99%Pass Pass 375 4/21 3 -2'Overlot Fill - 102'S 90'W NE corner Lot 6 Block 7 A 17.5%106.1 1.5%96%Pass Pass 374 4/21 2 -1'Overlot Fill - 104'S 12'E NE corner Lot 6 Block 7 A 17.2%108.4 1.2% 96%Pass Pass 373 4/21 1 ABC Aggregate Base Course - Intersection of Turnberry Rd & Serramante Dr PassB5.0%133.6 -2.0%98%Pass 372 4/20 8 ABC Aggregate Base Course - Turnberry Rd 600'S Serramante Dr B 5.9%130.9 -1.1% 370 4/20 6 ABC Aggregate Base Course - Turnberry Rd 200'S Serramante Dr Pass 371 4/20 7 ABC Aggregate Base Course - Turnberry Rd 400'S Serramante Dr B 5.5%134.2 -1.5% B 5.6%131.8 -1.4%96%Pass 98%Pass Pass 97%Pass Pass 369 4/20 5 -1'Sewer Main Backfill - Turnberry Rd STA 31+50 A 17.3%107.5 1.3%98%Pass Pass 368 4/20 4 -1'Sewer Main Backfill - Turnberry Rd STA 31+45 A 16.3%107.1 0.3% 96%Pass Pass 367 4/20 3 -3'Sewer Main Backfill - Turnberry Rd STA 31+50 PassA15.0%107.8 -1.0%98%Pass 366 4/20 2 -5'Sewer Main Backfill - Turnberry Rd STA 31+55 A 15.2%105.9 -0.8% 364 4/19 5 -3'Overlot Fill - 108'S 100'W NE corner Lot 6 Block 7 Pass 365 4/20 1 -8'Sewer Main Backfill - Turnberry Rd STA 31+60 A 17.9%108.8 1.9% A 18.7%106.9 2.7%97%Pass 99%Pass Pass 99%Pass Pass 363 4/19 4 -2'Overlot Fill - 105'S 60'E NE corner Lot 6 Block 7 A 18.4%106.6 2.4%97%Pass Pass 362 4/19 3 -4'Sewer Main Backfill - Turnberry Rd STA 27+75 A 16.0%109.1 0.0% 97%Pass Pass 361 4/19 2 -6'Sewer Main Backfill - Turnberry Rd STA 27+80 PassA17.8%106.8 1.8%97%Pass 360 4/19 1 -8'Sewer Main Backfill - Turnberry Rd STA 27+85 A 17.5%106.4 1.5% 358 4/18 7 -4'Overlot Fill - 100'S 33'W NE corner Lot 6 Block 7 Pass 359 4/18 8 -2.5'Overlot Fill - 104'S 30'E NE corner Lot 6 Block 7 A 17.2%106.7 1.2% A 19.0%104.8 3.0%95%Pass 97%Pass Pass 97%Pass Pass 357 4/18 6 -2'Sewer Main Backfill - Turnberry Rd STA 26+52 A 17.9%106.4 1.9%97%Pass Pass 356 4/18 5 -5'Sewer Main Backfill - Turnberry Rd STA 26+60 A 17.7%107.2 1.7% 98%Pass Pass 355 4/18 4 -7'Sewer Main Backfill - Turnberry Rd STA 26+65 PassA16.0%105.9 0.0%96%Pass 354 4/18 3 -3'Sewer Main Backfill - Turnberry Rd STA 26+69 A 16.8%108.2 0.8% 352 4/18 1 -8'Sewer Main Backfill - Turnberry Rd STA 26+82 Pass 353 4/18 2 -6'Sewer Main Backfill - Turnberry Rd STA 26+75 A 17.5%106.0 1.5% A 17.1%106.9 1.1%97%Pass 96%Pass Pass Pass 351 4/14 4 ABC Aggregate Base Course - Turnberry Rd STA 25+00 B 5.2%133.8 -1.8%98%Pass Pass Pass 349 4/14 2 ABC Aggregate Base Course - Turnberry Rd STA 29+00 Pass 350 4/14 3 ABC Aggregate Base Course - Turnberry Rd STA 27+00 B 5.8%131.0 -1.2% B 5.6%136.0 -1.4%99%Pass 96%Pass Moisture Compaction 348 4/14 1 ABC Aggregate Base Course - Turnberry Rd STA 31+00 B 5.4% Number Number ID Pe r c e n t Co m p a c t i o n (Pass/Fail) 131.6 -1.6%96%Pass Test Test Proctor Moisture Mo i s t u r e Va r i a b i l i t y Field Results DryMaterial Tested and LocationProjectDateDailyDepth Density Fort Collins, Colorado Project # 22-2002 April 2022 Field Moisture/Density Testing Summary COUNTRY CLUB RESERVE 2 of 11 Age Specimen (days) 1.3a 3 1.3b 3 1.7a 7 1.7b 7 1.14a 14 1.14b 14 1.28a 28 1.28b 28 1.56a 56 1.56b 56 22-2002 Summary of Cast-In-Place Concrete Test COUNTRY CLUB RESERVE Fort Collins, Colorado General Set #1 Application Location Inlet A3 Mix Code A4785 Inlet Wall Placement Date 4/1/22 Supplier SRM Concrete 1603 Sample Time 4:18 PM Water Added On Site 7 gallons Placement Type Chute Ticket #N/A Batch Time 4:08 PM Truck # Sampled At (yards)Field Personnel LK Project Specifications and Test Results Test Specifications Results Slump (in) ASTM C-143 4" Max 3" Air Content (%)ASTM C-231 5.0% - 8.0%5.0% Unit Weight (pcf)Field -145.0 Air Temperature @ Time of Placement -61 °F Concrete Temperature ASTM C-1064 90˚ Max 70 °F Compressive Strength Test Results (ASTM C-39/C-31) Maximum Applied Compressive Strength Rounded Avg. 28-day Compressive Strength (min)4,500 psi See Below - 62690 Cone/Shear 4989 494061530Cone/Shear 4896 Load (lbs)Failure Type (psi)(psi) ------ ----- ------- -- - Specimen Diameter = 4 in Specimen Cross-Sectional Area = 12.57 sq in ------ 2 of 5 Age Specimen (days) 1.3a 3 1.3b 3 1.7a 7 1.7b 7 1.14a 14 1.14b 14 1.28a 28 1.28b 28 1.56a 56 1.56b 56 - Specimen Diameter = 4 in Specimen Cross-Sectional Area = 12.57 sq in ------ ----- ------- -- - 60750 Cone/Shear 4834 495063750Cone/Shear 5073 Load (lbs)Failure Type (psi)(psi) ------ Compressive Strength Test Results (ASTM C-39/C-31) Maximum Applied Compressive Strength Rounded Avg. 28-day Compressive Strength (min)4,500 psi See Below Unit Weight (pcf)Field -140.8 Air Temperature @ Time of Placement -46 °F Concrete Temperature ASTM C-1064 90˚ Max 71 °F Slump (in) ASTM C-143 4" Max 4" Air Content (%)ASTM C-231 5.0% - 8.0%5.5% Project Specifications and Test Results Test Specifications Results Sampled At (yards)Field Personnel LK 1903 Sample Time 10:18 AM Water Added On Site None Placement Type Chute Ticket #13000345 Batch Time 9:21 AM Truck # Location Outlet A4 Mix Code A4785 Outlet Walls Placement Date 4/5/22 Supplier SRM Concrete General Set #2 Application 22-2002 Summary of Cast-In-Place Concrete Test COUNTRY CLUB RESERVE Fort Collins, Colorado Maximum COUNTRY CLUB RESERVE Approximate Test Location Density Date Test #Lift Mix With Theoretical Percent Percent FORT COLLINS, CO Project # 22-2002 APRIL 2022 Field Asphaltic Concrete Density Test Summary Gauge Specific Compaction Compaction (Pass/Fail) 4/19 1 BM 5493 145.3 155.2 94%92-96%PassTurnberry Road STA 31+00 Correction Gravity Required Pass 4/19 3 BM 5493 148.0 155.2 92-96%Pass95% 4/19 2 BM 5493 145.7 155.2 94%92-96%Turnberry Road STA 29+00 Turnberry Road STA 27+00 4/19 4 BM 5493 146.9 4/19 5 BM 5493 Turnberry Road STA 25+00 Turnberry Road STA 23+00 155.2 95%92-96%Pass 145.9 146.6 155.2 94%92-96%Pass 155.2 94%92-96%Pass 146.5 155.2 94%92-96%Pass 4/19 9 IM 5493 4/19 8 IM 5493 4/19 6 BM 5493 4/19 7 IM 5493 Turnberry Road STA 21+00 Turnberry Road STA 30+50 Turnberry Road STA 28+50 Turnberry Road STA 26+50 155.2 94%92-96%Pass 147.4 148.7 155.2 96%92-96%Pass 146.2 4/19 11 IM 5493 4/19 10 IM 5493Turnberry Road STA 24+50 Turnberry Road STA 22+50 155.2 95%92-96%Pass 147.2 146.9 155.2 95%92-96%Pass 4/21 13 BM 5493 4/19 12 IM 5493Turnberry Road STA 20+50 Intersection of Turnberry Road & Serramonte Drive 155.2 95%92-96%Pass 142.0 142.0 153.3 93%92-96%Pass 4/21 15 BM 5493 4/21 14 BM 5493Turnberry Road 80'S Serramonte Drive Turnberry Road 180'S Serramonte Drive 153.3 93%92-96%Pass 143.4 142.2 153.3 93%92-96%Pass 4/21 17 BM 5493 4/21 16 BM 5493Turnberry Road 280'S Serramonte Drive Turnberry Road 380'S Serramonte Drive 153.3 94%92-96%Pass 142.5 142.9 153.3 93%92-96%Pass 4/21 18 BM 5493 153.3 93%92-96%Pass 142.9 153.3 93%92-96%Pass Turnberry Road 480'S Serramonte Drive 4/22 21 IM 5493 4/22 20 IM 5493 4/21 19 BM 5493Turnberry Road 580'S Serramonte Drive Turnberry Road 100'S Serramonte Drive Intersection of Turnberry Road & Serramonte Drive 153.3 93%92-96%Pass 143.7 144.3 153.3 94%92-96%Pass 143.0 4/22 22 IM 5493 153.3 94%92-96%Pass 144.0 153.3 94%92-96%Pass Turnberry Road 200'S Serramonte Drive 4/22 25 IM 5493 4/22 24 IM 5493 4/22 23 IM 5493Turnberry Road 300'S Serramonte Drive Turnberry Road 400'S Serramonte Drive Turnberry Road 525'S Serramonte Drive 153.3 94%92-96%Pass 143.5 153.3 94%92-96%Pass 143.9 BM = Bottom Mat IM = Intermediate Mat COUNTRY CLUB RESERVE FORT COLLINS, CO Project #22-2002 APRIL 2022 ASPHALT EXTRACTION/GRADATION TEST SUMMARY EXTRACTION (ASTM D-2172) ASPHALT CONTENT (%)MIX DESIGN SPECIFICATION 5.26%-+/-- SIEVE ANALYSIS (ASTM C-136 & C-117) SIEVE SIZE SPECIFICATION PERCENT PASSING 1 1/2"100% 1"100% 3/4"-97% 1/2"-86% 3/8"-81% No. 4 -66% No. 8 -51% No. 16 -36% No. 30 -23% No. 50 -13% No. 100 -8% No. 200 -6.1% Sample Date/Time 4-19-22 Location Turnberry Road STA 23+00 Asphalt Mix 5493 Lift Bottom Supplier Martin Marietta Truck #RMTMM2009 Ticket #53056766 Lift Intermediate Supplier Martin Marietta Truck #RMTAKR047 Ticket #54027757 Sample Date/Time 4-21-22 Location Turnberry Road 420' S Serramonte Way Asphalt Mix 5493 No. 100 -9% No. 200 -5.9% No. 30 -24% No. 50 -14% 48% No. 16 -35% No. 4 -72% No. 8 - 3/8"-84% 1/2"-90% 3/4"-100% 1"100% SIEVE ANALYSIS (ASTM C-136 & C-117) SIEVE SIZE SPECIFICATION PERCENT PASSING 1 1/2"100% 5.60%-+/-- EXTRACTION (ASTM D-2172) ASPHALT CONTENT (%)MIX DESIGN SPECIFICATION ASPHALT EXTRACTION/GRADATION TEST SUMMARY COUNTRY CLUB RESERVE FORT COLLINS, CO Project #22-2002 APRIL 2022 B M V.P. V.P.V.P.V.P. A.R.V.GAS GAS V.P.V.P. X X X / / / / / / / / X X V.P. X X X X X X X X / / / / / / / // / / / / / / / / / / / / / / // / / / / / / /M XXFES MM FESFESMM TELE F.O. TELE FESFESFESMM / / / / / / / // / / / / / / / MGAS FESFESFESFES EEFES X MH / / / / / / / / MFES FESMM FES FESMM GAS FES EE FESXM TELE X / / / / / / / // / / / / / / / FES M FES TELE / / / / / / / // / / / / / / / FESM FES / / / / / / / // / / / / / / / XX / / / / / / / // / / / / / / / X XV.P. VAULT CABLE BOX CABLE M M GASGASV.P. GAS TH TH TH B B B B B B B B / / / / / / / / ST AW / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / // / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / // / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / / W W W W W W 14 " W 1 9 7 6 ( A C ) 14 " W 1 9 7 6 ( A C ) 14 " W 1 9 7 6 ( A C ) / / / / / / / / 15 " S S 15 " S S 15 " S S 15 " S S 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W IR IR 16 " W 16 " W 16 " W 16 " W 16 " W RAIN GARDEN 2 RAIN GARDEN 3 RAIN GARDEN 1 TU R N B E R R Y R O A D E. DOUGLAS ROAD TU R N B E R R Y R O A D E. DOUGLAS ROAD LID EXHIBIT FORT COLLINS, CO COUNTRY CLUB RESERVE E N G I N E E R N GI EHTRON R N 11.11.2020 D:\PROJECTS\1324-001\DWG\EXHIBITS\1324-001_LID ROUTING.DWG LEGEND: RAIN GARDEN 1 RAIN GARDEN 2 RAIN GARDEN 3( IN FEET ) 0 1 INCH = 250 FEET 250 250 LID Treatment Summary Table Raingarden ID Total Drainage Area (Ac.) Raingarden Req'd Min. Volume (Cu.-Ft.) Raingarden#1 8.02 5423 Raingarden#2 15.54 8294 Raingarden#3 6.32 3836 Total Newly Developed Area Treated 29.88 Ac. Total Newly Developed Area 33.43 Ac. Percent of Newly Developed Area Treated 89.38 % RAIN GARDEN 1 RAIN GARDEN 21 RAIN GARDEN 12 Rip-rap has been buried RAIN GARDEN 2 RAIN GARDEN 3 Rip-rap has been buried RAIN GARDEN 3 RAIN GARDEN 3 1 Blaine Mathisen From:Dan Mogen <dmogen@fcgov.com> Sent:Friday, February 28, 2025 11:41 AM To:Chris LaPlante; Blaine Mathisen; Marcus Steward; Amy Dolinger; JD Padilla; Nico Padilla Cc:Andrew Crecca; Dave Betley; Sophie Buckingham; Jeremy Fulks; Kathryne Marko Subject:RE: Country Club Reserve - Drainage Cert Follow Up Flag:Follow up Flag Status:Completed Hi Chris, Blaine, and all – We’re getting close, but we have a few ends to tie up or verify before I can sign off. I went back thru what’s been communicated thru emails and notes on the certification and I’m seeing three main things (see list below). Additionally, there is the issue with Prospect Energy and, I’m going to call it, the “re-certification” of the remediated area around rain garden #2. Prospect Energy has stopped work, and their consultant that was going to complete the re-certification (Apex) has communicated they are not stamping/re-certifying any re-work of the area impacted by Prospect’s remediation efforts. Kathryne, Drew, and I need some guidance from the City Attorney’s Office on how to proceed with that situation in light of these latest updates. In the meantime, I want to keep things moving with the other pieces to wrap up for acceptance. Blaine, can you please upload the ponds to the State portal? There are a couple items to include in addition to the docs referenced at the end of the certification package, but most are already included elsewhere in the package. Let me know if you have any questions about what should be uploaded (full list from the cert form is below). Dave, Sophie, or Jeremy – please see #2 below. Can you please let me know if anything further is needed on the encroachment permit? My apologies if I’ve missed a follow since I sent that note out last July. Chris/JD, can you please let me know who will be taking over maintenance responsibilities? We’ll need to have that party present at the close-out meeting, and we can start working on scheduling once we know all appropriate parties. 1. Need to upload ponds to State portal a. The cover sheet from the approved drainage report b. The stamped certification page from the approved drainage report c. As-built topographic survey d. Stamped certification page from the Overall Site & Drainage Certification e. PDF output from the Stormwater Detention and Infiltration Design Data Spreadsheet 2. An encroachment permit for the private outfall pipe needed. a. To include certification letter addressing outfall condition specifically. b. Dave to follow up on whether or not the encroachment has already been permitted and follow up with the group. 3. Close-out site walk needed to verify conditions and go over post-construction requirements. . . . . . . . . . . . . . . . . . . DAN MOGEN Pronouns: he/him Development Review Engineer 970-305-5989 mobile City of Fort Collins Stormwater Infrastructure and LID Inspection Form Project:Country Club Reserve Date of Inspection:9/27/2024 Inspector:Drew Crecca Feature Type:Condition at time of Inspection: Rain Garden Acceptable Feature Location on the site: Southeast Side Features Inspected on this visit: Inspection Notes: *Disclaimer: this inspection serves as a check on the current state of installation and is in no way a final acceptance or certification of the Stormwater Features. In Field Inspection Check Lists and Final Certification will be the responsibility of the installation contractor, contractor, and development engineer to complete and provide for acceptance by City Water Utility Engineers* Raingarden #2 was impacted by petrolium mining materials thet were released onto the site from a ruptured transmission line. Contractor removed all contaminated materials and rebuilt raingarden per original specifications. This inspection report serves as verification that all layers and unnderdrain were re- installed to the correct depths per approved utility plans. CITY INSPECTION REPORT FOR PROSPECT ENERGY CLEAN UP FOR RAIN GARDEN 2 Replaced Under-drain bedded in reservoir aggregate Layers of Reservoir Aggregate, Diaphragm Aggregate & Bio-media Verification of Material Depths CITY INSPECTION REPORT FOR PROSPECT ENERGY CLEAN UP FOR RAIN GARDEN 2 PROSPECT ENGERY CORRECTIONS BY DEVELOPMENT TEAM PHOTOS FROM 03.25.2025 RAIN GARDEN 2 FOREBAY REGRADED SWALE - SOUTH OF BLOCK 6 LOTS 1-3 NORTHERNENGINEERING.COM | 970.221.4158 DRAINAGE SITE CERTIFICATION LETTER: COUNTRY CLUB RESERVE FORT COLLINS | GREELEY APPENDIX Appendix C WATER QUALITY & DETENTION CAPTURE VOLUMES Country Club Reserve Final Drainage and Erosion Control Report 10 Pond 1 would overtop enter the Type C inlet and release 4.1 cfs (Please see the SWMM Blocked Outlet Scenario computations, Appendix C). In the unlikely scenario where the outlet pipe were to become overwhelmed or clogged, the full 44.91 ac-ft detention volume could be utilized. Flows in excess of that volume would spill to the southeast and into the Turnberry right- of-way. 6. 100-year overflow from Raingardens 1 through 3 will be directed across large vegetated areas, which will act as a means of spreading 100-year overflow. At each point of overflow we have added erosion fabric at a minimum which will act to stabilize overflow areas, and allow for revegetation of disturbed soil to occur. There is also riprap rundowns as well as concrete weirs that will more than adequately maintain stabilization. 100-year overflow areas are noted on the Drainage Exhibit. Please see overflow calculations provided in Appendix D. 7. A subdrain system is proposed for the development site, which will drain via the outfall pipe for proposed Pond 1. Per the groundwater study for the subdrain system an estimated peak discharge from the subdrain system is 0.022 cfs (10 gallons per minute). Ultimately, Country Club Reserve is releasing at 9.46 cfs from Pond 1 into the No. 8 Ditch and the subdrain is tying in downstream of our outlet structure therefore the max release rate into the No.8 Ditch is 9.482 (9.46+.022 = 9.482). The Ditch company has agreed to accept a flow rate of 10.0 cfs. Therefore, the subdrain flows have no impact on the SWMM modeling since they are not being detained and are bypassing detention. Please see the Utility Plans for additional information. Table 2, below, summarizes results of final SWMM modeling. Please see SWMM modeling output provided in Appendix C. TABLE 2 – SWMM SUMMARY TABLE 8. This development site is somewhat unique in that there is a significant portion of the overall property that will be merely regraded or left as untouched open space. For the purpose of calculating required LID treatment volume and water quality capture volume, we have determined a “Total Newly Developed Area” acreage of 33.43 acres as noted in the LID Exhibit provided in Appendix D. This area is based on residential lots, streets, and open space areas being developed within the site. Areas within the property boundary that are merely being regraded but will experience no additional imperviousness are not included in this area. 9. Rain Gardens (designed as porous landscape detention (PLD) holding cells) are proposed as the primary LID treatment method for the site. The PLD’s will provide standard 12-hour porous landscape detention (PLD) treatment. PLD basins will be incorporated in the upper stages of Ponds1 and 2. The site will provide in excess of the onsite LID treatment requirement 75% of newly developed areas. Please see LID computations and an LID Exhibit provided in Appendix D. Pond ID 100-Yr. Detention Vol. (Ac-Ft) Water Quality Capture Volume (Ac-Ft) Water Quality Capture Volume WSEL (Ft) Total Req'd Vol. (Ac-Ft) 100-Yr. WSEL (Ft) Peak Release (cfs) Pond 1 18.40 0.32 5057.00 18.72 5064.30 9.46 Pond 2 1.70 N/A N/A 1.70 5079.80 3.10 POND SUMMARY TABLE Project: Date: Pond No.: 5,055.00 13,940.00 cu. ft. 5,057.06 5,057.06 26,278.88 cu. ft.2.06 ft. 5,067.00 801,504 cu. ft. 5,064.26 Max. Elev. Min. Elev. cu. ft. acre ft cu. ft. acre ft 5,055.00 N/A 146 0.00 0.00 0.00 0.00 0.00 5,056.00 5,055.00 3,883 1.00 2,014.59 0.05 2,014.59 0.05 5,057.00 5,056.00 16,858 1.00 10,370.35 0.24 12,384.94 0.28 5,058.00 5,057.00 34,910 1.00 25,883.82 0.59 38,268.75 0.88 5,059.00 5,058.00 57,222 1.00 46,065.98 1.06 84,334.73 1.94 5,060.00 5,059.00 82,342 1.00 69,782.11 1.60 154,116.84 3.54 5,061.00 5,060.00 111,177 1.00 96,759.35 2.22 250,876.19 5.76 5,062.00 5,061.00 148,056 1.00 129,616.10 2.98 380,492.29 8.73 5,063.00 5,062.00 182,306 1.00 165,180.88 3.79 545,673.16 12.53 5,064.00 5,063.00 212,225 1.00 197,265.75 4.53 742,938.91 17.06 5,065.00 5,064.00 238,836 1.00 225,530.73 5.18 968,469.63 22.23 5,066.00 5,065.00 265,088 1.00 251,962.29 5.78 1,220,431.92 28.02 5,067.00 5,066.00 288,850 1.00 276,969.01 6.36 1,497,400.93 34.38 STAGE STORAGE CURVE Contour Contour Surface Area (ft2) Depth (ft) Incremental Volume Cummalitive Volume Pond Stage Storage Curve 1324-001 Fort Collins, CO B. Mathisen Elev at WQ Volume: Country Club Reserve April 3, 2023 Pond Outlet and Volume Data Outlet Elevation:Water Quality Volume: Elev at 100-yr Volume: Crest of Pond Elev.: Volume at Grate: Grate Elevation: Storage and Water Quality Pond 1 Project Number: Project Location: Calculations By:1 Water Quality Depth: 100-yr WQ Volume: 1 Project Number: Project Name: Project Location: Pond No:Calc. By:B. Mathisen Orifice Dia (in):10 8/16 Orifice Area (sf):0.60 Orifice invert (ft):5,055.00 Orifice Coefficient:0.65 Elevation Stage (ft)Velocity (ft/s)Flow Rate (cfs)Comments 5,055.00 0.00 0.00 0.00 5,056.00 1.00 5.21 3.12 5,057.00 2.00 7.37 4.41 5,058.00 3.00 9.03 5.40 5,059.00 4.00 10.43 6.23 5,060.00 5.00 11.66 6.97 5,061.00 6.00 12.77 7.64 5,062.00 7.00 13.79 8.25 5,063.00 8.00 14.75 8.82 5,064.00 9.00 15.64 9.35 5,064.26 9.26 15.87 9.49 100-YR WSEL 5,065.00 10.00 16.49 9.86 5,066.00 11.00 17.29 10.34 5,067.00 12.00 18.06 10.80 Orifice Rating Curve ORIFICE RATING CURVE 1324-001 Country Club Reserve Fort Collins Pond 1 Orifice Design Data Detention Pond 1 NORTHERNENGINEERING.COM | 970.221.4158 FORT COLLINS | GREELEY Project: Date: Pond No.: 5,055.00 13,940.00 cu. ft. N/A N/A N/A cu. ft.N/A ft. 5,067.00 74,052 cu. ft. 5,079.80 Max. Elev. Min. Elev. cu. ft. acre ft cu. ft. acre ft 5,079.00 N/A 74,143 0.00 0.00 0.00 0.00 0.00 5,079.20 5,079.00 77,076 0.20 15,121.90 0.35 15,121.90 0.35 5,079.40 5,079.20 80,046 0.20 15,712.20 0.36 30,834.10 0.71 5,079.60 5,079.40 83,053 0.20 16,309.90 0.37 47,144.00 1.08 5,079.80 5,079.60 86,099 0.20 16,915.20 0.39 64,059.20 1.47 5,080.00 5,079.80 89,525 0.20 17,562.40 0.40 81,621.60 1.87 Elev at 100-yr Volume: Crest of Pond Elev.: Volume at Grate: Grate Elevation: Storage and Water Quality Pond 2 Project Number: Project Location: Calculations By:2 Water Quality Depth: 100-yr WQ Volume: STAGE STORAGE CURVE Contour Contour Surface Area (ft2) Depth (ft) Incremental Volume Cummalitive Volume Pond Stage Storage Curve 1324-001 Fort Collins, CO A. Poincelot Elev at WQ Volume: Country Club Reserve May 5, 2023 Pond Outlet and Volume Data Outlet Elevation: Water Quality Volume: 1 STAGE STORAGE TABLE AREA DEPTH AVG END VOL AVG END TOTAL CONIC VOL CONIC TOTAL (SQ. FT)(FT)(CU. FT)(CU. FT)(CU. FT)(CU. FT) 5,070.00 8,560.08 N/A N/A 0.00 N/A 0.00 5,070.20 9,840.11 0.20 1,840.03 1,840.03 1,838.54 1,838.54 5,070.40 11,137.90 0.20 2,097.80 3,937.83 2,096.46 3,935.00 5,070.60 12,511.79 0.20 2,364.97 6,302.80 2,363.64 6,298.64 5,070.80 13,961.77 0.20 2,647.36 8,950.16 2,646.03 8,944.67 5,071.00 15,813.44 0.20 2,977.52 11,927.68 2,975.60 11,920.28 Rain Garden 1 ELEV 11,920 cu. ft. > 5,723 cu. ft. Therefore Rain Garden 1 meets FCSCM and the Approved Utility Plans. Sheet 1 of 2 Designer: Company: Date: Project: Location: 1. Basin Storage Volume A) Effective Imperviousness of Tributary Area, Ia Ia =59.0 % (100% if all paved and roofed areas upstream of rain garden) B) Tributary Area's Imperviousness Ratio (i = Ia/100)i = 0.590 C) Water Quality Capture Volume (WQCV) for a 12-hour Drain Time WQCV = 0.19 watershed inches (WQCV= 0.8 * (0.91* i3 - 1.19 * i2 + 0.78 * i) D) Contributing Watershed Area (including rain garden area) Area = 349,351 sq ft E) Water Quality Capture Volume (WQCV) Design Volume VWQCV =cu ft Vol = (WQCV / 12) * Area F) For Watersheds Outside of the Denver Region, Depth of d6 =0.43 in Average Runoff Producing Storm G) For Watersheds Outside of the Denver Region, VWQCV OTHER =5,423.2 cu ft Water Quality Capture Volume (WQCV) Design Volume H) User Input of Water Quality Capture Volume (WQCV) Design Volume VWQCV USER =cu ft (Only if a different WQCV Design Volume is desired) 2. Basin Geometry A) WQCV Depth (12-inch maximum)DWQCV =12 in B) Rain Garden Side Slopes (Z = 4 min., horiz. dist per unit vertical) Z = 4.00 ft / ft (Use "0" if rain garden has vertical walls) C) Mimimum Flat Surface Area AMin =4122 sq ft D) Actual Flat Surface Area AActual =5204 sq ft E) Area at Design Depth (Top Surface Area)ATop =6740 sq ft F) Rain Garden Total Volume VT=5,723 cu ft (VT= ((ATop + AActual) / 2) * Depth) 3. Growing Media 4. Underdrain System A) Are underdrains provided? B) Underdrain system orifice diameter for 12 hour drain time i) Distance From Lowest Elevation of the Storage y =ft Volume to the Center of the Orifice ii) Volume to Drain in 12 Hours Vol12 =N/A cu ft iii) Orifice Diameter, 3/8" Minimum DO =N/A in Design Procedure Form: Rain Garden (RG) BPM Northern Engineering October 16, 2019 Country Club Reserve Rain Garden #1 UD-BMP (Version 3.06, November 2016) Choose One Choose One 18" Rain Garden Growing Media Other (Explain): YES NO RainGarden1 - UD.xlsm, RG 10/16/2019, 1:45 PM Rain Garden 1 - From Approved Drainage Report Minimum flat areas are greater that was approved. See Stage Storage STAGE STORAGE TABLE ELEV AREA DEPTH AVG END AVG END CONIC CONIC 5,070.00 17,587.45 N/A N/A 0 N/A 0 5,070.20 18,246.30 0.2 3583.37 3583.37 3583.17 3583.17 5,070.40 18,945.25 0.2 3719.15 7302.53 3718.94 7302.11 5,070.60 19,914.15 0.2 3885.94 11188.47 3885.54 11187.64 Rain Garden 2 11,187 cu. ft. > 10,576 cu. ft. Therefore Rain Garden 2 meets FCSCM and the Approved Utility Plans. Sheet 1 of 2 Designer: Company: Date: Project: Location: 1. Basin Storage Volume A) Effective Imperviousness of Tributary Area, Ia Ia =41.5 % (100% if all paved and roofed areas upstream of rain garden) B) Tributary Area's Imperviousness Ratio (i = Ia/100)i = 0.415 C) Water Quality Capture Volume (WQCV) for a 12-hour Drain Time WQCV = 0.15 watershed inches (WQCV= 0.8 * (0.91* i3 - 1.19 * i2 + 0.78 * i) D) Contributing Watershed Area (including rain garden area) Area = 676,922 sq ft E) Water Quality Capture Volume (WQCV) Design Volume VWQCV =cu ft Vol = (WQCV / 12) * Area F) For Watersheds Outside of the Denver Region, Depth of d6 =0.43 in Average Runoff Producing Storm G) For Watersheds Outside of the Denver Region, VWQCV OTHER =8,294.2 cu ft Water Quality Capture Volume (WQCV) Design Volume H) User Input of Water Quality Capture Volume (WQCV) Design Volume VWQCV USER =cu ft (Only if a different WQCV Design Volume is desired) 2. Basin Geometry A) WQCV Depth (12-inch maximum)DWQCV =7 in B) Rain Garden Side Slopes (Z = 4 min., horiz. dist per unit vertical) Z = 4.00 ft / ft (Use "0" if rain garden has vertical walls) C) Mimimum Flat Surface Area AMin =5618 sq ft D) Actual Flat Surface Area AActual =17139 sq ft E) Area at Design Depth (Top Surface Area)ATop =19121 sq ft F) Rain Garden Total Volume VT=10,576 cu ft (VT= ((ATop + AActual) / 2) * Depth) 3. Growing Media 4. Underdrain System A) Are underdrains provided? B) Underdrain system orifice diameter for 12 hour drain time i) Distance From Lowest Elevation of the Storage y =ft Volume to the Center of the Orifice ii) Volume to Drain in 12 Hours Vol12 =N/A cu ft iii) Orifice Diameter, 3/8" Minimum DO =N/A in Design Procedure Form: Rain Garden (RG) BPM Northern Engineering November 11, 2020 Country Club Reserve Raingarden #2 UD-BMP (Version 3.06, November 2016) Choose One Choose One 18" Rain Garden Growing Media Other (Explain): YES NO RainGarden2 - UD.xlsm, RG 11/11/2020, 12:52 PM Rain Garden 2 - From Approved Drainage Report Minimum flat areas are greater than what was approved. See Stage Storage STAGE STORAGE TABLE ELEV AREA DEPTH AVG END AVG END CONIC CONIC 5,081.20 10,512.34 N/A N/A 0 N/A 0 5,081.40 11,612.48 0.2 2212.48 2212.48 2211.57 2211.57 5,081.60 12,746.10 0.2 2435.86 4648.34 2434.98 4646.55 Rain Garden 3 4646.55 cu. ft. > 3835.7 cu. ft. Therefore Rain Garden 3 meets FCSCM and the Approved Utility Plans. Sheet 1 of 2 Designer: Company: Date: Project: Location: 1. Basin Storage Volume A) Effective Imperviousness of Tributary Area, Ia Ia =51.0 % (100% if all paved and roofed areas upstream of rain garden) B) Tributary Area's Imperviousness Ratio (i = Ia/100)i = 0.510 C) Water Quality Capture Volume (WQCV) for a 12-hour Drain Time WQCV = 0.17 watershed inches (WQCV= 0.8 * (0.91* i3 - 1.19 * i2 + 0.78 * i) D) Contributing Watershed Area (including rain garden area) Area = 275,299 sq ft E) Water Quality Capture Volume (WQCV) Design Volume VWQCV =cu ft Vol = (WQCV / 12) * Area F) For Watersheds Outside of the Denver Region, Depth of d6 =0.43 in Average Runoff Producing Storm G) For Watersheds Outside of the Denver Region, VWQCV OTHER =3,835.7 cu ft Water Quality Capture Volume (WQCV) Design Volume H) User Input of Water Quality Capture Volume (WQCV) Design Volume VWQCV USER =cu ft (Only if a different WQCV Design Volume is desired) 2. Basin Geometry A) WQCV Depth (12-inch maximum)DWQCV =4 in B) Rain Garden Side Slopes (Z = 4 min., horiz. dist per unit vertical) Z = 4.00 ft / ft (Use "0" if rain garden has vertical walls) C) Mimimum Flat Surface Area AMin =2808 sq ft D) Actual Flat Surface Area AActual =11205 sq ft E) Area at Design Depth (Top Surface Area)ATop =12133 sq ft F) Rain Garden Total Volume VT=3,890 cu ft (VT= ((ATop + AActual) / 2) * Depth) 3. Growing Media 4. Underdrain System A) Are underdrains provided? B) Underdrain system orifice diameter for 12 hour drain time i) Distance From Lowest Elevation of the Storage y =ft Volume to the Center of the Orifice ii) Volume to Drain in 12 Hours Vol12 =N/A cu ft iii) Orifice Diameter, 3/8" Minimum DO =N/A in Design Procedure Form: Rain Garden (RG) BPM Northern Engineering October 16, 2019 Country Club Reserve Raingarden #3 UD-BMP (Version 3.06, November 2016) Choose One Choose One 18" Rain Garden Growing Media Other (Explain): YES NO RainGarden3 - UD.xlsm, RG 10/16/2019, 1:48 PM Rain Garden 3 - From Approved Drainage Report Minimum flat areas are greater that was approved. See Stage Storage NORTHERNENGINEERING.COM | 970.221.4158 DRAINAGE SITE CERTIFICATION LETTER: COUNTRY CLUB RESERVE FORT COLLINS | GREELEY APPENDIX Appendix D RECORD DRAWINGS 10 . 4 2 89. 7 4 89.39 89. 1 9 88.67 88. 1 6 87.6 9 86 . 3 9 88.1 7 86.0 5 86 . 5 7 87.47 88.3390.72 92.16 88.78 89.2 6 93.66 94.59 90.1 9 91.4 3 95.83 FG=90.08 TF=90.75 B FG=88.18 TF=88.85 B FG=91.67 TF=92.34 A FG=92.71 TF=93.38 A FG=93.79 TF=94.46 A FG=94.88 TF=95.55 A FG=93.34 TF=94.01 G FG=94.59 TF=95.26 G FG=95.84 TF=96.51 G FG=97.11 TF=97.78 G FG=92.09 TF=92.76 B 90.00 90.52 91.54 91.86 93.75 94.2 3 92.79 87. 6 8 16.38 15.5 5 14.3 2 10.99 9. 7 2 90.88 90.40 89.92 89.50 89.09 85.2 5 86.44 87.24 87.16 90.9 9 92.2 4 93.4 9 94.7 4 96.0 1 86.68 15. 4 5 14. 2 2 9.7 2 10 . 8 9 93.29 90 . 7 5 SIDEWALK CULVERT (2 . 0 0 ) 1.41 91.59 92.84 94.09 95.34 96.61 85.6 7 85.8 6 88.52 86. 5 9 88.00 88.58 88.00 86.99 86.99 85.86 85.86 85.3085.46 85.792.10 89.8 1 88.8 2 89.1 3 V.P.V.P.V.P. A.R.V. GAS X X X X X X X X X X X X X X X X X X X X X X X X XXXX / / / / / / / // / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / M XXXXXXXXXXXXXXX FES MM F ESFES M M XXXXTELE F.O. TELE F ES XX / / / / / / / / ST / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / AW / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / E E E. DOUGLAS ROAD BE T H P A G E D R . WINGED FOOT DR. REPLAT CHERRYWOOD ACRES TRACT 1A REPLAT CHERRYWOOD ACRES TRACT 1B 53' ROW 30' - 53' ROW 30' - 15' UTILITY EASEMENT SIDEWALK CULVERT (2 . 0 0 ) LOT 3 LOT 4 LOT 1 LOT 2 LOT 1 LOT 2 LOT 4 LOT 3 LOT 2 LOT 6 LOT 5 BLOCK 8 BLOCK 9 BLOCK 1 BLOCK 9 BLOCK 9 20' ACCESS DRIVE TRACT C ACCESS & DRAINAGE EASEMENT TRACT C ACCESS & DRAINAGE EASEMENT 10' PAN "STOP" SIGN EXISTING PUMP EXISTING WELL ROAD EXISTING WELL ROAD ABANDONED WELL SWALE EXISTING STORM CULVERT EXISTING STORM CULVERT EXISTING STORM CULVERT 5' WALKING TRAIL 9' U T I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T 9' UTILITY EASEMENT ST 50 9 4 . 6 5 AB 509 5 . 8 3 AB 508 8 . 3 3 AB 50 8 7 . 3 6 AB 508 7 . 9 6 AB 5088 . 4 8 AB 5088 . 1 5 AB 50 8 8 . 5 0 AB 508 6 . 2 4 AB 508 5 . 9 3 AB 5110.48 AB 51 1 2 . 2 3 AB 5089.4 8 AB 5089 . 8 4 AB 5089 . 2 8 AB 5088.72 AB 5088.5 8 AB 508 8 . 2 1 AB 508 7 . 7 6 AB 509 0 . 7 8 AB 5092 . 2 1 AB 509 3 . 5 9 AB 508 6 . 5 5 AB 50 9 1 . 0 2 AB 5090 . 0 2 AB 508 9 . 2 3 AB 50 8 9 . 1 0 AB 508 8 . 6 5 AB 509 0 . 5 6 AB 5091 . 8 3 AB 5093 . 0 6 AB 5094 . 3 0 AB 509 5 . 5 8 AB 5093 . 0 0 AB G1 GR A D I N G P L A N 8 NORTH CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R ( IN FEET ) 0 1 INCH = 40 FEET 40 40 80 120 Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 KEYMAP DOUGLAS RD TU R N B E R R Y R D LEGEND: 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.REFER TO THE PLAT FOR LOT AREAS, TRACT SIZES, EASEMENTS, LOT DIMENSIONS, UTILITY EASEMENTS, OTHER EASEMENTS, AND OTHER SURVEY INFORMATION. 3.ALL CURB SPOTS SHOWN ARE FLOWLINE ELEVATIONS. ALL OTHER SPOTS ARE FINISHED GRADE ELEVATIONS UNLESS OTHERWISE NOTED. 4.THE TOP OF FOUNDATION ELEVATIONS SHOWN ARE THE MINIMUM ELEVATIONS REQUIRED FOR PROTECTION FROM THE 100-YEAR STORM. 5.CROSSPANS ALONG PUBLIC STREETS AT THE INTERSECTION OF PRIVATE DRIVES SHALL HAVE CONCRETE EXTENDED TO THE RIGHT-OF-WAY LINE. 6.ALL PROJECT DATA IS ON THE CITY OF FORT COLLINS VERTICAL DATUM; NAVD 88 (UNADJUSTED). SEE COVER SHEET FOR BENCHMARK REFERENCES. 7.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 8.NO TREES SHALL BE REMOVED DURING THE SONGBIRD NESTING SEASON (FEBRUARY 1 TO JULY 31) WITHOUT FIRST HAVING A PROFESSIONAL ECOLOGIST OR WILDLIFE BIOLOGIST COMPLETE A NESTING SURVEY TO IDENTIFY ANY ACTIVE NESTS EXISTING ON THE PROJECT SITE. THE SURVEY SHALL BE SENT TO THE CITY ENVIRONMENTAL PLANNER. IF ACTIVE NESTS ARE FOUND, THE CITY CITY WILL COORDINATE WITH RELEVANT STATE AND FEDERAL REPRESENTATIVES TO DETERMINE WHETHER ADDITIONAL RESTRICTIONS ON TREE REMOVAL AND CONSTRUCTION APPLY. 9.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORT FOR TEMPORARY CONTROL MEASURES AND CONSTRUCTION SEQUENCING THAT SHALL BE USED TO PREVENT LOADING OF THIS DRAINAGE FACILITY WITH SEDIMENT DURING CONSTRUCTION. 36.25 (36.25) 2.0% NOTES: W LOT (WALK-OUT) EXISTING SPOT ELEVATION PROPOSED SPOT ELEVATION PROPOSED EASEMENT EXISTING RIGHT OF WAY PROPOSED LOT LINE PROPERTY BOUNDARY PROPOSED CURB AND GUTTER PROPOSED SWALE EXISTING CONTOUR PROPOSED CONTOUR PROPOSED STORM INLET PROPOSED STORM SEWER EXISTING STORM SEWER PROPOSED RIGHT OF WAY NATURAL HABITAT BUFFER ZONE (NHBZ) T PROPOSED SLOPES A LOT A B LOT B G LOT (GARDEN)G T LOT (TRANSITIONAL)T MA T C H L I N E - S E E S H E E T G2 MATCHLINE - SEE SHEET G4 G3G1G2 G6G5G4 78' R.O.W 48.6' EOP -  1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 (7 9 . 8 3 ) (79 . 6 2 ) (78 . 7 3 ) (78.8 4 ) (78.9 1 ) (78.7 0 ) (78.4 7 ) (79.2 6 ) (78.2 0 ) 89.39 88.67 86.0 5 86 . 5 7 85. 7 8 84. 9 9 85.0 5 84. 1 7 83.6 0 83.1 0 83. 4 1 84 . 2 0 82 . 6 2 82. 5 9 82.6 0 82.5 7 82 . 5 2 82.9 7 83.2 7 83.5 7 83.8 7 82 . 9 0 83. 2 0 83 . 5 0 83 . 8 0 84 . 1 0 84 . 4 0 84 . 7 0 85 . 0 0 85 . 3 0 85. 8 5 85 . 4 9 85. 6 1 85 . 8 9 86. 3 3 86.8 1 87. 0 0 86. 8 5 86 . 3 1 85.19 86.3 9 86 . 0 9 85.7 9 85.6 7 85 . 8 1 85 . 5 1 85.3 7 85.0 7 85 . 2 0 84. 8 9 84.7 7 84 . 5 9 84. 2 8 84.4 7 84.1 7 83 . 9 7 83. 6 6 83 . 3 5 83. 0 4 82. 7 7 82 . 8 6 82.7 6 83.04 83.3 3 80.79 81.29 79.72 78.51 78.70 75.92 83 . 4 1 82 . 6 5 82. 2 6 82 . 1 4 81 . 7 2 82. 3 9 84 . 1 4 80. 7 7 80 . 3 5 81 . 0 6 78.22 FG=85.30 TF=85.97 A FG=86.32 TF=86.99 A FG=85.39 TF=86.06 A FG=86.23 TF=86.90 A FG=86.36 TF=87.03 A FG=86.58 TF=87.25 A FG=86.46 TF=87.13 A FG=86.46 TF=87.13 B FG=86.24 TF=86.91 B FG=86.55 TF=87.22 B FG=86.86 TF=87.53 B FG=86.84 TF=87.51 B FG=88.18 TF=88.85 B FG=87.31 TF=87.98 B FG=86.48 TF=87.15 B FG=85.78 TF=86.45 B FG=85.10 TF=85.77 B FG=84.75 TF=85.42 B FG=85.05 TF=85.72 B FG=85.35 TF=86.02 B FG=85.65 TF=86.32 B FG=85.95 TF=86.62 B FG=86.30 TF=86.97 B FG=86.55 TF=87.22 B FG=86.85 TF=87.52 B FG=87.15 TF=87.82 B FG=87.60 TF=88.27 B FG=87.45 TF=88.12 B FG=87.74 TF=88.41 B FG=88.17 TF=88.84 B FG=88.82 TF=89.49 B FG=87.18 TF=87.85 A FG=87.66 TF=88.33 A FG=87.74 TF=88.41 A FG=87.28 TF=87.95 A FG=86.44 TF=87.11 A FG=82.95 TF=83.62 A FG=82.33 TF=83.00 A FG=87.89 TF=88.56 B FG=84.78 TF=85.45 B FG=82.64 TF=83.31 B FG=81.07 TF=81.74 B FG=80.05 TF=80.72 B FG=88.37 TF=89.04 80.57 84.28 79.90 87.60 88. 2 0 87 . 6 7 87.2 4 86.9 5 86.7 3 87.09 86 . 6 5 86. 3 5 86. 0 5 85 . 7 5 85 . 4 5 85 . 1 5 84. 8 5 84 . 5 5 84. 2 5 83. 9 0 83. 9 3 84 . 6 0 85 . 2 8 85. 9 8 86 . 8 187. 6 8 81 . 8 5 80 . 9 4 (78 . 3 8 ) (78 . 7 5 ) (79 . 8 4 ) (80 . 9 2 ) (82 . 6 7 ) (82 . 6 4 ) (79 . 4 4 ) (79 . 4 4 ) (78 . 8 2 ) (79.1 5 ) 81.46 81.83 82.26 80.47 81.46 84.98 83.7 9 84.1 0 84.3 0 84.7 1 85.0 2 86.5 9 85.9 6 85.6 1 85.5 6 85.4 3 86.3 6 86.0 5 85.7 4 85.6 5 85.9 6 85.9 2 85.8 6 84.8 2 84.5 1 84.2 3 84.3 2 84.8 0 84.8 9 84.92 84.95 84.72 84.94 84.79 85.2 5 86.44 87.24 85.94 86.57 87.16 85.97 86.91 86.87 85 . 1 8 85 . 6 3 81.50 81.03 80.69 85. 3 9 86.78 86.68 81. 9 4 81 . 9 2 80 . 9 4 80 . 9 4 80 . 9 4 81. 9 4 81 . 9 4 80 . 9 4 81.9 4 80 . 9 4 80 . 9 4 81 . 9 4 81 . 9 4 80 . 9 4 81.9 4 78. 0 5 79 . 5 0 82.45 80 . 5 0 78 . 6 8 78 . 2 0 78.45 79.55 82.14 88.34 85.6 7 85.8 6 88.52 86.04 86. 5 9 86.97 87.50 85.86 85.30 84.69 84.5 1 84. 3 4 83.4 8 84.1 6 84.5 3 84 . 6 1 83.76 83 . 7 6 78.18 80.55 80.55 78.18 86. 5 2 86 . 5 2 XXXXXX / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / FES M FES TELE / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / XXXX EUD UD UD UD UD UD WINGED FOOT DR. CAR N O U S T I E D R . E. DOUGLAS ROAD RO Y A L T R O O N A V E . 53' ROW 30' - 53' ROW 30' - 15' UTILITY EASEMENT (79.0 9 ) TRACT E ACCESS & DRAINAGE EASEMENT TRACT A DRAINAGE EASEMENT LOT 3 LOT 6 LOT 2 LOT 5LOT 4 LOT 6 LOT 16LOT 15LOT 14LOT 13LOT 12LOT 9 LOT 11LOT 10LOT 7 LOT 8 LOT 18 LOT 3 LOT 4 LOT 2 LOT 1 LOT 5 LOT 1 LOT 4 LOT 5 LOT 12LOT 11LOT 10LOT 9LOT 8LOT 7 LOT 19 LOT 18 LOT 3LOT 2 LOT 7 LOT 8 LOT 10 LOT 11 LOT 12 LOT 9 LOT 17 LOT 19 LOT 20 BLOCK 10 BLOCK 9 BLOCK 1 BLOCK 5 152.2' BLOCK 10 508 1 . 8 5 AB 5082.0 3 AB 508 0 . 8 3 AB 508 1 . 1 0 AB 508 1 . 4 7 AB 5081.8 1 AB SIDEWALK AND CONCRETE CULVERT 10' MIDBLOCK CROSS PAN 2' CONCRETE PAN SWALE EDGE OF WETLANDS EXISTING PUMP HOUSE LANDSCAPING WALL (BY OTHERS) SWALE NHBZ NATURAL HABITAT BUFFER ZONE NHBZ NHBZ WETLANDS 50' BUFFER ZONE FOREBAY (SEE DETAIL ON SHEET D8) STORM LINE D SEE SHEET ST3 CONCRETE WEIR RIP-RAP (TYP.) EXISTING STORM CULVERT WINGWALL (TYP.) UNDERDRAIN SEE SHEET U2 RAIN GARDEN 3 POND 2 (WETLANDS) PERMANENT WATER SURFACE ELEVATION = 5079 9' U T I L I T Y E A S E M E N T 9' UTILITY EASEMENT 9' UTILITY EASEMENT 9' UTILITY EASEMENT 9' UTILITY EASEMENT 9' UTILITY EASEMENT 9' U T I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T ST ST ST ST ST ST ST ST ST ST ST ST ST 5082 . 3 4 AB 508 2 . 7 3 AB 508 3 . 0 7 AB 50 7 8 . 1 6 AB 5078 . 3 3 AB 507 9 . 1 5 AB 507 9 . 4 5 AB 507 9 . 8 3 AB 50 8 5 . 5 2 AB 5086.86 5086.63 AB 508 6 . 5 5 AB5086.35 AB 508 6 . 0 6 AB 508 4 . 3 0 AB 508 6 . 2 4 AB 508 3 . 3 5 AB 508 5 . 6 8 AB 5085.39 AB 508 5 . 0 7 AB 5084. 6 6 AB 508 4 . 2 5 AB 5083 . 9 8 AB 508 3 . 7 3 AB 508 3 . 4 4 AB508 3 . 2 2 AB 5083 . 0 4 AB 50 8 2 . 7 3 AB 508 2 . 8 3 AB 508 5 . 9 3 AB 508 4 . 9 7 AB 508 4 . 1 4 AB 508 3 . 5 0 AB 508 2 . 9 8 AB 5082 . 8 4 AB 5083 . 1 5 AB 50 8 3 . 4 1 AB 508 3 . 7 4 AB 5084 . 0 0 AB 508 4 . 2 2 AB 508 4 . 5 0 AB 5084 . 8 5 AB 508 5 . 2 6 AB 508 5 . 6 2 AB 508 5 . 7 2 AB 5085.90 AB 5086.3 3 AB 5086 . 4 6 AB 508 6 . 7 4 AB 5087.2 1 AB 5078.96 AB 507 5 . 9 5 AB 507 8 . 5 7 AB 5080 . 8 7 AB 5083.36 AB 508 5 . 3 5 AB 5085 . 6 5 AB 508 5 . 9 2 AB 5086 . 6 7 AB 50 8 5 . 0 9 AB 50 8 4 . 8 0 AB 508 4 . 3 3 AB 508 4 . 2 0 AB 508 3 . 8 1 AB 508 2 . 8 3 AB 5083.49 AB 50 8 2 . 6 4 AB 5082.29 AB 50 8 2 . 2 0 AB 5081 . 7 8 AB 508 7 . 3 7 AB 5088 . 4 3 AB 508 8 . 2 1 AB 5086.90 AB 508 6 . 8 1 AB 5086.3 4 AB 508 5 . 9 3 AB 50 8 5 . 6 6 AB 5085.50 AB 5085 . 8 1 AB5085 . 3 0 AB 508 5 . 0 5 AB508 4 . 7 4 AB5084.44 AB 508 4 . 1 7 AB 5083 . 8 3 AB 508 3 . 5 0 AB 508 3 . 1 7 AB 5082 . 8 9 AB 508 2 . 6 2 AB 5082.64 AB 50 8 3 . 5 1 AB508 4 . 2 0 AB 508 5 . 0 8 AB 508 5 . 8 5 AB 508 6 . 5 5 AB 508 4 . 9 0 AB 508 2 . 6 7 AB 508 0 . 8 1 AB 508 0 . 0 2 AB 50 7 9 . 2 9 AB 507 8 . 2 7 AB 5077.78 AB AB 5080.37 AB 5081.87 AB 5083.30 AB 508 3 . 6 4 AB 5084.32 AB 5084.5 4 AB 508 4 . 4 0 AB 5084 . 3 6 AB 5084.27 AB 508 3 . 9 2 AB 5084. 1 4 AB 5084.4 3 AB 5080.04 AB 5082.29 AB 508 1 . 1 0 AB 50 8 4 . 8 3 AB 5082 . 4 3 AB 5082 . 4 5 AB G2 GR A D I N G P L A N 9 NORTH ( IN FEET ) 0 1 INCH = 40 FEET 40 40 80 120 Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 KEYMAP DOUGLAS RD TU R N B E R R Y R D LEGEND: 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.REFER TO THE PLAT FOR LOT AREAS, TRACT SIZES, EASEMENTS, LOT DIMENSIONS, UTILITY EASEMENTS, OTHER EASEMENTS, AND OTHER SURVEY INFORMATION. 3.ALL CURB SPOTS SHOWN ARE FLOWLINE ELEVATIONS. ALL OTHER SPOTS ARE FINISHED GRADE ELEVATIONS UNLESS OTHERWISE NOTED. 4.THE TOP OF FOUNDATION ELEVATIONS SHOWN ARE THE MINIMUM ELEVATIONS REQUIRED FOR PROTECTION FROM THE 100-YEAR STORM. 5.CROSSPANS ALONG PUBLIC STREETS AT THE INTERSECTION OF PRIVATE DRIVES SHALL HAVE CONCRETE EXTENDED TO THE RIGHT-OF-WAY LINE. 6.ALL PROJECT DATA IS ON THE CITY OF FORT COLLINS VERTICAL DATUM; NAVD 88 (UNADJUSTED). SEE COVER SHEET FOR BENCHMARK REFERENCES. 7.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 8.NO TREES SHALL BE REMOVED DURING THE SONGBIRD NESTING SEASON (FEBRUARY 1 TO JULY 31) WITHOUT FIRST HAVING A PROFESSIONAL ECOLOGIST OR WILDLIFE BIOLOGIST COMPLETE A NESTING SURVEY TO IDENTIFY ANY ACTIVE NESTS EXISTING ON THE PROJECT SITE. THE SURVEY SHALL BE SENT TO THE CITY ENVIRONMENTAL PLANNER. IF ACTIVE NESTS ARE FOUND, THE CITY CITY WILL COORDINATE WITH RELEVANT STATE AND FEDERAL REPRESENTATIVES TO DETERMINE WHETHER ADDITIONAL RESTRICTIONS ON TREE REMOVAL AND CONSTRUCTION APPLY. 9.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORT FOR TEMPORARY CONTROL MEASURES AND CONSTRUCTION SEQUENCING THAT SHALL BE USED TO PREVENT LOADING OF THIS DRAINAGE FACILITY WITH SEDIMENT DURING CONSTRUCTION. 36.25 (36.25) 2.0% NOTES: W LOT (WALK-OUT) EXISTING SPOT ELEVATION PROPOSED SPOT ELEVATION PROPOSED EASEMENT EXISTING RIGHT OF WAY PROPOSED LOT LINE PROPERTY BOUNDARY PROPOSED CURB AND GUTTER PROPOSED SWALE EXISTING CONTOUR PROPOSED CONTOUR PROPOSED STORM INLET PROPOSED STORM SEWER EXISTING STORM SEWER PROPOSED RIGHT OF WAY NATURAL HABITAT BUFFER ZONE (NHBZ) T PROPOSED SLOPES A LOT A B LOT B G LOT (GARDEN)G T LOT (TRANSITIONAL)T MA T C H L I N E - S E E S H E E T G3 MATCHLINE - SEE SHEET G5 MA T C H L I N E - S E E S H E E T G1 G3G2 G6G5G4 G1 CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R 1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 87.32 87. 0 0 81.39 83.41 87.36 87 . 2 7 87 . 5 4 87.36 86.96 84.56 81.46 78.92 77.55 76.24 74.99 73.77 73.02 72. 7 3 72.4 7 72.3 0 72 . 6 5 72 . 9 5 73 . 2 1 73 . 5 0 72. 3 0 72. 2 7 72.5 7 73.01 73.61 74.54 74. 2 6 75. 4 9 75.79 77.04 76 . 7 4 78.26 78 . 0 7 79. 4 6 80 . 7 1 79 . 4 7 81. 9 6 80.71 81.96 81. 2 6 81 . 3 6 81. 4 6 80. 2 1 78 . 9 8 77 . 7 6 76 . 5 4 75 . 2 9 74.0 4 73. 1 8 72. 4 5 72.2 7 79.67 79.33 79.31 79.00 73 . 2 7 69.67 70 . 0 4 66. 7 2 74. 1 0 74. 8 2 77 . 5 8 79 . 5 8 65.19 60.53 FG=88.82 TF=89.49 FG=88.86 TF=89.53 B FG=88.87 TF=89.54 B FG=87.05 TF=87.72 B FG=84.91 TF=85.58 B FG=88.37 TF=89.04 W FG=88.64 TF=89.31 W FG=88.64 TF=89.31 W FG=83.31 TF=83.98 B FG=86.98 TF=87.65 B FG=82.06 TF=82.73 B FG=80.79 TF=81.46 B FG=79.42 TF=80.09 B FG=78.09 TF=78.76 B FG=76.84 TF=77.51 B FG=75.61 TF=76.28 B FG=74.86 TF=75.53 B FG=74.57 TF=75.24 B FG=74.31 TF=74.98 B FG=74.37 TF=75.04 B FG=75.15 TF=75.82 B FG=75.89 TF=76.56 B FG=77.14 TF=77.81 B FG=78.39 TF=79.06 B FG=79.61 TF=80.28 B FG=80.82 TF=81.49 B FG=82.06 TF=82.73 B FG=83.31 TF=83.98 B FG=84.27 TF=84.94 B 80.22 82.81 81.56 80.32 79.11 77.89 76.64 75.39 74.49 73.87 73.5 2 79.90 87.60 87.87 80.30 80.31 88.14 87.96 80.77 82.8 1 81.56 80.29 78.92 77.59 76.34 75.11 74.36 74.07 73.81 73.52 84.29 86.42 88.24 88. 2 0 77.3 5 80.56 80.42 66. 2 3 82.34 81.1 0 82.97 84.95 86.91 67 . 5 3 (75.5 7 ) 63. 8 2 75.38 62. 3 2 76.43 61.46 71.76 55.20 70 . 2 1 69.21 69. 2 1 69. 2 1 70.21 70.21 69. 2 1 70.21 70.21 69. 2 1 85.54 58.63 67.13 57. 0 0 66. 5 3 66 . 5 1 DEPTH 71 . 2 3 67.3 8 67. 3 4 71.7 3 67. 6 4 72.2 3 71 . 7 0 69 . 3 5 71 . 7 0 69.45 70.96 76.96 54.6 9 54 . 5 0 77.35 79.90 79.90 83. 7 7 85 . 0 6 83. 3 6 83. 1 5 79 . 8 5 79. 8 5 73. 6 7 72. 7 6 73. 6 7 72 . 7 6 71 . 8 0 72 . 1 6 80 . 3 3 80 . 6 3 80 . 7 5 80. 9 0 STORM LINE A SEE SHEET ST1 54.50 55.4 9 56 . 6 3 78 . 6 1 78. 6 1 58.00 58.00 WINGWALL (TYP.) 56.64 78 . 1 2 78.3 0 54.5 0 55.4 7 77. 0 5 / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / V.P. / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / / / / / / / / / // / / / / / / / X / / / / / / / // / / / / / / // / / / / / / // / / / / / / / FESM FES / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / XXXXXXXXXXXXXX / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / X WSO X X X V.P. VAULT CABLE BOX CABLE X X GASGASV.P. GAS OH E OH E OH E OH E OH E OH E OH E OH E OHE OHE OHE OHE OHE OHE ST W W FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO G G G G G G G G G G G G G G G G G IR R IR R IR R IR R IR R IR R IR R IR R IR R IR R IR R IR R IR R IR R IR R UD UD UD BALLY N E A L D R . TU R N B E R R Y R O A D E. DOUGLAS ROAD WIN G E D F O O T D R . 53' ROW 30' - 53' ROW 30' - 72' ROW 50' -EOP 83.98 15' UTILITY EASEMENT TRACT B ACCESS & DRAINAGE EASEMENT LOT 2 LOT 3 LOT 4 LOT 8 LOT 10 LOT 9 LOT 11 LOT 2 LOT 1 LOT 3 LOT 6 LOT 1 LOT 7 LOT 6 LOT 5 LOT 7 LOT 22 LOT 23 LOT 24 LOT 21 LOT 20 LOT 2 LOT 4 LOT 3 LOT 5 LOT 8 LOT 9 LOT 10 LOT 1 BLOCK 2 BLOCK 3 BLOCK 1 BLOCK 4 20' STORM LINE A SEE SHEET ST1 WINGWALL (TYP.) 5054.67 AB 505 4 . 7 3 AB505 4 . 9 3 AB 5055 . 1 7 50 5 5 . 5 1 AB 5063 . 7 8 AB 5074.14 AB 507 3 . 2 7 AB 5072.75 AB 5066.99 AB 506 4 . 5 1 AB 506 3 . 4 2 AB 505 7 . 1 4 AB 50 7 6 . 5 8 AB 5075.94 AB 5067 . 6 7 AB 508 2 . 4 3 AB 5081.63 AB 5074.35 AB 5072.17 AB 5075.11 AB 506 5 . 8 8 AB 5071 . 1 0 AB 5068.55 AB 50 5 5 . 9 1 AB 5077.66 AB 5070.41 AB 5063.41 AB 5063.60 AB SWALE 10' PAN LANDSCAPING WALL (BY OTHERS) SWALE NHBZ 2' CONCRETE PAN NATURAL HABITAT BUFFER ZONE STORM LINE B SEE SHEET ST2 STORM LINE D SEE SHEET ST3 FOREBAY (SEE DETAIL ON SHEET D8) EXISTING STORM CULVERT 10' PAN EXISTING STORM CULVERT WINGWALL (TYP.) UNDERDRAIN SEE SHEET U3 RAIN GARDEN 1 9' UTI L I T Y E A S E M E N T 9' UT I L I T Y E A S E M E N T 6' UT I L I T Y E A S E M E N T 9' UT I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T 5079.4 8 AB 5077.55 AB 507 5 . 4 3 AB 50 7 4 . 5 6 AB 5073.6 0 AB 5072 . 7 9 AB 5077.16 AB 5075.79 AB 507 3 . 6 5 AB 5071.30 AB 507 0 . 7 4 AB 5070.25 AB 5070.58 AB 5070.39 AB 5072.59 AB 5075. 0 9 AB 507 2 . 9 1 AB 5070 . 6 4 AB507 1 . 6 1 AB 5072 . 1 9 AB 5066. 8 0 AB 50 6 6 . 3 9 AB 507 0 . 5 2 AB 5070 . 2 9 AB 50 7 0 . 5 4 AB 507 0 . 1 9 AB 507 1 . 4 8 AB 50 7 2 . 2 6 AB 5072.9 7 AB 507 2 . 1 3 AB 50 7 2 . 2 8 AB 5072.37 AB 5081.0 9 AB 508 1 . 2 9 AB 508 3 . 1 0 AB 5082.97 AB 508 1 . 8 9 AB 50 8 0 . 6 7 AB 507 9 . 8 1 AB 5079.45 AB 5078.24 AB 5076.95 AB 507 5 . 7 3 AB 5074.35 AB 507 3 . 4 8 AB 5073.46 AB 507 2 . 7 8 AB 507 2 . 6 8 AB 507 2 . 4 8 AB 507 2 . 4 2 AB 50 7 2 . 5 3 AB 5072.74 AB 5072.97 AB 507 3 . 4 4 AB 5074.10 AB 5075.28 AB 5076.57 AB 50 7 6 . 9 1 AB 5078.04 AB 5079.26 AB 50 7 9 . 7 0 AB 5080 . 5 8 AB 5081.82 AB 5083.48 AB 5084.78 AB 5086.56 AB 5087.08 AB 5087.0 5 AB 5086.86 AB 5086.63 AB 5087.2 1 AB 5087.24 AB 5085.42 AB 5083.38 AB 508 1 . 2 6 AB 5072 . 5 1 AB507 3 . 2 2 AB 5074.10 AB 5075 . 3 1 AB 5076.48 AB 5077.76 AB 507 9 . 0 0 AB 5080.24 AB 5081.48 AB 508 1 . 4 1 AB 5072.40 AB 5072.74 AB 5073.01 AB 5073.72 AB 50 7 5 . 0 0 AB 50 7 6 . 2 4 AB 5077.56 AB 5078.97 AB 5080.21 AB 50 8 1 . 4 8 AB 5084.58 AB 5078.96 AB 5079.3 3 AB 5079.3 8 AB 5079.74 AB 5083.36 5082 . 9 6 AB 5085 . 0 5 AB 5086.90 AB 508 6 . 8 1 AB 5073.34 AB 507 2 . 1 3 AB G3 GR A D I N G P L A N 10 NORTH ( IN FEET ) 0 1 INCH = 40 FEET 40 40 80 120 Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 KEYMAP DOUGLAS RD TU R N B E R R Y R D LEGEND: 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.REFER TO THE PLAT FOR LOT AREAS, TRACT SIZES, EASEMENTS, LOT DIMENSIONS, UTILITY EASEMENTS, OTHER EASEMENTS, AND OTHER SURVEY INFORMATION. 3.ALL CURB SPOTS SHOWN ARE FLOWLINE ELEVATIONS. ALL OTHER SPOTS ARE FINISHED GRADE ELEVATIONS UNLESS OTHERWISE NOTED. 4.THE TOP OF FOUNDATION ELEVATIONS SHOWN ARE THE MINIMUM ELEVATIONS REQUIRED FOR PROTECTION FROM THE 100-YEAR STORM. 5.CROSSPANS ALONG PUBLIC STREETS AT THE INTERSECTION OF PRIVATE DRIVES SHALL HAVE CONCRETE EXTENDED TO THE RIGHT-OF-WAY LINE. 6.ALL PROJECT DATA IS ON THE CITY OF FORT COLLINS VERTICAL DATUM; NAVD 88 (UNADJUSTED). SEE COVER SHEET FOR BENCHMARK REFERENCES. 7.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 8.NO TREES SHALL BE REMOVED DURING THE SONGBIRD NESTING SEASON (FEBRUARY 1 TO JULY 31) WITHOUT FIRST HAVING A PROFESSIONAL ECOLOGIST OR WILDLIFE BIOLOGIST COMPLETE A NESTING SURVEY TO IDENTIFY ANY ACTIVE NESTS EXISTING ON THE PROJECT SITE. THE SURVEY SHALL BE SENT TO THE CITY ENVIRONMENTAL PLANNER. IF ACTIVE NESTS ARE FOUND, THE CITY CITY WILL COORDINATE WITH RELEVANT STATE AND FEDERAL REPRESENTATIVES TO DETERMINE WHETHER ADDITIONAL RESTRICTIONS ON TREE REMOVAL AND CONSTRUCTION APPLY. 9.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORT FOR TEMPORARY CONTROL MEASURES AND CONSTRUCTION SEQUENCING THAT SHALL BE USED TO PREVENT LOADING OF THIS DRAINAGE FACILITY WITH SEDIMENT DURING CONSTRUCTION. 36.25 (36.25) 2.0% NOTES: W LOT (WALK-OUT) EXISTING SPOT ELEVATION PROPOSED SPOT ELEVATION PROPOSED EASEMENT EXISTING RIGHT OF WAY PROPOSED LOT LINE PROPERTY BOUNDARY PROPOSED CURB AND GUTTER PROPOSED SWALE EXISTING CONTOUR PROPOSED CONTOUR PROPOSED STORM INLET PROPOSED STORM SEWER EXISTING STORM SEWER PROPOSED RIGHT OF WAY NATURAL HABITAT BUFFER ZONE (NHBZ) T PROPOSED SLOPES A LOT A B LOT B G LOT (GARDEN)G T LOT (TRANSITIONAL)T MATCHLINE - SEE SHEET G6 MA T C H L I N E - S E E S H E E T G2 G3 G6G5G4 G2G1 CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R 1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 (?? ? ) 7.12 10 . 4 2 12.15 13 . 6 9 14 . 4 9 15 . 2 5 16. 2 2 16.5 5 16.8 3 18.0 9 13.22 12.91 11.95 11.05 9.86 8.83 13.47 18.98 12.93 13.44 13.1 0 10.4 8 5.24 12 . 6 2 11 . 6 2 10 . 7 2 9.4 2 6.2 1 2.81 0.6 1 99. 1 1 93.8296.1 498.3 6 0.55 2.65 3.77 4.50 92.8 7 92. 1 2 90.88 89.12 87.55 92.40 95.40 97. 6 7 89. 7 4 89.39 87.15 FG=97.11 TF=97.78 G FG=94.93 TF=95.60 G FG=96.01 TF=96.68 G FG=11.49 TF=12.16 A FG=12.54 TF=13.21 A FG=14.12 TF=14.79 A FG=14.76 TF=15.43 A FG=15.66 TF=16.33 A FG=16.66 TF=17.33 A FG=16.83 TF=17.50 A FG=15.00 TF=15.67 B FG=14.71 TF=15.38 B FG=13.72 TF=14.39 G FG=12.72 TF=13.39 G FG=11.92 TF=12.59 G FG=10.94 TF=11.61 G FG=7.36 TF=8.03 G FG=3.90 TF=4.57 G FG=1.71 TF=2.38 G FG=98.90 TF=99.57 G FG=97.61 TF=98.28 B FG=93.75 TF=94.42 B 9.0 8 10.99 11 . 7 6 13 . 0 0 13 . 6 2 13 . 3 5 14.26 15.0 6 16.1 6 15. 4 7 15 . 9 7 13.97 13.22 5.57 11.42 10.32 6.81 99.66 97. 4 4 95. 0 5 94.14 93 . 6 3 93.25 86.6 7 90.6 6 94.6 4 5.38 23.13 18.24 16.38 15.5 5 14.3 2 9. 7 2 5.9 1 6.15 90.88 94.43 96.0 1 14 . 4 1 14.16 11 . 7 9 14.27 18 . 3 4 16 . 2 8 15. 4 5 14. 2 2 9.7 2 10 . 8 9 12.87 13.53 13.2213.27 13.11 12. 3 6 12.73 12.05 11 . 7 4 11.45 11 . 6 5 12 . 3 8 93.01 23.03 24.21 21.73 26.96 21.79 22.11 24.6 3 96.61 15.16 6.28 12 . 2 2 4.97 3.65 1.75 3.41 1.2 1 99 . 7 1 98.27 97.9 4 99.5 5 97.1 3 97.0 6 12.82 11.36 10.55 9.64 0.8 9 8.75 10 . 5 3 0.8 9 12 . 8 2 11 . 3 2 96 . 9 5 96 . 9 5 GAS X X V.P.V.P. X X X X X X E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AW / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / E E E E E E E E E G G EE PH PH PH E E E E E E BALTU S R O L D R . BALT U S R O L C T . CHERRYWOOD ACRES TRACT 6 LOT 18 LOT 17 BLOCK 3 SERRAMONTE HIGHLANDS (LARIMER COUNTY) JU A N I T A L A N E (29 . 0 4 ) 53' ROW 30' - 5' WALKING TRAIL LOT 2 LOT 1 LOT 34 LOT 21 LOT 4 LOT 3 LOT 5 LOT 6 LOT 28 LOT 1 LOT 2 LOT 26 LOT 25 LOT 27 LOT 24 LOT 23 LOT 22 LOT 20 LOT 19 LOT 18 LOT 17 LOT 16 BLOCK 6 BLOCK 9 BLOCK 6 30 ' EA S E M E N T TRACT C ACCESS & DRAINAGE EASEMENT TRACT C ACCESS & DRAINAGE EASEMENT BLOCK 7 FLAT BOTTOM SWALE EXISTING WELL HEADEXISTING WELL ROAD 6' UTILITY EASEMENT 9' UTILIT Y E A S E M E N T 511 8 . 1 7 AB 5118. 8 7 AB 510 4 . 6 2 AB 5103.8 1 AB 5102.80 AB 509 8 . 4 3 AB 50 9 6 . 2 6 AB 50 9 2 . 2 5 AB 5110.48 AB 51 1 2 . 2 3 AB 5113.75 AB 5114.5 6 AB 5115.33 AB 5116.29 AB 5116.60 AB 511 6 . 8 9 AB 5112. 9 7 AB 511 0 . 5 8 AB 5105.3 3 AB 5100.6 5 AB 509 3 . 7 4 AB 509 2 . 8 4 AB 5090.74 AB 5089.14 AB 5089.4 8 AB 5089 . 8 4 AB 5091.78 AB5092 . 0 4 AB 5095.07 AB5096 . 7 4 AB 509 7 . 3 2 AB 509 5 . 5 8 AB 5096.68 AB 509 6 . 5 8 AB 5093 . 9 3 AB 5092.68 AB 509 8 . 7 7 AB510 0 . 2 6 AB 5100 . 5 9 AB 510 2 . 4 7 AB 5105. 8 0 AB 510 9 . 0 5 AB 5110.02 AB511 0 . 3 1 AB 5111 . 0 0 AB 5111.22 AB 5112.33 AB5112 . 5 2 AB 5112 . 8 9 AB 511 3 . 1 6 AB 5113.17 AB 511 2 . 8 6 AB 511 2 . 6 0 AB 511 2 . 4 5 AB 5111.52 AB 51 1 1 . 0 0 AB 51 1 0 . 6 7 AB 51 1 0 . 1 9 AB 51 0 9 . 4 8 AB 51 0 9 . 2 4 AB 5108.38 AB 5106 . 6 5 AB G4 GR A D I N G P L A N 11 NORTH ( IN FEET ) 0 1 INCH = 40 FEET 40 40 80 120 Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 KEYMAP DOUGLAS RD TU R N B E R R Y R D LEGEND: 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.REFER TO THE PLAT FOR LOT AREAS, TRACT SIZES, EASEMENTS, LOT DIMENSIONS, UTILITY EASEMENTS, OTHER EASEMENTS, AND OTHER SURVEY INFORMATION. 3.ALL CURB SPOTS SHOWN ARE FLOWLINE ELEVATIONS. ALL OTHER SPOTS ARE FINISHED GRADE ELEVATIONS UNLESS OTHERWISE NOTED. 4.THE TOP OF FOUNDATION ELEVATIONS SHOWN ARE THE MINIMUM ELEVATIONS REQUIRED FOR PROTECTION FROM THE 100-YEAR STORM. 5.CROSSPANS ALONG PUBLIC STREETS AT THE INTERSECTION OF PRIVATE DRIVES SHALL HAVE CONCRETE EXTENDED TO THE RIGHT-OF-WAY LINE. 6.ALL PROJECT DATA IS ON THE CITY OF FORT COLLINS VERTICAL DATUM; NAVD 88 (UNADJUSTED). SEE COVER SHEET FOR BENCHMARK REFERENCES. 7.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 8.NO TREES SHALL BE REMOVED DURING THE SONGBIRD NESTING SEASON (FEBRUARY 1 TO JULY 31) WITHOUT FIRST HAVING A PROFESSIONAL ECOLOGIST OR WILDLIFE BIOLOGIST COMPLETE A NESTING SURVEY TO IDENTIFY ANY ACTIVE NESTS EXISTING ON THE PROJECT SITE. THE SURVEY SHALL BE SENT TO THE CITY ENVIRONMENTAL PLANNER. IF ACTIVE NESTS ARE FOUND, THE CITY CITY WILL COORDINATE WITH RELEVANT STATE AND FEDERAL REPRESENTATIVES TO DETERMINE WHETHER ADDITIONAL RESTRICTIONS ON TREE REMOVAL AND CONSTRUCTION APPLY. 9.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORT FOR TEMPORARY CONTROL MEASURES AND CONSTRUCTION SEQUENCING THAT SHALL BE USED TO PREVENT LOADING OF THIS DRAINAGE FACILITY WITH SEDIMENT DURING CONSTRUCTION. 36.25 (36.25) 2.0% NOTES: W LOT (WALK-OUT) EXISTING SPOT ELEVATION PROPOSED SPOT ELEVATION PROPOSED EASEMENT EXISTING RIGHT OF WAY PROPOSED LOT LINE PROPERTY BOUNDARY PROPOSED CURB AND GUTTER PROPOSED SWALE EXISTING CONTOUR PROPOSED CONTOUR PROPOSED STORM INLET PROPOSED STORM SEWER EXISTING STORM SEWER PROPOSED RIGHT OF WAY NATURAL HABITAT BUFFER ZONE (NHBZ) T PROPOSED SLOPES A LOT A B LOT B G LOT (GARDEN)G T LOT (TRANSITIONAL)T MA T C H L I N E - S E E S H E E T G5 MATCHLINE - SEE SHEET G1 G6G5G4 G3G2G1 CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R 1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 87.55 92.40 89.39 75.92 82. 1 4 81. 7 2 80 . 7 7 80. 3 5 79 . 7 0 79 . 3 9 79 . 1 1 78. 8 3 78.56 78. 2 8 78 . 0 0 77 . 6 8 80 . 7 1 81. 0 6 78.22 75.5977.93 75.33 75.08 77.62 77.22 76.8 1 74.60 74.12 76.51 76.21 73.63 73.15 75.87 73.75 75.49 75.49 72.44 71.34 75.22 75.64 75 . 0 1 75.2 9 75.5 1 75.72 75 . 8 4 76 . 1 2 76. 7 2 76.46 76.94 77.89 77. 4 4 78 . 3 8 79. 3 3 78.84 80.2 1 79.79 80.93 81.42 82.81 82.32 83.75 84.24 85.67 85.18 86.67 87.15 88.67 89.27 90.77 87.17 85.71 70 . 8 1 70.61 69.81 FG=86.44 TF=87.11 A FG=84.71 TF=85.38 A FG=94.93 TF=95.60 G FG=94.30 TF=94.97 G FG=92.43 TF=93.10 G FG=90.15 TF=90.82 G FG=88.37 TF=89.04 B FG=86.77 TF=87.44 B FG=85.36 TF=86.03 B FG=83.72 TF=84.39 B FG=82.80 TF=83.47 T FG=81.36 TF=82.03 A FG=80.65 TF=81.32 A FG=79.67 TF=80.34 A FG=81.02 TF=81.69 A FG=81.29 TF=81.96 A FG=81.57 TF=82.24 A FG=81.85 TF=82.52 A FG=82.13 TF=82.80 A FG=82.40 TF=83.07 A FG=83.06 TF=83.73 A TF=83.62 FG=82.33 TF=83.00 A FG=81.96 TF=82.63 A FG=81.59 TF=82.26 A FG=81.17 TF=81.84 A FG=80.78 TF=81.45 A FG=80.02 TF=80.69 A FG=78.85 TF=79.52 A FG=93.75 TF=94.42 B FG=92.12 TF=92.79 B FG=90.02 TF=90.69 B FG=88.52 TF=89.19 B FG=87.03 TF=87.70 B FG=85.59 TF=86.26 B FG=84.17 TF=84.84 B FG=82.77 TF=83.44 B FG=81.64 TF=82.31 B FG=80.68 TF=81.35 B FG=79.74 TF=80.41 B FG=78.79 TF=79.46 B FG=78.19 TF=78.86 B FG=77.52 TF=78.19 B FG=77.16 TF=77.83 B FG=77.03 TF=77.70 B FG=77.27 TF=77.94 B FG=80.05 TF=80.72 B FG=79.57 TF=80.24 B FG=79.27 TF=79.94 B FG=78.97 TF=79.64 B FG=78.57 TF=79.24 B FG=78.16 TF=78.83 B FG=77.86 TF=78.53 B FG=77.56 TF=78.23 B 89.52 88.02 86.53 85.09 83.67 82.27 81.14 80.18 79.24 78.29 77.69 77.02 76.66 76.53 76.38 76.37 76.50 77.06 77.36 78.07 79.07 78.77 78.47 77.6 6 69.81 71.19 75.43 75.33 69.81 71.8 9 75 . 9 8 80.02 88.48 91.20 89.25 88.65 87.17 84.01 82.18 80.56 79.31 78.09 86.63 85.03 84.90 84.33 84.13 83.22 82.32 80.77 77 . 1 3 76.51 75.90 76.10 80.98 81.29 81.7981.79 81.83 81.85 81.87 81.90 82.04 82.29 82.37 82.69 83.00 83.64 83.82 85.44 86.74 87.29 80.86 79.93 80.15 78.35 80.68 80.79 81.02 82.56 81.54 81.02 80.74 80.46 80.18 79.46 79.06 78.52 77.49 80 . 2 8 81.09 81.46 77.71 77. 7 5 78 . 0 9 78 . 5 2 78. 9 5 79.38 79.71 80.47 79. 8 8 79.52 83.64 83.74 82.02 85.94 81.03 80.69 77.28 80 . 6 7 81 . 3 5 81. 6 3 81 . 9 0 78 . 9 7 79. 1 7 75 . 7 5 70.82 70.81 69.8 1 69.8 1 70.81 70. 9 6 69 . 8 1 70.81 69. 8 1 69 . 8 1 69.81 70. 7 2 93.01 88.34 74.84 FG=80.49 TF=81.16 A FG=79.64 TF=80.31 A 69.81 70. 8 1 70 . 8 1 70. 7 2 70 . 7 2 84.86 79.99 80.52 93.61 80 . 2 4 89.27 89.85 69.63 70.36 71.01 78. 0 4 79 . 3 6 78 . 0 4 79. 3 6 77. 2 7 77.14 77. 2 2 76. 6 7 76. 8 7 77.56 78.18 78.18 76.11 75.63 75.57 76 . 2 0 77 . 2 1 91.74 86.21 87.76 82. 7 0 75.95 77. 2 1 85.48 92.14 E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E X X X X X W UD UD UD UD CAR N O U S T I E D R . BALT U S R O L D R . RO Y A L T R O O N A V E . BLOCK 3 SERRAMONTE HIGHLANDS (LARIMER COUNTY) LOT 12 LOT 11 LOT 6 53' ROW 30' - 53' ROW 30' - 53' ROW 30' - LOT 29 LOT 5 LOT 6 LOT 7 LOT 8 LOT 9 LOT 10 LOT 11 LOT 13 LOT 18 LOT 16 LOT 13 LOT 14 LOT 17 LOT 15 LOT 34 TRACT D ACCESS, DRAINAGE & UTILITY EASEMENT LOT 13 LOT 33 LOT 12 LOT 32 LOT 17 LOT 28 LOT 15 LOT 22 LOT 19 LOT 21 LOT 27 LOT 18 LOT 16 LOT 12 LOT 23 LOT 20 LOT 14 LOT 31 LOT 24 LOT 25 LOT 26 LOT 30 LOT 14 LOT 16 LOT 15 LOT 11 LOT 9 LOT 10 LOT 12 LOT 13 LOT 8 LOT 7 LOT 5 LOT 4 LOT 6 LOT 2 LOT 1 LOT 3 BLOCK 6 BLOCK 5 55.2' TRACT C ACCESS & DRAINAGE EASEMENT BLOCK 9 BLOCK 9 BLOCK 10 5067.38 5076.13 AB 507 8 . 0 0 AB 506 9 . 8 3 AB 5070.53 AB 50 7 4 . 4 5 AB 50 7 4 . 5 6 AB 5074 . 7 0 AB 507 2 . 8 9 AB 5070 . 8 4 AB SIDEWALK CULVERT FLAT BOTTOM SWALE 4' CONCRETE PAN 10' MIDBLOCK CROSS PAN RIPRAP CONCRETE WEIR FOREBAY (SEE DETAIL ON SHEET D8) FOREBAY (SEE DETAIL ON SHEET D8) UNDERDRAIN SEE SHEET U5 RAIN GARDEN 2 9' U T I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T 6' U T I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T 6' U T I L I T Y E A S E M E N T POND 1 50 8 6 . 8 3 AB 5085.36 AB 5083 . 9 2 AB 5079.90 AB 507 8 . 9 3 AB 5078.06 AB 5077.03 AB 507 6 . 5 0 AB 50 7 5 . 7 0 AB 507 5 . 5 8 AB 50 7 5 . 1 6 AB 5074.91 AB 5080 . 7 5 AB 508 0 . 9 3 AB 508 1 . 7 8 AB 508 1 . 8 5 AB5089.14 AB 5087.5 8 AB 50 8 7 . 2 1 AB 5082.3 0 AB 5081 . 0 3 AB 5075.20 AB 5071.39 AB 5072 . 5 2 AB 5073.79 AB 5073.22 AB 507 3 . 6 7 AB 50 7 4 . 1 4 AB 507 4 . 6 4 AB 507 4 . 8 9 AB 507 5 . 0 3 AB 507 5 . 3 7 AB 5075.59 AB 507 5 . 9 5 AB50 8 2 . 2 0 AB 5081 . 7 8 AB 5080.93 AB 5081.26 AB 508 1 . 7 9 AB508 1 . 8 4 AB 5081.88 AB 508 1 . 9 7 AB 50 8 2 . 1 2 AB50 8 2 . 3 1 AB 5082.44 AB 5082 . 7 5 AB 5082.73 AB 5082.99 AB 5083.74 AB 5083 . 8 8 AB 5085.47 AB 5086 . 7 3 AB 508 7 . 3 7 AB 5088 . 4 3 AB 5077.78 AB 5077. 7 1 AB 5077.45 AB 5077.20 AB 507 7 . 0 8 AB 5076.79 AB 507 6 . 3 9 AB 5076.33 AB 5075.99 AB 5075.78 AB 507 5 . 4 2 AB 507 5 . 3 8 AB 507 5 . 1 8 AB 507 5 . 1 2 AB 5075 . 1 4 AB 5075.21 AB 5075.49 AB5075.72 AB 5075 . 7 7 AB 5076 . 3 1 AB5076.83 AB 507 7 . 0 7 AB 5078 . 0 3 AB 5078.97 AB 507 9 . 9 8 AB 508 3 . 9 0 AB 5085.16 AB5085 . 3 1 AB 50 8 6 . 7 6 AB 5088. 3 0 AB 5088 . 8 6 AB 5090.25 AB 5091.78 AB5092 . 0 4 AB 5093 . 9 3 5092.68 AB 509 1 . 6 0 AB 5090.74 AB 5088.74 AB 5088.13 AB 50 8 6 . 7 8 AB 508 5 . 3 1 AB 50 8 5 . 1 1 AB 5083.64 AB 5081.82 AB 5080.25 AB 5078. 9 3 AB 5077 . 7 0 AB 507 6 . 8 6 AB 5076.84 AB 5076.11 AB 5075.65 AB 5075.23 AB 5075.76 AB 5076.27 AB 5076.74 AB 5077.22 AB 5077.58 AB 507 7 . 6 0 AB 5077.92 AB 5078.12 AB 5078 . 3 3 AB 5078.67 AB 5078.91 AB 50 7 8 . 9 3 AB 5079.33 AB 5080.01 AB 5080.37 AB 5081.87 AB 5080.04 AB 50 7 9 . 2 7 AB 507 8 . 9 5 AB 50 7 8 . 9 2 AB 5078.48 AB 5078.04 AB 5081.10 AB 5081.36 AB 5081. 0 7 AB 5082 . 3 8 AB 5077. 6 4 AB 5077.56 AB 5077.18 AB 5076.77 AB 5076 . 7 1 AB 5077 . 0 7 AB 507 7 . 3 0 AB 71.29 TOB 71.2 9 TOB 71.29 TOB 71.29 TOB 71.29 TOB 71 . 2 9 TO B 50 7 1 . 1 1 AB 507 0 . 6 9AB 507 0 . 7 1 AB 5070.94 AB 507 0 . 3 8 AB 5070. 7 0 AB 5071.02 AB 507 0 . 6 8 AB 507 0 . 5 0 AB 50 7 1 . 4 8 AB 50 7 1 . 6 5 AB 50 7 1 . 1 3 AB 507 1 . 5 3 AB 5070 . 7 9 AB 5071 . 4 9 AB 5071 . 6 7 AB 50 7 0 . 8 4 AB 5069 . 7 3 AB 71.28 TOB 7 1 . 5 7 1 . 2 7 0 . 8 7 1 . 2 7 0 . 1 7 0 . 5 7 1 . 6 7 0 . 6 7 2 . 1 7 1 . 9 7 1 . 3 7 2 . 2 7 2 . 4 7 1 . 7 7 2 . 4 7 2 . 6 7 2 . 0 7 3 . 3 7 2 . 1 7 3 . 2 7 1 . 7 7 1 . 2 G5 GR A D I N G P L A N 12 NORTH ( IN FEET ) 0 1 INCH = 40 FEET 40 40 80 120 Sheet of 76 CO U N T R Y C L U B R E S E R V E 30 1 N o r t h H o w e s S t r e e t , S u i t e 1 0 0 Fo r t C o l l i n s , C o l o r a d o 8 0 5 2 1 E N G I N E E R N G I E H T R O N R N PH O N E : 9 7 0 . 2 2 1 . 4 1 5 8 ww w . n o r t h e r n e n g i n e e r i n g . c o m 02/25/21 KEYMAP DOUGLAS RD TU R N B E R R Y R D LEGEND: 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.REFER TO THE PLAT FOR LOT AREAS, TRACT SIZES, EASEMENTS, LOT DIMENSIONS, UTILITY EASEMENTS, OTHER EASEMENTS, AND OTHER SURVEY INFORMATION. 3.ALL CURB SPOTS SHOWN ARE FLOWLINE ELEVATIONS. ALL OTHER SPOTS ARE FINISHED GRADE ELEVATIONS UNLESS OTHERWISE NOTED. 4.THE TOP OF FOUNDATION ELEVATIONS SHOWN ARE THE MINIMUM ELEVATIONS REQUIRED FOR PROTECTION FROM THE 100-YEAR STORM. 5.CROSSPANS ALONG PUBLIC STREETS AT THE INTERSECTION OF PRIVATE DRIVES SHALL HAVE CONCRETE EXTENDED TO THE RIGHT-OF-WAY LINE. 6.ALL PROJECT DATA IS ON THE CITY OF FORT COLLINS VERTICAL DATUM; NAVD 88 (UNADJUSTED). SEE COVER SHEET FOR BENCHMARK REFERENCES. 7.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 8.NO TREES SHALL BE REMOVED DURING THE SONGBIRD NESTING SEASON (FEBRUARY 1 TO JULY 31) WITHOUT FIRST HAVING A PROFESSIONAL ECOLOGIST OR WILDLIFE BIOLOGIST COMPLETE A NESTING SURVEY TO IDENTIFY ANY ACTIVE NESTS EXISTING ON THE PROJECT SITE. THE SURVEY SHALL BE SENT TO THE CITY ENVIRONMENTAL PLANNER. IF ACTIVE NESTS ARE FOUND, THE CITY CITY WILL COORDINATE WITH RELEVANT STATE AND FEDERAL REPRESENTATIVES TO DETERMINE WHETHER ADDITIONAL RESTRICTIONS ON TREE REMOVAL AND CONSTRUCTION APPLY. 9.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORT FOR TEMPORARY CONTROL MEASURES AND CONSTRUCTION SEQUENCING THAT SHALL BE USED TO PREVENT LOADING OF THIS DRAINAGE FACILITY WITH SEDIMENT DURING CONSTRUCTION. 36.25 (36.25) 2.0% NOTES: W LOT (WALK-OUT) EXISTING SPOT ELEVATION PROPOSED SPOT ELEVATION PROPOSED EASEMENT EXISTING RIGHT OF WAY PROPOSED LOT LINE PROPERTY BOUNDARY PROPOSED CURB AND GUTTER PROPOSED SWALE EXISTING CONTOUR PROPOSED CONTOUR PROPOSED STORM INLET PROPOSED STORM SEWER EXISTING STORM SEWER PROPOSED RIGHT OF WAY NATURAL HABITAT BUFFER ZONE (NHBZ) T PROPOSED SLOPES A LOT A B LOT B G LOT (GARDEN)G T LOT (TRANSITIONAL)T MA T C H L I N E - S E E S H E E T G6 MATCHLINE - SEE SHEET G2 MA T C H L I N E - S E E S H E E T G4 G6G5G4 G3G2G1 CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R 1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 2 RE C O R D D R A W I N G BP M 03 / 2 5 / 2 5 BLUE INDICATES REVISED GRADING THAT WAS TRIGGERED BY PROSPECT ENERGY NOT COMPLETING THEIR SCOPE, COYOTE RIDGE FIXED ISSUE ON 03/24/2025 RAIN GARDEN 2 WAS REINSTALLED BY PROSPECT ENERGY CONTRACTORS. CITY OF FORT COLLINS WAS RESPONSIBLE FOR VERIFYING IT WAS INSTALLED CORRECTLY. 64.1 0 67.54 62. 3 2 65. 0 0 61 . 1 8 63.53 64.12 55.20 71.92 55 . 4 5 61.6161.97 63 . 2 8 70.23 73.04 73 . 1 0 DEPTH GAUGE 68. 5 0 (63.42) 68. 5 4 68.59 56.94 61.88 61.74 62. 9 4 (7 1 . 5 9 ) 71 . 7 8 71.7 8 64. 2 1 54.6 9 54 . 5 0 61.52 54.50 55.4 9 56 . 6 3 58.00 58.00 54 . 9 3 56.64 54.5 0 61 . 4 9 61 . 9 2 61 . 9 2 57. 6 8 56. 3 2 STORM LINE A SEE SHEET ST1 / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / XXXXXXXX E E E E E E E E E E E E E E E E E E E E E E / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / X X X X X X X X X X X X X X X X X X V.P. X X X X ST / / / / / / / / / / / / / / / / / / / / / / / / MGAS X X X X X OH E OH E OH E OH E OH E OH E OH E OH E OH E OH E OH E / / / / / / / / ST ST ST ST / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / E E E E E E W W W W W W W W W W W W W W W FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO FO G G G G G G G G G G G G G G G G G G G G G G IR R IR R TU R N B E R R Y R O A D LOT 5 LOT 1 BLOCK 3 SERRAMONTE HIGHLANDS (LARIMER COUNTY) 72' ROW 50' -EOP 30' SANITARY EASEMENT 15' UTILITY EASEMENT (73.9 3 ) (73 . 9 3 ) DEPTH GAUGE (63.42) TRACT C ACCESS & DRAINAGE EASEMENT (7 1 . 5 9 ) (73 . 9 7 ) (73.9 2 ) 78.7' 10 ' 20' ACCESS DRIVE STORM LINE A SEE SHEET ST1 5054.67 AB 505 4 . 7 3 AB505 4 . 9 3 AB 5055 . 1 7 AB 50 5 5 . 5 1 AB 5055.81 AB 5056.13 AB 5056.46 AB 5056 . 8 9 AB 5057.34 AB 5057.87 AB 5058.32 AB 5058.91 AB 5059.51 AB 506 0 . 1 7 AB 5060 . 6 8 AB 506 1 . 3 4 AB 505 6 . 7 7 AB 5058.08 AB 5059.69 AB 5060.56 AB 5061.44 AB 5061.81 AB 5062.37 AB 5063.24 AB 5063 . 7 8 AB 506 4 . 0 9 AB 5064.43 AB 506 5 . 2 2 AB 5065.70 AB 5066.33 AB 50 6 6 . 9 4 AB 5067.38 AB 5061.5 5 AB 506 4 . 5 1 506 3 . 4 2 AB 506 3 . 5 9 AB 50 6 4 . 6 0 AB 506 5 . 5 2 AB 506 7 . 4 5 AB506 7 . 4 7 AB 5068 . 0 7 AB 5068 . 1 1 AB 506 8 . 6 0 AB 50 6 9 . 2 4 AB 506 9 . 8 8AB 507 0 . 3 3 AB 506 9 . 8 0 AB 50 7 0 . 1 2 AB 507 0 . 7 9 AB 50 7 0 . 7 5 AB 50 7 0 . 8 4 AB 5070 . 5 5 AB 5069.97 AB 5069.79 AB 5071.1 5 AB 5072 . 6 9 AB 5074.27 AB 5076.13 AB 5075.94 AB 507 6 . 3 8 AB 507 5 . 3 9 AB 5075.64 AB 507 4 . 6 4 AB 50 7 4 . 3 2 AB 507 3 . 8 4 AB 5074.58 AB 5073 . 8 5 AB 5072. 6 2 AB 5076. 1 7 AB 5079.79 AB 508 2 . 0 5 AB 5086 . 1 9 AB 5086.4 0 AB 508 4 . 0 4 AB 50 8 4 . 2 0 AB 50 8 6 . 1 6 AB 508 6 . 7 8 AB 5087.29 AB 508 5 . 2 4 AB 508 0 . 3 2 AB 507 8 . 0 0 AB 5069.72 AB 507 9 . 4 5 AB 5075 . 6 7 AB 5077.71 AB 5068.55 AB AB 5070.53 5063.41 5064 . 3 4 AB 2' CONCRETE PAN 2' CONCRETE PAN EXISTING PUMP HOUSE EXISTING PUMP HOUSE EXISTING WELL ROAD GRAVEL ACCESS ROAD FOR BOXELDER (SEE DETAIL 702) STORM LINE C SEE SHEET ST2 STORM LINE E SEE SHEET ST2 STORM LINE F SEE SHEET ST1 4:1 TAPPER EXISTING STORM LINE POND 1 G6 GR A D I N G P L A N 13 NORTH ( IN FEET ) 0 1 INCH = 40 FEET 40 40 80 120 Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 KEYMAP DOUGLAS RD TU R N B E R R Y R D LEGEND: 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.REFER TO THE PLAT FOR LOT AREAS, TRACT SIZES, EASEMENTS, LOT DIMENSIONS, UTILITY EASEMENTS, OTHER EASEMENTS, AND OTHER SURVEY INFORMATION. 3.ALL CURB SPOTS SHOWN ARE FLOWLINE ELEVATIONS. ALL OTHER SPOTS ARE FINISHED GRADE ELEVATIONS UNLESS OTHERWISE NOTED. 4.THE TOP OF FOUNDATION ELEVATIONS SHOWN ARE THE MINIMUM ELEVATIONS REQUIRED FOR PROTECTION FROM THE 100-YEAR STORM. 5.CROSSPANS ALONG PUBLIC STREETS AT THE INTERSECTION OF PRIVATE DRIVES SHALL HAVE CONCRETE EXTENDED TO THE RIGHT-OF-WAY LINE. 6.ALL PROJECT DATA IS ON THE CITY OF FORT COLLINS VERTICAL DATUM; NAVD 88 (UNADJUSTED). SEE COVER SHEET FOR BENCHMARK REFERENCES. 7.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 8.NO TREES SHALL BE REMOVED DURING THE SONGBIRD NESTING SEASON (FEBRUARY 1 TO JULY 31) WITHOUT FIRST HAVING A PROFESSIONAL ECOLOGIST OR WILDLIFE BIOLOGIST COMPLETE A NESTING SURVEY TO IDENTIFY ANY ACTIVE NESTS EXISTING ON THE PROJECT SITE. THE SURVEY SHALL BE SENT TO THE CITY ENVIRONMENTAL PLANNER. IF ACTIVE NESTS ARE FOUND, THE CITY CITY WILL COORDINATE WITH RELEVANT STATE AND FEDERAL REPRESENTATIVES TO DETERMINE WHETHER ADDITIONAL RESTRICTIONS ON TREE REMOVAL AND CONSTRUCTION APPLY. 9.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORT FOR TEMPORARY CONTROL MEASURES AND CONSTRUCTION SEQUENCING THAT SHALL BE USED TO PREVENT LOADING OF THIS DRAINAGE FACILITY WITH SEDIMENT DURING CONSTRUCTION. 36.25 (36.25) 2.0% NOTES: W LOT (WALK-OUT) EXISTING SPOT ELEVATION PROPOSED SPOT ELEVATION PROPOSED EASEMENT EXISTING RIGHT OF WAY PROPOSED LOT LINE PROPERTY BOUNDARY PROPOSED CURB AND GUTTER PROPOSED SWALE EXISTING CONTOUR PROPOSED CONTOUR PROPOSED STORM INLET PROPOSED STORM SEWER EXISTING STORM SEWER PROPOSED RIGHT OF WAY NATURAL HABITAT BUFFER ZONE (NHBZ) T PROPOSED SLOPES A LOT A B LOT B G LOT (GARDEN)G T LOT (TRANSITIONAL)T MATCHLINE - SEE SHEET G3 MA T C H L I N E - S E E S H E E T G5 G3 G6G5G4 G2G1 CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R 1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 V.P. X W W W W W W W 14 " W 1 9 7 6 ( A C ) FO FO FO FO FO FO FO G G G G G G G IR R IR R IR R IR R 15 " S S 15 " S S 15 " S S 15 " S S 15 " S S SD SD SD SD SD 16 " W 16 " W 16 " W 16 " W 16 " W 16 " W SD FES A1 STA 10+00.00 N: 149389.48 E: 205496.52 54.45 LF 24" RCP @ 5.00% OUTLET A4 STA 11+80.46 N: 149403.60 E: 205317.59 NO . 8 D I T C H NO . 8 D I T C H DEPTH GAUGE SUBDRAIN B SEE SHEET SD2 TU R N B E R R Y R O A D 72' R.O.W 15 ' U T I L I T Y E A S E M E N T SANITARY OFFSITE SEWER SEE SHEET OS3 SUBDRAIN A SEE SHEET SD1 STORM LINE B SEE SHEET ST2 LOT 1LOT 2LOT 3 BLOCK 3 TRACT C ACCESS & DRAINAGE EASEMENT 2' CONCRETE PAN POND 1 TURNBERRY RD. WATER LINE SEE "UTILITY PLANS FOR COUNTRY CLUB RESERVE - OFFSITE WATER LINES" RIP-RAP (TYPE M) TO BE INSTALLED FROM CONCRETE RUNDOWN TO BOTTOM OF THE NO. 8 DITCH (10'x10'). CONTRACTOR TO PLACE GEOFABRIC DOWN PRIOR TO TYPE M RIP-RAP. ADDITIONALLY, CONTRACTOR TO INSTALL A 6" LAYER OF 3" MINUS (TYPE II) BEDDING BETWEEN TYPE M RIP-RAP AND GEOFABRIC. 29.10 LF 24" RCP @ 0.50% STRM MH A2 STA 11+19.70 N: 149403.02 E: 205378.35 INLET A3 STA 11+48.79 N: 149403.26 E: 205349.26 31.67 LF 24" RCP @ 0.48% 16" ELCO WATERLINE (SEE PLANS BY OTHERS) GAS AND OIL BUFFER 6'Ø DROP MH A STA 10+54.45 N: 149402.26 E: 205443.60 65.25 LF 24" RCP @ 0.50% 20' DRAINAGE EASEMENT 10' 10' CONTRACTOR TO PROTECT DROP SUBMERGED STRUCTURE OUTLET FROM DAMAGE DURING CONSTRUCTION 20' 20'x10'x6" (LxWxD) CONCRETE RUNDOWN (SEE DETAIL ON THIS SHEET) (45.9% ) 10' FROM EOA ST ST ST ST ST ST STST ST ST ST ST ST ST ST 5030 5035 5040 5045 5050 5055 5060 5065 5070 5075 5080 5085 5030 5035 5040 5045 5050 5055 5060 5065 5070 5075 5080 5085 9+5010+0011+0012+0013+00 OU T L E T A 4 ST A 1 1 + 8 0 . 4 6 FL . E L 5 0 5 8 . 0 ± IN V . O U T 5 0 5 4 . 5 0 ( E ) 54.45 LF 24" RCP @ 5.00% FE S A 1 ST A 1 0 + 0 0 . 0 0 IN V . 5 0 4 5 . 7 8 ( W ) PROPOSED GROUND EXISTING GROUND 2.6' ST R M M H A 2 ST A 1 1 + 1 9 . 7 0 RI M 5 0 7 0 . 6 ± IN V . I N 5 0 5 4 . 2 0 ( W ) IN V . I N 5 0 5 4 . 2 0 ( N W ) IN V . I N 5 0 5 4 . 2 0 ( S W ) IN V . O U T 5 0 5 4 . 2 0 ( E ) 29.10 LF 24" RCP @ 0.50% 16" PVC WATERLINE STA.=10+94.61 INV.=5064.30 EXISTING 14" AC WATERLINE STA.=11+03.36 INV.=5065.34 15" PVC SANITARY SEWER STA.=10+84.45 INV.=5058.91 IN L E T A 3 ST A 1 1 + 4 8 . 7 9 RI M 5 0 6 5 . 8 ± IN V . I N 5 0 5 4 . 3 5 ( W ) IN V . O U T 5 0 5 4 . 3 5 ( E ) 31.67 LF 24" RCP @ 0.48% 65.25 LF 24" RCP @ 0.50% 6' Ø D R O P M H A ST A 1 0 + 5 4 . 4 5 RI M 5 0 6 8 . 2 ± IN V . I N 5 0 5 3 . 8 8 ( W ) IN V . O U T 5 0 4 8 . 5 0 ( E ) CONCRETE RUNDOWN TO TOE OF SLOPE (20'x10'x6") TYPE M RIPRAP (10'x10') EXISTING 18" IRRIGATION STA.=10+91.18 INV.=5060.72 XXXXXXXXXXXXX XX OH E OH E OH E OH E OH E / / / / / / / / ST ST ST ST / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / W W W W W W W / / / / / / / / W FO FO FO FO FO FO FO G G G G G G G 15 " S S 15 " S S 15 " S S 15 " S S 15 " S S 8" SS 8" SS 8" SS 8" SS 8" SS 8" SS SD SD SD SD SD SD SD SD 16 " W 16 " W 16 " W 16 " W 16 " W 16 " W TU R N B E R R Y R O A D EXISTING 24" CMP 2' CONCRETE PAN POND 1 SANITARY SEWER A SEE SHEET SS1 SUBDRAIN A SEE SHEET SD1 SANITARY OFFSITE SEWER SEE SHEET OS3 72' R.O.W EXISTING 14" ELCO AC WATERLINE 30' SANITARY SEWER EASEMENT TO BE DEDICATED BY SEPARATE DOCUMENT 15 ' U T I L I T Y E A S E M E N T STORM LINE E SEE SHEET ST2 TRACT C ACCESS & DRAINAGE EASEMENT FES F1 STA 10+60.12 N: 148738.90 E: 205350.08 FES F2 STA 10+00.00 N: 148787.89 E: 205315.23 60.12 LF 24" HDPE @ 2.00% TURNBERRY RD. WATER LINE SEE "UTILITY PLANS FOR COUNTRY CLUB RESERVE - OFFSITE WATER LINES" GAS AND OIL BUFFER STSTSTST ST ST ST ST ST ST ARV H2O VE NT 5045 5050 5055 5060 5065 5070 5075 5080 5085 5045 5050 5055 5060 5065 5070 5075 5080 5085 9+50 10+00 11+00 11+50 FE S F 2 ST A 1 0 + 0 0 . 0 0 IN V . 5 0 6 1 . 7 4 ( S E ) 60.12 LF 24" HDPE @ 2.00% FE S F 1 ST A 1 0 + 6 0 . 1 2 IN V . 5 0 6 2 . 9 4 ( N W ) PROPOSED GROUND EXISTING GROUND 8" PVC SANITARY SEWER STA.=10+45.30 INV.=5056.60 Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 ST1 PL A N A N D P R O F I L E ST O R M L I N E A A N D F 40 CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R STORM LINE A KEYMAP DOUGLAS RD TU R N B E R R Y R D PROFILE SCALE: NORTH STRM A 8" W EXISTING WATER MAIN PROPOSED WATER MAIN PROPOSED STORMLINE LEGEND: NOTES: W OHE OHE T E EXISTING STORM SEWER ST PROPOSED ELECTRIC EXISTING TELEPHONE EXISTING OVERHEAD ELECTRIC PROPOSED UNDERDRAIN SUBDRAIN CLEANOUT SS PROPOSED CURB & GUTTER PROPOSED SANITARY SEWER PROPOSED FIRE HYDRANT PROPOSED LOTLINE RIGHT OF WAY PROPERTY BOUNDARY SS PROPOSED SUBDRAIN UD SD EXISTING FIRE HYDRANT PROPOSED STORMLINE NATURAL HABITAT BUFFER ZONE (NHBZ) EASEMENT LINE EXISTING SANITARY SEWER GEXISTING GAS 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL STORM DRAINS, SANITARY SEWER MAINS, WATER MAINS, AND SERVICES. 3.PIPE LENGTHS ARE CALCULATED FROM THE CENTER OF MANHOLES AND STRUCTURES. SPECIFIED LENGTH OF PIPE INCLUDES THE LAYING LENGTH OF FLARED END SECTIONS. 4.ALL RCP SHALL BE CLASS III OR GREATER. PIPE MATERIAL, BEDDING, AND INSTALLATION WITHIN PUBLIC RIGHTS-OF-WAY SHALL BE GOVERNED BY THE CITY OF FORT COLLINS. ALTERNATES (SUCH AS ADS N-12 OR HP SANITITE) OUTSIDE OF THE R.O.W. SHALL BE APPROVED IN ADVANCE BY THE ENGINEER. ALL JOINTS SHALL BE 'WATERTIGHT' USING APPROPRIATE GASKETS OR JOINT WRAPS (PER ASTM C443 FOR RCP AND PER ASTM F477 / D3212 FOR PLASTIC PIPE). 5.CONTRACTOR SHALL SHALL CONFIRM THAT MANHOLE DIAMETERS ARE SUFFICIENT FOR THEIR PROPOSED METHODS OF INSTALLATION (i.e., WITHIN PRE-CASTER'S TOLERANCES, ETC.). 6.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 7.ALL SUBDRAINS ARE TO BE PRIVATELY OWNED AND MAINTAINED BY THE OWNER. 8.SEE STORM LINE PROFILES FOR CLARIFICATION ON OWNERSHIP AND MAINTENANCE RESPONSIBILITIES. 9.RAIN GARDENS AND PONDS ARE TO BE PRIVATELY OWNED AND MAINTAINED BY THE OWNER. 10.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORTS FOR TEMPORARY AND PERMANENT CONTROL MEASURES. 11.SEE DETAIL SHEET EC3 FOR RIPRAP SCHEDULE. INLET SUMMARY INLET ID TYPE A3 TYPE C C1 CURB INLET-4 FT D1 DOUBLE CURB INLET D2 DOUBLE CURB INLET D3 DOUBLE CURB INLET D5 CURB INLET-4 FT D6 CURB INLET-4 FT E1 CURB INLET-4 FT ( IN FEET ) 0 1 INCH = 50 FEET 50 50 100 150 PROFILE SCALE: STORM LINE F STRM F PUBLICLY OWNED AND MAINTAINED PUBLICLY OWNED AND MAINTAINED 2 11 . 2 1 . 2 0 2 2 ST O R M L I N E A O U T F A L L I N T O N O . 8 D I T C H BP M 1 PRIVATELY OWNED AND MAINTAINED 2 2 GEOTECHNICAL REQUIREMENT NOTES: 1.COMPACTION TESTING, MAXIMUM LIFT, AND SOIL KEY SPECIFICATIONS FOR BACKFILLING AROUND 6'Ø DROP MH A SHALL FOLLOW REQUIREMENTS SET FORTH BY THE MODIFIED EMBANKMENT/EARTHWORK RECOMMENDATION (SEE NOTE 3) ORIGINALLY SET FORTH BY "PRELIMINARY GEOTECHNICAL EXPLORATION - BOMA FARM DEVELOPMENT" BY EARTH ENGINEERING CONSULTANTS, INC. TO ENSURE PROPER REBUILDING OF THE EMBANKMENT. 2.SEE COVER SHEET OF APPROVED DRAWINGS FOR ADDITIONAL INFORMATION ABOUT "PRELIMINARY GEOTECHNICAL EXPLORATION - BOMA FARM DEVELOPMENT" 3."THE SITE LEAN CLAY SOILS COULD BE USED FOR BACKFILLING IN OVEREXCAVATION BACKFILL AREAS AND THE EMBANKMENTS ASSOCIATED WITH THE No. 8 DITCH. OTHER APPROVED FILL MATERIALS WHICH ARE FREE FROM ORGANIC MATTER AND DEBRIS AND CONTAINING SUFFICIENT FINES TO PREVENT PONDING OF WATER IN THE SUBGRADES COULD ALSO BE USED. PLACEMENT OF BACKFILL MATERIAL WITHIN THE No. 8 DITCH EMBANKMENT ZONE SHOULD BE PLACED IN LOOSE LIFTS NOT TO EXCEED 9 INCHES THINK WITH MOISTURE CONTENTS IN THE RANGE OF -1 TO +3% OF STANDARD PROCTOR OPTIMUM MOISTURE CONTENT AND COMPACTED TO AT LEAST 95% OF STANDARD PROCTOR MAXIMUM DRY DENSITY AS DETERMINED BY (ASTM SPECIFICATION D698) TESTING PROCEDURES. 4.NOTE 3 CONFORMS TO LCUASS AND ASTM REQUIREMENTS. 4 2 10' 6" 1"CONCRETE 1.67%1.67% 6x6 - W14xW14 CONCRETE RUNDOWN STANDARD CONCRETE NOTES NOTE: PROVIDE CONTROL JOINTS AT 10' INTERVALS Ø24" INVERT = 5045.78 6" 24" 6" (TYP.) KEY TRENCHES (TYP.) 10' 10' EXTEND REINFORCEMENT TO KEY TRENCHES 24" RCP NATIVE SOIL TYPE M RIP-RAP TYPE II BEDDING 6" OVERLAP (MIN.) 50 6 7 . 7 5 ± 50 5 4 . 5 9 ( W ) 50 5 4 . 5 9 ( E ) 50 7 0 . 2 9 ± 50 5 8 . 1 1 ± 50 5 4 . 6 4 ( E ) 50 5 4 . 1 1 ( E ) 50 5 4 . 2 7 ( W ) 29.24 LF @ 0.17% 24.01 LF @ 1.79% 24.01 LF @ 1.79% 29.24 LF @ 0.17% 1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 74.03 LF @ 0.89% 46.37 LF @ 8.19% 74.03 LF @ 0.89% 46.37 LF @ 8.19% 50 6 6 . 8 0 ± 50 5 3 . 4 5 ( W ) 50 4 7 . 5 5 ( W ) 50 4 3 . 7 5 ( W ) 55.51 LF @ 2.02% 50 6 1 . 8 8 ( S E ) 50 6 3 . 0 0 ( N W ) 50 5 4 . 2 7 ( N W ) 50 5 4 . 2 7 ( S W ) / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / V. P . X WWWWWWWW14"W 1976 (AC) FO FO FO FO FO FO FO FO G G G G G G G G IRR IRRIRRIRRIRRIRR HEADWALL B1 STA 12+08.09 N: 149697.27 E: 205337.34 FES B3 STA 10+00.00 N: 149489.20 E: 205334.99 143.29 LF 24" RCP @ 0.50% 15" SS15" SS15" SS15" SS15" SS SD SD SD 8" W 8" W 8" W 8" W 8" S S 8" S S 8" S S SD SD SD SD 16" W16" W16" W16" W16" W16" W SD TURNBERRY ROAD LOT 10 LOT 1 BLOCK 3 BLOCK 2 SUBDRAIN B SEE SHEET SD2 SANITARY SEWER OFFSITE SEE SHEET OS4 SANITARY SEWER B SEE SHEET SS5 30' - 53' R.O.W 9' U T I L I T Y E A S E M E N T 9' U T I L I T Y E A S E M E N T 15' UTILITY EASEMENT 72' R.O.W 50' -EOP EXISTING 14" ELCO AC WATERLINE (TO BE ABANDONED) LOT 8 LOT 9 LOT 2 LOT 3 RIPRAP 2' CONCRETE PAN TRACT C ACCESS & DRAINAGE EASEMENT NO. 8 DITCH TURNBERRY RD. WATER LINE SEE "UTILITY PLANS FOR COUNTRY CLUB RESERVE - OFFSITE WATER LINES" STRM MH B2 STA 11+43.29 N: 149632.48 E: 205336.60 64.79 LF 24" RCP @ 0.50% PROPOSED WALL BA L L Y N E A L D R . PROPOSED 8" PVC WATER LINE STSTSTSTST FL = 5 0 6 4 . 8 2 FL = 5 0 6 5 . 9 5 FL = 5 0 6 6 . 6 7 65 . 8 L F 2 4 " R C P @ 0 . 4 3 % HYD STSTSTSTST 138.8 LF 24" RCP @ 0.61%99.5 LF 24" RCP @ 0.72% FL = 5 0 6 4 . 8 2 FL = 5 0 6 6 . 6 7 65 . 8 L F 2 4 " R C P @ 0 . 4 3 % W W W W STSTSTSTST ST O R M I N L E T FL = 5 0 6 6 . 6 7 65 . 8 L F 2 4 " R C P @ 0 . 4 3 % 47 . 2 6 L F 2 4 " RC P @ 8 . 0 0 % HYD STSTST 138.8 LF 24" RCP @ 0.61% FL = 5 0 6 4 . 8 2 ST O R M M H RI M = 5 0 7 1 . 9 8 BT M = 5 0 6 5 . 6 7 65 . 8 L F 2 4 " R C P @ 0 . 4 3 % 74 . 0 3 L F 2 4 " RC P @ 0 . 8 9 % ST 66 . 7 L F 6 " H D P E C S h2 o C S h2 o C S h2 o S h2 o CS h2 o CS h2 o C S h2 o ST O R M I N L E T BT M = 5 0 5 4 . 4 9 ST O R M M H RI M = 5 0 7 0 . 2 9 IN V = 5 0 5 4 . 2 7 ( N W , S W , W ) IN V O U T = 5 0 5 4 . 1 3 ( E ) HYD 5055 5060 5065 5070 5075 5080 5085 5090 5055 5060 5065 5070 5075 5080 5085 5090 9+5010+0011+0012+0012+50 143.29 LF 24" RCP @ 0.50% FE S B 3 ST A 1 0 + 0 0 . 0 0 IN V . 5 0 6 5 . 1 9 ( N ) HE A D W A L L B 1 ST A 1 2 + 0 8 . 0 9 IN V . 5 0 6 6 . 2 3 ( S ) EXISTING GROUND PROPOSED GROUND 8" PVC STA.=11+70.50 INV.=5063.61 (WATER LINE LOWERING) 8" PVC SANITARY SEWER STA.=11+60.50 INV.=5060.64 64.79 LF 24" RCP @ 0.50% ST R M M H B 2 ST A 1 1 + 4 3 . 2 9 FL . E L 5 0 7 2 . 2 ± IN V . I N 5 0 6 5 . 9 1 ( N ) IN V . O U T 5 0 6 5 . 9 1 ( S ) 6" PVC STORM STA.=11+58.50 INV.=5058.53 / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / X X X X W W W W W W W 14 " W 1 9 7 6 ( A C ) FO FO FO FO FO FO FO G G G G G G G IR R 50' -EOPPOND 1 15 " S S 15 " S S 15 " S S 15 " S S 15 " S S 15 " S S SD SD SD SD SD SD SD 16 " W 16 " W 16 " W 16 " W 16 " W 16 " W INLET C1 STA 10+91.33 N: 149150.60 E: 205380.76 91.33 LF 15" RCP @ 1.45% FES C2 STA 10+00.00 N: 149151.63 E: 205289.43 SANITARY OFFSITE SEWER SEE SHEET OS3 TU R N B E R R Y R O A D 15 ' U T I L I T Y E A S E M E N T RIPRAP 2' CONCRETE PAN SUBDRAIN B SEE SHEET SD2 TRACT C ACCESS & DRAINAGE EASEMENT TURNBERRY RD. WATER LINE SEE "UTILITY PLANS FOR COUNTRY CLUB RESERVE - OFFSITE WATER LINES" 72' ROW ST FL=5062.99 FL=5061.14 84.0 LF 15" RCP @ 2.20% ST FL=5062.99 FL=5061.14 84.0 LF 15" RCP @ 2.20% ST FL=5062.99 FL=5061.14 84.0 LF 15" RCP @ 2.20% FL=5054.64 29.2 LF 24" RCP @ 0.51% 24.0 LF 24" RCP @ 1.58% ST FL=5062.99 FL=5061.14 84.0 LF 15" RCP @ 2.20% STORM MH RIM=5070.29 BTM=5054.11 D ST ST ST ST ST ST ST 46.4 LF 6" HDPE 5055 5060 5065 5070 5075 5080 5085 5090 5055 5060 5065 5070 5075 5080 5085 5090 9+50 10+00 11+00 11+50 EXISTING GROUND PROPOSED GROUND 91.33 LF 15" R C P @ 1 . 4 5 % FE S C 2 ST A 1 0 + 0 0 . 0 0 IN V . 5 0 6 1 . 7 0 ( E ) IN L E T C 1 ST A 1 0 + 9 1 . 3 3 FL . E L 5 0 6 9 . 0 ± IN V . O U T 5 0 6 3 . 0 3 ( W ) 6" PVC SUBDRAIN STA.=10+55.33 INV.=5055.46 5050 5055 5060 5065 5070 5075 5080 5085 5050 5055 5060 5065 5070 5075 5080 5085 9+50 10+00 11+00 11+50 61.52 LF 15" RCP @ 3.00% IN L E T E 1 ST A 1 0 + 6 1 . 5 2 FL . E L 5 0 6 7 . 6 ± IN V . O U T 5 0 6 3 . 6 7 ( W ) FE S E 2 ST A 1 0 + 0 0 . 0 0 IN V . 5 0 6 1 . 8 3 ( E ) EXISTING GROUND PROPOSED GROUND / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / XXXXXXXX XX OH E OH E OH E OH E OH E / / / / / / / / / / / / / / / // / / / / / / // / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / // / / / / / / // / / / / / / / W W W W W W W / / / / / / / / W FO FO FO FO FO FO FO G G G G G G G 15 " S S 15 " S S 15 " S S 15 " S S 15 " S S 8" SS 8" SS 8" SS 8" SS SD SD SD SD SD SD 16 " W 16 " W 16 " W 16 " W 16 " W 16 " W STORM LINE F SEE SHEET ST1 TRACT C ACCESS & DRAINAGE EASEMENT 2' CONCRETE PAN POND 1 SANITARY SEWER A SEE SHEET SS1 SUBDRAIN A SEE SHEET SD1 SANITARY OFFSITE SEWER SEE SHEET OS3 72' R.O.W EXISTING 14" ELCO AC WATERLINE (TO BE ABANDONED) TU R N B E R R Y R O A D 30' SANITARY SEWER EASEMENT TO BE DEDICATED BY SEPARATE DOCUMENT FES E2 STA 10+00.00 N: 148808.58 E: 205315.38 61.52 LF 15" RCP @ 3.00% INLET E1 STA 10+61.52 N: 148807.88 E: 205376.89 15 ' U T I L I T Y E A S E M E N T TURNBERRY RD. WATER LINE SEE "UTILITY PLANS FOR COUNTRY CLUB RESERVE - OFFSITE WATER LINES" ST FL=5063.17 FL=5061.71 559. LF 15" RCP @ 2.61% ST FL=5063.17 FL=5061.71 559. LF 15" RCP @ 2.61% ST FL=5063.17 FL=5061.71 559. LF 15" RCP @ 2.61% ST FL=5063.17 FL=5061.71 559. LF 15" RCP @ 2.61% ST ST ST ST FL=5063.00 FL=5061.88 55.5 LF 24" HDPE @ 2.02% 50 9 . 7 L F 6 " H D P E ST ST FL=5063.00 FL=5061.88 55.5 LF 24" HDPE @ 2.02% AR V H2O VE NT KEYMAP DOUGLAS RD TU R N B E R R Y R D Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 ST2 PL A N A N D P R O F I L E ST O R M L I N E B , C , A N D E 41 CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R PROFILE SCALE: NORTH STORM LINE B STRM B ( IN FEET ) 0 1 INCH = 50 FEET 50 50 100 150 PROFILE SCALE: NORTH PROFILE SCALE: 8" W EXISTING WATER MAIN PROPOSED WATER MAIN PROPOSED STORMLINE LEGEND: NOTES: W OHE OHE T E EXISTING STORM SEWER ST PROPOSED ELECTRIC EXISTING TELEPHONE EXISTING OVERHEAD ELECTRIC PROPOSED UNDERDRAIN SUBDRAIN CLEANOUT SS PROPOSED CURB & GUTTER PROPOSED SANITARY SEWER PROPOSED FIRE HYDRANT PROPOSED LOTLINE RIGHT OF WAY PROPERTY BOUNDARY SS PROPOSED SUBDRAIN UD SD EXISTING FIRE HYDRANT PROPOSED STORMLINE NATURAL HABITAT BUFFER ZONE (NHBZ) EASEMENT LINE EXISTING SANITARY SEWER GEXISTING GAS 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL STORM DRAINS, SANITARY SEWER MAINS, WATER MAINS, AND SERVICES. 3.PIPE LENGTHS ARE CALCULATED FROM THE CENTER OF MANHOLES AND STRUCTURES. SPECIFIED LENGTH OF PIPE INCLUDES THE LAYING LENGTH OF FLARED END SECTIONS. 4.ALL RCP SHALL BE CLASS III OR GREATER. PIPE MATERIAL, BEDDING, AND INSTALLATION WITHIN PUBLIC RIGHTS-OF-WAY SHALL BE GOVERNED BY THE CITY OF FORT COLLINS. ALTERNATES (SUCH AS ADS N-12 OR HP SANITITE) OUTSIDE OF THE R.O.W. SHALL BE APPROVED IN ADVANCE BY THE ENGINEER. ALL JOINTS SHALL BE 'WATERTIGHT' USING APPROPRIATE GASKETS OR JOINT WRAPS (PER ASTM C443 FOR RCP AND PER ASTM F477 / D3212 FOR PLASTIC PIPE). 5.CONTRACTOR SHALL SHALL CONFIRM THAT MANHOLE DIAMETERS ARE SUFFICIENT FOR THEIR PROPOSED METHODS OF INSTALLATION (i.e., WITHIN PRE-CASTER'S TOLERANCES, ETC.). 6.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 7.ALL SUBDRAINS ARE TO BE PRIVATELY OWNED AND MAINTAINED BY THE OWNER. 8.SEE STORM LINE PROFILES FOR CLARIFICATION ON OWNERSHIP AND MAINTENANCE RESPONSIBILITIES. 9.RAIN GARDENS AND PONDS ARE TO BE PRIVATELY OWNED AND MAINTAINED BY THE OWNER. 10.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORTS FOR TEMPORARY AND PERMANENT CONTROL MEASURES. 11.SEE DETAIL SHEET EC3 FOR RIPRAP SCHEDULE. INLET SUMMARY INLET ID TYPE A3 TYPE C C1 CURB INLET-4 FT D1 DOUBLE CURB INLET D2 DOUBLE CURB INLET D3 DOUBLE CURB INLET D5 CURB INLET-4 FT D6 CURB INLET-4 FT E1 CURB INLET-4 FT NORTH STORM LINE C STORM LINE E STRM C STRM E PUBLICLY OWNED AND MAINTAINED PUBLICLY OWNED AND MAINTAINED PUBLICLY OWNED AND MAINTAINED 50 7 1 . 9 8 ± 50 6 5 . 6 7 ( N ) 50 6 5 . 6 7 ( S ) 50 6 4 . 8 2 ( N ) 50 6 5 . 9 5 ( S ) 65.09 LF @ 0.43%139.51 LF @ 0.61% 84.03 LF @ 2.20% 55.86 LF @ 3.62% 139.51 LF @ 0.61% 65.09 LF @ 0.43% 84.03 LF @ 2.20% 55.86 LF @ 3.62% 50 6 2 . 9 9 ( W ) 50 6 1 . 1 4 ( E ) 50 6 3 . 7 3 ( W ) 50 6 1 . 7 1 ( E ) 1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 THESE RECORD DRAWINGS, PRODUCED BY NORTHERN ENGINEERING SERVICES, INC., ARE BASED IN WHOLE, OR IN PART, UPON INFORMATION PROVIDED BY OTHERS. NORTHERN ENGINEERING SERVICES, INC. ASSUMES NO LIABILITY FOR THE ACCURACY OR COMPLETENESS OF THIS INFORMATION. RECORD DRAWING UD UD UD 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 12" W 8" W 8" W 8" W 8" S S SD W W W W W E E E E E / / / / / / / / / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / FES M FES TELE / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / XXX / / / / / / / // / / / / / / // / / / / / / / FESM FES / / / / / / / // / / / / / / // / / / / / / // / / / / / / // / / / / / / / XXXXX E INLET D1 STA 21+56.93 N: 150037.66 E: 203897.99 INLET D2 STA 17+31.93 N: 150032.86 E: 204322.96 INLET D6 STA 12+04.26 N: 149986.37 E: 204809.19 INLET D5 STA 12+34.93 N: 149986.71 E: 204778.52 INLET D3 STA 14+04.52 N: 150029.16 E: 204650.35 STRM MH D4 STA 13+63.52 N: 149988.17 E: 204649.94 FES D7 STA 10+00.00 N: 149971.92 E: 205012.93 425.00 LF 15" RCP @ 0.30%327.41 LF 15" RCP @ 0.50% 41.00 LF 15" RCP @ 0.48% 128.59 LF 15" HDPE @ 0.48% 30.67 LF 15" RCP @ 0.50% 204.26 LF 15" HDPE @ 0 . 5 0 % E. DOUGLAS ROAD E. DOUGLAS ROAD WI N G E D F O O T D R . POND 2 (WETLANDS) SWALE PRIVATE WATER LINE (CONTRACTOR TO FIELD LOCATE PRIOR TO MOBILIZATION) 48' -EOP 78' R.O.W 15' UTILITY EASEMENT 78' R.O.W RIPRAP 30' - 53' R.O.W TRACT A DRAINAGE EASEMENT TRACT B ACCESS & DRAINAGE EASEMENT LOT 1 LOT 23 LOT 24 LOT 2 LOT 3BLOCK 1 BLOCK 2 NATURAL HABITAT BUFFER ZONE (NHBZ) SWALE NATURAL HABITAT BOUNDARY ZONE SANITARY SEWER B4 SEE SHEET SS8RAIN GARDEN 3 DOUGLAS RD. WATER LINE SEE "UTILITY PLANS FOR COUNTRY CLUB RESERVE - OFFSITE WATER LINES" 10.61 LF 15" RCP @ 5.00% (PRIVATELY OWNED AND MAINTAINED) OUTLET D4 (PRIVATELY OWNED AND MAINTAINED) INV. OUT=5077.35 (E) FG=5079.46 WINGWALL PRIVATE ELECTRIC LINE (CONTRACTOR TO FIELD LOCATE PRIOR TO MOBILIZATION) UNDERDRAIN FOR RAIN GARDEN 3 PROPOSED 8" PVC WATER LINE ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST DD DD ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST CS h2o CS h2o 5065 5070 5075 5080 5085 5090 5095 5100 5065 5070 5075 5080 5085 5090 5095 5100 9+5010+0011+0012+0013+0014+0015+0016+0017+0018+0019+0020+0021+0022+00 204.26 LF 15" HDPE @ 0.50% FE S D 7 ST A 1 0 + 0 0 . 0 0 RI M 5 0 7 4 . 7 ± IN V . I N 5 0 7 3 . 2 7 ( W ) 30.67 LF 15" RCP @ 0.50% 128.59 LF 15" HDPE @ 0.48% IN L E T D 5 ST A 1 2 + 3 4 . 9 3 FL . E L 5 0 8 0 . 6 ± IN V . I N 5 0 7 4 . 4 5 ( W ) IN V . O U T 5 0 7 4 . 4 5 ( E ) IN L E T D 6 ST A 1 2 + 0 4 . 2 6 FL . E L 5 0 8 0 . 5 ± IN V . I N 5 0 7 4 . 3 0 ( W ) IN V . O U T 5 0 7 4 . 3 0 ( E ) 41.00 LF 15" RCP @ 0.48% 327.41 LF 15" RCP @ 0.50% ST R M M H D 4 ST A 1 3 + 6 3 . 5 2 RI M 5 0 8 0 . 5 ± IN V . I N 5 0 7 5 . 0 6 ( N ) IN V . I N 5 0 7 6 . 8 2 ( W ) IN V . O U T 5 0 7 5 . 0 6 ( E ) IN L E T D 3 ST A 1 4 + 0 4 . 5 2 FL . E L 5 0 8 0 . 5 ± IN V . I N 5 0 7 5 . 2 6 ( W ) IN V . O U T 5 0 7 5 . 2 6 ( S ) 425.00 LF 15" RCP @ 0.30% IN L E T D 2 ST A 1 7 + 3 1 . 9 3 FL . E L 5 0 8 1 . 0 ± IN V . I N 5 0 7 6 . 9 0 ( W ) IN V . O U T 5 0 7 6 . 9 0 ( E ) IN L E T D 1 ST A 2 1 + 5 6 . 9 3 FL . E L 5 0 8 1 . 9 ± IN V . O U T 5 0 7 8 . 1 7 ( E ) 8" PVC STA.=12+25.61 INV.=5072.00 (WATER LINE LOWERING) 1.5' Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 KEYMAP DOUGLAS RD TU R N B E R R Y R D ST3 PL A N A N D P R O F I L E ST O R M L I N E D 42 NORTH ( IN FEET ) 1 inch = ft. Feet05050 50 100 150 PROFILE SCALE: STORM LINE D PROPOSED GROUND EXISTING GROUND CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE, OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. CALL UTILITY NOTIFICATION CENTER OF COLORADO Know what'sbelow. before you dig.Call R 8" W EXISTING WATER MAIN PROPOSED WATER MAIN PROPOSED STORMLINE LEGEND: NOTES: W OHE OHE T E EXISTING STORM SEWER ST PROPOSED ELECTRIC EXISTING TELEPHONE EXISTING OVERHEAD ELECTRIC PROPOSED UNDERDRAIN SUBDRAIN CLEANOUT SS PROPOSED CURB & GUTTER PROPOSED SANITARY SEWER PROPOSED FIRE HYDRANT PROPOSED LOTLINE RIGHT OF WAY PROPERTY BOUNDARY SS PROPOSED SUBDRAIN UD SD EXISTING FIRE HYDRANT PROPOSED STORMLINE NATURAL HABITAT BUFFER ZONE (NHBZ) EASEMENT LINE EXISTING SANITARY SEWER GEXISTING GAS 1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES. 2.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL STORM DRAINS, SANITARY SEWER MAINS, WATER MAINS, AND SERVICES. 3.PIPE LENGTHS ARE CALCULATED FROM THE CENTER OF MANHOLES AND STRUCTURES. SPECIFIED LENGTH OF PIPE INCLUDES THE LAYING LENGTH OF FLARED END SECTIONS. 4.ALL RCP SHALL BE CLASS III OR GREATER. PIPE MATERIAL, BEDDING, AND INSTALLATION WITHIN PUBLIC RIGHTS-OF-WAY SHALL BE GOVERNED BY THE CITY OF FORT COLLINS. ALTERNATES (SUCH AS ADS N-12 OR HP SANITITE) OUTSIDE OF THE R.O.W. SHALL BE APPROVED IN ADVANCE BY THE ENGINEER. ALL JOINTS SHALL BE 'WATERTIGHT' USING APPROPRIATE GASKETS OR JOINT WRAPS (PER ASTM C443 FOR RCP AND PER ASTM F477 / D3212 FOR PLASTIC PIPE). 5.CONTRACTOR SHALL SHALL CONFIRM THAT MANHOLE DIAMETERS ARE SUFFICIENT FOR THEIR PROPOSED METHODS OF INSTALLATION (i.e., WITHIN PRE-CASTER'S TOLERANCES, ETC.). 6.THE NATURAL HABITAT BUFFER ZONE IS INTENDED TO BE MAINTAINED IN A NATIVE LANDSCAPE. PLEASE SEE SECTION 3.4.1 OF THE LAND USE CODE FOR ALLOWABLE USES WITHIN THE NATURAL HABITAT BUFFER ZONE. 7.ALL SUBDRAINS ARE TO BE PRIVATELY OWNED AND MAINTAINED BY THE OWNER. 8.SEE STORM LINE PROFILES FOR CLARIFICATION ON OWNERSHIP AND MAINTENANCE RESPONSIBILITIES. 9.RAIN GARDENS AND PONDS ARE TO BE PRIVATELY OWNED AND MAINTAINED BY THE OWNER. 10.PLEASE REFER TO THE EROSION CONTROL PLAN SHEETS AND REPORTS FOR TEMPORARY AND PERMANENT CONTROL MEASURES. 11.SEE DETAIL SHEET EC3 FOR RIPRAP SCHEDULE. INLET SUMMARY INLET ID TYPE A3 TYPE C C1 CURB INLET-4 FT D1 DOUBLE CURB INLET D2 DOUBLE CURB INLET D3 DOUBLE CURB INLET D5 CURB INLET-4 FT D6 CURB INLET-4 FT E1 CURB INLET-4 FT EXISTING PUMP HOUSE STRM D PUBLICLY OWNED AND MAINTAINED PHASE 2 PHASE 1 128.55 LF @ 0.36% 202.07 LF @ 0.50% 30.33 LF @ 0.49% 318.29 LF @ 0.46% 416.34 LF @ 0.34% 416.34 LF @ 0.34% 318.29 LF @ 0.46% 38.03 LF @ 0.50% 128.55 LF @ 0.36% 30.33 LF @ 0.49% 202.07 LF @ 0.50% 50 7 7 . 9 4 ( E ) 50 7 6 . 5 3 ( W ) 50 7 6 . 4 3 ( E ) 50 7 4 . 9 8 ( W ) 50 7 4 . 9 3 ( S ) 50 8 0 . 6 7 ± 50 7 4 . 3 7 ( W ) 50 7 4 . 3 7 ( E ) 50 8 0 . 6 2 ± 50 7 4 . 2 2 ( W ) 50 7 4 . 0 1 ( E ) 50 7 9 . 9 1 ± 50 7 6 . 7 7 ( N ) 50 7 6 . 7 7 ( W ) 50 7 4 . 8 3 ( E ) 50 7 2 . 9 9 ( W ) 38.03 LF @ 0.50%1 RE C O R D D R A W I N G SE R 11 / 0 5 / 2 2 THESE RECORD DRAWINGS, PRODUCED BY NORTHERN ENGINEERING SERVICES, INC., ARE BASED IN WHOLE, OR IN PART, UPON INFORMATION PROVIDED BY OTHERS. NORTHERN ENGINEERING SERVICES, INC. ASSUMES NO LIABILITY FOR THE ACCURACY OR COMPLETENESS OF THIS INFORMATION. RECORD DRAWING 50 8 0 . 8 2 ± 1/2" THK GALV. STEEL PLATE ORIFICE 1'-5" 1/2" Ø HOLES FOR 3/8" Ø EXPANSION BOLTS EMBEDDED 2" INTO CONCRETE WALL @ 12" O.C. MIN. INVERT ELEV. Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 100-YEAR ORIFICE PLATE602 INLET SUMMARY601 CC A A B B SECTION C-C SECTION A-A SECTION B-B WELL SCREEN FLOW CONTROL PLATE PLAN GENERAL NOTES SECTION D-D D D A A ABBREVIATIONS LEGEND A A B B SECTION A-A DETAIL "A" SECTION B-B CURB FACE ASSEMBLY DETAIL GENERAL NOTES PLAN VIEW 6 IN. STEEL DECK RING WITH 24 IN. HEAVY DENVER COVER BY MACLEAR OR APPROVED EQUAL. 6 IN. THICK SIDEWALL (TYP. BOTH SIDES) 3 FT.5 FT.3 FT. 6 IN.6 IN. BACK OF CURB FLOW LINE SEE DETAIL "A" 4 FT. OPENINGWARPED CURB & GUTTER (TYP. BOTH SIDES) 6 IN. 3 F T . - 3 I N . 17 I N . 14 IN. 11 FT. 6 IN. 2 FT.4 FT.- 6 IN. 6 IN. SEE CURB FACE ASSEMBLY DETAIL MANHOLE RUNGS-12 IN. O.C. 1% SLOPE FOR DRAINAGE 6 IN. 3 FT.-6 IN.4 FT. WARPED GUTTER DEPRESSED GUTTER NORMAL FLOW LINE TOP OF GUTTER ALTERED FLOW LINE 6 IN.6 IN. 1% SLOPE FOR DRAINAGE 6 IN. WALL 3 IN. RAD.6 IN. EXTEND CHANNEL TO OUTSIDE EDGE OF WALL 10 IN. EMBEDMENT 8 8.5 FLUSH WITH CURB FACE NTS 1 1/2 IN. R #4 BAR 18 IN. LONG 2 IN. 2 IN.4:16 IN. MAX/MIN. 8 IN. 2:1 #5 BAR 6 IN. 1 1/2 IN. PIPE SPACER AND 1 1/4 IN. LOCK NUT 4 IN. 1/4 IN. 1 1/4 IN. DIA. X 24 IN. GALV. 3 1/2 IN. AT TOP. 3 IN. X 3 IN. X 3/8 IN. PLATE 6 IN. 1/4 IN.-1 IN. LEG WARPED GUTTER VA R I A B L E MA X . H E I G H T - 1 0 F T . 2 F T . - 6 I N . M I N . (U N L E S S S Q U A S H P I P E IS U S E D ) STEEL ROD - THREADED 3 FT.-6 IN. 6 IN. 1. SEE D-8B FOR REINFORCEMENT. 2. FLOOR OF INLET SHALL BE SHAPED WITH ADDITION CONCRETE TO FORM INVERT TO PIPE CONNECTIONS. 3. MANHOLE RUNGS SHALL BE REQUIRED FOR INLET HEIGHT 4 FT. AND GREATER. 4. SIDEWALK SHALL BE 6 IN. THICK FOR 3 FT. ON EITHER SIDE OF INLET. 5. TOP SLAB OF INLET SHALL BE SLOPE TO MATCH SIDEWALK. SEE D-6. 6. EXPOSED STEEL SHALL BE GALVANIZED IN ACCORDANCE WITH AASHTO M-111. 4 F T . AA B B A A INLET SUMMARY INLET ID TYPE A3 TYPE C C1 CURB INLET-4 FT D1 DOUBLE CURB INLET D2 DOUBLE CURB INLET D3 DOUBLE CURB INLET D5 CURB INLET-4 FT D6 CURB INLET-4 FT E1 CURB INLET-4 FT D7 DE T A I L S ---- POND INV. ELEV.CIRCULAR ORIFICE DIAMETER (IN) 1 5054.60 10 2/4 2 5077.35 9 Pond 1 Pond 2 ELEV A.5054.50 5077.35 ELEV B.5057.20 5078.90 ELEV C.5058.20 5079.90 Dwq (FT.)2.70 N/A Ls (FT.)4 4 Ws (FT.)5 5 Wo (IN.)6 6 HOLE DIA. (IN.)1 N/A # OF ROWS 6 N/A # OF COLUMNS 1 N/A 600 OUTLET A4 AND D4 (POND 1 AND POND 2) WQ PLATE 6 1 1.2 2.5 5054.69 5057.09 5058.12 5076.79 5078.63 5079.72 4.4 5 4.3 5.3 66 SEE NEXT PAGE FOR AS-BUILT PICTURES POND 1: 100-YR ORIFICE POND 2: 100-YR ORIFICE 1/2" THK GALV. STEEL PLATE ORIFICE 1'-5" 1/2" Ø HOLES FOR 3/8" Ø EXPANSION BOLTS EMBEDDED 2" INTO CONCRETE WALL @ 12" O.C. MIN. INVERT ELEV. Sheet of 76 CO U N T R Y C L U B R E S E R V E 02/25/21 100-YEAR ORIFICE PLATE602 INLET SUMMARY601 CC A A B B SECTION C-C SECTION A-A WELL SCREEN PLAN GENERAL NOTES SECTION B-B D D A A ABBREVIATIONS LEGEND INLET SUMMARY INLET ID TYPE A3 TYPE C C1 CURB INLET-4 FT D1 DOUBLE CURB INLET D2 DOUBLE CURB INLET D3 DOUBLE CURB INLET D5 CURB INLET-4 FT D6 CURB INLET-4 FT E1 CURB INLET-4 FT POND 2 OUTLET UPDATE DE T A I L S ---- POND INV. ELEV.CIRCULAR ORIFICE DIAMETER (IN) 1 5054.60 10 2/4 2 5077.35 9 600 OUTLET A4 AND D4 (POND 1 AND POND 2) Pond 1 Pond 2 ELEV A.5054.50 5077.35 ELEV B.5057.20 5078.90 ELEV C.5058.20 5079.90 Dwq (FT.)2.70 N/A Ls (FT.)4 4 Ws (FT.)5 5 Wo (IN.)6 10 HOLE DIA. (IN.)1 N/A # OF ROWS 6 N/A # OF COLUMNS 1 N/A WQ PLATE NORTHERNENGINEERING.COM | 970.221.4158 DRAINAGE SITE CERTIFICATION LETTER: COUNTRY CLUB RESERVE FORT COLLINS | GREELEY APPENDIX Appendix E STATE PORTAL DOCUMENTS February 25, 2021 FINAL DRAINAGE AND EROSION CONTROL REPORT FOR COUNTRY CLUB RESERVE Fort Collins, Colorado Prepared for: Crystal Cove Development 8020 S. County Road 5, Unit 200 Fort Collins, CO 80528 Prepared by: 301 N. Howes, Suite 100 Fort Collins, Colorado 80521 Phone: 970.221.4158 Fax: 970.221.4159 www.northernengineering.com Project Number: 1324-001  This Drainage Report is consciously provided as a PDF. Please consider the environment before printing this document in its entirety. When a hard copy is absolutely necessary, we recommend double-sided printing. Stormwater Facility Name: Facility Location & Jurisdiction: User Input: Watershed Characteristics User Defined User Defined User Defined User Defined Selected BMP Type = EDB Stage [ft] Area [ft^2] Stage [ft] Discharge [cfs] Watershed Area = 35.38 acres 0.00 146 0.00 0.00 Watershed Length =3,468 ft 1.00 3,883 1.00 3.12 Watershed Length to Centroid = 445 ft 2.00 16,858 2.00 4.41 Watershed Slope =0.010 ft/ft 3.00 34,910 3.00 5.40 Watershed Imperviousness = 33.6%percent 4.00 57,222 4.00 6.23 Percentage Hydrologic Soil Group A = 0.0%percent 5.00 82,342 5.00 6.97 Percentage Hydrologic Soil Group B = 63.0%percent 6.00 111,177 6.00 7.64 Percentage Hydrologic Soil Groups C/D = 37.0%percent 7.00 148,056 7.00 8.25 Target WQCV Drain Time = 40.0 hours 8.00 182,306 8.00 8.82 9.00 212,225 9.00 9.35 User Input 10.00 238,836 10.00 9.86 11.00 265,088 11.00 10.34 12.00 288,850 12.00 10.80 After completing and printing this worksheet to a pdf, go to: https://maperture.digitaldataservices.com/gvh/?viewer=cswdif Create a new stormwater facility, and attach the PDF of this worksheet to that record. Routed Hydrograph Results Design Storm Return Period =WQCV 2 Year 5 Year 10 Year 50 Year 100 Year One-Hour Rainfall Depth =N/A 0.86 1.14 1.43 2.39 2.91 in CUHP Runoff Volume =0.478 0.703 1.129 1.795 4.774 6.513 acre-ft Inflow Hydrograph Volume =N/A 0.703 1.129 1.795 4.774 6.513 acre-ft Time to Drain 97% of Inflow Volume =1.4 2.6 3.4 4.7 9.7 12.3 hours Time to Drain 99% of Inflow Volume =1.5 2.7 3.5 4.8 9.9 12.7 hours Maximum Ponding Depth =2.42 1.71 2.37 3.11 5.06 5.82 ft Maximum Ponded Area =0.56 0.30 0.54 0.85 1.92 2.43 acres Maximum Volume Stored =0.479 0.180 0.451 0.960 3.642 5.291 acre-ft Once CUHP has been run and the Stage-Area-Discharge information has been provided, click 'Process Data' to interpolate the Stage-Area-Volume-Discharge data and generate summary results in the table below. Once this is complete, click 'Print to PDF'. Stormwater Detention and Infiltration Design Data Sheet Country Club Reserve Pond 1 Fort Collins SDI-Design Data v2.00, Released January 2020 Location for 1-hr Rainfall Depths (use dropdown): After providing required inputs above including 1-hour rainfall depths, click 'Run CUHP' to generate runoff hydrographs using the embedded Colorado Urban Hydrograph Procedure. Pond 1-STATE STATUE.xlsm, Design Data 4/3/2023, 3:28 PM Booleans for Message Booleans for CUHP Watershed L:W 1 CUHP Inputs Complete Watershed Lc:L 1 CUHP Results Calculated Watershed Slope FALSE Time Interval RunOnce 1 CountA 1 Draintime Coeff 1.0 User Precip 1 Equal SA Inputs 1 Equal SD Inputs 1 Stormwater Detention and Infiltration Design Data Sheet 0 10 20 30 40 50 60 70 80 90 0.1 1 10 FL O W [ c f s ] TIME [hr] 100YR IN 100YR OUT 50YR IN 50YR OUT 10YR IN 10YR OUT 5YR IN 5YR OUT 2YR IN 2YR OUT WQCV IN WQCV OUT 0 1 2 3 4 5 6 7 0.1 1 10 100 PO N D I N G D E P T H [ f t ] DRAIN TIME [hr] 100YR 50YR 10YR 5YR 2YR WQCV Pond 1-STATE STATUE.xlsm, Design Data 4/3/2023, 3:28 PM Stormwater Facility Name: Facility Location & Jurisdiction: User Input: Watershed Characteristics User Defined User Defined User Defined User Defined Selected BMP Type = EDB Stage [ft] Area [ft^2] Stage [ft] Discharge [cfs] Watershed Area = 12.20 acres 0.00 0 0.00 0.00 Watershed Length =1,168 ft 1.00 23,374 1.00 1.82 Watershed Length to Centroid = 500 ft 2.00 70,812 2.00 2.94 Watershed Slope =0.010 ft/ft 2.40 82,174 2.40 3.10 Watershed Imperviousness = 23.4%percent Percentage Hydrologic Soil Group A = 0.0%percent Percentage Hydrologic Soil Group B = 40.0%percent Percentage Hydrologic Soil Groups C/D = 60.0%percent Target WQCV Drain Time = 40.0 hours User Input After completing and printing this worksheet to a pdf, go to: https://maperture.digitaldataservices.com/gvh/?viewer=cswdif Create a new stormwater facility, and attach the PDF of this worksheet to that record. Routed Hydrograph Results Design Storm Return Period =WQCV 2 Year 5 Year 10 Year 50 Year 100 Year One-Hour Rainfall Depth =N/A 0.86 1.14 1.43 2.39 2.91 in CUHP Runoff Volume =0.131 0.157 0.292 0.513 1.541 2.145 acre-ft Inflow Hydrograph Volume =N/A 0.157 0.292 0.513 1.541 2.145 acre-ft Time to Drain 97% of Inflow Volume =2.1 3.3 4.1 5.1 9.0 11.1 hours Time to Drain 99% of Inflow Volume =2.3 3.6 4.4 5.4 9.7 11.8 hours Maximum Ponding Depth =0.70 0.43 0.67 0.97 1.82 2.16 ft Maximum Ponded Area =0.38 0.23 0.36 0.52 1.43 1.73 acres Maximum Volume Stored =0.131 0.050 0.120 0.251 1.077 1.610 acre-ft Once CUHP has been run and the Stage-Area-Discharge information has been provided, click 'Process Data' to interpolate the Stage-Area-Volume-Discharge data and generate summary results in the table below. Once this is complete, click 'Print to PDF'. Stormwater Detention and Infiltration Design Data Sheet Country Club Reserve Pond 2 Fort Collins SDI-Design Data v2.00, Released January 2020 Location for 1-hr Rainfall Depths (use dropdown): After providing required inputs above including 1-hour rainfall depths, click 'Run CUHP' to generate runoff hydrographs using the embedded Colorado Urban Hydrograph Procedure. Pond 2-STATE STATUE, Design Data 5/5/2023, 7:18 AM Booleans for Message Booleans for CUHP Watershed L:W 1 CUHP Inputs Complete Watershed Lc:L 1 CUHP Results Calculated Watershed Slope FALSE Time Interval RunOnce 1 CountA 1 Draintime Coeff 1.0 User Precip 1 Equal SA Inputs 1 Equal SD Inputs 1 Stormwater Detention and Infiltration Design Data Sheet 0 5 10 15 20 25 0.1 1 10 FL O W [ c f s ] TIME [hr] 100YR IN 100YR OUT 50YR IN 50YR OUT 10YR IN 10YR OUT 5YR IN 5YR OUT 2YR IN 2YR OUT WQCV IN WQCV OUT 0 0.5 1 1.5 2 2.5 0.1 1 10 100 PO N D I N G D E P T H [ f t ] DRAIN TIME [hr] 100YR 50YR 10YR 5YR 2YR WQCV Pond 2-STATE STATUE, Design Data 5/5/2023, 7:18 AM