November 28, 2022
Mr. Dan Mogan
Development Review Engineer
City of Fort Collins Stormwater
700 Wood Street
Fort Collins, Colorado 80522-0580
RE: West Vine Drive Storage
As-built Rain Garden Volume Certification
Mr. Mogan,
This letter is in regards to your request for a certification of the as-built rain garden
flat area and volumes for the West Vine Drive Storage project.
As you are aware, the initial construction of the rain gardens did not follow the
original design. The forebays were not built and the volume for all three rain
gardens was insufficient due to an over-loading of fill material along the retaining
walls and in the areas along the face of the buildings.
Since the initial construction, adjustments have been made to all three Rain Gardens
to conform to the designed plans. The forebays were correctly installed and the
elevation of the outlet weirs for each Rain Garden was raised and the over-fill along
the walls of the west and middle rain gardens have been removed to provide the
additional needed volume (see attached photographs).
The following calculations are based on survey data elevations that were obtained
during and after the recent excavation (see attached rain garden details).
The revised rain garden volumes are as follows;
West Rain Garden
Revised Weir Elevation 5010.01
Top of Wall Elevation 5011.01
Minimum Flat Surface Area 1122 Square Feet
Provided Flat Surface Area 2130 Square Feet
Required Volume per spread sheet 1683 cubic feet
Rain Garden Volume 3764 Cubic Feet
Surplus Volume 2081 cubic feet
3
West Rain Garden
Middle Rain Garden
1/19 Page 1 of 2
DURING CONSTRUCTION INSPECTION CHECKLIST
To be completed by Construction Superintendent
This checklist is to be completed during construction and included with the Overall Site and Drainage Certification.
• Use “Yes” for items completed as described.
• Use “N/A” for items that are not applicable to the site being certified.
• If any blanks are “No,” attach an explanation referencing the item number below.
Project Name: West Vine Storage Date: 5/25/2022
Building Permit Numbers: See Attached Sheets for Permit numbers & finish floor elevations
I. Compaction
A. Yes All berms and embankments meet the compaction requirements as specified in the project geotechnical report or comply with the
City’s standard, which is “soils should be compacted within a moisture content range of 2% below to 2% above optimum moisture content
and compacted to 95% of the Maximum Standard Proctor Density (ASTM D698).” Compaction requires verification during construction.
Provide testing log from contractor/engineer.
II. Storm Drain Pipe Installation Requirements
A. Yes The pipe trenches have been compacted in accordance with Section 02225-3.07.A.1. of the Fort Collins Development Construction
Standards for Water, Wastewater, Stormwater (e.g., the trenches in the roadways are to be 95% of maximum density and all other areas
are to be at 90%, both in accordance with ASTM D698).
III. Energy Dissipation and Erosion Protection - FCSCM Chapter 9, Section 7.0
A. Riprap
1. Yes The riprap bedding is a granular bedding of the gradation and thickness indicated on the approved construction plans.
2. N/A A filter fabric was installed instead of granular bedding and is the material shown on the approved construction plans or was an
approved equal. Provide documentation for an approved equal.
3. Yes The riprap is the gradation shown on the approved construction plans with a D50 of 9”.
4. Yes The riprap thickness is as shown on the approved construction plans and extends to the horizontal limits shown.
5. Yes The riprap is buried to the depth indicated on the approved construction plans. (A minimum of 6 inches of soil is required.)
B. Permanent Erosion Control Fabric - FCSCM Vol.1, Ch.7
1. Yes All fabric was installed per manufacturer’s specifications.
1/19 Page 2 of 2
IV. Other Permanent BMPs
A. Yes All cut-off walls have been installed in accordance with the approved construction plans. (Cut-off walls are required for irrigation ditch
crossings of storm drain pipes.)
V. Extended Detention Basins
A. N/A Installation of this facility was verified via inspection by a City-Stormwater Inspector at the point of installation of the water quality
control box(es). Provide date of inspection and name of inspector: N/A
Included certification sheet(s):
Please check the appropriate box(es) for the Low Impact Development
(LID) facilities found on this site and complete the corresponding
certification sheets.
☐ Permeable Interlocking Concrete Pavers
☒ Bioretention Cells (Rain Gardens)
☐ Sand Filters
☐ Vegetated Buffers
☐ Underground Infiltration
☐ Other LID – For certification of Dry Wells, Tree Filters,
Constructed Wetland Channels & Ponds, etc., contact City Staff
to determine requirements to exhibit the LID facility has been
constructed and functions as intended per the approved
drainage report.
*Please provide photographic documentation of the installation of all
stages of all LID facilities.
**Please contact the City Stormwater Inspector at
stormwaterinspection@fcgov.com to discuss inspection requirements
for each LID facility and request inspections.
***All facilities being certified must be “clean” – free of sediment &
construction debris – prior to certification or acceptance of the facility.
Completed by:
Name: Tracy Zwetzig, Kevin Forbes
Title: Project Manager
Email: taz@slbbi.com
Phone: 970-567-0677
Company: Clark Enterprises Construction
Address: 80 Factory Road
Eaton CO, 80615
1/19 Page 1 of 3
Bioretention Cells (Rain Gardens)
was held with City-Stormwater
Inspector to discuss installation, inspection, checklist, and ☒ ☐ ☐ location (i.e. DCP, initial erosion control
Underdrain and basecourse inspection(s):
facility was verified via inspection by a City-Stormwater
Inspector at the point of installation of the outlet, underdrain,
geomembrane layer, and base course (per design in Final Plan
☒ ☐ ☐
inspector’s name
Pea gravel and BSM inspection(s):
was verified via inspection by a City-Stormwater Inspector at
the point of installation of the pea gravel and bioretention ☒ ☐ ☐ inspector’s name vary
Excavation
☒ ☐ ☐
☒ ☐ ☐
☒ ☐ ☐
☒ ☐ ☐
Intake
☒ ☐ ☐
Forebay
☒ ☐ ☐ Provide photograph
There is a minimum 3” drop at the forebay entrance ☒ ☐ ☐ Provide photograph
Forebay will drain fully and not hold standing water ☒ ☐ ☐
Outlet Structure/Overflow
Emergency overflow elevation is confirmed
☒ ☐ ☐ overflow to top of media filter; provide
☐ ☐ ☒
1/19 Page 2 of 3
Overflow inlet invert elevation is at least 3 inches below
containment wall/berm (to direct overflow into inlet) ☐ ☐ ☒ inlet and top of containment wall/berm;
from erosion and maintain elevations ☒ ☐ ☐ photographs to be
Impermeable Liner
☒ ☐ ☐
☒ ☐ ☐ Provide photograph
Impermeable liner is buried with no exposure ☒ ☐ ☐
Any penetrations of the impermeable liner have been sealed
and checked for water-tightness ☒ ☐ ☐
Underdrain System
☒ ☐ ☐ Provide photograph
At least one cleanout is provided per underdrain lateral ☒ ☐ ☐ Provide photograph
Cleanout pipe is solid (not perforated/slotted) ☒ ☐ ☐ Provide photograph
Cleanout covers are installed and watertight ☒ ☐ ☐ Provide photograph
Verify the underdrain is NOT wrapped in geotextile fabric ☒ ☐ ☐ Provide photograph
Verify there is no orifice plate on the underdrain outfall ☒ ☐ ☐ Provide photograph
Underdrain integrity tested after backfilling using TV and/or
water test ☒ ☐ ☐ underdrains have been
Filter Media and Aggregate
- meets design specifications
☒ ☐ ☐ record depth installed
#8, #89, or #9):
- meets design specifications
☒ ☐ ☐ record depth installed
- meets design specifications
☒ ☐ ☐ record depth installed
☒ ☐ ☐ Provide load ticket
BSM is installed flat and level ☒ ☐ ☐ Provide photograph
Other Structural Components
Containment wall/berm is continuous and level ☒ ☐ ☐
1/19 Page 3 of 3
Landscaping
Verify final landscaping is free of sod ☒ ☐ ☐
☒ ☐ ☐ Provide photograph SiteVvisit verification
Vegetation is planted according to landscape design
specifications and final landscaping plan ☒ ☐ ☐
☒ ☐ ☐
Temporary irrigation installed
☐ ☐ ☒ irrigation is installed to establish/maintain has been installed
Close Out
☒ ☐ ☐
Northern
Colorado
Geotech
November 11, 2022 2956 29th Street, Unit 21
Greeley, Colorado 80631
Phone: (970) 506-9244
Fax: (970) 506-9242
Clark Enterprises
80 Factory Road
Eaton, Colorado 80615
Attn: Taz
Re: West Vine Storage
Fort Collins, Colorado
Northern Colorado Geotech Project No. c173-19
Northern Colorado Geotech performed density testing of the soil on the top of the ditch berm in
accordance with the request from the client. The soil appeared to meet standard industry
specifications of 95 percent compaction.
If you have any questions or if we may be of further assistance, please do not hesitate to contact us at
(970) 506-9244.
Sincerely,
NORTHERN COLORADO GEOTECH
Doug Leafgren, P.G.
President
Digitally signed by Doug Leafgren
DN: C=US, OU=President, O=Northern
Colorado Geotech, CN=Doug Leafgren,
E=dleafgren@msn.com
Reason: I am the author of this document
Location: your signing location here
Date: 2022.11.11 09:48:59-07'00'
Foxit PhantomPDF Version: 10.1.9
Doug
Leafgren
2956 29TH STREET, UNIT 21
GREELEY, COLORADO 80631
PHONE: (970) 506-9244
FAX: (970) 506-9242
SUMMARY OF FIELD DENSITY AND MOISTURE TEST RESULTS
CLIENT: Clark Enterprises PROJECT: West Vine Storage
80 Factory Road LOCATION: Fort Collins, Colorado
Eaton, Colorado 80615
ATTN: Taz NCG PROJECT No: c173-19
TECHNICIAN:DL REVIEWED BY: DML DATE: 11-Nov-22
TEST METHOD:DIRECT TRANSMISSION REMARKS: <> indicates failing test
MATERIAL DESIGNATION:1 2 3 4 5 6 7
MAXIMUM DRY DENSITY: 118.5 120.5 112.0 122.0
OPTIMUM MOISTURE: 12.0 11.5 13.5 13.0
MOISTURE TOLERANCE:ц2 ц2 ц2 ц2
ELEVATION WET UNIT DRY UNIT REQUIRED
TEST DATE LOCATION BELOW WEIGHT WEIGHT WATER PERCENT PERCENT MATERIAL
No. TESTED FIN. GRAD PCF PCF CONTENT % COMPACTION COMPACTION DESIGNATION
95 11/8/22 Top of Ditch Berm - west side FG 125.8 114.8 9.6 95 95 MIN 2
96 11/8/22 Top of Ditch Berm - east side FG 125.4 114.3 9.7 95 95 MIN 2
20190049823
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA
This unofficial copy was downloaded on Aug-19-2020 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com
For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA