HomeMy WebLinkAboutSite Certifications - 01/21/2022 December 24, 2021 Josh Erramouspe Olsson 1880 Fall River Drive, Suite 200 Loveland, CO 80538 RE: Lot and Grading Certification Analysis – Revised Major Amendment to a Portion of Foothills Mall Redevelopment Planning Area 3 (Lots 3, 4, 5, and 6 of Foothills Mall Redevelopment) Dear Mr. Erramouspe, We have completed an analysis of the following buildings and lots to complete the City of Fort Collins Overall Site and Drainage Certification and Certification of Lot Grading for each building: • Building 1-8 of Lot 3 at 312 E Foothills Parkway • Building 9-13 of Lot 4 at 3241 Stanford Road • Building 14-17 of Lot 5 at 3381 Stanford Road • Building 18-19 of Lot 6 at 3501 Stanford Road The analysis included review of following information provide to LandOne (See Appendix U): • Approved Grading Plans completed by Olsson • Foundation As-builts completed by Olsson • Improvement Location Certificate completed by ESC • Cycle Apartments Spot Grading Plans completed by Olsson • As-built Survey completed by ESC • Cycle Apartments Spot Grading Plans Record Drawings completed by Olsson • Amendment to Low Impact Design Analysis and Assessment of Rain Garden 33’s as- built by Olsson In addition to the information provided to LandOne, we completed two site visits: one on January 21st, 2019 and one on February 8th, 2021. The reason for the delay in completing the certifications is because of deficiencies in the original construction based on the improvement location certificate completed by ESC in 2019. Analysis of the deficiencies was completed by Olsson in 2019. Based on that analysis, the Cycle Apartments Spot Grading Plans were created to correct the deficiencies. Once the construction was finished, an as-built survey was completed by ESC and record drawings were created by Olsson. See Appendix U. N www.LandOne.co 361 71st Avenue, Suite 100 Greeley, CO 80634 970-632-2311 Lot and Grading Certification Analysis Major Amendment to a Portion of Foothills Mall Redevelopment Planning Area 3 (Lots 3, 4, 5, and 6 of Foothills Mall Redevelopment) December 24th, 2021 Page 2 Based on the analysis of the information and stated site visits, the original design intent in general is being met. The scope of the analysis is limited to the evaluation of the information provided and observations made during the site visits. The analysis is not a guaranty or warranty, either expressed or implied. The following is being provided to support the analysis and certifications: • Appendix A – Overall Site and Drainage Certification • Appendix B thru T – Building Certifications • Appendix U – Supporting Material If you have any questions or need additional information, please contact me. Sincerely, LandOne Engineering, LLC Daniel Hull, PE Principal/Owner Enclosures N 39337 30 ar 12/24/2021 N 39337 30 ar 12/24/2021 Exhibit B Overall Site and Drainage Certification Responses I. Water Quality and Quantity Detention Basin This section is not applicable since water quality and quantity detention basin are not applicable to this project. II. Channels/Swales This section is not applicable since channels and swales are not applicable to this project. III. Storm Pipes As-builts indicate there are deficiencies in the construction of the storm pipe. Since the storm drain system is private, the owner has accepted all as-built conditions. IV. Concrete Pans No comments V. Storm Drain Inlets As-builts indicate there are variations in the construction of the inlets. Since the storm drain system is private, the owner has accepted all as-built conditions. VI. Culverts This section is not applicable since culverts are not applicable to this project. VII. Sub-Drains This section is not applicable since sub-drains are not applicable to this project. VIII. Curb Cuts There is one curb cut called for on Lot 3 per Sheet C14.1. This curb cut was not constructed. IX. Sidewalk Culverts & Chases No comments X. Site Grading No comments XI. Permanent Erosion Control BMPs No comments XII. Post-Construction Site Cleanup No comments XIII. Certification of LID and Water Quality Facilities See Exhibit D - During Construction Inspection Checklist in Appendix B and Exhibit H – Amendment to Low Impact Design Analysis and Assessment of Rain Garden 33’s as-built by Olsson in Appendix U N XIV. Certification of Other Permanent BMPs No comments XV. Certification and Erosion Control Measures No comments XVI. Statement of Compliance No comments XVII. Signature and Stamp No comments N N B1601350 39337 30 ar 12/24/2021 N N B1601326 39337 30 ar 12/24/2021 N N B1601325 39337 30 ar 12/24/2021 N N B1601381330 39337 30 ar 12/24/2021 N N B1601323400 39337 30 ar 12/24/2021 N N B1601321 39337 30 ar 12/24/2021 N N B1601318 39337 30 ar 12/24/2021 N N B1601385 39337 30 ar 12/24/2021 N N B1601380 39337 30 ar 12/24/2021 N N B1601386 39337 30 ar 12/24/2021 N N B1601315 39337 30 ar 12/24/2021 N N B1601314 39337 30 ar 12/24/2021 N N B1601313 39337 30 ar 12/24/2021 N N B1601312 39337 30 ar 12/24/2021 N N B1601310 39337 30 ar 12/24/2021 N N B1601307 39337 30 ar 12/24/2021 N N B1601305 39337 30 ar 12/24/2021 N N 39337 30 ar 12/24/2021 N N B1601302 39337 30 ar 12/24/2021 N Appendix U Supporting Material Exhibit A: Approved Grading Plans dated 03/30/2016 – Original grading plans approved by the City of Fort Collins. Exhibit B: Foundation As-builts dated 09/15/2017 – As-built survey for the foundations. Exhibit C: Improvement Location Certificate dated 01/10/2019 – As-built survey completed by Engineering Service Company. Exhibit D: Cycle Apartments As-Constructed Drainage Analysis dated 11/7/2019 – Analysis completed by Olsson. Analysis is based on Improvements Location Certificate completed by Engineering Service Company. Exhibit E: Cycle Apartments Spot Grading Plans dated 12/24/2019 – Plans created to address deficiencies in the original construction. Exhibit F: As-built Survey dated 10/01/2020 – as-built survey completed but Engineering Service Company. Exhibit G: Cycle Apartments Spot Grading Plans Record Drawings dated 12/29/2020 – Record drawings of the spot grading plans. Exhibit H: Amendment to Low Impact Design Analysis and Assessment of Rain Garden 33’s as- built by Olsson, dated 10/31/2021 – analysis of the as-built to verify the intent of the design was met. N Response to Comments.pdf Markup Summary Subject: Callout Page Label: 7 Author: dmogen Date: 12/23/2021 9:14:09 AM Status: Completed set by Daniel Hull on 12/23/2021 at 9:14:09 AM Color: Layer: Space: No? Does system have adequate capacity per the design? Please clarify. dmogen (23) Subject: Re: Callout Page Label: 7 Author: Daniel Hull Date: 12/23/2021 3:04:36 PM Status: Color: Layer: Space: The as-builts do not match the design consistently. However, the stormwater systems have been oversized to convey the major event. It is reasonable to assume the pipes are capable of carrying the minor event. Subject: Callout Page Label: 7 Author: dmogen Date: 12/23/2021 3:01:27 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:01:27 PM Color: Layer: Space: No? Please clarify. Subject: Re: Callout Page Label: 7 Author: Daniel Hull Date: 12/23/2021 2:59:36 PM Status: Color: Layer: Space: The as-builts do not match the design consistently. However, the stormwater systems have been oversized to convey the major event. It is reasonable to assume the pipes are capable of carrying the minor event. Subject: Callout Page Label: 8 Author: dmogen Date: 12/23/2021 3:05:09 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:05:09 PM Color: Layer: Space: No? Please clarify the no's in this section. m drains) - FCSCM Ch. 9, Sec. 4.0 pacity: The as-built capacity of all pipes installed on this project has been r exceeds the capacity requirements shown in the approved drainage study for this rain pipe sizes and materials have been verified and are in conformance with the ction plans. (Indicate on the plan and profile sheets that they have been verified.) substitutions must be approved prior to installation. If a pipe size or material was onstruction, the certification engineer must attach the approval documents or supply tification. Approval documents must include a calculation documenting the capacity l or greater) of the substituted size. Exhibit A - Page 4 of 8 No No? Does system have adequate capacity per the design? Please clarify. bstituted size. e is as shown on the approved construction plans. The opes flatter than the designed slope on the constructio ons on an attached sheet. ve been verified and are shown on the plan and profile s ts: All pipes are installed in accordance with the tion specifications. ts for all pipes have been met as shown on the approved out in critical locations. as specified on the approved construction plans have be uction methods specified on the approved construction No No? Please clarify. CSCM Ch. 9, Sec. 3.0 lation: All storm drain inlets have been constructed in accordan on plans and construction specifications. nd type of inlets are consistent with the inlets shown on the approved writing “Verified” on each inlet on the plan sheet or list on a separate ype and size (length). If the inlet installed is other than the one on the detail sheet, provide the name and source of the detail with justificat Exhibit A - Page 5 of 8 No No? Please clarify the no's in this section. Subject: Re: Callout Page Label: 8 Author: Daniel Hull Date: 12/23/2021 3:05:01 PM Status: Color: Layer: Space: The as-builts do not match the design consistently. However, the stormwater systems have been oversized to convey the major event. It is reasonable to assume the pipes are capable of carrying the minor event. Subject: Callout Page Label: 10 Author: dmogen Date: 12/23/2021 3:19:11 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:19:11 PM Color: Layer: Space: should this be "n/a"? "underground infiltration" typically refers to StormTech facilities used for WQ/LID/detention and I don't think that was on this project. Subject: Re: Callout Page Label: 10 Author: Daniel Hull Date: 12/23/2021 3:19:05 PM Status: Color: Layer: Space: This item was revised Subject: Callout Page Label: 12 Author: dmogen Date: 12/23/2021 3:17:51 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:17:48 PM Color: Layer: Space: What are the deficiencies? Is stormwater still conveyed as intended? Is there documentation of acceptance by ownership? (Same ?s for section V) Subject: Re: Callout Page Label: 12 Author: Daniel Hull Date: 12/23/2021 3:16:22 PM Status: Color: Layer: Space: I revised to the word to variations. As noted, the stormwater systems have been oversized to convey the major event. It is reasonable to assume the pipes are capable of carrying the minor event. XIII.Certification of LID and Water Quality Facilities - FCSCM Ch. 7 A.Attached are the During Construction Inspection Checklist for Low Impact Development ( other items to be verified during construction, along with pictures and other required documen B.Attached is verification of the rain garden and/or sand filter flat surface area(s) and pond volume(s). This verification includes survey of critical elevations. C.Attached is verification of the underground infiltration required volume(s), weir elevation orifices, inspection ports and filtering fabric. This verification includes survey of critical elevation D.All visible LID design features were verified as part of the engineer's site visit. 11/19 Yes Yes Yes Yes should this be "n/a"? "underground infiltration" typically refers to StormTech facilities used for WQ/LID/detention and I don't think that was on this project. Exhibit B Overall Site and Drainage Certification Responses I. Water Quality and Quantity Detention Basin This section is not applicable since water quality and quantity detention basin are not applicable to this project. II. Channels/Swales This section is not applicable since channels and swales are not applicable to this project. III. Storm Pipes As-builts indicate there are deficiencies in the construction of the storm pipe. Since the storm drain system is private, the owner has accepted all as-built conditions. IV. Concrete Pans No comments V. Storm Drain Inlets As-builts indicate there are deficiencies in the construction of the inlets. Since the storm drain system is private, the owner has accepted all as-built conditions. VI. Culverts This section is not applicable since culverts are not applicable to this project. VII. Sub-Drains This section is not applicable since sub-drains are not applicable to this project. VIII. Curb Cuts There is one curb cut called for on Lot 3 per Sheet C14.1. This curb cut was not constructed. IX. Sidewalk Culverts & Chases What are the deficiencies? Is stormwater still conveyed as intended? Is there documentation of acceptance by ownership? (Same ?s for section V) Subject: Callout Page Label: 15 Author: dmogen Date: 12/23/2021 3:20:55 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:20:55 PM Color: Layer: Space: I don't believe there are any critical embankments (detention ponds, major channels, etc) associated with this project so this is ok. Subject: Re: Callout Page Label: 15 Author: Daniel Hull Date: 12/23/2021 3:20:43 PM Status: Color: Layer: Space: The comment is noted. Subject: Text Box Page Label: 17 Author: dmogen Date: 12/23/2021 3:26:20 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:26:20 PM Color: Layer: Space: Can eliminate pages that don't apply to the project. Subject: Re: Text Box Page Label: 17 Author: Daniel Hull Date: 12/23/2021 3:26:15 PM Status: Color: Layer: Space: The page was removed. Subject: Text Box Page Label: 18 Author: dmogen Date: 12/23/2021 3:27:13 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:27:13 PM Color: Layer: Space: Can eliminate pages that don't apply to the project. Multifamily – Cycle Apts Date: 6/15/2020 , 1326, 1325, 1381, 1323, 1321, 1318, 1385, 1380, 1386, 1315, 1314, 1313, 1312, 1310, 1307, 1305, 1304, meet the compaction requirements as specified in the project geotechnical report or comply with the uld be compacted within a moisture content range of 2% below to 2% above optimum moisture content imum Standard Proctor Density (ASTM D698).” Compaction requires verification during construction. r/engineer. - We do not have records of compaction but industry standard was followed. ements compacted in accordance with Section 02225-3.07.A.1. of the Fort Collins Development Construction Stormwater (e.g., the trenches in the roadways are to be 95% of maximum density and all other areas nce with ASTM D698). tection - FCSCM Chapter 9, Section 7.0 ular bedding of the gradation and thickness indicated on the approved construction plans. nstead of granular bedding and is the material shown on the approved construction plans or was an entation for an approved equal. hown on the approved construction plans with a D50 of VL. own on the approved construction plans and extends to the horizontal limits shown. epth indicated on the approved construction plans. (A minimum of 6 inches of soil is required.) - FCSCM Vol.1, Ch.7 I don't believe there are any critical embankments (detention ponds, major channels, etc) associated with this project so this is ok. al Requirements Submitted?/R date, inspector name, meeting (i.e. DCP, initial erosion control Can eliminate pages that don't apply to the project. sediment) sediment) d to the top ☐ ☐ ☐ record depth in ☐ ☐ ☐ of compaction Protection During Construction otherwise prote Can eliminate pages that don't apply to the project. Subject: Re: Text Box Page Label: 18 Author: Daniel Hull Date: 12/23/2021 3:26:31 PM Status: Color: Layer: Space: The page was removed. Subject: Callout Page Label: 21 Author: dmogen Date: 12/23/2021 3:03:51 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:03:51 PM Color: Layer: Space: Any notes of electric conduit running thru rain gardens and modifications that were made? Please provide. Subject: Re: Callout Page Label: 21 Author: Daniel Hull Date: 12/23/2021 2:46:51 PM Status: Color: Layer: Space: This comment was resolved at the field meeting. Subject: Callout Page Label: 21 Author: dmogen Date: 12/23/2021 2:59:55 PM Status: Completed set by Daniel Hull on 12/23/2021 at 2:59:55 PM Color: Layer: Space: Any additional pictures of construction with the wrapped conduits, etc? Subject: Re: Callout Page Label: 21 Author: Daniel Hull Date: 12/23/2021 3:02:43 PM Status: Color: Layer: Space: Owner has provided all available pictures from construction. Any notes of electric conduit running thru rain gardens and modifications that were made? Please provide. Any additional pictures of construction with the wrapped conduits, etc? Subject: Text Box Page Label: 22 Author: dmogen Date: 12/23/2021 3:27:19 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:27:19 PM Color: Layer: Space: Can eliminate pages that don't apply to the project. Subject: Re: Text Box Page Label: 22 Author: Daniel Hull Date: 12/23/2021 3:26:36 PM Status: Color: Layer: Space: The page was removed. Subject: Text Box Page Label: 23 Author: dmogen Date: 12/23/2021 3:27:25 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:27:25 PM Color: Layer: Space: Can eliminate pages that don't apply to the project. Subject: Re: Text Box Page Label: 23 Author: Daniel Hull Date: 12/23/2021 3:26:41 PM Status: Color: Layer: Space: The page was removed. Subject: Text Box Page Label: 24 Author: dmogen Date: 12/23/2021 3:27:30 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:27:30 PM Color: Layer: Space: Can eliminate pages that don't apply to the project. Can eliminate pages that don't apply to the project. ☐ ☐ ☐ ☐ ☐ ☐ Provide photographs befor “ripping” ☐ ☐ ☐ Provide photograph ☐ ☐ ☐ Provide photograph Intake ☐ ☐ ☐ Forebay (If Applicable) ☐ ☐ ☐ Provide photograph Can eliminate pages that don't apply to the project. ☐ ☐ ☐ Filter Media ☐ ☐ ☐ Provide load ticket, photograp record depth installed ☐ ☐ ☐ Provide load ticket, photograp record depth installed ☐ ☐ ☐ er Structural Components ☐ ☐ ☐ Landscaping Can eliminate pages that don't apply to the project. Subject: Re: Text Box Page Label: 24 Author: Daniel Hull Date: 12/23/2021 3:26:46 PM Status: Color: Layer: Space: The page was removed. Subject: Text Box Page Label: 25 Author: dmogen Date: 12/23/2021 3:27:48 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:27:48 PM Color: Layer: Space: Can eliminate pages that don't apply to the project. Subject: Re: Text Box Page Label: 25 Author: Daniel Hull Date: 12/23/2021 3:26:50 PM Status: Color: Layer: Space: The page was removed. Subject: Text Box Page Label: 26 Author: dmogen Date: 12/23/2021 3:28:03 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:28:03 PM Color: Layer: Space: Can eliminate pages that don't apply to the project. Subject: Re: Text Box Page Label: 26 Author: Daniel Hull Date: 12/23/2021 3:26:55 PM Status: Color: Layer: Space: The page was removed. Can eliminate pages that don't apply to the project. ☐ ☐ Provide photograph ☐ ☐ Provide photograph ☐ ☐ Provide photograph meable Liner ☐ ☐ Provide specifications of delivered material ☐ ☐ ☐ ☐ Provide photograph (if necessary) Can eliminate pages that don't apply to the project. Subject: Text Box Page Label: 27 Author: dmogen Date: 12/23/2021 3:27:06 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:27:06 PM Color: Layer: Space: Can eliminate pages that don't apply to the project. Subject: Re: Text Box Page Label: 27 Author: Daniel Hull Date: 12/23/2021 3:27:00 PM Status: Color: Layer: Space: The page was removed. Subject: Callout Page Label: 41 Author: dmogen Date: 12/23/2021 3:43:44 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:43:44 PM Color: Layer: Space: It looks like all of the lot grading certs merged together in responses for address, lot, permit, parcel, etc. Can you please flatten before combining the documents? Subject: Re: Callout Page Label: 41 Author: Daniel Hull Date: 12/23/2021 3:43:41 PM Status: Color: Layer: Space: The comment is noted. Subject: Callout Page Label: 78 Author: dmogen Date: 12/23/2021 3:44:06 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:44:06 PM Color: Layer: Space: Please complete. ☐ Can eliminate pages that don't apply to the project. CERTIFICATION OF LOT GRADING Pursuant to Fort Collins City Code § 26-544 & City Land Use Code § 3.3.2 (e) Date: Address: Lot: Block: Subdivision: Permit Application #: Larimer County Parcel #: Larimer County Reception #: (on development agreement) I, (print) , a Colorado registered professional engineer, verify that construction of all stormwater facilities and grading is complete and hereby submit this certification. Please answer the following questions by initialing the appropriate response. For each question initialed “No,” attach an explanation detailing how this will affect stormwater drainage for this lot and any adjacent lots. 1.Certification includes attached Stormwater-approved grading plan. (NOTE: City’s Building Department does not approve grading plans). 2.Certification includes the attached as-built survey dated (must be within 60 days of the date the certification is submitted) accurately and truthfully depicting elevations for: Top of foundation/finished floor Finished grade on each side of the structure Quarter points along each lot line (not more than 50 feet apart) No Yes No Yes Building 2 Exhibit A February 8, 2021 Foothills Mall Redevelopment 312 E Foothills Parkway B1601304 Fort Collins, CO 80525 9725330003 3 20160032131 Daniel Hull 1/10/2019 It looks like all of the lot grading certs merged together in responses for address, lot, permit, parcel, etc. Can you please flatten before combining the documents? Co PE Stamp Sign and date Please complete. Subject: Re: Callout Page Label: 78 Author: Daniel Hull Date: 12/23/2021 3:44:02 PM Status: Color: Layer: Space: Completed Subject: Callout Page Label: 85 Author: dmogen Date: 12/23/2021 3:31:06 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:31:06 PM Color: Layer: Space: Form says yes form this building? Subject: Re: Callout Page Label: 85 Author: Daniel Hull Date: 12/23/2021 3:31:00 PM Status: Color: Layer: Space: The certification was revised. Subject: Callout Page Label: 89 Author: dmogen Date: 4/1/2021 4:35:28 PM Status: Color: Layer: Space: different address but still duplicating from other building forms. Subject: Callout Page Label: 269 Author: dmogen Date: 12/23/2021 3:33:10 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:33:10 PM Color: Layer: Space: ? le due to paved areas adjacent to the building. le since this does not apply to this lot. le since there are no swales within the limits. ted to the stormwater system. No downspouts en areas. Form says yes form this building? Pursuant to Fort Collins City Code § 26-544 & City Land U Block: Subdivi Permit Applicatio Larimer County Parc Larimer County Recepti (on development agree , a Colorado registered profess acilities and grading is complete and hereby submit this certif following questions by initialing the appropriate response. Fo ng how this will affect stormwater drainage for this lot and an ng 10 , 2021 ord Road s, CO 80525 different address but still duplicating from other building forms. ct me. ? Subject: Re: Callout Page Label: 269 Author: Daniel Hull Date: 12/23/2021 3:33:04 PM Status: Color: Layer: Space: This letter was replaced with the a letter from Olsson. Subject: Callout Page Label: 269 Author: dmogen Date: 12/23/2021 3:32:26 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:32:26 PM Color: Layer: Space: please include email. Although, is this necessary to reference or include if the as-built volume is 2376cf? Is there additional media that should be added to the rain garden with the "extra" cross-section depth? The depths of the aggregate/media installed in the rain garden are unclear. Subject: Re: Callout Page Label: 269 Author: Daniel Hull Date: 12/23/2021 3:32:21 PM Status: Color: Layer: Space: This letter was replaced with the a letter from Olsson. Subject: Callout Page Label: 269 Author: dmogen Date: 12/23/2021 3:33:24 PM Status: Completed set by Daniel Hull on 12/23/2021 at 3:33:24 PM Color: Layer: Space: and site visit? Subject: Re: Callout Page Label: 269 Author: Daniel Hull Date: 12/23/2021 3:33:19 PM Status: Color: Layer: Space: This letter was replaced with the a letter from Olsson. 17, 2020 Collins ollege Avenue CO 80524 arden RG-33 Verification ndment to a Portion of Foothills Mall Redevelopment Planning Area 3 5, and 6 of Foothills Mall Redevelopment) May Concern: as evaluated the as-constructed survey information provided by The Weitz Company 14, 2019 related to rain garden RG-33 constructed in the northeast corner of Lot 3 Apartments project located adjacent to Foothills Mall. The design volume of the was 1,165 cubic-feet (with an additional allowed reduction of 10% based on an Dan Mogen dated August 2, 2018) and the as-constructed volume of the rain garden pillway is 2,376 cubic-feet. The designed minimum surface area of the rain garden uare-feet, and the as-constructed surface area is 613 square-feet. See attached my professional opinion, and based solely on the as-constructed survey information The Weitz Company, the as-constructed rain garden meets (or exceeds) the ea and volume requirements set forth in the City-approved site civil construction please include email. Although, is this necessary to reference or include if the as-built volume is 2376cf? Is there additional media that should be added to the rain garden with the "extra" cross-section depth? The depths of the aggregate/media installed in the rain garden are unclear. y is 2,376 cubic-feet. The designed mini feet, and the as-constructed surface area professional opinion, and based solely on Weitz Company, the as-constructed rain nd volume requirements set forth in the C questions or need additional information, p ering, LLC and site visit?