HomeMy WebLinkAboutLot Certifications - 12/09/20191218 W. ASH, STE. A, WINDSOR, COLORADO 80550 December 9, 2019 Mr. Dan Mogen City of Fort Collins Stormwater Utilities 700 Wood Street Fort Collins, Colorado 80522 RE: Gardens on Spring Creek Clarification of Lot Certification Items Dear Dan, Please accept this letter in support of items 1, 4, 5 and 6 of the Certification of Lot Grading dated November 22, 2019 for which we have noted the items as not being in conformance with the checklist description. As a result of this effort, we offer the following for your review and approval: 1.Item 4 – The east end of the new Conservatory building was designed and permitted with a stem wall and water proofing elements in order to allow for the exterior grades to be placed above the finished floor elevation to achieve positive drainage. See attached building permit plans sheets A7.1 and A7.2. Therefore, we would accept this condition as meeting the certification’s intent to ensure the structure is protected from flooding and water damage. 2.Item 5 – Along the east wall of the Conservatory there are locations where the grades are somewhat less than 5% away from the structure; however, this is an area that does not have downspouts and would not be prone to seeing significant drainage. A roof overflow drain is located in this vicinity and a cobble swale with a 4-inch perforated underdrain pipe at 2% to direct any potential overflow drainage to a 5-foot diameter Dry Well that was installed at the southeast corner of the Conservatory. The total area potentially draining to this Dry Well is approximately 500 sf: therefore, it is our opinion that the site grading is in general conformance to the design intent reflected on the final plans. 3.Item 6 – The cobble swale noted above does not maintain a consistent 2% grade in the flowline; however, the swale has a 4-inch perforated underdrain that was installed at approximately 2% grade to the Dry Well. Therefore, it is our opinion that the site drainage is in general conformance to the design intent reflected on the final plans. This letter is intended to supplement the Certification of Lot Grading and supports our belief that the grading and drainage for the referenced project has been completed substantially in conformance with the approved grading plan. We therefore request that the project listed above be deemed acceptable to the City of Fort Collins. 1218 W. ASH, STE. A, WINDSOR, COLORADO 80550 If you should have any questions or comments, please contact me at 460-8487. Thank you for your consideration. 12-9-19 2145 CENTRE AVE. 2145 CENTRE AVENUE FFE=5003.30 12 1 8 W . A s h , S u i t e A Wi n d s o r , C o l o r a d o 8 0 5 5 0 Ph o n e : ( 9 7 0 ) 6 7 4 - 3 3 0 0 Fa x : ( 9 7 0 ) 6 7 4 - 3 3 0 3 C O N S U L T I N G G R O U P I N T E R W E S T PR E P A R E D F O R PROJ. NO. DA T E : SC A L E ( H ) : SC A L E ( V ) : CH E C K E D B Y : DE S I G N E D B Y : PR O J E C T N A M E Ce n t r e F o r A d v a n c e d T e c h n o l o g y 2 2 n d F i l i n g Co m m u n i t y H o r t i c u l t u r e C e n t e r GR A D I N G P L A N 03 / 2 8 / 2 0 1 9 N/ A N/ A LA J RA 1370-095-00 1 of 3 AR C H I T E C T U R E W E S T , L L C 16 0 P A L M E R D R I V E FO R T C O L L I N S , C O 8 0 5 2 5 PH . 9 7 0 . 2 0 7 . 0 4 2 4 0 10' 2010510 SCALE: 1" = CHECKED BY: Date City of Fort Collins, Colorado UTILITY PLAN APPROVAL Parks and Recreation Traffic Engineer Stormwater Utility Water & Wastewater Utility City Engineer CHECKED BY: APPROVED: Environmental Planner CHECKED BY: CHECKED BY: CHECKED BY: CHECKED BY: Date Date Date Date Date Date CALL BEFORE YOU DIG CALL UTILITY NOTIFICATION CENTER OF COLORADO 1-800-922-1987 or 8-1-1 CALL 2-BUSINESS DAYS IN ADVANCE BEFORE YOU DIG, GRADE OR EXCAVATE FOR THE MARKING OF UNDERGROUND MEMBER UTILITIES. NOTES 1.ALL PROPOSED FLATWORK AND ASSOCIATED SPOT ELEVATION LOCATIONS SHOULD BE RELATIVE TO THE EXISTING BUILDING AND THE PROPOSED ADDITION. REFER TO ARCHITECTURAL PLANS FOR ALL BUILDING CORNER LOCATIONS AND GEOMETRY. THIS IS TO BE VERIFIED BY THE CONTRACTOR. 2.CONTRACTOR TO PROVIDE AND MAINTAIN ALL NECESSARY EROSION CONTROL MEASURES PRIOR TO AND THROUGHOUT CONSTRUCTION. PLACE EROSION CONTROL PROTECTION AT ALL EXISTING INLETS DOWNSTREAM FROM THE CONSTRUCTION AREA. EROSION CONTROL PROTECTION SHALL REMAIN IN PLACE UNTIL CONSTRUCTION IS COMPLETE AND ALL DISTURBED GROUND IS ADEQUATELY VEGETATED WITH OWNER'S APPROVAL FOR REMOVAL. 3.ALL MANHOLE RIM AND STORM DRAIN INLET GRATES SHALL BE ADJUSTED TO FINAL GRADES CONFIRMED IN THE FIELD. 4.ALL SUBGRADE TO BE PLACED/COMPACTED PER GEOTECHNICAL ENGINEER RECOMMENDATIONS. 5.ALL WALKS TO HAVE MAXIMUM 2.0% CROSS SLOPE TOWARDS PARKING AREAS, DRIVES, AND AWAY FROM STRUCTURES. 6.NO FILL SHALL BE PLACED IN THE FLOODWAY. 7.A FLOODPLAIN USE PERMIT IS REQUIRED PRIOR TO ANY CONSTRUCTION ACTIVITY, SUCH AS DRIVEWAYS, SIDEWALKS, UTILITY INSTALLATION, ETC., IN THE FLOODPLAIN / FLOOD FRINGE. 8.ANY UTILITY WORK IN THE FLOODWAY MUST BE PRECEDED BY A FLOODPLAIN USE PERMIT AND NO-RISE CERTIFICATION. 9.STORAGE OF EQUIPMENT AND/OR MATERIALS IS NOT ALLOWED WITHIN THE FLOODPLAIN. 100-YR FLOOD FRINGE 100-YR FLOODWAY LEGEND SITE FEATURES TO BE REMOVED (re: architectural plans) EMERGENCY ACCESS DETAIL BUILDING EXTERIOR DOOR PROPOSED HARDSCAPE AREA (re: architectural plans for material and patterns) PROJECT DATUM: NAVD88 BENCHMARK # 2-08 NORTH SIDE OF PROSPECT RD. APPROX. 0.5 MILES EAST OF LEMAY AVE. ON THE ISLAND CURB AT LONGS PEAK RD. ELEVATION: 4958.58 BENCHMARK #14-97 APPROXIMATELY 100 FEET WEST OF THE INTERSECTION OF CENTRE AVE. AND RESEARCH BLVD., ON THE WEST END OF THE SOUTH HEADWALL ON CENTRE AVE. ELEVATION: 5051.76 PLEASE NOTE: THIS PLAN SET IS USING NAVD88 FOR A VERTICAL DATUM. SURROUNDING DEVELOPMENTS HAVE USED NGVD29 UNADJUSTED (PRIOR CITY OF FORT COLLINS DATUM) FOR THEIR VERTICAL DATUMS. IF NGVD29 UNADJUSTED DATUM (PRIOR CITY OF FORT COLLINS DATUM) IS REQUIRED FOR ANY PURPOSE, THE FOLLOWING EQUATION SHOULD BE USED: NGVD29 UNADJUSTED (PRIOR CITY OF FORT COLLINS DATUM) = NAVD88 - 3.18' RECORD DRAWING THIS RECORD DRAWING HAS BEEN PREPARED, IN PART, BASED UPON INFORMATION FURNISHED BY OTHERS. WHILE THIS INFORMATION IS BELIEVED TO BE RELIABLE, INTERWEST CONSULTING GROUP AND THE CERTIFYING ENGINEER ASSUMES NO RESPONSIBILITY FOR THE ACCURACY OF THIS RECORD DRAWING DUE TO ANY ERRORS OR OMISSIONS THAT MAY HAVE BEEN INCORPORATED INTO IT AS A RESULT OF INCORRECT INFORMATION PROVIDED TO INTERWEST CONSULTING GROUP AND THE CERTIFYING ENGINEER. THOSE RELYING ON THIS RECORD DOCUMENT ARE ADVISED TO OBTAIN INDEPENDENT VERIFICATION OF ITS ACCURACY. DATE: DENOTES RECORDED DATA PER 11/22/19 KING SURVEYORS This unofficial copy was downloaded on Nov-25-2019 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA This unofficial copy was downloaded on Nov-25-2019 from the City of Fort Collins Public Records Website: http://citydocs.fcgov.com For additional information or an official copy, please contact Engineering Office 281 North College Fort Collins, CO 80521 USA SYSTEM NOTESSYSTEM NOTESSYSTEM NOTESSYSTEM NOTES---- ROOFSROOFSROOFSROOFS DESIGNATIONDESIGNATIONDESIGNATIONDESIGNATION DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION R2 FULLY ADHERED MEMBRANE ROOF OVER 3" RIGID INSULATION (R-21), 14”& 16" (R-44) BLOWN IN BATT INSULATION AND WOOD STRUCTURE BELOW, (REF: STR'L.) ROOF GENERAL NOTES 1. VERIFY ALL EXISTING ROOF ASSEMBLIES AND CONDITIONS AS REQUIRED 2. VERIFY & COORDINATE ALL DIMENSIONS WITH EXISTING CONDITIONS. 3. NOTIFY ARCHITECT IMMEDIATELY WITH ANY DISCREPENCIES REGARDING THE CONTRACT DOCUMENTS. R1 EXISTING ROOF TO REMAIN R4 INSULATED GLAZING IN ALUMNIMUM FRAME SYSTEM (VENDOR SUPPLIED) R3 FULLY ADHERED MEMBRANE ROOF OVER 3" RIGID INSULATION (R-21), 12”(R-38) BLOWN IN BATT INSULATION AND WOOD STRUCTURE BELOW, (REF: STR'L.) SYSTEM NOTESSYSTEM NOTESSYSTEM NOTESSYSTEM NOTES---- CEILINGSCEILINGSCEILINGSCEILINGS DESIGNATIONDESIGNATIONDESIGNATIONDESIGNATION DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION C2 2X4 SUSPENDED ACOUSTICAL CEILING TILE SYSTEM C3 2X2 SUSPENDED ACOUSTICAL CEILING TILE SYSTEM C4 1/2" GYP. BOARD (OVER WD. FRAMING, REF: STR’L.) C5 1"X CLEAR SEALED BEETLE-KILL PINE T&G CEILING, OVER OSB WOOD SHEETING AND WOOD STRUCTURE CEILING GENERAL NOTES 1. VERIFY ALL EXISTING CEILING ASSEMBLIES AND CONDITIONS AS REQUIRED 2. ALL CEILINGS TO BE C2 UNLESS OTHERWISE NOTED 3. REFERENCE INTERIOR ELEVATIONS & MECHANICAL FOR SOFFIT LOCATIONS C1 EXISTING CEILING SYSTEM (TO REMAIN) C6 GREENHOUSE ROOF STRUCTURE B.O. (REF:VENDOR/SUPPLIER) S2 GYP. BOARD SOFFITS (OVER FRAMING, REF:STR'L) S1 P.F.M. SOFFITS (OVER WOOD FRAMING, REF:STR'L) SYSTEM NOTESSYSTEM NOTESSYSTEM NOTESSYSTEM NOTES---- WALLSWALLSWALLSWALLS DESIGNATIONDESIGNATIONDESIGNATIONDESIGNATION DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION W1 EXISTING WALL (TO REMAIN) W5 ALUMINUM STOREFRONT SYSTEM W/ INSULATED GLAZING W6A 2"X6" WOOD STUDS W6B 2"X6" WOOD STUDS WITH 1”SPRAY FOAM (R-7) FLASH-IN BATTS, WITH BLOWN-IN BATT INSULATION (R-15), ½” EXTERIOR GRADE SHEATHING, AIR BARRIER, UNDER 1” RIGID INSULATION (R-7) & HARDCOAT STUCCO FINISH W6C 2"X6" WOOD STUDS WITH 1”SPRAY FOAM (R-7) FLASH-IN BATTS, WITH BLOWN-IN BATT INSULATION (R-15), ½” EXTERIOR GRADE SHEATHING, AIR BARRIER, UNDER 1” RIGID INSULATION (R-7) & 4”STONE VENEER, (PROVIDE WALL ANCHORS, WEEPS & FLASHING) W8 8" CMU WALL (REF: STR'L.) W9 REINFORCED CONCRETE FOUNDATION WALLS & FOOTINGS (REF: STR'L.) A (STANDARD) 1 LAYER OF 5/8" GYPSUM BOARD ON EACH SIDE OF STUD FRAMING WITH SOUND BATT INSULATION (R-13 MIN.) IN STUD CAVITIES, EXTEND FRAMING, SOUND BATTS AND GYPSUM TO UNDERSIDE OF ROOF OR FLOOR SYSTEM ABOVE, USE SLIP TRACK CHANNEL, B (ONE SIDE FINISHED) 1 LAYER OF 5/8" GYPSUM BOARD ON ONE SIDE OF STUD FRAMING ONLY C (ONE SIDE FINISHED) 1 LAYER OF 5/8" GYPSUM BOARD ON ONE SIDE OF STUD FRAMING, FRAMING TO EXTEND FULL HEIGHT TO ATTACH TO UNDERSIDE OF ROOF OR FLOOR SYSTEM ABOVE, USE SLIP TRACK CHANNEL E (WET WALL) 1 LAYER OF 5/8" MOISTURE-RESISTANT (MR) GYPSUM BOARD ON WET WALL SIDE OF STUD FRAMING D (FURRING WALL) 1 LAYER OF 5/8" GYPSUM BOARD ON 2-1/2" STUDS AT 16" O.C. EXTEND TO 2" ABOVE ADJACENT CEILINGS GENERAL WALL NOTES 1. ALL WALLS TO BE W3-A UNLESS OTHERWISE NOTED 2. PROVIDE DOUBLE 20 GA. STUDS (MIN.) AT ALL DOOR JAMBS 3. ALL DIMENSIONS ARE TO GRID LINES, FACE OF STUDS OR MASONRY WALL UNLESS OTHERWISE NOTED 4. EXTEND GYPSUM BOARD ON WALLS TO 2" ABOVE ALL ADJACENT CEILINGS AND TO UNDERSIDE OF GYPSUM CEILINGS UNLESS OTHERWISE NOTED 5. PROVIDE GYPSUM CONTROL JOINTS IN WALLS OVER 25' IN LENGTH W2A 2 1/2" METAL FURRING WITH 1/2" WOOD SHEATHING AND 5/8" GYP. BOARD W2B 2 1/2" METAL FURRING WITH 1/2" WOOD SHEATHING AND STUCCO HARDCOAT W4 2"X4" WOOD STUDS W7 6" CHAISE WALL (REF: PLUMBING) W4B 2 2"X4" WOOD STUDS WITH 2" RIGID INSULATION W12 12" REINFORCED CONCRETE WALL (REF: STR'L.) W10 SANDED FACE OF EXISTING CMU WITH APPLIED FINISH 1 SYSTEM NOTESSYSTEM NOTESSYSTEM NOTESSYSTEM NOTES---- FLOORSFLOORSFLOORSFLOORS DESIGNATIONDESIGNATIONDESIGNATIONDESIGNATION DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION F2 SEALED 4" CONCRETE SLABS OVER 4" GRAVEL (REF: STR'L.) F3 WOOD DECKING ON JOISTS (REF: STR'L) F1 EXISTING CONCRETE FLOORS (TO REMAIN) P2 EXISTNG CONCRETE WALKS TO REMAIN, PATCH & REPAIR AS NEEDED P3 EXISTING STONE PAVERS REMOVED AND REINSTALLED P1 EXISTING TO REMAIN, PATCH & REPAIR AS NEEDED P4 NEW 4" CONCRETE WALKS P5 NEW/REPLACEMENT DRIVEWAY PAVEMENT (REF: GEO-TECHNICAL) R4 R2 R2 C2C2 C2 F2 23.03 W6B W8B CONFERENCECONFERENCECONFERENCECONFERENCE 313 CONSERVATORYCONSERVATORYCONSERVATORYCONSERVATORY 308 LOBBYLOBBYLOBBYLOBBY 301 5342 61 (BY OTHERS)(BY OTHERS)(BY OTHERS)(BY OTHERS) 3' - 0" 115' - 3 1/4" CRICKET TO R.D.113' - 4" 110' - 10 1/2" 1' - 4" C5 C2 W6C A 23.03 23.03 6.04 6.036.03 F2F2F2 R4 R2 CONSERVATORYCONSERVATORYCONSERVATORYCONSERVATORY 308 CAFECAFECAFECAFE 306 LOBBYLOBBYLOBBYLOBBY 301 C2 5342 61 W4 305 102' - 0 3/4" GIFT SHOPGIFT SHOPGIFT SHOPGIFT SHOP 312 1' - 6" 1' - 6" B 8.04 CRICKET TO R.D.113' - 4 3/4" 108' - 7" 109' - 10" 110' - 10 1/2" R2 C5 RECEPTIONRECEPTIONRECEPTIONRECEPTION 303 CONSERVATORYCONSERVATORYCONSERVATORYCONSERVATORY 308 LOBBYLOBBYLOBBYLOBBY 301301301301 R4 F2 8.04 W6B A W5 S1 P2 534 6 A7.2 2 GIFT SHOPGIFT SHOPGIFT SHOPGIFT SHOP 312 CRICKET TO R.D.1' - 6" 110' - 10 1/2" 113' - 4 3/4" 111' - 5 1/2" SHEET NUMBER SHEET NAME ISSUE DATE REVISIONS CHECKED BY JOB NUMBER DRAWN BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER THE COPYRIGHT PROTECTION ACT OF 1990. -ALL CONSTRUCTION SHALL CONFORM TO CURRENT UNIFORM BUILDING CODE AND ALL OTHER APPLICABLE CODES. -DO NOT SCALE DRAWINGS FOR DIMENSIONS. CONSTRUCTION MANAGERS, SUB-CONTRACTORS AND ALL OTHER SUPPLIERS TO THIS PROJECT, HAVE THE COMPLETE RESPONSIBILITY TO NOTIFY ENGINEERS, ARCHITECTS AND ALL OTHER DESIGN PROFESSIONALS OF ANY DIS-CREPANCIES, CONFLICTS, BUILDING OR OTHER CODE REQUIREMENTS AS REP-RESENTED BY THESE CONSTRUCTION DOCUMENTS. ANY PROFESSIONAL LIABILITY CLAIMS SHALL BE LIMITED TO THE EXTENT OF SAID DESIGNERS FEE, ONLY AND IS HEREBY RECOGNIZED AS SUCH BY ANY CLAIMANTS, OWNERS, LIEN HOLDERS OR OTHERS. A7.1 SECTIONS-BUILDING 12.07.18 Checker Author Project Number CI T Y O F F O R T C O L L I N S 21 4 5 C E N T R E A V E . FO R T C O L L I N S , C O 8 0 5 2 6 TH E G A R D E N S O N S P R I N G C R E E K 04.18.19 KEY NOTESKEY NOTESKEY NOTESKEY NOTES NO.NO.NO.NO. DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION 1.01 OWNER PROVIDED EQUIPMENT - VERIF & COORD. 2.01 EXISTING TO BE RELOCATED 5.01 PRE-FINISHED METAL FLASHING, GUTTERS & DOWNSPOUTS 5.02 8"X8" STL. PTD. COLUMN (REF:STR'L) 6.02 EXISTING CABINETS/ CASEWORK 6.03 NEW CABINETS/ CASEWORK 6.04 COUNTERTOP 6.05 WALL MOUNTED MIRROR 7.01 ROOF VENT/ PENETRATIONS (BY VENDOR) 7.02 ROOF DRAIN & OVERFLOW SCUPPERS (REF: M&P) 7.03 EX. ROOF DRAIN TO REMAIN 7.04 EX. ROOF DRAIN DEMO 8.01 GYP. BOARD BULKHEAD 8.02 ATTIC ACCESS PANEL AS REQUIRED 8.03 INSULATED ROLLING GRILLE 8.04 SECURITY GATE 8.05 AUTO DOOR OPERATORS 9.01 PLYWOOD WALL FINISH 10.01 FOLDING PARTITION WALL 11.01 LOCKERS 13.01 LIVING WALL B.O. (VERIFY & COORD. ALL REQUIREMENTS.) 16.01 ELECTRICAL PANEL (REF: ELECTRICAL) 22.01 FLOOR DRAIN ( REF: PLUMBING DRWG) 22.02 MOP SINK (REF: PLUMBING) 22.03 DRINKING FOUNTAIN (REF: PLUMBING) 23.01 EXISTING EQUIPMENT (REF: MECHANICAL) 23.02 NEW MECHANICAL EQUIPMENT (REF: MECHANICAL) 23.03 FUTURE P.V. PANELS 23.04 ROOF LINE ABOVE 23.05 LIGHT TUBES 26.01 TV MONITOR (B.O.) 1/4" = 1'-0"A7.1 1 SSSS----N BUILDING SECTIONN BUILDING SECTIONN BUILDING SECTIONN BUILDING SECTION 1/4" = 1'-0"A7.1 2 NNNN----S BUILDING SECTIONS BUILDING SECTIONS BUILDING SECTIONS BUILDING SECTION 1/4" = 1'-0"A7.1 3 SSSS----N LOBBY SECTIONN LOBBY SECTIONN LOBBY SECTIONN LOBBY SECTION NOTE: PROVIDE CONTINUOUS EXTERIOR AIR BARRIER & SEALING AT ALL EXTERIOR WALLS, CONNECTIONS TO NEW EXISTING CONSTRUCTION. ALL EXTERIOR WALL CAVITIES TO HAVE 1” MIN. FOAM SEALING (AT EXTERIOR WALL FACE) WITH FULL DEPTH B.I.B. BLOWN IN BATT INSULATION, WALLS AND ROOFS CAULK/FOAM AT ALL JOINTS, CHANGE IN MATERIALS, FRAMING CONNECTIONS, PENETRATIONS. 1 1 1 1 1 1 1 1 1 1 SYSTEM NOTESSYSTEM NOTESSYSTEM NOTESSYSTEM NOTES---- ROOFSROOFSROOFSROOFS DESIGNATIONDESIGNATIONDESIGNATIONDESIGNATION DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION R2 FULLY ADHERED MEMBRANE ROOF OVER 3" RIGID INSULATION (R-21), 14”& 16" (R-44) BLOWN IN BATT INSULATION AND WOOD STRUCTURE BELOW, (REF: STR'L.) ROOF GENERAL NOTES 1. VERIFY ALL EXISTING ROOF ASSEMBLIES AND CONDITIONS AS REQUIRED 2. VERIFY & COORDINATE ALL DIMENSIONS WITH EXISTING CONDITIONS. 3. NOTIFY ARCHITECT IMMEDIATELY WITH ANY DISCREPENCIES REGARDING THE CONTRACT DOCUMENTS. R1 EXISTING ROOF TO REMAIN R4 INSULATED GLAZING IN ALUMNIMUM FRAME SYSTEM (VENDOR SUPPLIED) R3 FULLY ADHERED MEMBRANE ROOF OVER 3" RIGID INSULATION (R-21), 12”(R-38) BLOWN IN BATT INSULATION AND WOOD STRUCTURE BELOW, (REF: STR'L.) SYSTEM NOTESSYSTEM NOTESSYSTEM NOTESSYSTEM NOTES---- CEILINGSCEILINGSCEILINGSCEILINGS DESIGNATIONDESIGNATIONDESIGNATIONDESIGNATION DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION C2 2X4 SUSPENDED ACOUSTICAL CEILING TILE SYSTEM C3 2X2 SUSPENDED ACOUSTICAL CEILING TILE SYSTEM C4 1/2" GYP. BOARD (OVER WD. FRAMING, REF: STR’L.) C5 1"X CLEAR SEALED BEETLE-KILL PINE T&G CEILING, OVER OSB WOOD SHEETING AND WOOD STRUCTURE CEILING GENERAL NOTES 1. VERIFY ALL EXISTING CEILING ASSEMBLIES AND CONDITIONS AS REQUIRED 2. ALL CEILINGS TO BE C2 UNLESS OTHERWISE NOTED 3. REFERENCE INTERIOR ELEVATIONS & MECHANICAL FOR SOFFIT LOCATIONS C1 EXISTING CEILING SYSTEM (TO REMAIN) C6 GREENHOUSE ROOF STRUCTURE B.O. (REF:VENDOR/SUPPLIER) S2 GYP. BOARD SOFFITS (OVER FRAMING, REF:STR'L) S1 P.F.M. SOFFITS (OVER WOOD FRAMING, REF:STR'L) SYSTEM NOTESSYSTEM NOTESSYSTEM NOTESSYSTEM NOTES---- WALLSWALLSWALLSWALLS DESIGNATIONDESIGNATIONDESIGNATIONDESIGNATION DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION W1 EXISTING WALL (TO REMAIN) W5 ALUMINUM STOREFRONT SYSTEM W/ INSULATED GLAZING W6A 2"X6" WOOD STUDS W6B 2"X6" WOOD STUDS WITH 1”SPRAY FOAM (R-7) FLASH-IN BATTS, WITH BLOWN-IN BATT INSULATION (R-15), ½” EXTERIOR GRADE SHEATHING, AIR BARRIER, UNDER 1” RIGID INSULATION (R-7) & HARDCOAT STUCCO FINISH W6C 2"X6" WOOD STUDS WITH 1”SPRAY FOAM (R-7) FLASH-IN BATTS, WITH BLOWN-IN BATT INSULATION (R-15), ½” EXTERIOR GRADE SHEATHING, AIR BARRIER, UNDER 1” RIGID INSULATION (R-7) & 4”STONE VENEER, (PROVIDE WALL ANCHORS, WEEPS & FLASHING) W8 8" CMU WALL (REF: STR'L.) W9 REINFORCED CONCRETE FOUNDATION WALLS & FOOTINGS (REF: STR'L.) A (STANDARD) 1 LAYER OF 5/8" GYPSUM BOARD ON EACH SIDE OF STUD FRAMING WITH SOUND BATT INSULATION (R-13 MIN.) IN STUD CAVITIES, EXTEND FRAMING, SOUND BATTS AND GYPSUM TO UNDERSIDE OF ROOF OR FLOOR SYSTEM ABOVE, USE SLIP TRACK CHANNEL, B (ONE SIDE FINISHED) 1 LAYER OF 5/8" GYPSUM BOARD ON ONE SIDE OF STUD FRAMING ONLY C (ONE SIDE FINISHED) 1 LAYER OF 5/8" GYPSUM BOARD ON ONE SIDE OF STUD FRAMING, FRAMING TO EXTEND FULL HEIGHT TO ATTACH TO UNDERSIDE OF ROOF OR FLOOR SYSTEM ABOVE, USE SLIP TRACK CHANNEL E (WET WALL) 1 LAYER OF 5/8" MOISTURE-RESISTANT (MR) GYPSUM BOARD ON WET WALL SIDE OF STUD FRAMING D (FURRING WALL) 1 LAYER OF 5/8" GYPSUM BOARD ON 2-1/2" STUDS AT 16" O.C. EXTEND TO 2" ABOVE ADJACENT CEILINGS GENERAL WALL NOTES 1. ALL WALLS TO BE W3-A UNLESS OTHERWISE NOTED 2. PROVIDE DOUBLE 20 GA. STUDS (MIN.) AT ALL DOOR JAMBS 3. ALL DIMENSIONS ARE TO GRID LINES, FACE OF STUDS OR MASONRY WALL UNLESS OTHERWISE NOTED 4. EXTEND GYPSUM BOARD ON WALLS TO 2" ABOVE ALL ADJACENT CEILINGS AND TO UNDERSIDE OF GYPSUM CEILINGS UNLESS OTHERWISE NOTED 5. PROVIDE GYPSUM CONTROL JOINTS IN WALLS OVER 25' IN LENGTH W2A 2 1/2" METAL FURRING WITH 1/2" WOOD SHEATHING AND 5/8" GYP. BOARD W2B 2 1/2" METAL FURRING WITH 1/2" WOOD SHEATHING AND STUCCO HARDCOAT W4 2"X4" WOOD STUDS W7 6" CHAISE WALL (REF: PLUMBING) W4B 2 2"X4" WOOD STUDS WITH 2" RIGID INSULATION W12 12" REINFORCED CONCRETE WALL (REF: STR'L.) W10 SANDED FACE OF EXISTING CMU WITH APPLIED FINISH 1 SYSTEM NOTESSYSTEM NOTESSYSTEM NOTESSYSTEM NOTES---- FLOORSFLOORSFLOORSFLOORS DESIGNATIONDESIGNATIONDESIGNATIONDESIGNATION DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION F2 SEALED 4" CONCRETE SLABS OVER 4" GRAVEL (REF: STR'L.) F3 WOOD DECKING ON JOISTS (REF: STR'L) F1 EXISTING CONCRETE FLOORS (TO REMAIN) P2 EXISTNG CONCRETE WALKS TO REMAIN, PATCH & REPAIR AS NEEDED P3 EXISTING STONE PAVERS REMOVED AND REINSTALLED P1 EXISTING TO REMAIN, PATCH & REPAIR AS NEEDED P4 NEW 4" CONCRETE WALKS P5 NEW/REPLACEMENT DRIVEWAY PAVEMENT (REF: GEO-TECHNICAL) S1S1 R2 F2 C5 W5 W6B ENTRYENTRYENTRYENTRY 300 LOBBYLOBBYLOBBYLOBBY 301 F 300 E C.U.H. OPEN TO R.R. SLOPE DOWN CRICKET W2A 111' - 2 1/4" 10' -9" 111' - 6 1/4" 11' -2 1/2" A W6B C1 C4 WOMEN'S RRWOMEN'S RRWOMEN'S RRWOMEN'S RR 304 FAMILY RRFAMILY RRFAMILY RRFAMILY RR 112 MEN'S RRMEN'S RRMEN'S RRMEN'S RR 113 1.1 3.12.1 R3 NEW 2"x4' CONTINUOUS RIGID INSULATION S2 EX.EX.EX.EX.EX.EX.EX.EX. SLOPE DOWN 108' - 4 1/2" 108' - 7" 110' - 0" 7 1/4" MECHANICALMECHANICALMECHANICALMECHANICAL 311 CHRYSALISCHRYSALISCHRYSALISCHRYSALIS 310 VESTIBULEVESTIBULEVESTIBULEVESTIBULE 309 C4C2 R2 W6B A W4 A W4 A S1 308B 4 6 R1 W4 B S2 9' - 8" 1' - 6" F2 F2 F2 SLOPE DOWN 1/4:12 P4 5. 0 1 109' - 8" OVERHANG 5' - 5" 109' - 2" BRG S1 R2 R4 P4 D CONSERVATORYCONSERVATORYCONSERVATORYCONSERVATORY 308 113' - 4 3/4" W8 W8D B R4 GREENHOUSE WALLS & FRAMING B.O. 4" CONCRETE OVER 4" GRAVEL 2" CONTINUOUS R-10 RIGID INSULTATION W5 METAL FLASHING A7.3 H 6 1/2" EXPANSION JOINT & CONTINUOUS CAULKING 114' - 0 3/4" W8B 13.01 R4 R2 C2 5.01 4 WORKWORKWORKWORK STATIONSSTATIONSSTATIONSSTATIONS 315 CONSERVATORYCONSERVATORYCONSERVATORYCONSERVATORY 308 GREENHOUSE WALLS & FRAMING SLOPED (B.O.) 2 A7.2 113' - 4 3/4" CRICKET TO R.D. INSULATED GLAZING AND METAL CONSERVATORY (B.O.), VERIFY & COORD. ALL REQUIREMENTS W8B R2 R4 ADHERED TPO MEMBRANE ROOF (& AIR BARRIER) OVER 3” RIGID INSULATION (R-21) OVER M.R. SHEATHING, WOOD RAFTERS (REF: STR’L.), WITH FULL DEPTH (BIB) BLOWN-IN BATT INSULATION (R-44) AND ½” GYP. BOARD FINISH 1” AIR CAVITY WOOD RAFTERS & BLOWN IN BATT INSULATION (REF: STRL) 5/8” GYPSUM BOARD OVER 2X6 STUD WALLS WITH BATT INSULATION (R-19), ½” M.R. SHTH'G AND FLUID APPLIED AIR/MOISTURE BARRIER 8” (CMU) CONCRETE MASONRY UNIT WITH INTEGRAL WATER REPELLANT (IWR) & COLOR AND 1” AIR SPACE REINF’D. CMU (REF: STR’L.) CONTINUOUS AIR BARRIER INTERIOR FACE OF CMU (TYPICAL) BLOWN IN BATT INSULATION CONT. P.F. METAL FLASHING (INT. TO EXTERIOR) ROOF SLOPE DOWN 6"1"8" 3/4" MOISTURE TREATED PLYWOODCRICKET SHEET NUMBER SHEET NAME ISSUE DATE REVISIONS CHECKED BY JOB NUMBER DRAWN BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION AS AN 'ARCHITECTURAL WORK' UNDER THE COPYRIGHT PROTECTION ACT OF 1990. -ALL CONSTRUCTION SHALL CONFORM TO CURRENT UNIFORM BUILDING CODE AND ALL OTHER APPLICABLE CODES. -DO NOT SCALE DRAWINGS FOR DIMENSIONS. CONSTRUCTION MANAGERS, SUB-CONTRACTORS AND ALL OTHER SUPPLIERS TO THIS PROJECT, HAVE THE COMPLETE RESPONSIBILITY TO NOTIFY ENGINEERS, ARCHITECTS AND ALL OTHER DESIGN PROFESSIONALS OF ANY DIS-CREPANCIES, CONFLICTS, BUILDING OR OTHER CODE REQUIREMENTS AS REP-RESENTED BY THESE CONSTRUCTION DOCUMENTS. ANY PROFESSIONAL LIABILITY CLAIMS SHALL BE LIMITED TO THE EXTENT OF SAID DESIGNERS FEE, ONLY AND IS HEREBY RECOGNIZED AS SUCH BY ANY CLAIMANTS, OWNERS, LIEN HOLDERS OR OTHERS. A7.2 SECTIONS-BUILDING & WALL 12.07.18 Checker Author Project Number CI T Y O F F O R T C O L L I N S 21 4 5 C E N T R E A V E . FO R T C O L L I N S , C O 8 0 5 2 6 TH E G A R D E N S O N S P R I N G C R E E K 04.18.19 KEY NOTESKEY NOTESKEY NOTESKEY NOTES NO.NO.NO.NO. DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION 1.01 OWNER PROVIDED EQUIPMENT - VERIF & COORD. 2.01 EXISTING TO BE RELOCATED 5.01 PRE-FINISHED METAL FLASHING, GUTTERS & DOWNSPOUTS 5.02 8"X8" STL. PTD. COLUMN (REF:STR'L) 6.02 EXISTING CABINETS/ CASEWORK 6.03 NEW CABINETS/ CASEWORK 6.04 COUNTERTOP 6.05 WALL MOUNTED MIRROR 7.01 ROOF VENT/ PENETRATIONS (BY VENDOR) 7.02 ROOF DRAIN & OVERFLOW SCUPPERS (REF: M&P) 7.03 EX. ROOF DRAIN TO REMAIN 7.04 EX. ROOF DRAIN DEMO 8.01 GYP. BOARD BULKHEAD 8.02 ATTIC ACCESS PANEL AS REQUIRED 8.03 INSULATED ROLLING GRILLE 8.04 SECURITY GATE 8.05 AUTO DOOR OPERATORS 9.01 PLYWOOD WALL FINISH 10.01 FOLDING PARTITION WALL 11.01 LOCKERS 13.01 LIVING WALL B.O. (VERIFY & COORD. ALL REQUIREMENTS.) 16.01 ELECTRICAL PANEL (REF: ELECTRICAL) 22.01 FLOOR DRAIN ( REF: PLUMBING DRWG) 22.02 MOP SINK (REF: PLUMBING) 22.03 DRINKING FOUNTAIN (REF: PLUMBING) 23.01 EXISTING EQUIPMENT (REF: MECHANICAL) 23.02 NEW MECHANICAL EQUIPMENT (REF: MECHANICAL) 23.03 FUTURE P.V. PANELS 23.04 ROOF LINE ABOVE 23.05 LIGHT TUBES 26.01 TV MONITOR (B.O.) 1/4" = 1'-0"A7.2 1 EAST LOBBY SECTIONEAST LOBBY SECTIONEAST LOBBY SECTIONEAST LOBBY SECTION 1/4" = 1'-0"A7.2 3 EAST RESTROOM SECTIONEAST RESTROOM SECTIONEAST RESTROOM SECTIONEAST RESTROOM SECTION 1/4" = 1'-0"A7.2 4 EAST CHRYSALIS SECTIONEAST CHRYSALIS SECTIONEAST CHRYSALIS SECTIONEAST CHRYSALIS SECTION 3/4" = 1'-0"A7.2 A WALL SECTION AWALL SECTION AWALL SECTION AWALL SECTION A 3/4" = 1'-0"A7.2 B WALL SECTION BWALL SECTION BWALL SECTION BWALL SECTION B 3/4" = 1'-0"A7.2 C WALL SECTION CWALL SECTION CWALL SECTION CWALL SECTION C ARCADIA GLAZING SYSTEM SLOPED (B.O.) NOTE: PROVIDE CONTINUOUS EXTERIOR AIR BARRIER & SEALING AT ALL EXTERIOR WALLS, CONNECTIONS TO NEW EXISTING CONSTRUCTION. ALL EXTERIOR WALL CAVITIES TO HAVE 1” MIN. FOAM SEALING (AT EXTERIOR WALL FACE) WITH FULL DEPTH B.I.B. BLOWN IN BATT INSULATION, WALLS AND ROOFS CAULK/FOAM AT ALL JOINTS, CHANGE IN MATERIALS, FRAMING CONNECTIONS, PENETRATIONS. METAL FLASHING SET IN A FULL BED OF SEALANT AGAINST THE AIR BARRIER TO PREVENT AIR LEAKAGE AND WATER PENETRATION BETWEEN THE FLASHING AND AIR BARRIER TO ALLOW CONTINUITY BETWEEN THE GREENHOUSE AND WALL ASSEMBLY CONTINUOUS AIR BARRIER METAL FLASHING SET IN A FULL BED OF SEALANT AGAINST THE AIR BARRIER TO PREVENT AIR LEAKAGE AND WATER PENETRATION BETWEEN THE FLASHING AND AIR BARRIER TO ALLOW CONTINUITY BETWEEN THE GREENHOUSE AND WALL ASSEMBLY CONTINUOUS AIR BARRIER REF: STRUCTURAL & ARCADIA DETAILS 1 1/2" = 1'-0"A7.2 2 CONSERVATORY ROOF DETAILCONSERVATORY ROOF DETAILCONSERVATORY ROOF DETAILCONSERVATORY ROOF DETAIL 1 1 1 1 1 1 3/4" MOISTURE TREATED PLYWOOD CONTINUOUS VERTICAL MEMBRANE 1" AIR SPACE 1" AIR CAVITY 1 1 1 111