HomeMy WebLinkAboutWater - D16A - STANDARD SETTING FOR 1 1/2-INCH AND 2-INCH WATER METERS (PDF) - 4/20/20226"8" LAYER OF 3/4" TO 1 1/2" GRAVEL8"12"
(MIN.)
CURB BOX
1-1/2" METERS
FLOW
2" METERS
17 1/4" FOR
13 1/4" FOR
48"
24"54" (MIN.)66" (MAX.)16" (MAX.)7" (MIN.)3" (MAX.)
1" (MAX.)
2' (MAX.)
3/4" ROCK FOR GRADE
ADJUSTMENT (IF REQ'D)
12"
(MIN.)(MAX.)CURB STOP
GENERAL NOTES:
1.SUPPORT METER SETTERS BY (2) 18 INCH LENGTHS OF 1 INCH IRON PIPE INSERTED THROUGH BRACE PIPE EYELETS AND SET ATOP (4) 8 INCH SQUARE CONCRETE BLOCKS OR APPROVED EQUAL.
2.METER PITS AND VAULTS SHALL NOT BE INSTALLED IN ANY STREET, ALLEY, PARKING AREA OR DRIVEWAY. ANY PIT OR VAULT INSTALLED IN A SIDEWALK DUE TO LIMITED OPTIONS MUST BE
PRE-APPROVED IN THE DEVELOPMENT REVIEW PROCESS AND WILL REQUIRE A TRAFFIC RATED METER PIT AND LID.
3.NO LANDSCAPING (TREES, SHRUBS, BOULDERS, ETC.) OR RETAINING WALLS TO BE WITHIN 4 FEET OF METER PIT AND NO TREES WITHIN 6 FEET.
4.THE METER PIT AND AMR POD(S) MUST REMAIN OPEN AND ACCESSIBLE FOR METER READING AND MAINTENANCE.
5.SLOPE GROUND SURROUNDING METER PIT AWAY FROM LID AT 2% GRADE OR GREATER.
6.MAKE NO PLUMBING CONNECTIONS (TEES, COUPLINGS, ETC.) IN METER PIT.
7.ALL TEES, COUPLINGS AND CONNECTION FITTINGS TO BE A MINIMUM OF 2 FEET FROM METER PIT WALL ON OUTLET SIDE.
8.GRADE ACCEPTANCE AFTER METER PIT INSTALLATION REQUIRES THAT THE OWNER ADJUST METER PIT COVER TO 1/2 INCH ABOVE LANDSCAPED FINAL GRADE.
9.IF A PRESSURE REDUCING VALVE IS REQUIRED BY PLUMBING CODE, IT SHALL BE INSTALLED INSIDE THE BUILDING, IMMEDIATELY FOLLOWING THE MAIN SHUTOFF VALVE.
10.A SEPARATE AMR POD MUST BE INSTALLED FOR EACH METER REGISTER.
11.CONCRETE FOOTERS AND RATED RING/COVER REQUIRED IN TRAFFIC RATED AREAS.
12.REFER TO QUICK REFERENCE FOR INSTALLATION OF THE STANDARD SETTING FOR 1 1/2 " AND 2" WATER METERS (QUICK REFERENCE 16 A&B)
ARMOUR-FLEX TUBING
AND GROUT KNOCKOUT
BEFORE BACKFILLING OR
APPROVED EQUAL
PRECAST CONCRETE
MANHOLE
APPROVED JOINT
SEALANT (TYP. ALL
JOINTS)
1/2" EMT OR PVC
CONDUIT THROUGH
VAULT OR PIT TOP
INTO YOKEBOX
MANHOLE RUNGS
12" O.C.
COMPRESSION
CONNECTION
(TYP.)METER
SETTER
1" DIA. IRON
PIPE BRACE
(TYP.)
PRE-CAST CONCRETE GRADE
RINGS (IF REQUIRED)
ALUMINUM MANHOLE RING AND
COVER WITH LOCK NUT
AMR POD (FORD YOKE BOX PART
#YUC-7 WITH FORD YOKE BOX LID
PART #YL-TP WITH 1 27/32" DIA.
HOLE AND REMOVABLE PLUG)
FINISHED GRADE
2% SLOPE
TOP OF AMR LID TO
BE 1/2" ABOVE
FINISHED GRADE
INSTALL LID 1/2 IN. ABOVE
FINAL LANDSCAPED GRADE
MORTAR OR
MASTIC
4" X 6" SUPPORT BLOCK
BY-PASS VALVE SHALL BE
ON THE UPSTREAM SIDE
IN BETWEEN SETTER
APPROVED:
DRAWN BY:DETAILS
CONSTRUCTION DATE REVISED:
DETAILWATER
STANDARD SETTING FOR 1-1/2" AND 2" WATER METERS
4/20/2022
SAA
W-16A