HomeMy WebLinkAboutCITY OF FORT COLLINS UTILITY SERVICE CENTER PDP AND PLAT - 16 90E - CORRESPONDENCE - STAFF'S PROJECT COMMENTS (2)'a STAFF PROJECT REVIEW
City of FortCollins
July 2, 2002
LOUISE HERBERT
C/O VF RIPLEY ASSOCIATES
401 WEST MOUNTAIN AVE., S= 201
FORT COLLINS, CO 80524
Dear Louise:
Welcome back from Germany and England. I trust you had a wonderful time. Staff has
reviewed your submittal for CITY OF FORT COLLINS UTILITY SERVICE CENTER
PDP/REPLAT, and we offer the following comments:
Be sure to add a six foot wide sidewalk connection at the north terminus of Whitcomb
Street that will tie into the proposed path connecting Elm Street to The Farm at
Martinez Park.
2. Be sure to denote on the Landscape Plan exactly which trees are serving as the
mitigation trees as per the discussion with Ralph Zentz, Assistant City Forester. It is
our understanding that ten existing trees are to be removed and that evergreen trees, at
a height that exceeds the minimum, will act as the mitigation trees.
OTHER ISSUES:
Department: Engineering
Topic: General
10
Need to add signature block for ELCO
Issue Contact: Dave Stringer
11
Is signature block required for Griffin Drain ownership?
12
Add note to demo plan about remove and replace any damaged curb and gutter on Elm Street
in area to be constructed
13
Call out curb and gutter type, Elm Street and parking lot
14
Show location of Griffin Drain on x-section sheet CS302
Page I
15
Will existing Fire hydrant on Elm need to be relocated? The valve may be, in Gutter or curb
head
16
Appears off -site easements are require for pond, retaining wall and trail
17
How will existing alley terminate at the North end?
18
Provide elevations of existing gutter at Loomis and Elm for tie in points
Department: Light & Power Issue Contact: Bruce Vogel
Topic: General
3
NO COMMENTS
Department: Natural Resources Issue Contact: Doug Moore
Topic Wetlands
7
A Wetland Delineation is require for this project but was not submitted. The delineation
needs to be shown on plans.
3.4.1(D)
8
A mitigation plan is needed showing how the wetlands will be mitigated and what planting
will be done.
9
To request to remove the existing wetlands and mitigate for their loss a modification from the
Planning and Zoning board is needed. 3.4.1(E)3
Department: Police Issue Contact: Joseph Gerdom
Topic: General
5
For security and safety, lighting levels should be above lfc (verticle) throughout the parking
area and both pedestrian and vehicular exits and circulation areas.
Page 2
i
i
i
i
I
Department: Stormwater Utility Issue Contact: Basil Hamdan
Topic: Box Culvert Maintenance Access
27
The proposed box culvert seems to be very deep in some locations. Pleaseprovide a
maintenance access into the box culvert. Please contact Maureen Scullion to make sure that
the proposed access complies with all Federal, State and City safety regulations. re
Topic: Box Culvert Trash Rack
32
It seems that the box culvert is experiencing high velocities
Topic.: Channel Design
31
Please provide a hard copy as well as digital copies of the HEC RAS input and output files
for review.
Please show the limits of the floodplain along Elm Street and in the channel on the plans.
Topic: Detention Requirement
30
Due to the proximity of this site to the Poudre River no water quantity detention is required.
Topic: Erosion and sediment control
25
June 20, 2002
Standard City erosion control notes need to be on the plan.
The BMP's mentioned in the report versus those on the plan, versus those in the calculations
do not match. Please make it so.
Project Schedule?
What happens where with permanent revegetation? How are the swales and the new pond to
be protected from erosion until vegetation is established?
Topic: Floodplain
4
Please show future floodplain delineation on ODP Plans, after proposed improvements are
completed.
24
Please delineate floodplain downstream of the water quality pond all the 'Way to the Poudre
River. This will need to be delineated by hydraulic modeling of the areal from the water
Page 3
quality pond spillway to the river. That area should be then reserved from future
developement through a right of way designation agreement with the City Parks Department.
Topic: Future Building
29
Please specify the Finish Floor elevation of the future proposed building.
Topic: Plat
26
Please call out the limits of the floodplain on the plat.
Please make sure that the swale along Elm Street and the box culver are called out as
drainage easements..
Topic: Water Quality Pond
28
Please clarify who will maintain the proposed water quality pond. If the pond is on Parks
property, the area of the pond should be reserved through a City right of way reservation.
Please design a spillway for the water quality pond. Please make sure that the spillway is
adequately armored. Please call out spillway elevation on the plan;
Please specify the spacing in the Water Quality the trah rack. Specify no more than 4" clear
between rods.
The water quality design calculations in the report are unreadable due to poor reproduction,
please make sure they are readable so that they can be reviewed.
Please provide an opening on the downstream side of the water quality stilling basin for
dewatering.
Department: Transportation Planning Issue Contact: Tom Reiff
Topic: General
6
According to the City's LUC a facility that is designed for both pedestrians and bikes should.
be 8 feet in width as a minimum in order to safely accommodate the intended users.
Currently the trail is shown as 6 feet. Please increase to 8 feet and include an access ramp at
the comer of Elm Street and Loomis for cyclists to safely access the trail from the street.
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: General
19
Maintain 10 feet of separation between existing buildings and sanitary sewer trunks and
proposed relocated.ELCO water main.
Page 4
® 0
20
Clearly define all aspects of existing and proposed water/ sewer services (Ie size, location,
etc.). j
21
Provide signature blocks for ELCO and NWCWD.
22
Will existing 6" City of Fort Collins water main be abandoned with future building? Clearly
define all aspects of future building impacts on existing water/sewer.
23
Provide all appropriate details on detail sheet (Le. water main lowering, meter pits, etc.).
See site, landscape and utility plans for other comments.
Department: Zoning Issue Contact: Peter Barnes
Topic: zoning
1. The term T.U.D." should be removed from the name of the plat since we don't do
PUD's anymore. It should just be City of FC Service Center 6th Filing.
2. Their narrative states that there will be an 8'tall security fence to tie in with the existing.
Will the fence have barbed wire? If it does, then they'll have to comply with the
standards in 3.8.11(B).
Be sure and return all of your redlined plans when you re -submit. As always, if you have any
questions regarding these issues or any other issues related to this project, please feel free to
call me at (970) 221-6750.
Sincerely:
Ted Shepard
Chief Planner
Page 5