HomeMy WebLinkAboutFORT COLLINS SECOND AND HARMONY PUD AT THE VILLAGES AT HARMONY WEST LOT ONE PRELIMINARY AND FINAL - 3 90E, F - SUBMITTAL DOCUMENTS - ROUND 1 - GEOTECHNICAL (SOILS) REPORT® 0 SUBSURFACE EXPLORATION REPORT PROPOSED CHURCH OF JESUS CHRIST OF LATTER DAY SAINTS REGENCY DRIVE AND HARMONY ROAD FORT COLLINSv COLORADO JOB NO. 12915055 Job No. 12915055 Terracon December 18, 1991 Page 8 recommend the exposed soils be scarified to a minimum depth of 9 inches, adjusted in moisture content and compacted to at least 95 percent of the material's maximum dry density as determined in accordance with ASTM Specification D-698, the standard Proctor procedure. The moisture content of the scarified soils should be adjusted to a minimum of the soil's standard Proctor optimum moisture content. Fill required to develop the subgrades should consist of approved, low -volume change material free from organic matter and debris. Those soils should be placed in loose lifts not to exceed 9 inches thick, adjusted in moisture content as outlined for the scarified soils, and compacted to at least 95 percent of standard procter maximum dry density. care should be taken during construction to avoid disturbing prepared subgrades. Subgrades disturbed by construction activities should be reworked in place or removed and replaced prior to placement of the overlying floor slabs or pavements. A Hveem stabilometer R-value of 12 was determined in laboratory testing on a representative sample of subgrade materials obtained from the site. Based on that R-value and assumed traffic loadings, pavement sections were evaluated using the 1986 "AASHTO Guide for Design of Pavement Structures." Reliabilities of 75 percent and standard deviations of 0.44 and 0.34 were assumed for the flexible and rigid pavements, respectively. Serviceability losses of 2.5 were assumed to be acceptable for the pavement areas and drainage was assumed to be good. Terracon Job No. 12915055 December 18, 1991 Page 9 Based on the above outlined assumptions, recommended pavement sections for both flexible and rigid pavements are provided below. Those pavement sections are minimums and, as such, periodic maintenance should be expected. TABLE 1 - Recommended Pavement Sections Light Duty (Parking Only) A) Portland Cement Concrete PCC Pavements B) Full Depth Asphalt ACC Pavement C) Asphalt on Aggregate Base ACC Pavement Aggregate Base 5.0" 3.5" 2.0" 6.0" Heavy Duty (Drives) 6.0" 4.5" 3.0" 6.0" Aggregate base for the flexible pavements should consist of Class 5 or Class 6 base as defined by City of Fort Collins standard specifications. That aggregate base material should be placed and compacted as outlined above for the subgrades. Asphaltic concrete for use in the pavement sections should consist of SC1 or SC2 mixes as defined by City of Fort Collins standards. Portland cement concrete for the pavement should be air entrained ready mix concrete with a minimum 28-day compressive strength of 3,500 psi. Positive drainage should be developed across and away from the pavement edges to provide positive drainage. Water allowed to pond on or adjacent to the pavements could result in saturation of pavement subgrades and premature failure of the pavement sections. Terracon Job No. 12915055 December 18, 1991 Page 10 GENERAL COMMENTS The analysis and recommendations presented in this report are based upon the data obtained from the soil borings performed at the indicated locations and from any other information discussed in this report. This report does not reflect any variations which may occur between borings or across the site. The nature and extent of such variations may not become evident until construction. If variations appear evident it will be necessary to re-evaluate the recommendations of this report. It is recommended that the geotechnical engineer be retained to review the plans and specifications so that comments can be made regarding the interpretation and implementation of our geotechnical ' recommendations in the design and specifications. It is further recommended that the geotechnical engineer be retained for testing and observation during earthwork and foundation construction phases to help determine that the design requirements are fulfilled. This report has been prepared for the exclusive use of our client for specific application to the project discussed and has been prepared in accordance with generally accepted geotechnical engineering practices. No other warranty, expressed or implied, is made. In the event that any changes in the nature, design or location of the project as outlined in this report are planned, the conclusions and recommendations contained in this report shall not be considered valid unless the changes are reviewed and the conclusions of this report modified or verified in writing by the geotechnical engineer. GENERAL NOTES DRILLING & SAMPLING SYMBOLS: SS : Split Spoon - 1%" I.D., 2" O.D., unless otherwise noted PS Piston Sample ST : Thin -Walled Tube - 2" O.D., Unless otherwise noted WS Wash Sample PA : Power Auger FT Fish Tail bit HA : Hand Auger RB Rock Bit DB : Diamond Bit - 40, N, B BS Bulk Sample AS : Auger Sample PM Pressuremeter HS : Hollow Stem Auger DC Dutch Cone WB Wash Bore Standard "N" Penetration: Blows per foot of a 140 pound hammer falling 30 inches on a 2 inch OD split spoon, except where noted. WATER LEVEL MEASUREMENT SYMBOLS: WL . Water Level WS . While Sampling WCI : Wet Cave In WD . While Drilling DCI . Dry Cave In BCR Before Casing Removal At After Boring ACR : After Casing Removal Water levels indicated on the boring logs are the levels measured in the borings at the times indicated. In pervious soils, the indicated levels may reflect the location of groundwater. In low permeability soils, the accurate deter- mination of ground water levels is not possible with only short term observations. DESCRIPTIVE SOIL CLASSIFICATION: Soil Classification is based on the Unified Soil Classification System and ASTM Designations D-2487 and D-2488.. Coarse Grained Soils have more than 50% of their dry weight retained on a #200 sieve; they are described as: boulders, cobbles, gravel or sand. Fine Grained Soils have less than 50% of their dry weight retained on a #200 sieve; they are described as: clays, if they are plastic, and silts if they are slightly plastic or non -plastic. Major con- stituents may be added as modifiers and minor constituents may be added according to the relative proportions based on grain size. In addition to gradation, coarse grained soils are defined on the basis of their relative in -place density and fine grained soils on the basis of their consistency. Example: Lean clay with sand, trace gravel, stiff (CL); silty sand, trace gravel, medium dense (SM). CONSISTENCY OF FINE-GRAINED SOILS: Unconfined Compressive Strength, Our psf Consistency < 500 Very Soft 500 - 1,000 Soft 1,001 - 2,000 Medium 2,001 - 4,000 Stiff 4,001 - 8,000 Very Stiff 8,001-16,000 Hard >-16,006 Very Hard RELATIVE PROPORTIONS OF SAND AND GRAVEL Descriptive Term(s) (of Components Also Percent of Present in Sample) Dry Weight Trace < 15 With 15 - 29 Modifier > 30 RELATIVE PROPORTIONS OF FINES Descriptive Term(s) (of Components Also Percent of Present in Sample) Dry Weight Trace < 5 With 5-12 Modifier > 12 RELATIVE DENSITY OF COARSE -GRAINED SOILS: N-Blowslft. Relative Density 0-3 Very Loose 4.9 Loose 10-29 Medium Dense 30-49 Dense 50.80 Very Dense 80+ Extremely Dense GRAIN SIZE TERMINOLOGY Major Component Of Sample Size Range Boulders Over 12 in. (300mm) Cobbles Gravel Sand Silt or Clay 12 in. to 3 in. (300mm to 75mm) 3 in. to #4 sieve (75mm to 4.75mm) #4 to #200 sieve (4.75mm to 0.075mm) Passing #200 sieve (0.075mm) Form 108-6-85 1%rran L Job p Fom, 104-685 BORING LOCATION DIAGRAM PROPOSED LDS CHURCH FORT COLLINS, COLOtRADO Date now 1001 Drawn AuK/ntc 1.r.rr�C � r-I Ah LOG OF BORING NO. B-1 Page 1 of 1_ OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects sITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS IL E C Z Z- U DESCRIPTION m Z\ IL F £ m W O 3 0 D OW ¢ Z a W H U) £ 7 LL ? U W F O D.J m O )- L mU U-M IL Z+-0 - o Surface Elev.: 97.7 ft. 4 a z m m m £ o D. 3 m D. --0.4 4" Topsoil 97.3 JPAJ •9000+ CL 1 ST 12" 11.5 2.5 SILTY LEAN CLAY 95.2 Dark Brown PA Very Stiff 5 SP 2 AS 15.9 5'0 SILTY SAND 92.7 Brown Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hand Penetrometer' BETWEEN SOIL AND ROCK TYPES; IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS err a� BORING STARTED 12-9-91 WL � None WD or Ws Y None AB1 BORING COMPLETED 12-9-91 WL RIG CME-55 FOREMAN AL M WL APPROVED LLL JOB # 12915055 Ask A& LOG OF BORING NO. B-2 Page 1 of 1 OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS F \ } F O O O + J O J - F- m IL w M W _IL H t0i DESCRIPTION W Z \ W 1z = W D 1 Ol F- O Z Z n. I-Ea0oIL C N }IL aMIL o Surface Elev.: 96.4 ft. o a i � M 0) M E o M 3, W a_ 0.4 4" Topsoil 96.0 PA SILTY LEAN CLAY '9000+ CL 1 ST 14" 11.7 Brown Very Stiff PA 5.0 91.4 5 CL 2 AS l 5 Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hand Penetrometer* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS 1 err c BORING STARTED 12-9-91 WL 7 None WD or WS I None AB BORING COMPLETED 12-9-91 WL RIG CME-55 FOREMAN AML WL APPROVED LLL Jos # 12915055 AM n LOG OF BORING NO. B-3 Page 1 of I OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TE5TS \ Y a DESCRIPTION " 0 M, W Z j W IL HIO H O R H E a U 1- O ►i E IL o a U M IL 3 as o Surface Elev : 97.8 ft. o a- i, ►}- ¢ vai'io a~i 0.3 3" Topsoil 97.5 PA SILTY LEAN CLAY WITH '9000+ CL 1 ST 5" 16.0 S6J�m PA Light Brown 5.0_ 92 Very Stiff 8 With Calcareous Deposits 5 CL -2 AS 10.8 Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hand Penetrometer* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS Irerracon BORING STARTED 12-9.-.91 WL 9 None WD or ws Y None AB BORING COMPLETED 12-9-91 WL RIG CME-55 FOREMAN AML WL APPROVED LLL JJOB# 12915055 Ah Mw LOG OF BORING NO. B-4 Page 1 of 1 OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS z ? I- U DESCRIPTION > M z C a f E mWpp W O 3 1- O z W 8 C IY a W I- 0 E a a } U W F- O a J w >. a M U M'.a z F-; N o Surface Elev.: 99.6 ft. o_ a z r M m m 2 o a w a 0.4 4" Topsoil 99.2 PA *9000+ CL 1 ST 8" 7.3 SILTY. SANDY_ LEAN CLAY Dark Brown PA 4.0 Very Stiff 95.6 5 SILTY FINE SAND 94.6 SM 2 AS 9.2 Light Brown Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hand Penetrometer* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS Irerractin BORING STARTED 12-9-91 7 None WD or WS Y None AB BORING COMPLETED 12-9-91 1WL RrL RIG CME-55 FoREMnx AML WL APPROVED LLL JOB # 12915055 Alk LOG OF BORING NO. B-5 Page 1 of 1 OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS J 0-m LL + h~i W U DESCRIPTION IL } ¢ Z.\ m Z m � M = 2 W i N H O ZZ x yak p o Surface .Eler.: _ 99.6 ft. W o 0 C > l�- W m aJ N m O x CU o IL ZIP-0 3 m a 0.3 3" Topsoil 99.3 PA - SILTY SANDY LEAN CLAY '9000+ CL 1ST 7" 9.5 Dark Brown PA Very Stiff 5.0 94.6 5 Cl, 2 AS 11.0 Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXTNATE BOUNDARY LINES Calibrated Hand Penetrometer* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS 1rerrconL BORING STARTED 124-91 L _ y None WD or WS I None AB BORING COMPLETED 12-9-91 I Ric CME-55 FOREMAN AML L APPROVED LLL JOB # 12915055 1 rercon CONSULTANTS SE, INC. 1609 OakRidge Drive, Suite 101 Ft. Collins, Colorado 80525 (303) 226-5611 Gerald R. Olson, P.E. James A. Cunningham, P.E. C. Fred Schoell, P.E. December 18, 1991 Lester L. Litton, P.E. Glaser Associates Architects 215 Jefferson Fort Collins, Colorado 80524 ATTN: Mr. Carl Glaser RE: Subsurface Exploration Report Proposed Church of Jesus Christ of Latter Day Saints Regency Drive and Harmony Road Fort Collins, Colorado Job No. 12915055 Mr. Glaser: Enclosed, herewith, are the results of the subsurface exploration performed for the referenced project. In summary, the soils observed in the test borings at the site consisted of low plasticity silty and/or sandy clays. Occasional zones of more granular soils were also observed with depth in the boring. In our opinion, the site soils can be used for direct support of the proposed building on footing foundations. The site materials could also be used for direct support of floor slabs and pavements. Recommendations concerning design and construction of the foundations and support of the floor slabs and pavements are presented in the text of this report. We appreciate the opportunity to be of service to you on this project. If you have any questions concerning this report, or if we can be of further service to you in any other way, please do not hesitate to contact us. very truly yours, TERRAWN CONSULTANTS SE, INC. Lester L. Litton, P.E. Colorado No. 23957 Craig X. Denny, P. Colorado No. 27757 LLL/dmf Offices of The Terracon Companies, Inc. Geotechnical, Environmental and Materials Engineers Colorado: Denver, Ft. Collins a Iowa: Cedar Falls, Cedar Rapids, Davenport, Des Moines, Storm Lake Illinois: Bloomington, Naperville, Rock Island ■ Kansas: Lenexa, Topeka, Wichita ■ Minnesota: St. Paul Missouri: Kansas City a Nebraska: Omaha a Oklahoma: Oklahoma City, Tulsa QUALITY ENGINEERING SINCE 1965 Adh n LOG OF BORING NO. B-6 Page 1 of 1 OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS M W O .. la -J DESCRIPTION F- W } 1~{, Z w m Z H F ►Vi = a. N ¢ O r 3 n W IL O O W- ¢. I-- IL E 1- m E W LL U F- O U) m } U. U M L Surface Elev.: 100.2 ft. o C z aaEoaDaa oi m m 0.3 3" Topsoil 99.9 PA SM 1 ST 12" 7.0 SILTY FINE SAND WITH SP PA GRAVEL Light Brown 5.0 Medium Dense 95.2 5 SM 2 AS 8.2 Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hard Penetrometer' BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS Irerr con BORING STARTED 12-9-91 L Q None wD or ws Y None AB BORING COMPLETED 12-9-91 L IW RIG CME-55 FOREMAN AMLL APPROVED LLL JOB # 12915055 r-1 LOG OF BORING NO. B-7 Page 1 of 1 OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS U DESCRIPTION M Z 7 Z H ~_ ~ 0M a o F E a 0 FO ►�i T_ }a. L a a Surface Elev.: 100.5 ft. a i � M W m O. a~i 0.4 4" Topsoil 100.1 JPAJ SILTY LEAN CLAY *7000 CL 1 ST 9" 14.5 Dark Brown PA Very Stiff 5.0 95.5 5 CL 2 AS 10.5 Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hand Penetrometer* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL;. WATER LEVEL OBSERVATIONS Irerracon BORING STARTED 12-9-91 WL Q None WD or WS Y None AB BORING COMPLETED 12-9-91 WL RIG CME-5$ FOREMAN AML WL APPROVED LLL JOB # 1291$0$$ Ah r� Ivor ­ LOG OF BORING NO. B-8 Page 1 of i OWNER. ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES- TESTS U DESCRIPTION W Z\MW"I- E m w o1 3H °owa a IL IL a M I-° Q. m N E >.IL n 0¢ft. z r m a Surface Elev.: 99.6 ft. o a 0 oa za_0 ""` 0.4 4" Topsoil 98.2 PA SILTY CLAY 2.0 Dark Brown 96.6 CL I ST 8" 9.4 '9000+ SILTY SANDY LEAN CLAY PA Brown Very Stiff 5 *9000+ CL 2 -SS 8" 22 10.9 7.0 91.6 *9000+ S.M 3 SS 10" 40 10.6 SILTY SAND WITH GRAVEL SP PA Red Brown Medium Dense 10 Occasional Clayey Zones *3000 SM 4 SS 1 8" 16 19.3 SP SM 5 AS 1 5.1 15.0 83.6 15 SP Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROKIMATE BOUNDARY LINES calibrated Hand Penetrowter* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS Irearracon BORING STARTED 12-9-91 g None WD or WS SE None AB BORING COMPLETED 12=9-91 w'L rW �G CME-55 FOREMAN AML WL APPROVED LLL IJOB# 12915055 Ah n LOG OF BORING NO. B-9 Page I of I OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS_ Church SAMPLES TESTS } J H DESCRIPTION > M Z\ M Z H f 9) K W 7 W LL O .Q IL LL H E R U F- O H 0 LL. U R LL. rface Elev.: 98.3 ft. o a z � M m M i o a. 5 u) aoil 97.9 PA CLAYrown 96.3 CL 1 ST 8" -8.6 PA (:.:fWitrhCalcareous 5 *9000+ CL 2 SS 8" 46 15.1 LEAN CLAY WITHD 09000+ CL 3 10" -10 9.0 rown 89.8 iff SS pA alcareous Deposits 10 FINE TO COARSE SILTY SAND WITH GRAVEL SP 4 SS 8" 24 4.5 Red Brown Medium Dense SP 5 AS 4.8 15.0 83.3 15 Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hand Penetrometer* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS BORING STARTED I2-9-91 L Q None WD or WS Y None AB BORING COMPLETED_ 12-9-91 rWwwL LIrerrac®n RIG CME-55F OREMAN AML L APPROVED LLL JOB # 1291 0055 Ask Ah IF MW LOG OF BORING NO. B40 Page 1 of 1 OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS. U DESCRIPTION W z` N 7 W I~L o E a UOW ►i OQ.EIL 0MQ IL ¢ o Surface Elev.: 99.4 fL W o_ M a 7 z > W a aJ 0oM O E MU G D. zHVI 3 W a 0.4 4" Topsoil 99:0 PA 2.0 SILTY LEAN CLAY WITH 97.4 nND *9000+ CL 1 ST 10" -6.3 Brows With Calcareous Deposits PA SILTY FINE SAND 5 *9000+ SM 2 SS 10" 39 9.7 Light Brown 7.0 Medium Dense 92.4 With Calcareous Deposits *8000 IDAI SP 3 12" 17 14.2 Ss CL PA SILTY FINE TO. COARSE SAND 10 Red Brown Medium Dense SP 4 SS 10" 15 17.5 *3000 Occasional Calcareous Deposits SP 5 AS 11.4 15.0 84.4 15 Bottom of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES calibrated Hard Penetrometer* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS I rerracaumn BORING STARTED 12-9-91 WL Q None WD or WS Y None AB BORING COMPLETED 12-9-91 WL RIG CME-55 jFoREMAN AML WL APPROVED LLL JOB # 229150 55 Ah LOG OF BORING NO. B-11 Page I of I OWNER ARCHITECT/ENGINEER Church of.Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS F- ` F O p O J F m a M W FO+ DESCRIPTION N Ix W =\ M W H O EEa a M >a W F- ofz a w F-o a M o a u 0aa z F- m o Surface Elev.: 98.5 ft. o a z a mm L 0a zNa 0.4 4" Topsoil 98.1 PA SILTY LEAN CLAY WITH SAND •9000+ CL 1 SS 10" 20 13.5 Brown PA Very Stiff 5.0 With Calcareous Deposits 93 5 5 °9000+ SM 2 ST 13.2 1.0 SILTY FINE SAND 91.5 - Light Brown *5000 SP 3 SS 10" 17 18.1 Medium Dense SM PA With Calcareous Deposits 10 SILTY FINE TO COARSE _ SAIlLI2 Red rown um SP 4 SS 12" 23 4.0 Med Dense 1 Occasional Clayey Zones SP 5 AS 9.8 15.0 83.5 15 Bottom of Boring I Li I THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hard Penetrometer* BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION MAY BE GRADUAL. WATER LEVEL OBSERVATIONS Nerracon BORING STARTED 12-9-91 II None WD or WSJ! None AB BORING COMPLETED 12-9-91 LWL WL RIG CME-55 FOREMAN AML WL APPROVED LLL ljoB# 12915055 r1 Ah LOG OF BORING NO. B-12 Page 1 of 1 OWNER ARCHITECT/ENGINEER Church of Jesus Christ of the Latter Day Saints Glaser Associates Architects SITE Harmony Road & Regency Drive PROJECT Fort Collins, Colorado Proposed LDS Church SAMPLES TESTS LL . M W O J F J m DESCRIPTION " N W Z j W H ~_ ►0 OILFEILU UCa M W N 0 Y W 1-O O.J O L MU a. ZI-U) a Surface Elev.: 98.3 ft. o a z a U) m r_ o a 3 a IL ` 0.5 5" Topsoil 97.8 PA SILTY LEAN CLAY WITH SANDCL *8000 1 SS 1 10" 21 13.2 Brown PA Very Stiff 5.0 With Calcareous Deposits 93.3 5 *7000 SM 2 SS 8" 13 9.4 SM 3 SS 3" 28 6.3 SILTY FINE SAND PA Light Brown Medium Dense 10 With Calcareous Deposits 12.0 86.3_ SP 4 SS I 10" 20 5.5 SILTY FINE TO COARSE SAND PA Red Brown IS Medium Dense Occasional Clayey Zones Y SP 5 SS 12" 23 16.5 - PA 20 >'> 22.0 76.3 CL 6 SS 10" 38 14.1 CH PA LEAN TO FAT CLAY Gray Brown Very Stiff 25 CL 7 SS 12" 30 19.4 28.5 69.8 CH Bottom -of Boring THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES Calibrated Hand Penetrometer' BETWEEN SOIL AND ROCK TYPES: IN -SITU, THE TRANSITION HAY BE GRADUAL. WATER LEVEL OBSERVATIONS Irerracon BORING STARTED 12-9-91 BORING COMPLETED 12-9-91 WL .Q 17.0' WD or WS Y 17.0' AB RIG CME-55 lFoREMAN AML WL APPROVED LLL JOB # 12915055 WL W V Z u i- W WW Q. I SWELL / CONSOLIDATION TEST li l l I� I' 'li I;lil�iljlill;ll !III I tI I I ilIliill � IIII' l ll�lll l.l; Irl II -; - IIII :_: I - ! _-I _h 14_ _I ,I I j. j: �-I I I i -1f- 1 I .i I- I I �II I�IT ill ill II Li ll Illi ,:I .I I I it I 'I ; i-II L-�I� III �� III t I IIII III I I I'I'i IIII I� IIII: I! ullj ll�i "III''i'I l�il'li J .il i' II'li' II IIiIII III j J � i I i i l:i-L.:i I; i I I it I I IIII III; I iI I'. jll i i I I �� r_I:i �LIi I l �I ll .LIII l �IIIIII IL�I I 111 IIII Iljl I III I 1, I I'' Ili I Iii1 11 l L, i i - l il'I j l -,.., ♦li. I, t I I� I �. I '� i I, L Ill I fill., i t i� _-L.. i I I I ;11 III I 1 ll. I_.; LIL III Iili l IIII IIII. I I I 1111 "I I re I'Ajdl ltl II ._I r;dl I I.L. L. I .j ilj. i i r li I Ljll I ,III l�l I'I Lilr i I_ 1 1 I I I. II II'IiI'Ilili L I II IIII !!I I' I li I ill Il;l 1� l IIII 4 I In I; I IIII iIi Illljli I' I IIII _I� il..l. I 1.._L. I- I .I I i I i '-1 (II_jl .Li. I'l l 111 i1. lj Ili i LLi l L Il I I ILI' III �ii it i,l II Intl III Il 'Ill IIli1 I;i I�:��i I I I � I I I i' l l I i I I I I l.li it i.l. 1. ILI II'I It Illlli I '�i ill .LII III I I I .III I IIII 'I;l I• lul ji I- III I (L. I l I II,I I ;..I_ j' II. I I Il�,jl ' I I:: .LI '1. I IL IiII Dili; flll Il jl ill II IIII IIII f Ili �' i I'I.— .i II - Il II _, � 1 L....I j_: _. i 1 _tl II I.L.I. 1.1 I� i. i I l III I I I I..; I 1 III II ! I i;I I;�'I IIII I, III II'l lull •IIII Ilii IIIIII Ill, II I , I),I _i I_i:. 1_I ..Ill. I I ,il 1 I, IIIII II ' I I.I I !. ILL. it Ili I Illl III I I, IIIII I1i11 'It I II IIII .I -I "I ll;l i i I I I ll._ I_ I I ( I I I I , LI I It'IlL�� i LI.II li IIIII'II , 1 I .I. III I 1 _ i III i. � Ea 0.05 0.1 0.2 U.4 CONFINING PRESSURE (Tons per square foot) Boring No. 6-3 Sample Nat Depth 1 1 or Elev.— Description Sample Diameter 2.50 in. Liquid Limit 39 %° Sample Height 0 75 in. 21 Initial Water I Plastic Limit Initial Dry Density 106 pcf Plasticity Index 18 project Proposed LDS Church - Regency Rd & Harmony Rd. Fort Collins Colorado Job Na 12915055 Dale December 1991 - Swell Pressure Water Content After Test Swell .O N_L_pst 20.6 % 0 % Fonn 121 1Terracon UNIFIED SOIL CLASSIFICATION SYSTEM Criteria for Assigning Group Symbols and Group Names Using Laboratory Tests Coarse -Grained Soils More than.509/6 retained on No. 200 sieve Fine -Grained Soils 50%n or more passes the No. 200 sieve Gravels More than 50% of coarse fraction retained on No. 4 sieve Sands 50% or more of coarse fraction passes No. 4 sieve Silts and Clays Liquid limit less than 50 Soil Classification Group Name" Clean Gravels Cu a 4 and 1 s Cc s 3E GW Well -graded gravelF Less than 5% finesc --- Cu < 4 and/or 1 > Cc > 3E GP Poorly graded gravel° Fines classify as ML or MH GM Silty gravel - Gravels with Fines More than 12% finesc Fines classify as CL or CH GC Clayey gravelF• G. H Clean Sands Cu a 6 and 1 s Cc s 3E SW Well -graded sand' Less than 5% fines -- Cu < 6 andior 1> Cc > 3E SO Poorly graded sand' Fines classify as ML or MH SM Silty sandG• "•l Sands with Fines. More than 12% fines[) Fines classify as CL or CH SC Clayey sand 6, N•' Inorganic PI > 7 and plots on or above "A•' line' CL Lean. day K,.L, M — PI < 4 or plots below "A" line ML SiltK, L, M Liquid limit — oven dried Organic CIayK, L. M; N organic .— < 0.75 OL -- Liquid limit — not dried Organic siltK, L. M, o Silts and Clays inorganic PI plots on or above "A" line CH Fat clayK L M Liquid limit 50 or more PI plots below "A" line MH Elastic siltK, L, M Liquid limit — oven dried Organic clayK, L,. M. P organic --- < 0.75 Li uid limit — not dried OH — Organic silty L M, 11 q _ Hiahly orqanic soils Primarily organic. matter, dark in color, and organic odor PT Peat.. I Based on the material passing the 3-In. (75-mm) sieve. "If field sample contained cobbles or boulders, or both, add "with cobbles or boulders, or both" to group name. CGravels with 5 to 12% fines require dual Symbols: GW-GM well -graded gravel with silt GW-GC well -graded gravel with clay GP -GM poorly graded gravel with silt GP -GC poorly graded gravel with clay °Sands with 5 to 12% fines require dual Symbols: SW-SM well -graded sand with silt SW -SC well -graded sand with clay SP-SM poorly graded sand with silt SPSC poorly graded sand with clay 60 50 EL X 40 W 0 Z_ } 30 f- U Q 20 J a 10 7 4 0 0 10 16 20 30 40 50 60 70 80 90 100 110 LIQUID LIMIT (LL) ECu = D6WD10 Cc = (1330)z Div x D60 Flf soil contains >_ 15% sand, add "with sand" to group name. GI fines classify as CL-ML, use dual symbol GC - GM, or SC-SM. Nlf fines are organic, add "with organic fines" to group name. 'if soil contains z 15% gravel, add "with gravel" to group name. 'If Atterberg limits plot in shaded area, soil is a CL- ML, silty clay. Klf soil contains 15 to 29% plus No. 200, add "with sand" or "with gravel", whichever is predominant. LIf soil contains >_ 30%, plus. No. 200 predominantly sand, add "sandy" to. group name. "if soil contains >_ 30% plus No. 200, predominantly gravel, add "gravelly" to group name. NPI >_ 4 and plots on or above "A" line. GPI < 4 or plots below "A" line. PPI plots on or above "A" line. GPI plots below "A" line. For classification of fine-grained soils and fine-grained fraction of coarse• grained soils Equation of "A"- line N Horizontal at PI = 4 to LL = 25.5. then PI = 0.73 (LL - 20) °\ j Q,<\ .•P Equation of "U" - line Vertical at LL = 16 to PI = 7, , CJ� then PI = 0.9 (LL - 8) MH OR OH ZI/ & — r - CL--ML MLOROL Form SUBSURFACE EXPLORATION REPORT PROPOSED CHURCH OF JESUS CHRIST OF LATTER DAY SAINTS REGENCY ROAD AND HARMONY DRIVE FORT COLLINSj COLORADO Job No: 12915055 Date: December 18, 1991 INTRODUCTION Terracon The subsurface exploration for the proposed building for the Church of Jesus Christ of Latter Day Saints at Regency Road and Harmony Drive in Fort Collins has been completed. Five soil borings extending to depths of approximately 15 to 28 feet below existing site grades were advanced in the proposed vicinity of the building and 7 additional borings extending to depths of approximately 5 feet below present site grades were advanced in drive and parking areas. Individual boring logs and a diagram showing the approximate boring locations are included with this report. We understand the new church facility will be constructed north of. Harmony Road and east of Regency brive in Fort Collins. The new facility will be a single -story, slab -on -grade (non -basement) structure. Foundation loads for the new church will be light to moderate with continuous wall loads less than 5 kips per lineal foot and column loads less than 70 kips. Floor loads will be light, less than 100 psf. Paved drive and parking areas will be constructed along with the new building. We understand up to 4 feet of new fill may be required in the building area to develop site grades. The purpose of this report is to describe the subsurface conditions encountered in the borings, analyze and evaluate the test data and provide geotechnical recommendations concerning design and construction of foundations and support of floor slabs and pavements. Terracon Job No. 12915055 December 18, 1991 Page 2 EXPLORATION AND TESTING PROCEDURES The boring locations were selected and located in the field by Terracon Consultants personnel. Field locations were established by pacing and estimating angles from the references shown on the attached boring location diagram. Surface elevations at the boring locations were determined by Terracon personnel using differential leveling techniques. The tie down bolt (identified with a chisled "X") on the electrical transformer near the east property line of the site was used as the reference benchmark with an assumed elevation of 100.0 feet. The locations and elevations of the borings should be considered accurate only to the degree implied by the methods used to make these measurements. The borings were performed using a truck -mounted, rotary type drill rig equipped with a hydraulic head employed in drilling and sampling operations. The boreholes were advanced using continuous flight augers and samples of the subsurface materials encountered were obtained using thin -walled tube and split -barrel sampling procedures in general accordance with ASTM Specifications D-1587 and D-1586, respectively. In the thin -walled tube sampling procedure, a thin -walled seamless steel tube with a sharpened cutting edge is pushed into the ground with hydraulic pressure to obtain a relatively undisturbed sample of cohesive or moderately cohesive material. In the split -barrel sampling procedure, a standard 2-inch O.D. split -barrel sampler is driven into the ground by means of a 140-pound hammer falling a distance of 30 inches. The number of blows required to advance the split -barrel sampler is recorded and is used to estimate the in -situ relative density of cohesionless soils and, to a lesser degree of accuracy, the consistency of cohesive soils. All samples obtained in the field were sealed and returned to the laboratory for further examination, classification and testing. ' Job No. 12915055 Terracon December 18, 1991 ' Page 3 ' Moisture content tests were performed on all samples returned to the laboratory. In addition, calibrated hand penetrometer tests were performed on cohesive soil samples and dry density and unconfined compressive strength tests were performed on representative portions of the thin -walled tube samples, where possible. The calibrated hand penetrometer provides an approximation of the unconfined compressive strength of a cohesive or moderately cohesive material by measuring the sample's resistance to penetration of a small, spring calibrated cylinder. Results of the above -outlined tests are shown on the attached boring logs. Atterberg limits and one swell/consolidation test were performed on selected subgrade samples. The Atterberg limits and swell/consolidation tests were performed to evaluate the soil's tendency to change volume with variation in moisture content. In addition, a washed sieve analysis test was performed to evaluate the percent of fines (material passing a No. 200 sieve) in the subgrade soils. Results of those tests are shown on the attached 1 summary sheets. one Hveem stabilometer R-value was also performed on a selected sample. The R-value test provides information relative to the remolded strength of the subgrade materials and those test results are used in design of pavement sections. Results of the R-value ' test are shown on the attached summary sheet and those results are discussed in a later section of this report. Topsoil at the site was also tested for pH and nutrient levels. Results of that testing and recommendations concerning the additions of nutrients for landscape purposes will be forwarded in a separate report. 1 II Job No. 12915055 Terracon December 18, 1991 ' Page 4 As a part of the testing program, all samples were examined in the laboratory by an engineer and classified in accordance with the attached General Notes and the Unified Soil Classification System based on the soil's texture and plasticity. The estimate group symbol for the Unified Soil Classification System is shown in the ' appropriate column on the boring logs and a brief description of that classification system is included with this report. SITE AND SUBSURFACE CONDITIONS The proposed church site is located north of Harmony Road and east of Regency Drive in Fort Collins. The site is presently an undeveloped grass field. Surface drainage is towards the south and east with a maximum difference in surface elevations across the site on the order of 2 feet. Evidence of prior building construction was not observed at the site by our drill crew. Field logs of the materials encountered during drilling were prepared by the drill crew. Those logs contain descriptions of the subsurface materials encountered based on visual and tactual observation of the recovered samples and auger cuttings. The final logs included with this report may contain modifications to the field logs based on results of laboratory testing and engineering evaluation. Based on results of the field borings, subsurface conditions can be generalized as follows. Three to five inches of vegetation and/or topsoil was encountered at the surface at the boring locations. The topsoil and/or vegetation was underlain by lean clay with varying amounts of sand and/or silt. The lean clay cohesive soils extended to depths ranging from approximate 5 to 7 feet below surface in the building area and to the bottom of many of the parking lot borings at depths of approximately 5 feet. The lean clay was underlain by silty Terracon Job No. 12915055 December 18, 1991 Page 5 granular soils containing varying amounts of gravel. Those granular materials were colored light brown and reddish brown and were medium dense. Occasional clayey zones were observed in the granular materials. Those materials extended to the bottom of the borings except for boring B-12. At that location, the silty sand was underlain by very stiff, lean to fat clay which extended to the bottom of the boring at a depth of approximately 28 feet. The lean to fat clay was colored brown. The stratification boundaries shown on the boring logs represent the approximate location of changes in soil types; in -situ, the transition of materials may be gradual and indistinct. WATER LEVEL OBSERVATIONS Observations were made while drilling and after completion of the borings to detect the presence and level of free water. Free water was observed only in boring B-12 (at a depth of approximately 17 feet) as the borings were being advanced. Immediately after completion of that boring, free water was again observed in the borehole at a depth of approximately 17 feet. The silty granular soils and cohesive materials observed in the borings have low permeability so that longer term observations would be required to ' more accurately evaluate groundwater conditions. Zones of perched and/or trapped water may occur in the overburden soils at times throughout the year depending on variations in hydrologic conditions and other conditions not apparent at the time of this report. Installation of piezometers and/or monitoring wells which are sealed from the influence of surface water would be required to further evaluate groundwater conditions. Terracon Job No. 12915055 December 18, 1991 Page 6 ANALYSIS AND RECOMENDATIONS Foundations Based on the materials observed at the boring locations, it is our opinion that footing foundations bearing on the natural site soils could be used for support of the proposed building. We recommend those footing foundations extend through all existing vegetation and/or topsoil and bear in the natural, very stiff lean clay with varying amounts of sand or underlying natural, medium dense silty sand with varying amounts of gravel. For design of footing foundations bearing on the natural, very stiff cohesive soils or natural, medium dense granular soils, we recommend using a net allowable total load soil bearing pressure not to exceed 3,000 psf. The net bearing pressure refers to the pressure at foundation bearing level in excess of the minimum surrounding overburden pressure. With approximately 4 feet of fill being placed in the building area to develop site grades, it may be desirable to support footing foundations directly on the newly placed and compacted fill. We recommend at least 1 foot of new fill be present beneath the footing foundations or that the foundations be extended to bear on the underlying natural soils. Fill required to develop foundation bearing levels should consist of approved, low -volume change material, free from organic matter and debris. Normally, soils with a plasticity index of 18 percent or less and containing a minimum of 15 percent fines could be used for low -volume change fill. We recommend those soils be placed in loose lifts not to exceed 9 inches thick, adjusted in moisture content and compacted to at least 100 percent of the material's maximum dry density as determined in accordance with ASTM Specification D-698, the standard Proctor procedure. The moisture content of the fill soils ' Job No. 12915055 Terracon December 18, 1991 ' Page 7 ' should be adjusted to within the range of minus 2 to plus 2 percent of standard Proctor optimum moisture. Footing foundations bearing on properly placed and compacted fill as outlined above could be designed for a net allowable total load soil bearing pressure not to exceed 3,000 psf. Exterior foundations and foundations in unheated areas should be located at least 30 inches below adjacent exterior grade to provide frost protection. We recommend formed continuous footings have a minimum width of 16 inches and isolated column foundations a minimum width of 30 inches. The suitability of trenched foundations will depend largely upon the fill materials used in the building area. If used, we recommend trenched foundations have a minimum width of 12 inches. No unusual problems are anticipated in completing the excavations required for the construction of footing foundations. Prior to placement of fill in the building area, all existing vegetation and/or topsoil should be removed. In addition, care should be taken to minimize moisture fluctuations in the bearing soils. Loosened or disturbed materials or extremely wet or dry materials should be removed from the foundation excavations prior to placement of reinforcing steel and foundation concrete. We estimate the long-term settlement of footing foundations designed and constructed as recommended above would be small, less than 3/4-inch. Floor Slab and Pavement Subarades All existing vegetation and/or topsoil should be removed from the floor and pavement areas. After stripping and completing all cuts and prior to placement of any fill, floor slabs or pavements, we