HomeMy WebLinkAbout3405 S TIMBERLINE RD WIRELESS TELECOMMUNICATIONS EQUIPMENT - BDR200014 - SUBMITTAL DOCUMENTS - ROUND 2 - RESPONSE TO STAFF REVIEW COMMENTS,F�`ort_Collins September 29, 2020 Jaclyn Levine Nexius Solutions 7025 S Fulton St Suite 100 Centennial, CO 80112 RE: 3405 S Timberline Rd AT&T Wireless Telecommunications, BDR200014, Round Number 1 Please see the following summary of comments from City staff and outside reviewing agencies for your submittal of 3405 S Timberline Rd AT&T Wireless Telecommunications. If you have questions about any comments, you may contact the individual commenter or direct your questions through your Development Review Coordinator, Tenae Beane via phone at 970-224-6119 or via email at tbeane@fcgov.com. Comment Summary: Department: Light And Power Contact: Rob Irish, 970.224-6167, rirish(cDfcgov.com Topic: General Community Development and Neighborhood Services 281 North College Avenue PO Box 580 Fort Collins, CO 80522 970.221.6689 970.224.6134 - fax fcgov.com/deve/opmentreview Comment Number: 1 Comment Originated: 09/14/2020 09/14/2020: Information Only: the existing property at 3405 S. Timberline is currently a primary metered customer. Light & Power feeds primary to the customers primary metered cubicle on the switchgear. Everything beyond this point is customer owned. Will the applicant need a separate service or transformer for this installation?? Comment Number: 2 Comment Originated: 09/28/2020 09/28/2020: For Hearing: If the applicant anticipates taking power directly from COFC Light & Power, a dedicated transformer will need to be installed. The nearest available power feed is a primary vault along Danfield Ct. or primary running adjacent to this site along Timberline Rd. There were no utilities shown on the plans, but depending on where the fiber is coming into the site, Light & Power could do a joint trench to bring in a dedicated service to feed the WTF. Power is to be pulled directly from property owner. AT&T will submeter off of their building power, we will not need a new transformer from Light & Power. Comment Number: 3 Comment Originated: 09/28/2020 09/28/2020: For Hearing: Any existing and/or proposed Light & Power electric facilities that will remain within the limits of the project must be located within public right-of-way or in a utility easement. No changes to existing Light & Power electric facilities. Proposed project stays within private property using existing electric facilities Comment Number: 4 Comment Originated: 09/28/2020 09/28/2020: For Hearing: Any relocation or modification to existing electric facilities will be at the expense of the owner/developer. No relocation of electric facilities Comment Number: 5 Comment Originated: 09/28/2020 09/28/2020: For Hearing: A One -line diagram will need to be submitted to Light & Power for review. One -line diagram added to plans for review. Comment Number: 6 Comment Originated: 09/28/2020 09/28/2020: For Hearing: If the applicant anticipates having a transformer set, a C-1 Form will need to be submitted and a transformer location will need to be coordinated with Light & Power. No Transformer Required Comment Number: 7 Comment Originated: 09/30/2020 09/30/2020: For Final: Electric Capacity Fee, Building Site charges, and any system modification charges necessary will apply to this development. Please contact Light & Power Engineering at ElectdcProjectEngineedng@fcgov.com. Please reference our Electric Service Standards, development charges and fee estimator at the following link: http://www.fcgov.com/utilities/business/bu ilders-and-developers/plant-investmen t-development-fees Department: Planning Services Contact: Will Lindsey, wlindsey(a)fcgov.com Topic: General Comment Number: Comment Originated: 09/28/2020 09/28/2020: FOR APPROVAL: The antenna locations do not adequately address 3.8.13(C) (3) which states, 'all wireless telecommunication equipment shall be located as far from the edge of the roof as possible.' What other design/roof location options have you considered? The idea of turning the installation into an architectural feature could help alleviate the required setback from the edge of the building. Original designs submitted to the property owner were set back from the roof edges. Upon review, the Property owner requested that we engage their architecture firm to create a design that would enhance the exterior of the building. The final design proposal for the four sectors brought the enclosures closer to the roof edge in order to create new architectural features to the building. I% Comment Number: 09/28/2020: FOR APPROVAL: Comment Originated: 09/28/2020 Updated - Upon further review of the site plan and the architectural renderings it appears that there is a discrepnacy between the height of the Delta Tower shroud. The site plan reflects that the height of the shroud is 15', but the architectural rendering lists 20'. Please clarify the maximum intended height, and ensure it is consistent across all plans for future submittals. IF the current delta tower does exceed the maximum allowable 15' height for WTE as specified in 3.8.13(C)(3) which states, "Whenever a wireless telecommunication antenna is attached to a building roof, the height of the antenna shall not be more than fifteen (15) feet over the height of the building." than a modification of standard would be necessary for the project. For details regarding the Modification of Standard process please consult Land Use Code Division 2.8: https:Hlibrary.municode.com/co/fort_collins/codes4and_use? node ld=ART2AD DIV2.8MOST Regardless, as discussed previosly the height of the delta tower concealment wall is out of scale with the existing architectural character and overall aesthetics of the building. A reduction of height or an adjustment to the proportionality of the shroud to match the buildings existing height will be necessary to better integrate with the overall architecture. Delta sector has been re -designed. The re -design includes lowering the sector 4-feet and expanding the enclosure to resemble the other sectors. Additionally, the color palette has been updated making it more compatible with the rest of the structure. While this design brought Delta sector closer to the roof edge, it has now become an architectural feature of the building. Per additional discussions with planning, it was determined that the Delta sector height is permitted to be 15-feet above the highest point of the building which stands at 30'-6". The updated design is now 4-feet shorter than originally proposed. The need for the extra height for this sector is due to the PRPA parking structures to the West of the building. These parking structures have metal roofs which may cause interference issues with the antennas if they are unable to transmit over those structures. Department: Engineering Development Review Contact: Dave Betley, 970-221-6573, dbetley(a?fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/24/2020 09/24/2020. The site does not seem to have any offsite improvements at this time. Engineering has no comments. If any on site easements needed for Emergency access, Engineering will help process the documents. Comment Number: 2 Comment Originated: 09/24/2020 09/24/2020: If there are any improvements or street cuts needed for the right of way, the plans will need to comply with the Larimer County Urban Area Street standards. If additional information is needed, please feel free to contact me at 970-829-8882. 3 Department: Stormwater Engineering Contact: Dan Mogen, 970-305-5989, dmogen a(�fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/21/2020 09/21/2020: INFORMATION: The proposed site changes shown in this submittal are not substantial enough to trigger Stormwater requirements; therefore, no requirements apply at this time. Please note: it is assumed based on the provided plans that the existing grading and drainage patterns will be maintained. If this assumption is incorrect or if future submittals include site or grading changes that are not shown on these plans, please contact Dan Mogen at (970)305-5989 or dmogen@fcgov.com to coordinate and determine what requirements, if any, will apply. Department: Water -Wastewater Engineering Contact: Dan Mogen, 970-305-5989, dmo en fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/21/2020 09/21/2020: FOR APPROVAL: Please clarify how fiber, and any other necessary connections, will be made - that is, where is the connecting fiber being routed. If possible, please show proposed alignment(s) and identify all crossings/conflicts with other utilities. If a proposed alignment is not currently known, please show all water utilities (water, wastewater, and stormwater - both public and private) on and adjacent to the site. Please contact me for a map showing schematic locations of these existing utilities. Fiber route has been incorporated into plans. The proposed route will not conflict with Existing utilities according to the schematic map provided by Dan Mogen. Comment Number: 2 Comment Originated: 09/21/2020 09/21/2020: INFORMATION: It does not appear this project will cause a change to the existing water or sewer services, adjacent City facilities, or the usage within the building. If this is incorrect or if plans change, please contact me directly to discuss. Please note that the existing water and fire services appear to come into the building at or near the southeast corner of the building where Beta & Gamma Sectors are proposed. Department: Erosion Control Contact: Basil Hamdan, 970-222.1801, bhamdanpfcgov.com Topic: Erosion Control Comment Number: 2 Comment Originated: 09/23/2020 09/23/2020: INFORMATION ONLY: No Comment from Erosion and Sediment Control. Based on the submitted planning materials it has been determined that this project, will disturb less than 10,000 sq. ft., is not proposed to be in a sensitive area, has no steep slopes (greater than 3H:1 V) within or adjacent to the project, and is not part of a larger 4 common development that will or is under construction. Therefore, no Erosion and Sediment Control materials submittal is needed. If this project substantially changes in size, scope or design where the above cited criteria would apply, erosion and sediment control materials should be submitted. Though the project at this time requires no erosion control and sediment materials submittal, the project still must be swept and maintained to prevent dirt, saw cuttings, concrete wash, trash debris, landscape materials and other pollutants from potentially leaving the site and entering the storm sewer system at all times during the project in accordance with Municipal Code Section 26498. If complaint driven or site observation of the project show that there is any pollutant discharge, the City may require the project to install erosion and sediment control measures. Nearby inlets that may be impacted by the pollutants, in particular dirt, should be protected as a good preventive practice and individual lots should be protected from any material deposition on the sidewalk. If at building permit issuance any issues arise please email erosion@fcgov.com to facilitate getting any permits signed off. Department: PFA Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler(a)poudre-fire.orq Topic: General Comment Number: 1 Comment Originated: 09/28/2020 09/28/2020: This building recently underwent fire code modifications relative to redevelopment. The building is currently code compliant. So long as the generator or other backup power remains on the ground, there are no fire department comments specifically related to the proposed WTF install. Comment Number: 2 Comment Originated: 09/28/2020 09/28/2020: ADDRESS POSTING New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible, visible from the street or road fronting the property, and posted with a minimum of eight -inch numerals on a contrasting background. Department: Forestry Contact: Molly Roche, 224-616-1992, mroche ar7.fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/30/2020 9/30/2020, PRE -SUBMITTAL: Forestry Tree Inventory If there are existing trees on -site, please schedule an field meeting with City Forestry to obtain existing tree inventory and mitigation information. This meeting should occur whether trees are planned to be protected or not. Existing significant trees shall be preserved and protected to the extent reasonably feasible. The proposal does not require any tree removal. Comment Number: 2 Comment Originated: 09/30/2020 9/30/2020: FOR HEARING If applicable, please provide a landscape plan that meets the Land Use Code 3.2.1 requirements. This should include the existing tree inventory, any proposed tree removals with their locations clearly noted and any proposed tree plantings (including species, size, quantity and method of transplant). The plans 5 should also include the following City of Fort Collins notes: Landscape plan not required. All ground equipment will be enclosed within an existing fenced Area behind the building General Landscape Notes Tree Protection Notes Street Tree Permit Note, when applicable. These notes are available from the City Planner or by following the link below and clicking on Standard Plan Set Notes: hftps://www.fcgov.com/developmentreview/applications.php Required tree sizes and method of transplant: Canopy Shade Tree: 2.0" caliper container or equivalent Evergreen tree: 6.0' height container or equivalent Ornamental tree: 2.0" caliper container or equivalent Canopy Shade Tree as a street tree on a local or collector street only: 1.25" caliper container or equivalent Required mitigation tree sizes: Canopy Shade Tree: 2.0" caliper balled and burlapped Evergreen tree: 8.0' height balled and burlapped Ornamental tree: 2.0" caliper balled and burlapped Comment Number: 3 Comment Originated: 09/30/2020 9/30/2020: FOR HEARING If applicable, please include locations of utilities on the landscape plan including but not limited to water service/mains, sewer service/mains, gas, electric, streetlights, and stop signs. Please adjust tree locations to provide for proper tree/utility separation. 10' between trees and public water, sanitary, and storm sewer main lines 6' between trees and water or sewer service lines 4' between trees and gas lines 10' between trees and electric vaults 40' between canopy shade trees and streetlights 15' between ornamental trees and streetlights For any trenching that may occur, please delineate the length and width of the trench especially when in close proximity to trees. Comment Number: 4 Comment Originated: 09/30/2020 9/30/20: INFORMATION ONLY FOR PDP If applicable, please provide an "Existing Tree Removal Feasibility Letter" for City Forestry staff to review. Proposals to remove significant existing trees must provide a justification letter detailing the reason for tree removal. This is required for all development projects proposing significant tree removal regardless of the scale of the project. The purpose of this letter is to provide a document of record with the project's approval and for the City to maintain a record of all proposed significant tree removals and justifications. Existing significant trees within the project's Limits of Disturbance (LOD) and within natural area buffer zones shall be preserved to the extent reasonably feasible. Streets, buildings and lot layouts shall be designed to minimize the disturbance 6 to significant existing trees. (Extent reasonably feasible shall mean that, under the circumstances, reasonable efforts have been undertaken to comply with the regulation, that the costs of compliance clearly outweigh the potential benefits to the public or would unreasonably burden the proposed project, and reasonable steps have been undertaken to minimize any potential harm or adverse impacts resulting from noncompliance with the regulation.) Where it is not feasible to protect and retain significant existing tree(s) or to transplant them to another on -site location, the applicant shall replace such tree(s) according to City mitigation requirements. Department: Building Services Contact: Russell Hovland, 970-416.2341, rhovland(a.fcgov.com Topic: Building Insp Plan Review Comment Number: 1 Comment Originated: 09/28/2020 09/28/2020: Construction shall comply with adopted codes as amended. Current adopted codes are: 2018 International Building Code (IBC) with local amendments. 2020 National Electrical Code (NEC) as amended by the State of Colorado Copies of current City of Fort Collins code amendments can be found at fcgov.com/building. Snow Load Live Load: 30 PSF / Ground Snow Load 30 PSF. Frost Depth: 30 inches. Wind Loads: Risk Category II (most structures): 140mph (Ultimate) exposure B or Front Range Gust Map published by The Structural Engineer's Association of Seismic Design: Category B. INFORMATIONAL ITEMS: 1. This new equipment must designed with attachments that meet the wind and snow load and plans must be stamped be a CO lic architect or engineer. 2. A City licensed commercial general contractor is required to construct any new commercial structure. Department: Technical Services Contact: Jeff County, 970.221-6588, jcounty(&fcgov.com Topic: Building Elevations Comment Number: 4 09/28/2020: All plan sheets are required to be 24"x36". Comment Number: 5 09/28/2020: There are line over text issues. See redlines. Topic: General Comment Originated: 09/28/2020 Comment Originated: 09/28/2020 Comment Number: 1 Comment Originated: 09/28/2020: TELECOM SET: Some of the sheet titles & sheet numbers in the sheet index do not match the noted sheets. See redlines. Comment Number: 2 Comment Originated: 09/28/2020 09/28/2020 VA 09/28/2020: TELECOM SET: Please provide the following information for the Benchmark Statement in the EXACT format shown below. PROJECT DATUM: NAVD88 BENCHMARK # w/ DESCRIPTION ELEVATION: BENCHMARK # w/ DESCRIPTION ELEVATION: PLEASE NOTE: THIS PLAN SET IS USING NAVD88 FOR A VERTICAL DATUM. SURROUNDING DEVELOPMENTS HAVE USED NGVD29 UNADJUSTED DATUM (PRIOR CITY OF FORT COLLINS DATUM) FOR THEIR VERTICAL DATUMS. IF NGVD29 UNADJUSTED DATUM (PRIOR CITY OF FORT COLLINS DATUM) IS REQUIRED FOR ANY PURPOSE, THE FOLLOWING EQUATION SHOULD BE USED: NGVD29 UNADJUSTED DATUM (PRIOR CITY OF FORT COLLINS DATUM) = NAVD88 DATUM - X.XX'. Comment Number: 3 Comment Originated: 09/28/2020 09/28/2020: TELECOM SET: There are line over text issues. See redlines. Comment Number: 6 Comment Originated: 09/28/2020 09/28/2020: ROOF PLAN: All plan sheets are required to be 24"x36". Comment Number: 7 Comment Originated: 09/28/2020 09/28/2020: ROOF PLAN: There are line over text issues. See redlines. Comments addressed in updated plan sets.