August 25, 2020
Chris O'Sullivan
NCO REAL ESTATE COMPANY LLC & BROTHER'S BBQ
4645 W Colfax Ave
Denver, CO 80204
RE: Brothers BBQ, PDP200005, Round Number 3
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of Brothers BBQ. If you have questions about any comments,
you may contact the individual commenter or direct your questions through your
Development Review Coordinator, Brandy Bethurem Harras via phone at 970-416-2744 or
via email at bbethuremharras@fcgov.com.
Comment Summary:
Department: Historic Preservation
Contact: Maren Bzdek, 970-221-6206, mbzdek(a)fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 06/16/2020
06/16/2020: INFORMATION: As noted in your conceptual review, this project isn't subject to
historic review regarding the exterior alterations to the building because the
survey form determined that the building, as is, does not qualify as a historic
resource due to lack of integrity.
Because your project constitutes a historic restoration project, generally
speaking, it might be worth considering whether it would meet the historic
character/integrity requirements for a local landmark once the project is
complete. If we could establish that the answer is yes (through further evaluation
with the Historic Preservation Division), AND if you wished to designate the
property in order to take advantage of the state tax credit opportunities for
historic properties, you would want to begin that dialogue with us before any
significant work on the building exterior begins. If this is of interest to you,
please contact me asap.
Department: Engineering Development Review
Contact: Spencer Smith, 970-221-6603, smsmith fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 06/15/2020
06/15/2020: FOR FINAL
The demolition and relocation plan needs to contain more information and
details for all demolition and relocation of existing infrastructure. See redlines
for more details.
Per conversation with Spence on 9/28, further clarification was provided regarding demolition information needed. This included
information regarding the need for the demolition plan to include the extent and square footage of demo'd asphalt required for
widened sidewalks and drive access. The revised demo site plan included in the FDP identifies the extent and square footage.
Also, please note that the proposed location of new utilities and infrastructure is included on the site plan (sheet Al03), not the
demolition plan.
Comment Number: 3
Comment Originated: 06/15/2020
06/15/2020: FOR FINAL
Identify specific curb type (vertical) for all proposed curb and gutter in the public
right-of-way.
Per conversation with Spence on 9/28 it was confirmed that this information is already on site plan and was missed in last review.
Comment Number: 7
Comment Originated: 06/15/2020
08/03/2020: FOR FINAL
Thank you for submitting the DA information form. A draft of the DA will be
prepared and provided to you for review during the FDP stage of the approval
process.
Thank you for letting us know. The Brother's BBQ owners will look forward to receiving the Draft DA.
06/15/2020: FOR FINAL
A Development Agreement will be required for this project. A draft of the
agreement will be prepared by the City after the first final plan submittal. Prior
to preparing the draft, I will need the development agreement information form
to be completed by the developer. This form is available at:
hftps://www.fcgov.com/engineering/devrev.php. This form can be submitted at
any time. If the form is not submitted with the first final plan (FDP) submittal, it
could delay preparation of the draft DA.
See previous comment. Development agreement information form was previously submitted by owners.
Comment Number: 8
Comment Originated: 06/15/2020
06/15/2020. INFORMATION ONLY
All public sidewalk, driveways and ramps, existing or proposed, adjacent or
within the site, need to meet ADA standards. If they currently do not, they will
need to be reconstructed so that they do meet current ADA standards as a part
of this project.
Comment Number: 9
Comment Originated: 06/15/2020
2
06/15/2020: INFORMATION ONLY
A Development Construction Permit (DCP) will need to be obtained prior to
starting any work on the site.
Comment Number: 11 Comment Originated: 08/03/2020
08/03/2020: FOR FINAL
I am providing a copy of a utility plan for reference. Please use it as a guide in
the level of design detail and information that should be on the utility plan sheets,
demolition plan, etc.
Thank you for providing this as a reference.
Comment Number: 13
Comment Originated: 08/03/2020
08/03/2020: FOR FINAL
The sheet titled "Grading Plan" is not a grading plan. The sheet should
probably be renamed something more accurate.
This drawing was created as a request from Matt Simpson to show a "simple grading plan" which in effect shows existing water
flows on the site. However, I noticed the flow arrows layer was turned off and these are turned back on in the submitted FDP
drawings. Also, Please note I have changed the title of this drawings to read "Site Plan With Drainage Arrows sHOWN"
Comment Number: 14
Comment Originated: 08/03/2020
08/03/2020: FOR FINAL
Please adjust leaders, callouts, text, etc. to avoid linework or text over text (see
redlines for examples).
I have done additional drawing coordination to improve leaders, callouts, text, etc. In the FDP submittal the notes and callouts have
been moved to the margins where possible to improve the legibility of the site plan. Thank you!
Comment Number: 15
Comment Originated: 08/03/2020
08/03/2020: FOR FINAL
Per previous discussions, we will need to see what is proposed for the sidewalk
connection at the southeast corner of the site. You should provide some sort of
barricade, signage, etc. making it clear to cyclists and pedestrians that the
sidewalk narrows to 4 foot at the property line.
Per phone call with Spencer on 9/28, Spencer will follow up with other City Staff and let Nathan know what they would like to have
done regarding this issue soon. In a follow up email on Oct. Nathan offered a couple of suggestions: For example, on Taft Hill,
perhaps we should add a sign below the existing "Bike Lane" sign on the light pole announcing "Path Narrows"? On Mulberry St
perhaps we should add a stand-alone sign in front of the fence also announcing "Path Narrows'? The project owners are happy to
accommodate whatever the City feels ricis best as long as they can reasonably accommodate. We are still awaiting a response at
this time.
Comment Number: 16
08103/2020: FOR FINAL
Detail 707.2 is not needed.
applicable to this site.
This detail has been removed.
Comment Originated: 08/03/2020
The detail is for high volume driveways, which is not
k,
Comment Number: 17
Comment Originated: 08/25/2020
08/25/2020: FOR FINAL
Please see redlines for additional comments to be addressed during the FDP
process.
The following note was included on engineering redlines: "FOR FINAL PLANS:- COLORED LINEWORK IS NOT GENERALLY
PREFERRED. YOU MAY WANT TO USE A DIFFERENT LINETYPE FOR THE FLOODWAY/FLOOD FRINGE LINEWORK THIS IS IN
GRAYSCALE-SOME OF THE DIMENSION TEXT IS ON THE SMALL SIDE. IF YOU CAN INCREASE THE FONT SIZE ON THE FINAL
PLANS, THAT WOULD BE GREAT" Colored linework has been removed in the FDP. Dimension Text has been increased on the
FDP. (Note: this was the only comment included on the redlines and comment has been addressed as described above).
Department: Traffic Operation
Contact: Martina Wilkinson, 970-221-6887, mwilkinson(cDfcgov.com
Topic: General
Comment Number: 3
07/27/2020: no comments.
Department: Erosion Control
Contact: Basil Hamdan, 970-222-1801,
Topic: Erosion Control
Comment Number: 2
bhamdan@fcgov.com
Comment Originated: 07/27/2020
Comment Originated: 06/12/2020
08/19/2020: FOR FINAL:
08/05/2020:
Per discussions there might be a large amount of asphalt work. Any work that
will disturb down to the sub -grade needs to be considered part of of the
disturbed area. If this project disturbs greater then 10,000 square feet including
parking areas erosion control materials will be required. Please verify the how
the asphalt is going to be replaced or ground off and resealed so that we can
make sure that the project does or doesn't require erosion control materials to
be supplied.
The following notes has been added to Sheets A101, A102 and A103 on the FDP: "RESURFACE AND RESEAL THE TOP LAYER
OF ALL EXTG ASPHALT ON NORTH AND EAST SIDES OF THE BUILDING TO ACHIEVE A LEVEL AND SMOOTH SURFACE.
MAINTAIN ALL EXISTING GRADES AND DO NOT DISTURB SUB -GRADE."
In addition, a legend has been added to sheet A101 identifying those areas to be resurfaced without disturbing sub grade and those
areas where complete removal is required. The total combined area of all resurfaced and completely removed areas, as noted on
Sheet A101, is 9,817 SF.
07/20/2020:
06/12/2020. FOR INFORMATION:
Based upon the submitted Planning Materials it has been determined that this
project; will disturb less than 10,000 sq. ft., is not proposed to be in a sensitive
area, has no steep slopes (greater than 3H:1V) within or adjacent to the project,
and is not part of a larger common development that will or is under
construction. Therefore, no Erosion Control Material submittal is needed. If this
project substantially changes in size or design where the above criteria now
4
apply, erosion control materials should be submitted. Though the project at this
time requires no erosion control material submittal, the project still must be
swept and maintained to prevent dirt, saw cuttings, concrete wash, trash debris,
landscape materials and other pollutants from the potential of leaving the site
and entering the storm sewer at all times during the project in accordance with
City Code 26-498. If complaint driven or site observation of the project seem
not to prevent the pollutant discharge the City may require the project to install
erosion and sediment control measures. Nearby inlets that may be impacted by
the pollutants, in particular dirt, should be protected as a good preventative
practice and individual lots should be protected from material escaping onto the
sidewalk. If at building permit issuance any issues arise please email
erosion@fcgov.com to help facilitate getting these permits signed off.
Department: Water -Wastewater Engineering
Contact: Matt Simpson, (970)416-2754, masimpson(a)fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 06/08/2020
08/03/2020: FOR INFORMATION: Water service sizing memo accepted.
Comment resolved. Thank you!
06/08/2020: FOR HEARING:
Utilities will need confirmation that the existing 1/4-inch water service is sufficient
for the proposed restaurant. This typically takes the form of a 1-page memo
and supporting water demand calculations from the project mechanical
engineer. This will be required with the Round 2 submittal. I encourage you to
contact me with any questions at masimpson(d�fcgov.com
See comment #1 above. Water sizing memo was accepted and comment has been resolved.
Comment Number: 6
Comment Originated: 06/22/2020
08/03/2020: FOR FINAL: Please locate and show the curb stop (City water
valve) on the site plan.
Per phone conversation on 9/28, Matt will send city inspector to verify location of City Water Valve and get back to Nathan. Based
on city records, Curb stop location (City Water Valve) is located 5' west of the west curb of Taft Hill Rd. We will add info to site plan
as soon as available. In a follow up email sent of Oct. 5, Matt noted that we are working with Water Utilities to located the curb stop
and will add this to plans in the future.
06/22/2020: FOR HEARING:
On the site plans, please show and label the existing water meter and curb stop.
Please see attached redlines for more information.
This is the same comment as above. Per phone conversation on 9/28, Matt will send city inspector to verify location of City Water
Valve and get back to Nathan. Based on city records, Curb stop location (City Water Valve) is located 5' west of the west curb of
Taft Hill Rd. Nathan will add info to site plan as soon as available.
Comment Number: 8
08/03/2020: FOR FINAL:
Comment Originated: 08/03/2020
4�
On the mechanical plans, the grease interceptor needs to be shown on the
same location as on the site plan.
During a phone conversation w/ Matt Simpson on 9/28/2020 it was confirmed that the location of the grease interceptor are
consistent on the Site Plan and MEP drawings.
Comment Number: 9
08/04/2020: FOR INFORMATION ONLY:
Ready for Hearing
Department: Environmental Planning
Contact: Scott Benton, sbenton fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 08/04/2020
Comment Originated: 08/03/2020
08/03/2020: READY FOR HEARING: Thank you for addressing Round 1
comments, Environmental Planning is ready for hearing. Please keep me
informed of the results of the search for the oil/water interceptor system -
whether one is found and properly removed, or whether one is not found.
Department: Forestry
Contact: Molly Roche, 224-616-1992, mroche(a)fcgov.com
Topic: General
Comment Number: 8 Comment Originated: 08/07/2020
8/7/2020: FOR FINAL APPROVAL
As required in the Land Use Code and General Landscape Notes, all trees and
other landscaping on -site shall receive direct automatic irrigation. The street
trees in grates shall be on their own irrigation zone. Please contact Eric Olson in
Water Utilities to develop an adequate irrigation plan for this site. Forestry will
provide Eric details for a double drip -ring assembly. Thank you!
The submitted FDP notes drip irrigation for all new trees and plantings. Per phone call with Eric Olsen on 10/6/2020 the owner will
need drip irrigation to all new trees and plantings before a building permit can be issued. I have added the inline pipe drip
assembly detail from Eric (see detail #5 on sheet All 00. Also, see additional notes about irrigation plan requirements at the end of
this document under "water Conservation' comments provided by Eric.
Comment Number: 9
Comment Originated: 08/24/2020
8/24/2020: FOR FINAL APPROVAL
Please add the new Kentucky Coffeetree 'Espresso' to the plant list.
Kentucky Coffeetree has been added to the tree schedule.
Please also note that per conditions of the Planning and Zoning Board approval of the PDP, a second Kentucky Coffeetree has
been added near the NE corner of the building. In addition, we have added a Crimson Fire Columnar Oak to the schedule (to be
placed on South Patio). There are now a total of 6 new trees included on the FDP site plan.
Comment Number: 10
8/24/2020: FOR FINAL APPROVAL
Comment Originated: 08/24/2020
R
Please update the label on tree #5 to REMOVE. Currently, the status is still
showing this tree to be preserved. Review Forestry redlines for further
clarification.
This has been updated on the FDP submittal.
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, ilynxwiler(a�poudre-fire.org
Topic: General
Comment Number: 5 Comment Originated: 07/31/2020
07/31 /2020:
Prior PFA comments resolved. No new comments. Ready for hearing.
Department: Building Services
Contact: Katy Hand, khand(cDfcgov.com
Topic: Building Insp Plan Review
Comment Number: 1 Comment Originated: 06/15/2020
06/15/2020: For Building Permit: Be aware that outdoor seasonal patio
occupancy must now be included in the required plumbing fixture count.
Please note the outdoor patios are both included in the required plumbing fixture count as reflected in the code analysis.
Noted
Contact: Russell Hovland, 970-416-2341, rhovland(cDfcgov.com
Topic: Building Insp Plan Review
Comment Number: 2 Comment Originated: 08/03/2020
08/03/2020: This is a change of occupancy and will require a building permit
and require the building meet current code for the new restaurant occupancy.
Department: Technical Services
Contact: Jeff County, 970-221.6588, jcounty(cDfcgov.com
Topic: General
Comment Number: 2 Comment Originated: 06/09/2020
07/29/2020: INFORMATION ONLY:
Unless required during PDP, a complete review of all plans will be done at
FDP.
06/09/2020: INFORMATION ONLY:
Unless required during PDP, a complete review of all plans will be done at
FDP.
Topic: Plat
Comment Number: 3 Comment Originated: 07/29/2020
07/29/2020: FOR FINAL APPROVAL:
Please make changes as marked. If changes are not made or you disagree
rA
with comments, please provide written response of why corrections were not
made. Please provide any responses on redlined sheets and/or in response
letter.
Our surveyor/civil engineer has been in direct communication with Jeff County and John Von Nieda re: resolving outstanding ROW
questions and received additional ROW documents that affect our site on 10/6. An updated Plat will be sent shortly.
Department: Water Conservation
Contact: Eric Olson, 970-221-6704, eolsonna.fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 07/21/2020
07/21/2020: Irrigation plans are required no later than at the time of building
permit. The irrigation plans must comply with the provisions outlined in Section
3.2.1(J) of the Land Use Code. Direct questions concerning irrigation
requirements to Eric Olson, at 221-6704 or eolson fcgov.com
Per phone call with Eric on 10/6/2020 the owner will need drip irrigation to all new trees and plantings before a building permit can
be issued. Irrigation line sleeves are required to all new landscaped areas. These sleves should also extend to the southern edge
of the property (if the extg trees there need to be irrigated at some point and future active irrigation is needed). Irrigation plan will
need to specify a watering budget requirements (e.g., Kentucky Coffeetree has a moderate water budget requirement with exception
of 111 two years to get it established). Landscape contractors in Fort Collins will typically provide the irrigation plan as part of their
service, not the architect.
N