HomeMy WebLinkAboutOAK 140 - PDP200009 - SUBMITTAL DOCUMENTS - ROUND 1 - SUPPORTING DOCUMENTATION (3)N G DETAIL NOTES 1 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED PER NEC 250, INCLUDING METAL UNDERGROUND WATER PIPE, METAL FRAME OF THE BUILDING, CONCRETE-ENCASED ELECTRODE, AND ROD AND PIPE ELECTRODES. 2 SURGE PROTECTION DEVICE INTEGRAL TO SWITCHBOARD/PANELBOARD. SPD IS INSTALLED AND WIRED BY THE MANUFACTURER. PROVIDE OVER CURRENT PROTECTION DEVICE AS REQUIRED. 3 LIGHTING CONTROL PANEL FOR CONTROL OF EXTERIOR/INTERIOR LIGHTING. PROVIDE FEED THROUGH PANEL WITH DIMMING MODULES BASED UPON LIGHT FIXTURE SCHEDULE AND FIXTURE SUBMITTAL. 4 TYPICAL DWELLING UNIT LOAD CENTER. 208V, 1 PHASE, 3 WIRE, 125 AMPS, 10KAIC SERIES RATED. 5 PRIMARY RACEWAYS, CONDUCTORS, AND TERMINATIONS BY FORT COLLINS LIGHT & POWER. 1. PROVIDE INCREASED FEEDER CONDUCTOR SIZES AS REQUIRED TO ACCOMODATE VOLTAGE DROP. MAXIMUM VOLTAGE DROP ALLOWED AT DISTRIBUTION PANELS IS 2%. PROVIDE ALL NECESSARY JUNCTION BOXES AND SPLICES AS REQUIRED TO REDUCE OVERSIZED CONDUCTORS IN ORDER TO TERMINATE ON PANELBOARD LUGS. 2. PROVIDE SLEEVES AS REQUIRED FOR VERTICAL ROUTING OF FEEDERS. RACEWAYS ON LEVELS ABOVE THE PARKING GARAGE SHALL BE CONCEALED. ROUTE THROUGH WALLS AS REQUIRED. COORDINATE SLEEVE LOCATIONS AND RACEWAY ROUTING WITH STRUCTURAL ENGINEER AND GENERAL CONTRACTOR PRIOR TO ROUGH-IN. 3. MAINTAIN FIRE RATING OF ALL PENETRATIONS. 4. ELECTRICAL EQUIPMENT MUST FIT IN THE SPACE PROVIDED WHILE MAINTAINING ALL CLEARANCE AND WORKING SPACE REQUIREMENTS. 5. ALUMINUM ALLOY CONDUCTORS SHALL BE PERMITTED WHERE ALLOWED BY THE NEC EXCEPT TO ROTATING EQUIPMENT INCLUDING MECHANICAL EQUIPMENT AND ELEVATORS. 6. ALUMINUM BUSSING IS PERMITTED IN ALL ELECTRICAL EQUIPMENT. 7. APPLICABLE OVERCURRENT PROTECTION DEVICES SHALL COMPLY WITH ARC ENERGY REDUCTION REQUIREMENTS OF NEC 240.87. GENERAL NOTES 1 BUILDING STEAL METAL UNDERGROUND WATER PIPE CONCRETE ENCASED ELECTRODE GROUND ROD 1 E0.01 ELECTRICAL ONE-LINE DIAGRAM NO SCALE 400A/3P 2 SPD MAIN SWITCHBOARD : MSB-1 2000A, 120/208V, 3Ø, 4W, 100,000 AIC TYPICAL DWELLING UNIT LOAD CENTER 4 FCL&P PAD MOUNTED TRANSFORMER 120/208V SECONDARY 5 FIRST FLOOR N G DETAIL NOTES 1 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED PER NEC 250, INCLUDING METAL UNDERGROUND WATER PIPE, METAL FRAME OF THE BUILDING, CONCRETE-ENCASED ELECTRODE, AND ROD AND PIPE ELECTRODES. 2 SURGE PROTECTION DEVICE INTEGRAL TO SWITCHBOARD/PANELBOARD. SPD IS INSTALLED AND WIRED BY THE MANUFACTURER. PROVIDE OVER CURRENT PROTECTION DEVICE AS REQUIRED. 3 LIGHTING CONTROL PANEL FOR CONTROL OF EXTERIOR/INTERIOR LIGHTING. PROVIDE FEED THROUGH PANEL WITH DIMMING MODULES BASED UPON LIGHT FIXTURE SCHEDULE AND FIXTURE SUBMITTAL. 4 TYPICAL DWELLING UNIT LOAD CENTER. 208V, 1 PHASE, 3 WIRE, 125 AMPS, 10KAIC SERIES RATED. 5 PRIMARY RACEWAYS, CONDUCTORS, AND TERMINATIONS BY FORT COLLINS LIGHT & POWER. 1. PROVIDE INCREASED FEEDER CONDUCTOR SIZES AS REQUIRED TO ACCOMODATE VOLTAGE DROP. MAXIMUM VOLTAGE DROP ALLOWED AT DISTRIBUTION PANELS IS 2%. PROVIDE ALL NECESSARY JUNCTION BOXES AND SPLICES AS REQUIRED TO REDUCE OVERSIZED CONDUCTORS IN ORDER TO TERMINATE ON PANELBOARD LUGS. 2. PROVIDE SLEEVES AS REQUIRED FOR VERTICAL ROUTING OF FEEDERS. RACEWAYS ON LEVELS ABOVE THE PARKING GARAGE SHALL BE CONCEALED. ROUTE THROUGH WALLS AS REQUIRED. COORDINATE SLEEVE LOCATIONS AND RACEWAY ROUTING WITH STRUCTURAL ENGINEER AND GENERAL CONTRACTOR PRIOR TO ROUGH-IN. 3. MAINTAIN FIRE RATING OF ALL PENETRATIONS. 4. ELECTRICAL EQUIPMENT MUST FIT IN THE SPACE PROVIDED WHILE MAINTAINING ALL CLEARANCE AND WORKING SPACE REQUIREMENTS. 5. ALUMINUM ALLOY CONDUCTORS SHALL BE PERMITTED WHERE ALLOWED BY THE NEC EXCEPT TO ROTATING EQUIPMENT INCLUDING MECHANICAL EQUIPMENT AND ELEVATORS. 6. ALUMINUM BUSSING IS PERMITTED IN ALL ELECTRICAL EQUIPMENT. 7. APPLICABLE OVERCURRENT PROTECTION DEVICES SHALL COMPLY WITH ARC ENERGY REDUCTION REQUIREMENTS OF NEC 240.87. GENERAL NOTES 1 BUILDING STEAL METAL UNDERGROUND WATER PIPE CONCRETE ENCASED ELECTRODE GROUND ROD 1 E0.02 ALTERNATE ELECTRICAL ONE-LINE DIAGRAM NO SCALE 400A/3P 2 SPD MAIN SWITCHBOARD : MSB-1 2000A, 120/208V, 3Ø, 4W, 100,000 AIC TYPICAL DWELLING UNIT LOAD CENTER 4 FCL&P VAULT TRANSFORMER 120/208V SECONDARY 5 FIRST FLOOR G 100kW/125KVA RATED GENERATOR AT SITE ELEVATION, SUB-BASE FUEL TANK WITH FUEL CAPACITY FOR 2 HOURS OF RUN-TIME, SOUND ATTENUATING WEATHER PROOF ENCLOSURE AND SOUND PRESSURE REDUCING MUFFLER. ATS-EM G TAP BOX TEMP GENERATOR K PROVIDE KIRK KEY INTERLOCK BETWEEN CIRCUIT BREAKERS. K 200/3 SPD 400/3 PANEL GEN: NEMA-3R, 400A, 277/480V, 3Ø, 4-WIRE, 22,000 AIC 400/3 ATS-EM 200/3 3 POLE 100kAIC NEMA 3R PANEL GEN 250A/3P 600A/3P 200A/3P LIGHTING CONTROL PANEL 3 FIRE PUMP 60 HP ASSUMED G N M UTILITY METER BOND TO SERVICE GROUND 400A CT CABINET FIRE PUMP CONTROLLER SUPPLIED AND INSTALLED BY DIVISION 23. 400A/3P M COMBINER BOX DISC. DISC. TO INVERTER AND PV ARRAYS ON ROOF (1)3"C. (1)3"C. (1)3"C. (1)3"C. (1)3"C. E.C. SHALL PROVIDE SPECIFIED CONDUIT FOR CONNECTION OF GRID TIED PV SYSTEM. DASHED LIGHT LINE WEIGHT EQUIPMENT TO BE PROVIDED BY PV SYSTEM PROVIDER. COORDINATE CONDUIT ROUTING AND REQUIREMENTS WITH PV SYSTEM PROVIDER. PROVIDE A CAT-5 CABLE ROUTED FROM THE INVERTERS TO THE MANAGER'S OFFICE. FIELD VERIFY STUB OUT LOCATIONS WITH PV SYSTEM 1"C. PROVIDER. 300A/3P INSTALL CIRCUIT BREAKER AT END OF THE BUSWAY PER 2017 NEC 705.12(B)(2)(3)(b). PROVIDE PERMANENT WARNING LABEL. ELEV -1 400/3 ATS-ST 200/3 ATS-ST 200/3 3 POLE 100kAIC NEMA 3R PANEL GEN 200A/3P 200A MLO 42-POLE SPD PANEL ST 2 200A MLO 42-POLE SPD PANEL EM1 2 200A MLO 42-POLE SPD PANEL EM3 2 400A MLO 42-POLE PANEL L1 PANEL L1 250A MLO 42-POLE PANEL L3 250A MLO 42-POLE PANEL L6 600A MLO 42-POLE PANEL M6 400A MLO 42-POLE PANEL M1 MM 200A/3P SPACE 200A/3P SPACE MM UTILITY METER COMM. #2 MM COMM. #1 500A/3P 2000A/3P 250A FRN 250A/3P 250A FRN 250A/3P WIREWAY 500A JJN 600A/3P 500A JJN 600A/3P 500A JJN 600A/3P 500A JJN 600A/3P 500A JJN 600A/3P 500A JJN 600A/3P 1600A/3P SECOND FLOOR THIRD FLOOR FOURTH FLOOR FIFTH FLOOR SIXTH FLOOR G N BOND TO SERVICE GROUND MAIN SWITCHBOARD : MSB-2 2000A, 120/208V, 3Ø, 4W, 100,000 AIC 7[4-500kCMIL Al, 3-1/2"C] FEEDER SCHEDULE ALUMINUM 4000/W 3000/W 2500/W 2000/W 1600/W 1200/W 1000/W 800/W 750/W 600/W 500/W 400/W 350/W 300/W 250/W 225/W 200/W 175/W 150/W 125/W 100/W 90/W 80/W 70/W 60/W 50/W 40/W THIS TABLE INDICATES MINIMUM CONDUCTOR SIZE FOR FEEDERS OF THE AMPACITY INDICATED WHERE #/W INDICATES THE #-AMPACITY AND W-NUMBERS OF WIRE, #S/W INDICATES NO GROUND. ALL CONDUCTORS SHALL BE ALUMINUM UNLESS NOTED OTHERWISE. *CONDUCTOR AMPACITIES SHALL BE BASED ON TABLE 310.15(B)(16) 60 DEGREE COLUMN UP TO 100 AMPS AND 75 DEGREE COLUMN ABOVE 100 AMPS UNLESS OTHERWISE PERMITTED BY NEC. AMPACITY RATING SHALL BE SELECTED IN ACCORDANCE WITH NEC 110.14 (C). THE MASTER ELECTRICIAN SHALL BE RESPONSIBLE FOR ENSURING THAT NO FEEDERS OR BRANCH CIRCUITS ARE INSTALLED IN A MANNER OR SIZED IN SUCH A WAY AS TO VIOLATE NEC SERVICE GROUND TABLE 150G/CU #6 200G/CU #4 300G/CU 2 500G/CU 1/0 1000G/CU 2/0 >1000G/CU 3/0 SERVICE GROUND CONDUCTORS SIZED PER NEC TABLE 250.66 EQUIPMENT GROUND CONDUCTORS SIZED PER NEC TABLE 250.122 ALL CONDUCTORS SHALL BE ALUMINUM UNLESS NOTED OTHERWISE THE SERVICE GROUND CHART INDICATES THE MINIMUM SERVICE GROUND CONDUCTOR BASED ON #G WHERE # IS THE AMPACITY FROM THE CHART ABOVE, AND THE EQUIPMENT GROUND CHART INDICATES THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR SIZE #EG WHERE # IS THE RATING/SETTING OF THE OVERCURRENT DEVICE PROTECTING THE CONDUCTORS AND EQUIPMENT WHERE DISCREPANCIES OCCUR BETWEEN THE FEEDER SCHEDULE SCHEDULE AND THE GROUNDING TABLES, THE LARGER CONDUCTOR SHALL BE USED UNLESS OTHERWISE PERMITTED BY THE NEC. THE INSTALLATION SHALL MEET ALL NEC 250 GROUNDING AND BONDING REQUIREMENTS INCLUDING 250.4 PATH FOR FAULT CURRENT. PROVIDE COMPLETE RACEWAY SYSTEMS METALLICALLY JOINED, CONNECTED, AND FITTINGS AS REQUIRED FOR ELECTRICAL CONTINUITY PER NEC 300.10 11[W-700kcmil, 750kcmilG, 4"C] 8[W-700kcmil, 600kcmilG, 4"C] 7[W-700kcmil, 600kcmilG, 4"C] 6[W-600kcmil, 400kcmilG, 4"C] 5[W-600kcmil, 350kcmilG, 4"C] 4[W-500kcmil, 250kcmilG, 3-1/2"C] 4[W-350kcmil, 4/0G, 3"C] 3[W-400kcmil, 3/0G, 3"C] 3[W-350kcmil, 3/0G, 3"C] 2[W-500kcmil, 2/0G, 3-1/2"C] 2[W-350kcmil, 1/0G, 3"C] 2[W-250kcmil, #1G, 3"C] 2[W-4/0, #1G, 2-1/2"C] W-500kcmil, #2G, 3-1/2"C W-350kcmil, #2G, 3"C W-300kcmil, #2G, 3"C W-250kcmil, #4G, 3"C W- 4/0, #4G, 2-1/2"C W- 3/0, #4G, 2"C W- 2/0, #4G, 2"C W-1/0, #6G, 2"C W-1/0, #6G, 2"C W#1, #6G, 1-1/2"C W#2, #6G, 1-1/4"C W#2, #8G, 1-1/4"C W#4, #8G, 1-1/4"C W#6, #8G, 1"C EQUIPMENT GROUND TABLE 20EG #10 60EG #8 100EG #6 200-1200A PER ABOVE 1600EG 350KCMIL 2000EG 400KCMIL 2 1. PROVIDE A PRICE SEPARATE FROM THE BASE BID TO INSTALL THE ELECTRICAL DISTRIBUTION AS SHOW BELOW IN LIEU OF THE SYSTEM AS DEPICTED ON SHEET E0.01. MAJOR CHANGE IS THE QUANTITY AND MATERIAL OF SERVICE CONDUCTORS AND CHANGE FROM SINGLE PAD MOUNTED TRANSFORMER TO TWO VAULT TRANSFORMERS. PRICING NOTES EXISTING SERVICE REFEED (NOT IN SCOPE) FCL&P VAULT TRANSFORMER 120/208V SECONDARY 5 7[4-500kCMIL Al, 3-1/2"C] EQUIPMENT LOCATED IN FORT COLLINS LIGHT & POWER SUBGRADE VAULT. INSTALLATION SHALL COMPLY WITH ALL UTILITY AND LOCAL AUTHORITY HAVING JURISDICTIONAL REQUIREMENTS. 600A JJN 600A/3P M M M M M M M M M M M M METER CENTER-3B 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M M METER CENTER-4B 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M METER CENTER-4A 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M M METER CENTER-5B 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M METER CENTER-5A 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M METER CENTER-6B 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M METER CENTER-6A 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M PROJECT #: DRAWN: REV: SCALE: NO. SHEET TITLE: REVIEWED: DATE: FILE: 5 4 3 2 1 A B C D 6 E 7 7 6 5 4 3 2 1 A B C D E MVC SD-NOT FOR CONSTRUCTION MTV 2020-037-00 06/11/20 C:\Users\marcus\appdata\local\temp\AcPublish_33664\E0.02.dwg marcus 06.14.20 11:39 am SPARK 140 EAST OAK ST FORT COLLINS, CO AS NOTED ALTERNATE ELECTRICAL ONE-LINE E0.02 E0.02.dwg G 100kW/125KVA RATED GENERATOR AT SITE ELEVATION, SUB-BASE FUEL TANK WITH FUEL CAPACITY FOR 2 HOURS OF RUN-TIME, SOUND ATTENUATING WEATHER PROOF ENCLOSURE AND SOUND PRESSURE REDUCING MUFFLER. ATS-EM G TAP BOX TEMP GENERATOR K PROVIDE KIRK KEY INTERLOCK BETWEEN CIRCUIT BREAKERS. K 200/3 SPD 400/3 PANEL GEN: NEMA-3R, 400A, 277/480V, 3Ø, 4-WIRE, 22,000 AIC 400/3 ATS-EM 200/3 3 POLE 100kAIC NEMA 3R PANEL GEN 250A/3P 600A/3P 200A/3P LIGHTING CONTROL PANEL 3 FIRE PUMP 60 HP ASSUMED G N M UTILITY METER BOND TO SERVICE GROUND 400A CT CABINET FIRE PUMP CONTROLLER SUPPLIED AND INSTALLED BY DIVISION 23. 400A/3P M COMBINER BOX DISC. DISC. TO INVERTER AND PV ARRAYS ON ROOF (1)3"C. (1)3"C. (1)3"C. (1)3"C. (1)3"C. E.C. SHALL PROVIDE SPECIFIED CONDUIT FOR CONNECTION OF GRID TIED PV SYSTEM. DASHED LIGHT LINE WEIGHT EQUIPMENT TO BE PROVIDED BY PV SYSTEM PROVIDER. COORDINATE CONDUIT ROUTING AND REQUIREMENTS WITH PV SYSTEM PROVIDER. PROVIDE A CAT-5 CABLE ROUTED FROM THE INVERTERS TO THE MANAGER'S OFFICE. FIELD VERIFY STUB OUT LOCATIONS WITH PV SYSTEM 1"C. PROVIDER. 300A/3P INSTALL CIRCUIT BREAKER AT END OF THE BUSWAY PER 2017 NEC 705.12(B)(2)(3)(b). PROVIDE PERMANENT WARNING LABEL. ELEV -1 400/3 ATS-ST 200/3 ATS-ST 200/3 3 POLE 100kAIC NEMA 3R PANEL GEN 200A/3P 200A MLO 42-POLE SPD PANEL ST 2 200A MLO 42-POLE SPD PANEL EM1 2 200A MLO 42-POLE SPD PANEL EM3 2 400A MLO 42-POLE PANEL L1 PANEL L1 250A MLO 42-POLE PANEL L3 250A MLO 42-POLE PANEL L6 600A MLO 42-POLE PANEL M6 400A MLO 42-POLE PANEL M1 MM 200A/3P SPACE 200A/3P SPACE MM UTILITY METER COMM. #2 MM COMM. #1 500A/3P M M M M M M M M M M M M METER CENTER-3B 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC 600A JJN 600A/3P 2000A/3P 250A FRN 250A/3P 250A FRN 250A/3P WIREWAY M M M M M M M M M M M METER CENTER-4B 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M METER CENTER-4A 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M M METER CENTER-5B 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M METER CENTER-5A 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M METER CENTER-6B 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC M M M M M M M M M M METER CENTER-6A 600A, 208V, 3PHASE IN, 1PHASE OUT 65kAIC 500A JJN 600A/3P 500A JJN 600A/3P 500A JJN 600A/3P 500A JJN 600A/3P 500A JJN 600A/3P 500A JJN 600A/3P 1600A/3P SECOND FLOOR THIRD FLOOR FOURTH FLOOR FIFTH FLOOR SIXTH FLOOR G N BOND TO SERVICE GROUND MAIN SWITCHBOARD : MSB-2 2000A, 120/208V, 3Ø, 4W, 100,000 AIC 5[4-600kCMIL Cu, 4"C.] 5[4-600kCMIL Cu, 4"C.] FEEDER SCHEDULE ALUMINUM 4000/W 3000/W 2500/W 2000/W 1600/W 1200/W 1000/W 800/W 750/W 600/W 500/W 400/W 350/W 300/W 250/W 225/W 200/W 175/W 150/W 125/W 100/W 90/W 80/W 70/W 60/W 50/W 40/W THIS TABLE INDICATES MINIMUM CONDUCTOR SIZE FOR FEEDERS OF THE AMPACITY INDICATED WHERE #/W INDICATES THE #-AMPACITY AND W-NUMBERS OF WIRE, #S/W INDICATES NO GROUND. ALL CONDUCTORS SHALL BE ALUMINUM UNLESS NOTED OTHERWISE. *CONDUCTOR AMPACITIES SHALL BE BASED ON TABLE 310.15(B)(16) 60 DEGREE COLUMN UP TO 100 AMPS AND 75 DEGREE COLUMN ABOVE 100 AMPS UNLESS OTHERWISE PERMITTED BY NEC. AMPACITY RATING SHALL BE SELECTED IN ACCORDANCE WITH NEC 110.14 (C). THE MASTER ELECTRICIAN SHALL BE RESPONSIBLE FOR ENSURING THAT NO FEEDERS OR BRANCH CIRCUITS ARE INSTALLED IN A MANNER OR SIZED IN SUCH A WAY AS TO VIOLATE NEC SERVICE GROUND TABLE 150G/CU #6 200G/CU #4 300G/CU 2 500G/CU 1/0 1000G/CU 2/0 >1000G/CU 3/0 SERVICE GROUND CONDUCTORS SIZED PER NEC TABLE 250.66 EQUIPMENT GROUND CONDUCTORS SIZED PER NEC TABLE 250.122 ALL CONDUCTORS SHALL BE ALUMINUM UNLESS NOTED OTHERWISE THE SERVICE GROUND CHART INDICATES THE MINIMUM SERVICE GROUND CONDUCTOR BASED ON #G WHERE # IS THE AMPACITY FROM THE CHART ABOVE, AND THE EQUIPMENT GROUND CHART INDICATES THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR SIZE #EG WHERE # IS THE RATING/SETTING OF THE OVERCURRENT DEVICE PROTECTING THE CONDUCTORS AND EQUIPMENT WHERE DISCREPANCIES OCCUR BETWEEN THE FEEDER SCHEDULE SCHEDULE AND THE GROUNDING TABLES, THE LARGER CONDUCTOR SHALL BE USED UNLESS OTHERWISE PERMITTED BY THE NEC. THE INSTALLATION SHALL MEET ALL NEC 250 GROUNDING AND BONDING REQUIREMENTS INCLUDING 250.4 PATH FOR FAULT CURRENT. PROVIDE COMPLETE RACEWAY SYSTEMS METALLICALLY JOINED, CONNECTED, AND FITTINGS AS REQUIRED FOR ELECTRICAL CONTINUITY PER NEC 300.10 11[W-700kcmil, 750kcmilG, 4"C] 8[W-700kcmil, 600kcmilG, 4"C] 7[W-700kcmil, 600kcmilG, 4"C] 6[W-600kcmil, 400kcmilG, 4"C] 5[W-600kcmil, 350kcmilG, 4"C] 4[W-500kcmil, 250kcmilG, 3-1/2"C] 4[W-350kcmil, 4/0G, 3"C] 3[W-400kcmil, 3/0G, 3"C] 3[W-350kcmil, 3/0G, 3"C] 2[W-500kcmil, 2/0G, 3-1/2"C] 2[W-350kcmil, 1/0G, 3"C] 2[W-250kcmil, #1G, 3"C] 2[W-4/0, #1G, 2-1/2"C] W-500kcmil, #2G, 3-1/2"C W-350kcmil, #2G, 3"C W-300kcmil, #2G, 3"C W-250kcmil, #4G, 3"C W- 4/0, #4G, 2-1/2"C W- 3/0, #4G, 2"C W- 2/0, #4G, 2"C W-1/0, #6G, 2"C W-1/0, #6G, 2"C W#1, #6G, 1-1/2"C W#2, #6G, 1-1/4"C W#2, #8G, 1-1/4"C W#4, #8G, 1-1/4"C W#6, #8G, 1"C EQUIPMENT GROUND TABLE 20EG #10 60EG #8 100EG #6 200-1200A PER ABOVE 1600EG 350KCMIL 2000EG 400KCMIL 2 EXISTING SERVICE REFEED (NOT IN SCOPE) M M M M PROJECT #: DRAWN: REV: SCALE: NO. SHEET TITLE: REVIEWED: DATE: FILE: 5 4 3 2 1 A B C D 6 E 7 7 6 5 4 3 2 1 A B C D E MVC SD-NOT FOR CONSTRUCTION MTV 2020-037-00 06/11/20 J:\2020\2020-037-00\Cad\Elec\E0.01.dwg marcus 06.14.20 11:39 am SPARK 140 EAST OAK ST FORT COLLINS, CO AS NOTED ELECTRICAL ONE-LINE DIAGRAM E0.01 E0.01.dwg