HomeMy WebLinkAboutBROTHERS BBQ - PDP200005 - SUBMITTAL DOCUMENTS - ROUND 1 - UTILITY PLANSDEMOLITION NOTES: SHEET METAL GENERAL NOTES 1. EXISTING HVAC PIPING, DUCTWORK AND EQUIPMENT SHOWN IS BASED ON EXISTING AND FIELD OBSERVATION WITHOUT DEMOLITION. DURING DEMOLITION, ANY CLARIFICATION REQUIRED TO DETERMINE SCOPE OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. 2. THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH EXISTING CONDITIONS, PRIOR TO STARTING DEMOLITION. 3. DRAWINGS DO NOT SHOW EVERY EXISTING PIPE, CONDUIT, DUCT, ETC. CONTRACTOR SHALL TAKE CARE TO REMOVE ONLY ITEMS REQUIRED TO BE REMOVED AND VERIFY PIPES, DUCTS, ETC. BEFORE REMOVAL. 1. INSTALL CEILING REGISTERS A MINIMUM OF ” FROM 12 EXTERIOR WALL. 2. PROVIDE A MINIMUM OF THREE TIMES THE FAN DIAMETER OF STRAIGHT DUCTWORK OFF THE SUPPLY AIR DISCHARGE BEFORE ANY TAKEOFFS OR ELBOWS. 3. PROVIDE LOCKING QUADRANT VOLUME BALANCING DAMPERS AT ALL BRANCH TAKEOFFS TO CEILING/SIDEWALL SUPPLY AND EXHAUST DEVICES 4. SPACE ABOVE CEILING IS TO BE USED AS A RETURN AIR PLENUM WHERE DUCTWORK IS NOT INDICATED ABOVE RETURN AIR GRILLES. 5. PROVIDE ACCESS DOORS IN DUCTWORK WHERE INDICATED OR REQUIRED FOR ACCESS TO SYSTEM COMPONENTS INCLUDING THE FOLLOWING: DAMPER MOTORS AND/OR MOTOR OPERATED DAMPERS, FIRE DAMPERS AND SMOKE DAMPERS. 6. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE NET FREE INTERIOR, NOT INCLUDING LINING OR INSULATION. 7. CONTRACTOR MAY RESIZE DUCTWORK SHOWN ON DRAWINGS IF REQUIRED PROVIDED RESIZED DUCTWORK HAS SAME CROSS SECTIONAL AREA AS SPECIFIED DUCT SIZE GENERAL NOTES: 1. GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH MECHANICAL DRAWING OF THIS SET. SEE EACH DRAWING FOR SPECIFIC NOTES APPLICABLE TO THAT DRAWING. 2. OUTSIDE AIR INTAKE OPENINGS FOR VENTILATION AIR SHALL BE LOCATED 10 FEET MEASURED IN ANY DIRECTION FROM ANY FLUES, VENTS, CHIMNEYS, GAS METERS, GAS REGULATORS, PLUMBING VENTS UNLESS TOP OF SUCH INTAKE OPENING IS 2 FEET BELOW ANY OF THE LISTED ITEMS. 3. OVERHEAD PIPING IN SPACES WITHOUT HUNG CEILINGS SHALL BE RUN AS CLOSE TO ROOF DECK AS PRACTICABLE, AS CLOSE TO PARALLEL JOISTS AS POSSIBLE AND ABOVE LIGHTING FIXTURES TO CONCEAL PIPING. 4. OVERHEAD DUCTWORK AND PIPING IN SPACES WITH CEILINGS SHALL BE CONCEALED UNLESS OTHERWISE NOTED. 5. COORDINATE LOCATION OF GRILLES, REGISTERS, DIFFUSERS, THERMOSTATS AND OTHER WALL OR CEILING MOUNTED HVAC ACCESSORIES WITH REFLECTED CEILING PLAN. COORDINATE LIGHTING FIXTURE LAYOUT AND ACCESSORIES INSTALLED BY OTHER TRADES SO AS TO PRESENT A NEAT AND ATTRACTIVE INSTALLATION THROUGHOUT THE ENTIRE BUILDING. IT IS THE INTENT FOR CEILING MOUNTED GRILLES, REGISTERS AND DIFFUSERS TO BE INSTALLED IN THE CENTER OF CEILING PANELS. 6. ARRANGE PIPING AND DUCTWORK, PARTICULARLY ABOVE CEILING, AS REQUIRED TO CLEAR STRUCTURE, DUCTS, CONDUIT, ETC., ALLOWING SPACE FOR PIPE HANGERS, EXPANSION LOOPS AND ACCESS TO VALVES, FILTERS AND MAINTENANCE OF EQUIPMENT. 7. THE DIAMETER OF THE SUPPLY PIPE AT ANY GAS FIRED EQUIPMENT SHALL NOT BE OF A SMALLER SIZE THAN THE INLET CONNECTION TO THE EQUIPMENT. 8. EQUIPMENT WITH FILTERS SHALL BE INSTALLED SO THAT FILTERS CAN BE EASILY REMOVED AND REPLACED. 9. CONTRACTOR SHALL VERIFY REFRIGERANT PIPE SIZES WITH EQUIPMENT MANUFACTURER FOR THE INDICATED INSTALLATION. 10. COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER TRADES. 11. THERMOSTATS SHALL BE LOCATED IN THE ROOMS INDICATED. INSTALL ” ABOVE AT 4'-0 FINISH FLOOR. 12. VALVES AND SPECIALTIES SHALL BE LINE SIZE, EXCEPT FOR CONTROL & BALANCING VALVES OR UNLESS NOTED OTHERWISE. 13. EXTEND DRAIN LINES TO NEAREST FLOOR DRAIN OR AS INDICATED. ROUTING SHALL NOT INTERFERE WITH PASSAGEWAYS AND MAINTENANCE. DRAINS FROM AIR CONDITIONING CONDENSATE DRAIN PANS SHALL BE TRAPPED. SLOPE SUSPENDED CONDENSATE DRAIN PIPING BASIC REQUIREMENTS: ALL OF THE DRAWINGS AND SPECIFICATIONS ARE CONSIDERED A PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SEARCHING ALL CONTRACT DOCUMENTS TO DETERMINE THE SCOPE OF WORK REQUIRED IN FINAL CONNECTIONS TO EQUIPMENT PROVIDED BY OTHER CONTRACTS OR CONTRACTORS. IT IS THE INTENT OF THE DRAWINGS TO PROVIDE AS MUCH INFORMATION AS POSSIBLE ON EQUIPMENT PROVIDED BY OTHERS. HOWEVER, THE EXTENT OF FINAL CONNECTIONS AND TYPE OF FINAL CONNECTIONS SHALL BE DETERMINED BY THE ACTUAL EQUIPMENT SUPPLIED BY OTHERS. THIS CONTRACTOR SHALL INCLUDE IN HIS BASE BID, REASONABLE COST FOR THE INSTALLATION OF EQUIPMENT PROVIDED BY OTHERS. HE SHALL NOT BE AWARDED EXTRA COSTS AFTER THE CONTRACT IS AWARDED UNLESS THE EQUIPMENT SO INSTALLED IS NOT SHOWN ON ANY OF THE CONTRACT DOCUMENTS. WORK INCLUDED UNDER THIS DIVISION SHALL CONSIST OF FURNISHING ALL MATERIALS, SUPPLIES, EQUIPMENT, TOOLS, INSURANCE, TRANSPORTATION AND FACILITIES, AND PERFORMING ALL LABOR AND SERVICES NECESSARY FOR COMPLETE INSTALLATION OF THE NEW MECHANICAL SYSTEM(S). ARRANGE FOR PIPE SPACES, CHASES, SLOTS, AND OPENINGS IN BUILDING STRUCTURE DURING PROGRESS OF CONSTRUCTION, TO ALLOW FOR MECHANICAL INSTALLATIONS. COORDINATE REQUIREMENTS FOR ACCESS PANELS AND DOORS FOR MECHANICAL ITEMS REQUIRING ACCESS THAT ARE CONCEALED BEHIND FINISHED SURFACES. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH CURRENT INTERNATIONAL BUILDING, FIRE, PLUMBING, MECHANICAL, ENERGY CONSERVATION CODES AND LOCAL JURISDICTION AMMENDMENTS. PAY FOR ALL FEES AND PERMITS AS ARE NECESSARY FOR THE COMPLTE INSTALLATION OF MECHANICAL SYSTEMS. DRAWINGS ARE DIAGRAMMATIC, INDICATING ONLY APPROXIMATE LOCATIONS OF SERVICES, DUCTWORK, APPARATUS, AND PIPING UNLESS NOTED OTHERWISE, AND ARE NOT TO BE SCALED. ACTUAL INSTALLATION MUST CONFORM TO ACTUAL BUILDING CONDITIONS, AND VERIFIED IN THE FIELD. THE ARCHITECT/ ENGINEER RESERVES THE RIGHT TO EFFECT REASONABLE CHANGES IN THE LOCATION OF EQUIPMENT UP TO THE TIME OF ROUGH-IN WITHOUT ADDITIONAL COST TO THE OWNER. ANY AND ALL CHANGES SHALL BE APPROVED BY THE ARCHITECT/ ENGINEER. MAINTAIN MANUFACTURERS RECOMMENDED CLEARANCES AROUND ALL EQUIPMENT. PROJECT SHALL BE COORDINATED WITH THE EXISTING BUIDING SERVICES AND SHALL INCLUDE ALL ITEMS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL TENANT MECHANICAL SYSTEMS. MAKE CONNECTIONS TO AND EXTEND SYSTEMS INSTALLED BY OTHERS AND/OR FURNISHED BY OTHERS. PROVIDE ACCESSORIES AND INCIDENTAL ITEMS AS REQUIRED FOR A COMPLETE AND FULLY OPERATIONAL SYSTEM WHETHER OR NOT SPECIFICALLY SPECIFIED AND/OR SHOWN ON THE PLANS. DO NOT SCALE DRAWINGS. COORDINATE WITH OTHER TRADES FOR A COORDINATED INSTALLATION WITHIN THE AVAILABLE SPACE. WHERE CROWDED CONDITIONS EXIST, PREPARE COORDINATION DRAWINGS SHOWING ALL TRADE CONFLICTS AND SUBMIT TO THE ARCHITECT FOR APPROVAL AND DIRECTION PRIOR TO ROUGH-IN OR INSTALLATION. RELOCATION OF INLETS, OUTLETS, AND/OR APPARATUS MADE PRIOR TO ROUGH-IN OR REQUIRED BY FIELD CONDITIONS FOR COORDINATION SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER OR HIS AGENTS. ALL WORK SHALL BE PERFORMED BY PROPERLY LICENSED MECHANICS OR UNDER THEIR DIRECT SUPERVISION. ALL MATERIALS AND EQUIPMNT SHALL MEET THE REQUIREMENTS OF THE APPLICABLE STANDARDS OF UL AND SHALL BEAR THE UL LABEL AS EVIDENCE THAT THE MATERIAL AND/OR EQUIPMNT MEETS THIS REQUIREMENT. INSTALL ALL EQUIPMENT PER MANUFACTURER’S RECOMMENDATIONS AND DETAILS UNLESS OTHERWISE NOTED IN THESE PLANS. ALL EQUIPMENT START UP AND TESTING SHALL BE PERFORMED BY THE EQUIPMENT MANUFACTURER TRAINED SERVICE TECHNICIAN. SUBMIT MANUFACTURER’S LITERATURE (SHOP DRAWINGS) FOR MATERIALS AND EQUIPMENT. SUBMITTAL SHALL INCLUDE EQUIPMENT PERFORMANCE DATA AT ELEVATION AND/OR LOCAL CONDITIONS. EQUIPMENT CUTSHEETS OR CATALOG COPIES ARE NOT ACCEPTABLE. SUBMITTAL SHALL BEAR THE APPROVAL OF THE GENERAL CONTRACTOR FOR COMPLIANCE WITH COORDINATION AND THESE SPECIFICATIONS PRIOR TO SUBMITTAL TO ARCHITECT AND/OR HIS AGENCIES. ANY EQUIPMENT SUBSTITUTED FOR WHAT IS SCHEDULED SHALL BE EQUAL TO THAT SCHEDULED IN CONTROLS, ACCESSORIES, AND PERFORMANCE REGARDLESS OF MANUFACTURER. SEPARATE PDF FILE PACKAGES SHALL BE SUPPLIED FOR EACH SECTION AND EACH SUBMITTAL TYPE, EACH PDF SAHLL REPRESENT A SINGLE STANDALONE SUBMITTAL. SUBMITTAL AND SHOP DRAWINGS SHALL INDENTIFY EACH SUBMITTED ITEM WITH NUMBERS OF LETTERS MFR 1. RESTAURANT DUTY, GREASE CUP, HINGED HOOD ROOF MTD HOOD 1 EF-1 UPBLAST SYMBOL TYPE SERVICE FAN ELEC ACCUREX XRUB-161HP-7 16 1,600 1.2 1,443 IN MODEL DIA WHEEL @ SL CFM IN WC SP @ 5300' RPM APPROX --- --- 3/4 208V-3Ø MIN HP FPM SPEED TIP SONES FAN SCHEDULE BELT TYPE DRIVE NONE --- REMARKS OPENING ROOF APPROX TYPE DAMPER EF-2 BURNER SHALL BE DESIGNED TO FIRE ON NATURAL GAS, 6" WC. 830 BTU/CF. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE LOSSES FOR UNIT CASING, FILTERS, HEAT EXCHANGER(S), OR EVAPORATIVE COOLING MEDIA. 2. 1. MAU-1 ACCUREX SYMBOL MFR XDG-112-H20 4,000 1.0 1,317 5.0 208V-3Ø -10.0 70.0 307.4 282.8 MODULATING 12 9.0 70 --- --- --- HEAT EXCHANGER DATA OUTPUT MODEL CFM IN WC @ 5300' @ SL ESP APPROX RPM SUPPLY FAN DATA FAN ELEC TEMP TEMP INPUT HP F F @ SL @ 5300' MIN ENT AIR LVG AIR MBH MBH EVAPORATIVE COOLER DATA DEPTH AREA EFF IN WC PUMP ELEC NO STEPS IN SQ FT % @ SL HP CELL MIN FACE SAT AIR PD ROOFTOP MAKE-UP AIR UNIT SCHEDULE --- --- --- 86"x36" 1,300 CURB HOOD DETAILS NOT TO SCALE GENERAL NOTES: HOOD/GREASE DUCT CONSTRUCTION THROUGH ANOTHER HANGING CONNECTED TO ROOF JOIST 1/2" DIA. ALL THREAD ROD HANGING ANGLE IS PRE-PUNCHED AT FACTORY ROD AND NUTS TO BE SUPPLIED BY INSTALLING CONTRACTOR ONE ABOVE AND ONE BELOW 1/2" DIA. HEAVY DUTY NUT HANGING ANGLE REMOTE MANUAL PULL STATION REMOVABLE STAINLESS STEEL SERVICE DOOR AGENT TANK OEM RELEASE/ BRACKET ASSEMBLY PLENUM PROTECTION NOZZLE DUCT PROTECTION NOZZLE DETECTORS APPLIANCE PROTECTION NOZZLE OPTIONAL PRE-WIRED ELECTRICAL TERMINAL BOX WITH TERMINAL STRIPS, 3-PHASE CONTACTORS AND OVERLOADS FAN AND LIGHT (IF APPLICABLE) CONTROL PANEL TYPICAL HOOD SECTION TYPICAL HOOD FIRE PROTECTION SYSTEM LAYOUT HANGING ANGLE DETAIL GREASE EXHAUST DUCT FROM HOOD TO EXHAUST FAN, OFFSET AS REQUIRED AND SHOWN ON PLANS, DUCT TO BE WRAPPED WITH 2 LAYERS OF UL LISTED ZERO CLEARANCE FIRE RATED GREASE DUCT WRAP EQUAL TO 3M FIRE BARRIER DUCT WRAP 15A OR PROVIDE MINIMUM 18" CLEARANCE TO COMBUSTIBLE CONSTRUCTION ON ALL SIDES OF DUCT HANGING ANGLES HOOD REAR WALL TO BE OF NON-COMBUSTIBLE CONSTRUCTION 16" SS BAFFLE WITH HANDLES AND HOOK GREASE DRAIN WITH REMOVABLE CUP ON EQUIPMENT WITH CASTORS PROVIDE RIGIDLY ATTACHED RESTRAINT CABLE. CABLE LENGTH TO BE 6" SHORTER THAN GAS CONNECTOR LENGTH EQUIPMENT GAS SUPPLY CONNECTIONS WITH SHUT-OFF VALVE, DIRT LEG, LISTED AND LABLED QUIICK-DISCONNECT AND APPLIANCE CONNECTOR TO COMPLY WITH IFGC SECTION 411 ENERGY COMPLIANCE COMCHECKS M-005 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N ENERGY COMPLIANCE COMCHECK M-006 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N VESTIBULE 108 DINING ROOM 101 FOOD SERVICE AREA 102 STORAGE 103 FOOD COUNTER 104 KITCHEN 110 PREP AREA 105 STORAGE 112 MENS R.R. 107 WOMENS R.R. 109 MECH. /UTILITY 106 FRONT DINING PATIO 114 WALK-IN COOLER 111 DINING PATIO 113 2436 x5 1830 x4 SCALE: 1/4" = 1'-0" FLOOR PLAN - HVAC SHEET NOTES X 1. 22/22 MAKE-UP AIR DUCT UP THROUGH ROOF TO MAU-1 2. 6"Ø EXHAUST DUCT FROM EXHAUST FAN UP THROUGH ROOF TO FLAT ROOF DISCHARGE JACK MINIMUM 12" ABOVE ROOF DECK AIRFLOW AIRFLOW 6"Ø 12"Ø 12"Ø 18"Ø 14"Ø 26/12 26/12 14"Ø 14"Ø 22/14 22/22 22/12 SR-1 12"x8" 175 cfm SR-1 12"x8" 175 cfm SR-1 12"x8" 175 cfm SR-1 12"x8" HOOD SYSTEM DETAILS M-201 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I HOOD SYSTEM DETAILS M-202 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I HOOD SYSTEM DETAILS M-203 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I HOOD SYSTEM DETAILS M-204 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I HOOD SYSTEM DETAILS M-205 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I HOOD SYSTEM DETAILS M-206 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I HOOD SYSTEM DETAILS M-207 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I AFG AFF ALP AP BFP CL DNZ CB ABOVE FINISHED GRADE ABOVE FINISHED FLOOR ALARM PANEL BACKFLOW PREVENTER ACCESS PANEL DOWNSPOUT NOZZLE CATCH BASIN CENTERLINE MECHANICAL CONTRACTOR NORMALLY CLOSED EC EL FPC FCO (E) KEC IE GC ELECTRICAL CONTRACTOR FIRE PROT. CONTRACTOR FLOOR CLEAN OUT KIT. EQ. CONTRACTOR INVERT ELEVATION GENERAL CONTRACTOR ELEVATION EXISTING NTS NIC (N) LCO MANHOLE LINE CLEAN OUT NOT TO SCALE NORMALLY OPEN NOT IN CONTRACT MC NC NEW MH NO THERMOSTATIC MIXING VALVE POINT OF CONNECTION SAFETY RELIEF VALVE WALL CLEAN OUT PUBLIC SERVICE COMPANY PRESSURE REDUCING VALVE SURFACE CLEAN OUT POC PRV PSCO SCO SRV BASIC REQUIREMENTS: ALL OF THE DRAWINGS AND SPECIFICATIONS ARE CONSIDERED A PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SEARCHING ALL CONTRACT DOCUMENTS TO DETERMINE THE SCOPE OF WORK REQUIRED IN FINAL CONNECTIONS TO EQUIPMENT PROVIDED BY OTHER CONTRACTS OR CONTRACTORS. IT IS THE INTENT OF THE DRAWINGS TO PROVIDE AS MUCH INFORMATION AS POSSIBLE ON EQUIPMENT PROVIDED BY OTHERS. HOWEVER, THE EXTENT OF FINAL CONNECTIONS AND TYPE OF FINAL CONNECTIONS SHALL BE DETERMINED BY THE ACTUAL EQUIPMENT SUPPLIED BY OTHERS. THIS CONTRACTOR SHALL INCLUDE IN HIS BASE BID, REASONABLE COST FOR THE INSTALLATION OF EQUIPMENT PROVIDED BY OTHERS. HE SHALL NOT BE AWARDED EXTRA COSTS AFTER THE CONTRACT IS AWARDED UNLESS THE EQUIPMENT SO INSTALLED IS NOT SHOWN ON ANY OF THE CONTRACT DOCUMENTS. WORK INCLUDED UNDER THIS DIVISION SHALL CONSIST OF FURNISHING ALL MATERIALS, SUPPLIES, EQUIPMENT, TOOLS, INSURANCE, TRANSPORTATION AND FACILITIES, AND PERFORMING ALL LABOR AND SERVICES NECESSARY FOR COMPLETE INSTALLATION OF THE NEW PLUMBING SYSTEM(S). ARRANGE FOR PIPE SPACES, CHASES, SLOTS, AND OPENINGS IN BUILDING STRUCTURE DURING PROGRESS OF CONSTRUCTION, TO ALLOW FOR PLUMBING INSTALLATIONS. COORDINATE REQUIREMENTS FOR ACCESS PANELS AND DOORS FOR PLUMBING ITEMS REQUIRING ACCESS THAT ARE CONCEALED BEHIND FINISHED SURFACES. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH CURRENT INTERNATIONAL BUILDING, FIRE, PLUMBING, MECHANICAL, ENERGY CONSERVATION CODES AND LOCAL JURISDICTION AMMENDMENTS. PAY FOR ALL FEES AND PERMITS AS ARE NECESSARY FOR THE COMPLTE INSTALLATION OF PLUMBING SYSTEMS. DRAWINGS ARE DIAGRAMMATIC, INDICATING ONLY APPROXIMATE LOCATIONS OF SERVICES, DUCTWORK, APPARATUS, AND PIPING UNLESS NOTED OTHERWISE, AND ARE NOT TO BE SCALED. ACTUAL INSTALLATION MUST CONFORM TO ACTUAL BUILDING CONDITIONS, AND VERIFIED IN THE FIELD. THE ARCHITECT/ ENGINEER RESERVES THE RIGHT TO EFFECT REASONABLE CHANGES IN THE LOCATION OF EQUIPMENT UP TO THE TIME OF ROUGH-IN WITHOUT ADDITIONAL COST TO THE OWNER. ANY AND ALL CHANGES SHALL BE APPROVED BY THE ARCHITECT/ ENGINEER. MAINTAIN MANUFACTURERS RECOMMENDED CLEARANCES AROUND ALL EQUIPMENT. PROJECT SHALL BE COORDINATED WITH THE EXISTING BUIDING SERVICES AND SHALL INCLUDE ALL ITEMS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL TENANT PLUMBING SYSTEMS. MAKE CONNECTIONS TO AND EXTEND SYSTEMS INSTALLED BY OTHERS AND/OR FURNISHED BY OTHERS. PROVIDE ACCESSORIES AND INCIDENTAL ITEMS AS REQUIRED FOR A COMPLETE AND FULLY OPERATIONAL SYSTEM WHETHER OR NOT SPECIFICALLY SPECIFIED AND/OR SHOWN ON THE PLANS. DO NOT SCALE DRAWINGS. COORDINATE WITH OTHER TRADES FOR A COORDINATED INSTALLATION WITHIN THE AVAILABLE SPACE. WHERE CROWDED CONDITIONS EXIST, PREPARE COORDINATION DRAWINGS SHOWING ALL TRADE CONFLICTS AND SUBMIT TO THE ARCHITECT FOR APPROVAL AND DIRECTION PRIOR TO ROUGH-IN OR INSTALLATION. RELOCATION OF INLETS, OUTLETS, AND/OR APPARATUS MADE PRIOR TO ROUGH-IN OR REQUIRED BY FIELD CONDITIONS FOR COORDINATION SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER OR HIS AGENTS. ALL WORK SHALL BE PERFORMED BY PROPERLY LICENSED MECHANICS OR UNDER THEIR DIRECT SUPERVISION. ALL MATERIALS AND EQUIPMNT SHALL MEET THE REQUIREMENTS OF THE APPLICABLE STANDARDS OF UL AND SHALL BEAR THE UL LABEL AS EVIDENCE THAT THE MATERIAL AND/OR EQUIPMNT MEETS THIS REQUIREMENT. INSTALL ALL EQUIPMENT PER MANUFACTURER’S RECOMMENDATIONS AND DETAILS UNLESS OTHERWISE NOTED IN THESE PLANS. ALL EQUIPMENT START UP AND TESTING SHALL BE PERFORMED BY THE EQUIPMENT MANUFACTURER TRAINED SERVICE TECHNICIAN. SUBMIT MANUFACTURER’S LITERATURE (SHOP DRAWINGS) FOR MATERIALS AND EQUIPMENT. SUBMITTAL SHALL INCLUDE EQUIPMENT PERFORMANCE DATA AT ELEVATION AND/OR LOCAL CONDITIONS. EQUIPMENT CUTSHEETS OR CATALOG COPIES ARE NOT ACCEPTABLE. SUBMITTAL SHALL BEAR THE APPROVAL OF THE GENERAL CONTRACTOR FOR COMPLIANCE WITH COORDINATION AND THESE SPECIFICATIONS PRIOR TO SUBMITTAL TO ARCHITECT AND/OR HIS AGENCIES. ANY EQUIPMENT SUBSTITUTED FOR WHAT IS SCHEDULED SHALL BE EQUAL TO THAT SCHEDULED IN CONTROLS, ACCESSORIES, AND PERFORMANCE REGARDLESS OF MANUFACTURER. SEPARATE PDF FILE PACKAGES SHALL BE SUPPLIED FOR EACH SECTION AND EACH SUBMITTAL TYPE, EACH PDF SAHLL REPRESENT A SINGLE STANDALONE SUBMITTAL. SUBMITTAL AND SHOP DRAWINGS SHALL INDENTIFY EACH SUBMITTED ITEM WITH NUMBERS OF STORAGE MBH INLET OUTLET RECOVERY WATER TEMP F 2. BURNER SHALL BE DESIGNED TO FIRE ON NATURAL GAS, 6" W.C., 830 BTU/CF 1. HEATER TO BE PROVIDED WITH INTERNAL HEAT TRAPS GWH-1 SYMBOL MFR EF-100T-199E-3N 100 GAL MODEL TANK 199.0 @ SL INPUT 40 WATER TEMP F 140 239 120V-1Ø GPM RATE ELEC GAS WATER HEATER SCHEDULE REMARKS BRADFORD WHITE 1,2 TOTAL CONNECTED GAS LOAD SCHEDULE TOTAL CONNECTED LOAD = INPUT EACH (BTUH) GAS DISTRIBUTION PRESSURE SHALL BE 6" W.C. INSTALLATION OF GAS METER AND SERVICE PIPING TO BE PERFORMED BY XCEL ENERGY COMPANY EQUIPMENT MAU-1 RTU-1 QTY 1 1 1,150,400 --- 307,400 130,000 INPUT TOTAL (BTUH) 307,400 130,000 REMARKS --- --- GAS DISTRIBUTION SYSTEM PIPE SIZING BASED ON TOTAL DEVELOPED LENGTH OF 125 FT. NOTES: 2. XXX 1. XXX 3. XXX REMARKS: DEEP FRYER RTU-2 1 1 140,000 130,000 140,000 130,000 --- --- GRIDDLE 1 124,000 124,000 --- BROILER 1 120,000 120,000 --- FINISHED ASPHALT 95% COMPACTED BEDDING MATERIAL C.I. COMBO 4"SCO GREASE INTERCEPTOR DETAIL NOT TO SCALE 24" HEAVY DUTY CAST IRON 24" NON-ROCKING DESIGN; TOP SHALL BE FLUSH W/ FINISHED ASPHALT. TYP. OF 2 MANHOLE COVER & RING, JOINT SEALANT BUTYL RESIN SEAL JOINTS W/ 12" 15" CLEANOUT TYP. 2 24" 9" 12" 2" C.I. VENT 4" BEND C.I. 1/8 CONCRETE MANHOLE RINGS TO GRADE TYP. OF 2 PRECAST REINFORCED C.I. "Y" FITTING PRECAST REINFORCED CONCRETE BASIN; 1,000 GALLONS HOLDING CAPACITY: 4" COMBO SANI-TEE (TYP. 2) 4" SCO WASTE AND VENT RISER DIAGRAM TRAP PRIMERS SHALL BE INSTALLED ON ALL FLOOR DRAINS AND FLOOR SINKS GAS SUPPLY, SIZE PER PLAN VIEW FULL SIZES SUPPLY LINE GAS SHUT-OFF VALVE GROMMET AT GAS APPLIANCE NIPPLE FULL SIZE UNION CONNECTION GAS FIRED APPLIANCE SAME DIAMETER PIPING AS UNIT CONNECTION SIZE 6" DIRT LEG NOT TO SCALE CONNECTION DETAIL TYPICAL OF (2) SIDES VESTIBULE 108 DINING ROOM 101 FOOD SERVICE AREA 102 STORAGE 103 FOOD COUNTER 104 KITCHEN 110 PREP AREA 105 STORAGE 112 MENS R.R. 107 WOMENS R.R. 109 MECH. /UTILITY 106 FRONT DINING PATIO 114 WALK-IN COOLER 111 DINING PATIO 113 2436 x5 1830 x4 SCALE: 1/4" = 1'-0" FLOOR PLAN - HVAC SHEET NOTES X 1. CONNECT NEW 4" SANITARY DRAIN TO EXISTING 4" BUILDING DRAIN LINE BELOW GRADE, VERIFY EXACT LOCATION, SIZE, DEPTH AND FLOW DIRECTION OF EXISTING IN FIELD PRIOR TO START OF WORK 2. 2" VENT UP TO 3" VENT THROUGH ROOF 3. 2 - 2" VENTS UP FROM BELOW GRADE TO 12" ABOVE FLOOR, COMBINE TO SINGLE 2" VENT UP TO 3" VENT THROUGH ROOF 4. 2" DRAIN UP THROUGH ROOF TO AUTO FILL/DRAIN CONNECTION AT MAU-1 EVAPORATIVE COOLER 5. 2" DRAIN DOWN IN WALL TO DISCHARGE AT FLOOR SINK 4" 2" 4" 4" 2" 2" 4" 4" 4" 2" 2" 2" 2" 2" 4" 3" 3" 2" 2" 2" 3" 4" 2" VESTIBULE 108 DINING ROOM 101 FOOD SERVICE AREA 102 STORAGE 103 FOOD COUNTER 104 KITCHEN 110 PREP AREA 105 STORAGE 112 MENS R.R. 107 WOMENS R.R. 109 MECH. /UTILITY 106 FRONT DINING PATIO 114 WALK-IN COOLER 111 DINING PATIO 113 2436 x5 1830 x4 SCALE: 1/4" = 1'-0" FLOOR PLAN - HVAC SHEET NOTES X 1. CONNECT NEW 3 4" CW TO EXISTING 3 4" CW BELOW GRADE, VERIFY EXACT LOCATION, SIZE AND DEPTH PRIOR TO START OF WORK 2. 3 4" CW UP THROUGH SLAB TO 3 4" WATER METER PER FORT COLLINS UTILITY REQUIREMENTS, INCREASE SERVICE SIZE TO 1" DOWNSTREAM OF METER 3. 1 2" CW DOWN TO CONNECTION AT WATER FILTRATION SYSTEM FOR ICE MACHINE, VERIFY CONNECTION LOCATION AND REQUIREMENTS WITH KITCHEN EQUIPMENT VENDOR PRIOR TO START OF WORK 4. 1 2" CW DOWN TO CONNECTION AT SODA AND TEA MAKERS, VERIFY CONNECTION LOCATION AND REQUIREMENTS WITH KITCHEN EQUIPMENT VENDOR PRIOR TO START OF WORK 5. 1 2" CW UP THROUGH ROOF TO CONNECTION AT AUTO FILL/DRAIN CONNECTION AT MAU-1 EVAPORATIVE COOLER 6. NEW GAS SERVICE/METER BY XCEL ENERGY, PROVIDE 21 2" GAS LINE FROM METER UP WALL TO ROOF 7. 1" GAS CONNECTION TO ROOFTOP UNIT, PROVIDE SHUT-OFF VALVE, UNION AND MINIMUM 6" DEEP DIRT LEG 8. 11 2"GAS CONNECTION TO MAKE-UP AIR UNIT, PROVIDE SHUT-OFF VALVE, UNION AND MINIMUM 6" DEEP DIRT LEG 9. 11 4" GAS DOWN THROUGH ROOF TO CONNECTION AT WATER HEATER, PROVIDE SHUT-OFF VALVE, UNION AND MINIMUM 6" DEEP DIRT LEG 10. 11 2" GAS DOWN IN WALL TO MANIFOLD ALONG BACK OF COOKING LINE AT 24" ABOVE FLOOR, PROVIDE MECHANICAL SHUT-OFF VALVE INTERLOCKED WITH HOOD FIRE PROTECTION SYSTEM 11. PROVIDE 3" PVC/CPVC COMBUSTION AIR AND VENT PIPE FROM WATER HEATER UP THOUGH ROOF TO FLAT ROOF TERMINATION PER MANUFACTURE INSTRUCTIONS G G G G G G G G G AIRFLOW AIRFLOW RTU-2 RTU-1 MAU-1 G G G G G G G G G G G G G G G G G G G G G G G G G G G 157 cfh 370 cfh 157 cfh 463 cfh GWH-1 DCP-1 240 cfh 12 " 1" 34 " 12 " 12 " 12 " 12 " 1" 1" 12 " 34 " 12 " 12 " 34 " 1"BFP-1 34 " 12 " 7 11 1 5 8 2 9 10 7 6 1" 1" 11 2" 11 4" 11 2" 11 2" 2" 2" 21 2" 21 21 2" 2" 21 2" 4 3 WC-1 L-1 TS-1 PS-1 HS-1 HS-2 MSB-1 GD/SR-1 HS-1 WC-1 L-1 WH-1 WH-1 FLOOR PLAN - PLUMBING WATER & GAS P-201 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G 2" 2 2 3 1 WC-1 1 L-1 2"FD-1 GGI-1 TS-1 PS-1 HS-1 3"FS-1 HS-2 AAV-1 3"FS-1 3"FS-1 3"FS-1 MSB-1 GD/SR-1 HS-1 WC-1 L-1 2"FD-1 2"FS-2 2" AIRFLOW AIRFLOW MAU-1 2" 2" 5 4 2"FD-1 FLOOR PLAN - PLUMBING WASTE & VENT P-101 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G 12 GA. ALUMINUM CHANNEL, TYP. OF (4) SIDES DRESS EDGES, TURN UP AND WELD, TYPICAL SIZE AS REQUIRED TO CHANNEL, STRAP SECURED BOLTED PIPE MINIMUM SIZE 24"x6" 10 GAGE ALUMINUM BASE, PIPE WELD 18" 60° NOT TO SCALE PIPE STAND DETAIL 12" MIN DRILL 1/4"Ø HOLE AT MINIMUM (4) CORNERS FOR WATER DRAINAGE SOLVENT WELDED FITTING, TYPICAL CLEANOUT PLUG WALL COVER CLEANOUT TEE WALL WASTE/SOIL PIPE SIZE AS SHOWN ON DRAWINGS FINISH FLOOR WALL CLEANOUT DETAIL NOT TO SCALE VENT, AS SHOWN ON DRAWINGS GAS APPLIANCE INDIRECT WASTE DRAIN OR FLOOR SINK FLOOR VENT TRAP ARM WASTE INDIRECT DRAIN PIPING - CLUSTER CLOSELY TOGETHER AIR GAP PER IPC SECTION 9.3.1 NOT TO SCALE INDIRECT WASTE DRAIN DETAIL VALVE NOT TO SCALE PREVENTER CLEARANCE DETAIL REDUCED PRESSURE BACKFLOW OVERHEAD OBSTRUCTION, CEILING, ETC. 36" MIN. 12" MIN. 6" RPBP WALL OR OBSTRUCTION, TYP. BOTH SIDES B.V. B.V. STRAINER B.V. NOTE: IF INSTALLED 5'-0" OR MORE ABOVE FINISH FLOOR, A PLATFORM IS REQUIRED FINISH FLOOR, PIPING PLATFORM, ETC. ELEVATION SIDE VIEW INLET/OUTLET PIPING 24" 12" BALANCING WALL OR OBSTRUCTION WALL OR OBSTRUCTION REDUCED PRESSURE BACKFLOW ASSEMBLY CLEANOUT NOT TO SCALE DETAIL MAIN IS OVER 4") REDUCING BRANCH IF PVC WYE (WYE WITH FLOW SIZE, 4" MAX. PVC 1/8 BEND, FULL ADJUSTING COLLAR FINISHED FLOOR FINISHED FLOOR SCORIATED COVER IN PLUG IF END OF LINE PVC RISER BODY CLEANOUT PLUG & FINISHED GRADE PAD (GRADE C.O.) 18"x18"x6" THICK CONCRETE TRACTOR COVER (GRADE C.O.) HEAVY DUTY CAST IRON FLOW ADJUSTING COLLAR, OUT FITTING, 4" MAX. PVC 2-WAY CLEAN- FINISHED GRADE TYPICAL 2-WAY CLEANOUT DETAIL NOT TO SCALE FLOW PVC RISER BODY, TYPICAL CLEANOUT PLUG & 24"x18"x6" THICK CONCRETE PAD TRACTOR COVER HEAVY DUTY CAST IRON NOT TO SCALE WATER HEATER DETAIL HOT WATER TO FIXTURES COLD WATER SUPPLY Finished Floor HOT WATER RETURN SHUT-OFF VALVE -TYPICAL DOMESTIC CIRC PUMP RE: SCHD's T&P VALVE PIPE TO OPEN DRAIN CHECK VALVE -TYPICAL EXPANSION TANK FLOOR DRAIN OR APPROVED RECEPTOR PUBLIC TOILET LAVATORY DOMESTIC HOT WATER RECIRCULATION LOOP BRANCH CONNECTION AT PUBLIC TOILET SHALL BE MADE WITHIN 2'-0" OF DESIGNATED LAVATOR 4"(E) 4" WCO L-1 2" 2" 2"FD-1 2" 2" WCO WC-1 2" 4" 4" WCO HS-2 2" 2" WCO HS-1 2" 2" 4" WCO L-1 2" 2" 2"FD-1 2" 2" WCO WC-1 2" 4" 2" 2" 4" 4" 2" 2" 2" 2" 3"VTR 2" 2" 2" 2" 2" 2" 2" 2" 4"(E) GI-1 2" 2" 2" 3"VTR 2" 4" 2"FS-1 2" 2" 3" 3"FS-1 2" 3" 3"FS-1 2" 3" 3" 3" 3" 3"FS-1 3" 2" AAV-1 WCO HS-1 2" 2" 3" 3"FS-1 2" 3" MSB-1 2" 3" 3" 3" 3" 3"VTR 2" 2" 2" 2" 2" 2" PLUMBING DETAILS P-004 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G GWH-1 1 199,000 199,000 --- WH-1 WALL HYDRANT WOODFORD MODEL B65 SERIES CLOSE COUPLED BOX TYPE W/ INTEGRAL VACUUM BREAKER POLISHED BRASS FINISH, 3/4" ROTATABLE FPT INLET, 3/4" HOSE THREAD OUTLET, LOOSE TEE KEY. JAY R. SMITH FIG 2010-A-U-PB, DUCO C.I. BODY AND FLASHING FS-1 8" SQ. FLOOR SINK TOP, 6" DEEP W/ FLASHING CLAMP, DOME BOTTOM STRAINER, NICKEL BRONZE RIM AND ALUMINUM RECESSED GRATE SECURED W/ V.P. SCREWS. JAY R. SMITH FIG 3100-C-15-U, C.I. FLANGED RECEPTOR, 8" SQ. FD-1 FLOOR DRAIN COLLAR W/ POLISHED BRONZE, ROUND STRAINER AND VANDAL PROOF SCREWS. BFP-1 FCO-1 FLOOR CLEANOUT JAY R. SMITH FIG 4023-U-PB, DUCO C.I. W/ ROUND ADJ. SCORIATED VANDAL PROOF, POLISHED BRONZE TOP AND TAPER THREAD BRONZE PLUG. WCO-1 WALL CLEANOUT JAY R. SMITH FIG 4710-U, S.S. SHALLOW COVER W/ VANDAL PROOF CENTER SCREW. FEBCO MODEL 825YD INLET AND OUTLET AS NOTED ON PLANS, COMPLETE REDUCED PRESSURE BACKFLOW PREVENTER STEEL TRIM AND AGD-L AIR GAP DRAIN. EXTEND DRAIN TO FLOOR DRAIN. CAPS, DUCTILE IRON BODY CONSTRUCTION, W/ BRONZE & STAINLESS W/ RESILIENT WEDGE OS&Y GATE VALVES, BALL VALVE TEST COCKS W/ PLUMBING EQUIPMENT SCHEDULE KEY DESCRIPTION BASIS OF DESIGN KEY DESCRIPTION BASIS OF DESIGN 2-WAY SCO-2 GRADE CLEANOUT SAME AS SCO-1, PROVIDE TYLER PIPE #5460 SERIES 2-WAY CLEANOUT AND #5626 45 DEGREE OFFSETS. (2) COVERS REQUIRED. SCO-1 GRADE CLEANOUT VANDAL PROOF SCREWS AND TAPER THREAD BRONZE PLUG. JAY R. SMITH FIG 4253-U-G, GALVANIZED C.I. W/ DOUBLE FLANGED HOUSING, HEAVY DUTY SECURED SCORIATED COVER W/ LIFTING DEVICE, AAV AIR ATTMITANCE VALVE STUDOR 'MINI-VENT' MODEL 20301 FOR PVC CONNECTION (STUDOR VALVE) MODEL 20300 FOR ABS CONNECTION STRAINER/OFFSET TAILPIECE KOHLER K-13885 HS-1 HAND SINK 1 1/2" 2" 2" 1/2" 1/2" --- MSB-2424 832-AA FAUCET MOP BASIN HOSE & HOSE BRACKET MSB-1 FIAT FIAT FIAT 830-AA 3" 3" 2" 1/2" 1/2" 5 K-2196 K-7514-CP COUNTERTOP LAVATORY L-1 FAUCET KOHLER KOHLER 1 1/4" 2" 2" -- 1/2" 1,14 KEY DESCRIPTION MANUF MODEL TRAP W V CW H/TW REMARKS KEY DESCRIPTION MANUF MODEL TRAP W V CW H/TW REMARKS CONNECTIONS PLUMBING FIXTURE SCHEDULE CONNECTIONS WC-1 FLUSH TANK SYSTEM SLOAN FLUSHMATE INT. 4" 2" 1/2" SEAT KOHLER K-4666 -- 1,11 FLR. MTD. WATER CLOSET KOHLER K-3519 GGI-1 INTERCEPTOR, 1000 GAL. CAPACITY GRAVITY GREASE INTERCEPTOR COPLAND ENTERPRISES PRE-CAST TYPE A CONCRETE GREASE GENERAL SCHEDULE NOTES: A. REFER TO ARCHITECTURAL DRAWINGS AND ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT ELEVATIONS OF ALL PLUMBING FIXTURES PRIOR TO INSTALLATION B. PROVIDE ALL FIXTURES WITH CHROME PLATED CAST BRASS, ADJUSTABLE 'P' TRAPS WITH CLEANOUT PLUGS, TUBING OUTLETS AND WALL FLANGES UNLESS FIXTURE IS FURNISHED WITH AN INTEGRAL TRAP OR IS PROVIDED ONE AS A STANDARD ACCESSORY C. PROVIDE ALL FIXTURES WITH CHROME PLATED SUPPLIES WITH ANGLE OR STRAIGHT PATTERN LOOSE KEY STOPS UNLESS FIXTURE IS FURNISHED WITH INTEGRAL STOPS OR STOPS ARE PROVIDED AS STANDARD ACCESSORIES D. ALL FLUSH VALVES SHALL HAVE A.D.A COMPLIANT HANDLES E. ALL EXPOSED PIPING SHALL BE POLISHED CHROME F. COORDINATE ALL CASEWORK MOUNTED FIXTURES WITH BASE CABINET DIMENSIONS PRIOR TO ORDERING FIXTURES. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY IF A CONFLICT EXISTS G. ACCESSIBLE WATER CLOSETS SHALL BE OPERABLE FROM THE WIDE SIDE OF THE STALL SCHEDULE REMARKS: (NOT ALL REMARKS MAY BE APPLICABLE TO THIS PROJECT) 1. FIXTURE DESIGNATED TO BE IN COMPLIANCE WITH THE AMERICANS WITH DISABILITIES ACT (A.D.A) 2. REFRIGERATION SYSTEM CHARGED WITH R-134A REFRIGERANT 3. FAUCET COMPLETE WITH RIGID GOOSENECK SPOUT, E3-VP AERATOR AND 317 WRIST BLADE HANDLES. INSULATE TRAP AND WATER SUPPLIES 4. EXTEND CHROME PLATED TAILPIECE TO PLASTER TRAP 5. FAUCET TO HAVE ROUGH CHROME FINISH AND SHALL BE MOUNTED 3'-6" A.F.F. PROVIDE MSG 2424 S.S. WALL GUARD AND VANDAL-PROOF DRAIN 6. FAUCET LEDGE SHALL BE PUNCHED FOR SINGLE HOLE FAUCET SPECIFIED 7. PROVIDE CHROME PLATED TAILPIECE EXTENSION AND TURN DOWN TO ALLOW FOR KNEE-SPACE CLEARANCE. 8. INSTALL DISPOSER IN RIGHT-HAND COMPARTMENT AND DRAIN STRAINER IN LEFT-HAND COMPARTMENT 9. ROUGH-IN AND CONNECT TO SINK BASIN FURNISHED AND INSTALLED BY CASEWORK SUPPLIER 10. MOUNT SHOWER HEAD AT 6'-0" A.F.F. 11. 1.1 GALLONS PER FLUSH 12. 0.5 GALLONS PER FLUSH 13. COORDINATE FLUSH VALVE ROUGH-IN ELEVATION WITH GRAB BAR MOUNTING HEIGHT PRIOR TO INSTALLATION 14. PROVIDE KOHLER K-13601 THERMOSTATIC MIXING VALVE SET AT 105°F TACO SERIES 003-IFC IN-LINE CIRCULATING PUMP, 2.0 GPM @ 4.0 FT. DCP-1 DOMESTIC CIRC. PUMP HEAD, 120V-1Ø, 1/20 HP, INTEGRAL FLOW CHECK VALVE, 24HR-7DAY TIMER/AQUASTAT FS-2 12" SQ. FLOOR SINK TOP, 6" DEEP W/ FLASHING CLAMP, DOME BOTTOM STRAINER, NICKEL BRONZE RIM AND ALUMINUM RECESSED GRATE SECURED W/ V.P. SCREWS. JAY R. SMITH FIG 3140-C-15-U, C.I. FLANGED RECEPTOR, 12 1/2" SQ. REFER TO KITCHEN EQUIPMENT VENDOR DRAWINGS FOR SPECIFICATIONS HS-2 HAND SINK 1 1/2" 2" 2" 1/2" 1/2" --- REFER TO KITCHEN EQUIPMENT VENDOR DRAWINGS FOR SPECIFICATIONS TS-1 3-COMP SINK 1 1/2" 2" 2" 1/2" 1/2" INDIRECT WASTE REFER TO KITCHEN EQUIPMENT VENDOR DRAWINGS FOR SPECIFICATIONS PS-1 4-COMP PREP SINK 1 1/2" 2" 2" 1/2" 1/2" INDIRECT WASTE REFER TO KITCHEN EQUIPMENT VENDOR DRAWINGS FOR SPECIFICATIONS GD/SR-1 GARBAGE DISPOSER/SPRAY RINSE 1 1/2" 2" 2" 1/2" 1/2" --- REFER TO KITCHEN EQUIPMENT VENDOR DRAWINGS FOR SPECIFICATIONS PLUMBING SCHEDULES P-003 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G LETTERS IDENTIAL TO THOSE LISTED OR SCHEDULED ON THE DRAWINGS OR SPECIFICATIONS, SUBMITTALS NOT INCLUDING SUCH MARKINGS WILL BE RETURNED NOT REVIEWED. SUBMITTING SUBCONTRACTOR SHALL ALLOW FIFTEEN (15) DAYS, FOR REVIEW AND COMMENT. FIELD LABEL ALL PLUMBING EQUIPMENT AND PIPING AS INDICATED ON THE PLANS PER PLUMBING AND LOCAL CODE REQUIREMENTS. INDICATE DIRECTION OF FLOW ON PIPING. BASIC MATERIALS:. PROVIDE SUPPLEMENTAL STEEL AND SUPPORTS AS REQUIRED FOR INSTALLATION OF PLUMBING MATERIALS, EQUIPMENT, AND APPARATUS. PROVIDE VIBRATION ISOLATION ON ALL PLUMBING EQUIPMENT. INSTALL FLEXIBLE DUCT CONNECTORS ON ALL AIR HANDLING UNIT SUPPLY OUTLET AND RETURN INLET. ALL WORK IN FINISHED AREAS SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED AS EXPOSED ON THE PLANS. PRIOR TO THE INSTALLATION OF ANY EXPOSED WORK THIS CONTRACTOR SHALL VERIFY AND OBTAIN ARCHITECTURAL APPROVAL OF LOCATION AND EXTENT. CONFIRM ACTUAL VOLTAGES, PHASE AND CHARACTERISTICS OF EXISTING EQUIPMENT AND APPARATUS FURNISHED BY TENANT, OTHER TRADES, AND/OR DIVISIONS. CONFIRM PRIOR TO ROUGH-IN. IF DISCREPANCIES ARE NOTED TO THE INSTRUCTIONS OF THESE PLANS AND SPECIFICATIONS, SUBMIT THE NOTED DISCREPANCIES TO THE ARCHITECT FOR DIRECTION PRIOR TO PROCEEDING. PROVIDE PRESSURE REDUCING VALVE ASSEMBLY AT BUILDING WATER SERVICE ENTRY WHERE PRESSURE EXCEEDS 65 PSI. PRESSURE REDUCING VALVE TO BE SET TO 65 PSI. PROVIDE SANITARY SEWER SYSTEM CLEANOUTS AS REQUIRED BY LOCAL CODES. PROVIDE BRANCH SHUT-OFF VALVES ON ALL WATER LINES EXTENDING FROM MAINS. THE CONTRACTOR SHALL LOCATE AND FURNISH FOR INSTALLATION BY OTHERS, ALL ACCESS PANELS AS REQUIRED FOR ACCESS TO VALVES, DAMPERS, MOTORS, ETC. AND THE PROPER SERVICING OF EQUIPMENT AND LINES INSTALLED UNDER THIS CONTRACT. ALL MATIRIAL LOCATED IN CEILING PLENUMS SHALL BE SUITABLE FOR RETURN AIR PLENUM. PIPING SANITARY AND STORM PIPING ABOVE GRADE SHALL BE CAST IRON HUBLESS WITH STAINLESS STEEL BANDS OR SCHEDULE 40 PVC WITH SOLVENT JOINTS. SANITARY AND STORM PIPING BELOW GRADE SHALL BE CAST IRON HUBLESS WITH STAINLESS STEEL BANDS OR SCHEDULE 40 PVC WITH SOLVENT JOINTS. DOMESTIC WATER PIPING ABOVE GRADE SHALL BE TYPE L COPPER WITH SOLDERED JOINTS OR PEX WITH MANUFACTURE APPROVED JOINING METHOUD. DOMESTIC WATER PIPING BELOW GRADE SHALL BE TYPE K COPPER WITH SILVER SOLDERED JOINTS. CONDENSATE DRAIN PIPING SHALL BE TYPE M COPPER WITH SOLDERED JOINTS OR SCHEDULE 40 PVC WITH SOLVENT JOINTS. COMPRESSED AIR PIPING SHALL BE TYPE L COPPER WITH SOLDERED JOINTS OR SCHEDULE 40 BLACK STEEL WITH MALLEABLE THREADED FITTINGS GAS PIPING 2-1/2” INCHES AND LARGER SHALL BE SCHEDULE 40 STEEL WITH WELDED JOINTS. GAS PIPING 2 INCHES AND SMALLER SHALL BE SCHEDULE 40 STEEL WITH MALLEABLE THREADED FITTINGS. DENTAL GAS PIPING (OXYGEN, NITROUS OXIDE, NITROGEN) SHALL BE TYPE L OR K COPPER MEDICAL GAS TUBE IDENTIFIED WITH MANUFACTURE MAKINGS FOR “OXY”, “MED”, “OXY/MED”, “OXY/ACR” OR “ACR/MED” IN BLUE (TYPE L), OR GREEN (TYPE K) WITH BRAZED JOINTS DENTAL VACUUM PIPING SHALL BE TYPE L COPPER WITH SOLDERED JOINTS OR AS SPECIFIED BY DENTAL EQUIPMENT SUPPLIER GAS PIPING BELOW GRADE SHALL BE WRAPPED WITH PROTECTIVE PIPE COVERING AND VENTED IN ACCORDANCE WITH LOCAL JURISDICTIONS HAVING AUTHORITY. FIRE STOP ALL PIPING MATERIALS PASSING THROUGH FIRE RATED STRUCTURES OR FIRE RATED ASSEMBLIES IN ACCORDANCE WITH THE REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. USE CURRENTLY LISTED U.L. CLASSIFIED PRODUCTS, TESTED BY ASTM E814. USE FOR ALL APPLICABLE PIPE PENETRATIONS THROUGH FIRE RATED FLOORS, WALLS, OR FLOOR CEILING ASSEMBLIES IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS. INSULATION ALL COLD AND HOT WATER PIPING SHALL HAVE A MINIMUM CONDUCTANCE VALUE BETWEEN 0.21 AND 0.28 COLD WATER PIPING SHALL BE INSULATED WITH 1/2 INCH THICK FIBER GLASS INSULATION WITH AN ALL-SERVICE JACKET. COLD WATER PIPING EXPOSED TO WEATHER SHALL BE INSULATED WITH 1 1/2” FIBERGLASS INSULATION. HOT WATER PIPING 2” OR LESS SHALL BE INSULATED WITH 1-INCH FIBERGLASS INSULATION. HOT WATER PIPING GREATER THAN 2-INCHES SHALL BE INSULATED WITH 1 ½ “ FIBERGLASS INSULATION. RUNOUTS, NOT EXCEEDING 12 FEET, UP TO 2-INCHES SHALL BE INSULATED WITH ½-INCH THICK FIBER GLASS INSULATION WITH AN ALL-SERVICE JACKET. STORM DRAIN PIPING ABOVE GRADE SHALL BE INSULATED WITH ½-INCH THICK FIBER GLASS INSULATION WITH AN ALL-SERVICE JACKET. CONDENSATE DRAIN PIPING SHALL BE INSULATED WITH ½-INCH THICK FIBER GLASS INSULATION WITH AN ALL-SERVICE JACKET.. WATER PIPING IN UNCONDITIONED SPACE AND EXTERIOR WALLS SHALL BE INSULATED WITH 2” FIBERGLASS INSULATION. PLUMBING FIXTURES FURNISH AND INSTALL PLUMBING FIXTURES AS SCHEDULED ON THE PLANS. PROVIDE CHROME PLATED ANGLE STOPS AND ESCUTCHEON PLATES ON ALL EXPOSED FIXTURE RUNOUTS. PROVIDE INSULATION AND ROUGH-IN AS REQUIRED FOR COMPLIANCDE WITH ADA REQUIREMENTS. PROVIDE ALL ACCESSORIES AND SPECIALTY ITEMS AS REQUIRED FOR A COMPLETE FIXTURE INSTALLATION. REDUCED PRESSURE BACKFLOW PREVENTERS FURNISH AND INSTALL REDUCED PRESSURE BACKFLOW PREVENTER FOR THE PRIMARY DOMESTIC COLD WATER SERVICE IN ACCORDANCE WITH STATE, LOCAL, AND JURISDICTIONAL WATER DISTRICT REQUIREMENTS. FURNISH AND INSTALL REDUCED PRESSURE BACKFLOW PREVENTERS FOR PLUMBING EQUIPMENT REQUIRED OF THIS OR OTHER SECTIONS OF THESE SPECIFICATIONS. ELECTRIC WATER HEATERS FURNISH AND INSTALL A GLASS LINED ELECTRIC WATER HEATER AS SCHEDULED ON THE PLANS. ACCEPTABLE MANUFACTURERS ARE A.O. SMITH, BRADFORD WHITE, RHEEM, OR STATE. FURNISH HEATER WHICH ARE CSA INTERNATIONAL CERTIFIED AND MEET THE REQUIREMENTS OF LOCAL MUNICIPALITIES. WATER HEATER LOCATED IN CEILING SHALL BE PROVIDED WITH 2 ½ “ DEEP DRAIN PAN. TERMINATE DRAIN TO NEAREST FLOOR DRAIN, FLOOR SINK OR LAV TRAP. GAS WATER HEATERS FURNISH AND INSTALL A GLASS LINED HIGH EFFICIENCY WATER HEATER AS SCHEDULED ON THE PLANS. ACCEPTABLE MANUFACTURERS ARE A.O. SMITH, BRADFORD WHITE, RHEEM, OR STATE. FURNISH HEATER WHICH ARE UL LABELED AND MEET THE REQUIREMENTS OF LOCAL MUNICIPALITIES. COMPLETION: CLEAN INSULATION COVERING, DUCTS, PIPES, EQUIPMENT AND ACCESSORIES TO RECEIVE PRIME COAT OF PAINT. CLEAN EQUIPMENT RECIVED WITH PRIME COAT TO RECEIVE FINAL COAT. REPLACE AIR FILTERS IF UNITS WERE OPERATED DURING CONSTRUCTION. CLEAN DUCTS. BLOWERS, AND COILS IF UNITS WERE OPERAED WITHOUT FILTERS DURING CONSTRUCTION. INSTRUT OWNER IN OPERATION AND MAINTENANCE OF PLUMBING SYSTEMS. MINIMUM PARTICIPANTS SHALL INCLUDE PLUMBING CONTRACTOR AND CONTROLS CONTRACTOR REPRESENTATIVES. AFTER TESTS AND ADJUSTMENTS HAVE BEEN MADE AND SYSTEM IS PRONOUNCED SATISFACTORY FOR PERMANENT OPERATION, REFINISH DAMAGED FlNISH AND LEAVE EVERYTHING IN PROPER WORKING ORDER AND APPEARANCE. ON COMPLETION OF WORK. REMOVE TOOLS, SCAFFOLDING, DEBRIS. ETC. FROM GROUNDS AND LEAVE PREMISES CLEAN. OPERATION AND MAINTENANCE MANUALS: PRIOR TO COMPLTION OF PROJECT, SUBMIT THREE (3) SETS OF MAINTENANCE MANUALS COVERING OPERATION AND MAINTENANCE OF PLUMBING EQUIPMENT WITH MOVING OR MOVABLE PARTS, INCLUDING PLUMBING SYSTEMS INSTRUCTIONS SHALL BE IN PAMPHLET OR TYPEWRITTEN FORM IN THREE RING BINDERS. INSTRUCTIONS FOR EACH UNIT SHALL BE INDICATED BY SEPARATE TAB. INCLUDE CERTIFIED TEST AND BALANCE REPORT. INCLUDE STARTING. TOPPING. LUBRICATION, PREVENTATIVE MAINTENANCE SCHEDULE. AND ADJUSTMENT INFORMATION FOR EACH PIECE OF EQUIPMENT. INCLUDE GUARANTEES AND WARRANTIES OF ALL EQUIPMENT. INCLUDE AS-BUILT DRAWINGS OF COMPLETED HVAC AND PLUMBING SYSTEMS PLUMBING SPECIFICATIONS PLUMBING SPECIFICATIONS P-002 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G TYP WCO TMV TYPICAL WSP CSP D DSP SPK F SYMBOL P/T DESCRIPTION CONNECT NEW TO EXISTING MECHANICAL / PLUMBING REFERENCE BUBBLE DESIGNATION RISER BUBBLE EQUIPMENT DESIGNATION DETAIL NUMBER OR SECTION LETTER REFERENCE DRAWING NUMBER SYMBOL DESCRIPTION ABBV. DESCRIPTION DE LA LV CV MV SYMBOL O CO2 DI VAC(L) N 2 MA N2O LI FM PD IW FD TR CA T G LPG MPG SOD AW AW GW AV OD SS BD BS OD SD SD W 140° M SYMBOL ABBV. DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION NOT ALL ITEMS LISTED BELOW ARE USED ON THIS SET OF DRAWINGS FIRE SPRINKLER AUTO. SPRINKLER LINE DRY STANDPIPE DRAIN COMBINED STANDPIPE WET STANDPIPE PIPING SYMBOLS OR MEDICAL GAS N2O MA 2 N VAC-L DI CO2 O FLOOR SINK ROOF DRAIN OVERFLOW DRAIN FLOOR CLEANOUT CATCH BASIN THRUST BLOCK MANHOLE GAS METER WATER METER GATE VALVE WITH CURB BOX NITROGEN NITROUS OXIDE MEDICAL AIR OXYGEN VACUUM LOW PRESSURE DISTILLED WATER CARBON DIOXIDE PIPING SYMBOLS HOSE BIBB WALL HYDRANT YARD HYDRANT BALANCING VALVE/ BALL VALVE OS&Y GATE VALVE GLOBE VALVE BUTTERFLY VALVE CHECK VALVE SHUT-OFF VALVE GAS VALVE VALVE SOLENOID VALVE MIXING VALVE PRESSURE REDUCING FLOW SWITCH ARRESTER BREAKER REDUCED PRESSURE WATER HAMMER RBFP CIRCULATING SOIL OR WASTE AT TEMP. SHOWN BELOW FLOOR STORM DRAIN ABOVE FLOOR STORM DRAIN ABOVE FLOOR BUILDING SEWER SANITARY VENT OVERFLOW DRAIN BUILDING DRAIN DOMESTIC HOT WATER DOMESTIC HOT WATER DOMESTIC COLD WATER DOMESTIC HOT WATER STORM SEWER BELOW FLOOR GREASE WASTE ACID VENT OVERFLOW DRAIN NATURAL GAS NATURAL GAS PROPANE GAS TEMPERED WATER COMPRESSED AIR SEDIMENT & OIL DRAIN MEDIUM PRESSURE ACID WASTE ABV. FLOOR ACID WASTE BEL. FLOOR PLUMBING LEGEND FLOW MEASURING DEVICE ATMOSPHERIC VACUUM BACKFLOW PREVENTER PLUMBING PIPING SOD MPG LPG G T CA AW AV GW AW SD SD OD SS OD HWC HW BS BD W V HW CW ALP ZV MV CV LV LA # * GENERAL ALP ZV # * SHT.# # ALARM PANEL ZONE VALVE MEDICAL VACUUM CENTRAL VACUUM LAB. VACUUM LAB. COMPRESSED AIR UNION STRAINER PRESSURE GAUGE STRAINER WITH BLOW-OFF VALVE THERMOMETER PRESSURE AND TEMPERATURE TAP ECCENTRIC REDUCER AREA/FLOOR DRAIN DOWNSPOUT NOZZLE LINE CLEANOUT WALL CLEANOUT ABBREVIATIONS FLEXIBLE CONNECTOR CIRCULATION FOOTING DRAIN TEMPERED WATER INDIRECT WASTE FORCE MAIN LAWN IRRIGATION PUMP DISCHARGE LINE CONCENTRIC REDUCER TR FD IW PD FM LI RELIEF VALVE DE DEIONIZED WATER FIRE PROTECTION PIPING FIRE HOSE/VALVE CABINET FIRE HYDRANT POST INDICATOR VALVE UPRIGHT SPRINKLER HEAD PENDANT SPRINKLER HEAD NEW LOCATION EXISTING SPRINKLER HEAD REMOVE & RELOCATE SPRINKLER HEAD REMOVE EXISTING DRY PENDANT EXISTING SPRINKLER HEAD EXISTING SPRINKLER HEAD ANGLE VALVE W/ DRAIN SECTIONAL VALVE W/ DRAIN DOUBLE CHECK VALVE PUMP TEST HEADER FIRE DEPT. CONNECTION SIDEWALL SPRINKLER FDC FIRE DEPT. CONNECTION VTR VENT THROUGH ROOF EXPANSION JOINT TEMPERATURE CONTROL AUTOMATIC 3-WAY TEMPERATURE CONTROL AUTOMATIC 2-WAY ALIGNMENT GUIDE VALVE VALVE PLUG VALVE PIPE ANCHOR FLOW SWITCH LINE CLEANOUT STEAM TRAP STEAM TRAP INVERTED BUCKET TRAP B FLOAT & THERMOSTATIC THERMOSTATIC STEAM MANUAL AIR VENT SPRINKLER HEAD POINT OF DISCONNECT /DEMO EQUIP-X SYMBOL DESCRIPTION SLOPE DOWN REMOVE EXISTING ARROW IN LINE INDICATES PIPE BOTTOM PIPE CONNECTION OF FLOW INDICATES DIRECTION PUMP PIPING DOWN PIPING UP PIPING CAP OR PLUG FIXTURE OR DRAIN TRAP PIPING SYMBOLS VAC(H) VAC-H VACUUM HIGH PRESSURE IA IA INSTRUMENT AIR (DENTAL) DEMOLITION NOTES: PLUMBING GENERAL NOTES 1. EXISTING HVAC PIPING, DUCTWORK AND EQUIPMENT SHOWN IS BASED ON EXISTING AND FIELD OBSERVATION WITHOUT DEMOLITION. DURING DEMOLITION, ANY CLARIFICATION REQUIRED TO DETERMINE SCOPE OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. 2. THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH EXISTING CONDITIONS, PRIOR TO STARTING DEMOLITION. 3. DRAWINGS DO NOT SHOW EVERY EXISTING PIPE, CONDUIT, DUCT, ETC. CONTRACTOR SHALL TAKE CARE TO REMOVE ONLY ITEMS REQUIRED TO BE REMOVED AND VERIFY PIPES, DUCTS, ETC. BEFORE REMOVAL. 1. MAKE PROPER PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT EVEN THOUGH ALL BRANCH MAINS, ELBOWS AND CONNECTIONS ARE NOT SHOWN. 2. COORDINATE WITH ARCHITECTURAL WORKING DRAWINGS BEFORE ROUGHING-IN PLUMBING FIXTURES. 3. UNLESS OTHERWISE NOTED, PIPING SHALL BE RUN AS HIGH AS POSSIBLE, CONCEALED ABOVE CEILINGS, IN WALLS AND PARTITIONS, AND IN PIPE CHASES. 4. SLOPES AND INVERT ELEVATIONS SHALL BE ESTABLISHED BEFORE ANY PIPING IS INSTALLED IN ORDER THAT PROPER SLOPES WILL BE MAINTAINED. 5. SANITARY WASTE PIPING SHALL BE SLOPED 1 AT 8-INCH PER FOOT MINIMUM FOR ALL PIPING 4-INCH AND LARGER AND AND AT 1/4-INCH PER FOOT FOR ALL PIPING 3-INCH AND SMALLER 6. ALL PIPING SHALL BE LOCATED AND DETERMINED WHERE TO BE RUN TO AVOID CONFLICT WITH OTHER TRADES. 7. ALL WALL HYDRANTS SHALL BE MOUNTED ” ABOVE 24 FINISHED GRADE UNLESS OTHERWISE SPECIFIED. 8. ALL HOSE BIBBS SHALL BE MOUNTED ” ABOVE 18 FINISHED FLOOR UNLESS OTHERWISE SPECIFIED. 9. COORDINATE WORK WITH OTHER TRADES SO AS NOT TO DISTURB NEW OR REPAIRED FINISHES. 10. ALL PLUMBING VENTS IN EXTERIOR WALLS SHALL BE OFF-SET A MINIMUM ” AT OF ROOF 3'-0 BEFORE ROOF PENETRATION. 11. ALL PLUMBING VENTS WITHIN A 10'-” RADIUS 0 OF EXHAUST VENTS SHALL BE EXTENDED TO A HEIGHT OF 2'-” 0 ABOVE EXHAUST VENT CROWN. 12. ALL HOT AND COLD WATER PIPING INDICATED TO BE RUN ABOVE FINISHED CEILINGS OR IN EXTERIOR WALLS SHALL BE INSTALLED ON THE CONDITIONED SPACE SIDE OF THE BUILDING INSULATION. 13. SLOPES AND INVERT ELEVATIONS OF EXTERIOR SEWERS, MANHOLES, ETC. SHALL BE ESTABLISHED AND VERIFIED BY THE CONTRACTOR BEFORE ANY PIPING IS INSTALLED IN ORDER THAT PROPER SLOPES WILL BE MAINTAINED AND NECESSARY INVERT ELEVATION OBTAINED. 14. PROVIDE DEEP SEAL P-TRAPS ” MAX) (4 WITH TRAP SEAL PRIMERS FOR ALL FLOOR DRAINS. 15. INDIRECT WASTE FROM FIXTURES AND SPECIALTIES, AND EQUIPMENT DRAIN LINES TERMINATING AT FLOOR DRAINS, OR APPROVED RECEPTACLES SHALL HAVE A MINIMUM 2" AIR GAP. SUPPORT PIPING SO INDIRECT WASTE CANNOT BE DEFLECTED FROM DRAIN OPENING. 16. PLUMBING CONTRACTOR TO PROVIDE AND INSTALL NAIL PLATES WHERE PIPING PASSES THROUGH STUD(S) WITHIN 2" OF HAILING SURFACE TO PROTECT PIPE FOR MAINLS OR DRYWALL SCREWS 17. PLUMBING CONTRACTOR SHALL INSTALL APPROVED WATER HAMMER ARRESTORS IN WATER LINES, BOTH HOT AND COLD, SERVING BATTERY AND BACK TO BACK FIXTURE INSTALLATIONS IN PIPE SPACE AND PIE CHASES AND SHALL BE ACCESSIBLE GENERAL NOTES: 1. GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH MECHANICAL DRAWING OF THIS SET. SEE EACH DRAWING FOR SPECIFIC NOTES APPLICABLE TO THAT DRAWING. 2. OUTSIDE AIR INTAKE OPENINGS FOR VENTILATION AIR SHALL BE LOCATED 10 FEET MEASURED IN ANY DIRECTION FROM ANY FLUES, VENTS, CHIMNEYS, GAS METERS, GAS REGULATORS, PLUMBING VENTS UNLESS TOP OF SUCH INTAKE OPENING IS 2 FEET BELOW ANY OF THE LISTED ITEMS. 3. OVERHEAD PIPING IN SPACES WITHOUT HUNG CEILINGS SHALL BE RUN AS CLOSE TO ROOF DECK AS PRACTICABLE, AS CLOSE TO PARALLEL JOISTS AS POSSIBLE AND ABOVE LIGHTING FIXTURES TO CONCEAL PIPING. 4. OVERHEAD DUCTWORK AND PIPING IN SPACES WITH CEILINGS SHALL BE CONCEALED UNLESS OTHERWISE NOTED. 5. COORDINATE LOCATION OF GRILLES, REGISTERS, DIFFUSERS, THERMOSTATS AND OTHER WALL OR CEILING MOUNTED HVAC ACCESSORIES WITH REFLECTED CEILING PLAN. COORDINATE LIGHTING FIXTURE LAYOUT AND ACCESSORIES INSTALLED BY OTHER TRADES SO AS TO PRESENT A NEAT AND ATTRACTIVE INSTALLATION THROUGHOUT THE ENTIRE BUILDING. IT IS THE INTENT FOR CEILING MOUNTED GRILLES, REGISTERS AND DIFFUSERS TO BE INSTALLED IN THE CENTER OF CEILING PANELS. 6. ARRANGE PIPING AND DUCTWORK, PARTICULARLY ABOVE CEILING, AS REQUIRED TO CLEAR STRUCTURE, DUCTS, CONDUIT, ETC., ALLOWING SPACE FOR PIPE HANGERS, EXPANSION LOOPS AND ACCESS TO VALVES, FILTERS AND MAINTENANCE OF EQUIPMENT. 7. THE DIAMETER OF THE SUPPLY PIPE AT ANY GAS FIRED EQUIPMENT SHALL NOT BE OF A SMALLER SIZE THAN THE INLET CONNECTION TO THE EQUIPMENT. 8. EQUIPMENT WITH FILTERS SHALL BE INSTALLED SO THAT FILTERS CAN BE EASILY REMOVED AND REPLACED. 9. CONTRACTOR SHALL VERIFY REFRIGERANT PIPE SIZES WITH EQUIPMENT MANUFACTURER FOR THE INDICATED INSTALLATION. 10. COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER TRADES. 11. THERMOSTATS SHALL BE LOCATED IN THE ROOMS INDICATED. INSTALL ” ABOVE AT 4'-0 FINISH FLOOR. 12. VALVES AND SPECIALTIES SHALL BE LINE SIZE, EXCEPT FOR CONTROL & BALANCING VALVES OR UNLESS NOTED OTHERWISE. 13. EXTEND DRAIN LINES TO NEAREST FLOOR DRAIN OR AS INDICATED. ROUTING SHALL NOT INTERFERE WITH PASSAGEWAYS AND MAINTENANCE. DRAINS FROM AIR CONDITIONING CONDENSATE DRAIN PANS SHALL BE TRAPPED. SLOPE SUSPENDED CONDENSATE DRAIN PIPING AT 1/8” PER FOOT (1 PER 100). 14. PIPING AND DUCTWORK INSULATION SHALL BE RUN CONTINUOUSLY THROUGH NON-RATED FLOORS, WALLS AND PARTITIONS, UNLESS OTHERWISE NOTED. 15. NO PIPING SHALL BE SMALLER THAN ½” UNLESS OTHERWISE NOTED. 16. RUN-OUTS SHALL PITCH DOWN IN DIRECTION OF FLOW A MINIMUM ” PER OF 1/8 FOOT (1PER 100). 17. FOR PIPE SIZES NOT INDICATED ON PLANS SEE EQUIPMENT CONNECTION DETAILS, FLOW DIAGRAMS, RISER DIAGRAMS AND SCHEDULES. 18. PROVIDE UNION OR FLANGED CONNECTIONS AT EACH PIECE OF EQUIPMENT AND ON BOTH SIDES OF CONTROL VALVES AND PRESSURE REGULATING VALVES. PROVIDE SHUT-OFF VALVES ON BOTH SIDES OF AUTOMATIC VALVES. 19. RELIEF VALVE DRAIN PIPING SHALL BE EXTENDED ” TO ABOVE 6 FINISHED FLOOR UNLESS OTHERWISE NOTED. 20. FLOOR MOUNTED EQUIPMENT IN THE MECHANICAL ROOM SHALL BE LOCATED ” THICK ON 6 CONCRETE PADS WITH CHAMFERED EDGES UNLESS OTHERWISE NOTED. 21. PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE SPECIFICATION. ADDITIONAL SUPPORTS OR HANGERS SHALL BE ADJACENT TO ELBOWS, TO PREVENT WEIGHT OF PIPING BEING PLACED ON THE EQUIPMENT. 22. CORRECT SETTING ON BALANCING FITTINGS SHALL BE PERMANENTLY MARKED. 23. LOCATE AND SIZE CONCRETE PADS AND CURBS FOR MECHANICAL EQUIPMENT IN ACCORDANCE WITH ACTUAL EQUIPMENT PURCHASED. 24. FOR LOCATION OF MOTOR STARTERS, SEE ELECTRICAL DRAWINGS. GREASE INTERCEPTOR SIZING GRAVITY GREASE INTERCEPTOR SIZE IS BASED ON THE FOLLOWING FORMULA: TURNOVER RATE * CATEGORICAL USE FACTOR * 2.5 gal. * SEATING CAPACITY = INTERCEPTOR SIZE (gal.) FOR RESTAURANTS THE TURNOVER RATE IS 2.0; THE CATEGORICAL USE FACTOR IS 1.25. A FACTOR OF 0.5 SHALL BE ADDED TO THE CATEGORICAL USE FACTOR FOR EACH WOK RANGE, OR DEEP FRYER OVER THE BASE SINGLE FRYER. GRAVITY GREASE INTERCEPTOR SIZE SHALL BE INCREASED BY 10% OVER THE BASE IF A GARBAGE DISPOSAL IS CONNECTED TO THE INTERCEPTOR A SIT DOWN OR QUICK SERVE RESTAURANT WITH A MAXIMUM SEATING CAPACITY OF 98 HAS BEEN ASSUMED FOR SIZING OF THE GREASE INTERCEPTOR GRAVITY GREASE INTERCEPTOR SIZING: (2.0 * 1.25 * 2.5 * 98 SEATS) * 1.1 = 674 GAL. 1,000 GAL. NOMINAL SIZE GREASE INTERCEPTOR SHALL BE INSTALLED PLUMBING LEGEND & GENERAL NOTES P-001 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G SR-1 175 cfm 12"x8" 175 cfm SR-1 12"x8" 175 cfm SR-1 12"x8" 175 cfm SR-1 12"x8" 175 cfm SR-1 12"x8" 110 cfm SR-1 12"x8" 110 cfm SR-1 12"x8" 110 cfm SR-1 12"x8" 110 cfm SR-1 12"x8" 110 cfm CD-2 6"Ø 50 cfm CD-2 6"Ø 50 cfm CD-2 6"Ø 50 cfm CD-2 6"Ø 50 cfm CD-2 8"Ø 110 cfm CD-2 8"Ø 110 cfm CD-1 10"Ø 275 cfm CD-1 10"Ø 275 cfm CD-1 10"Ø 275 cfm CD-1 10"Ø 275 cfm SR-1 24"x10" 530 cfm 10/12 18/16 14/16 14/16 8/10 CG-1(2) 22"x22" RTU-2 RTU-1 HOOD #2 HOOD #1 EF-2 EF-2 MAU-1 EF-3 EF-4 SD SD T T 1 EF-1 16"Ø 22/12 22/12 2 2 CD-1 12"Ø 400 cfm FLOOR PLAN - HVAC M-101 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G GAS SUPPLY MANIFOLD FLOOR LEFT AND RIGHT QUARTER END PANELS OVERHEAD STRUCTURE MAKE-UP AIR SUPPLY DUCT HIGH TEMP LIGHT FIXTURE 23.5% OPEN STAINLESS STEEL PERFORATED PANEL SUPPLY RISER WITH VOLUME DAMPER CEILING KITCHEN HOOD SHALL BE CONSTRUCTED OF TYPE 430 STAINLESS STEEL; TYPE 1 MINIMUM 20 GA.; TYPE II MINIMUM 24 GA. ALL SEAMS SHALL BE WELDED OR IN CONFORMANCE WITH UL 710 THE HOOD SHALL BE ETL LISTED, COMPLY WITH UL 710 STANDARDS AND SHALL BE BUILD IN ACCORDANCE WITH HFPA 96. HOOD SHALL BE TESTED FOR COMPLIANCE WITH THE ETL SANITATION MARK HOOD CONSTRUCTION AND INSTALLATION SHALL COMPLY WITH ALL APPLICABLE PORTIONS OF IMC SECTIONS 507, 508 AND 509 GREASE DUCT SHALL BE CONSTRUCTED OF 16 GA. MINIMUM BLACK STEEL WITH ALL WELDED JOINTS, BUTT WELDING NOT ALLOWED. GREASE DUCT INSTALLATION SHALL BE IN COMPLIANCE WITH IMC SECTION 506.3 CONTRACTOR SHALL PROVIDE, PRIOR TO INSTALLATION, FOR REVIEW A COMPLETE SET OF SHOP DRAWINGS FOR BOTH THE TYPE 1 AND TYPE 2 HOOD, INCLUDING ANSUL FIRE PROTECTION SYSTEM FOR TYPE 1 HOODS. DRAWINGS SHALL BE FULL SIZE REPRODUCIBLE AND SHALL INCLUDE UL LISTINGS, DUCT COLLAR SIZES FOR SUPPLY AND EXHAUST, CERTIFIED AIRFLOW RATINGS, NOZZLE SIZE AND LOCATION AND CONSTRUCTION DETAILS. CONTRACTOR SHALL PROVIDE, AT TIME OF FINAL INSPECTION, TO INSPECTOR COMPLETE AIR BALANCE REPORT INCLUDING ALL HVAC UNITS, EXHAUST FANS AND KITCHEN EXHAUST HOODS. EQUIPMENT BY OTHERS INSULATION ROOF DECK SUPPORT STRUCTURAL SHAPE AS PER SMACNA (ANGLE IRON OR PIPE) SUPPORT LEGS WELD TO ANGLE (TYPICAL) ANGLE IRON FASTENED TO EQUIPMENT SUPPORT COUNTER FLASHING HOOD MEMBRANE ROOF PREFABRICATED EQUIPMENT INVERTED ANGLE IRON ANCHOR EQUIPMENT SUPPORT TO ROOF DECK DUCTWORK SUPPORTED AS PER SMACNA SEAL ALL ANGLES WEATHER TIGHT GREASE EXHAUST DUCT - UNWRAPPED ANGLE IRON WELD TO PIPE OR ANGLE IRON (TYPICAL) AT ROOF DUCT SUPPORT-INSULATE OVER ANGLE IRON SUPPORTS AND SEAL ALL CORNERS OF ANGLES IN A WEATHER TIGHT MANNER MINIMUM 2'-0" NOT TO SCALE DUCT SUPPORT ON ROOF DETAIL SUPPLY/RETURN DUCT - 2" LINER (R-8 min) DRAW BAND WITH SILICONE SEALER SUPPLY DUCT COLLAR HAND DAMPER FLEX DUCT MAX. 5'-0" CEILING DIFFUSER (SIDE OF DUCT CONNECTION) CEILING FLEX DUCT SIZE SHALL MATCH NECK SIZE OPPOSED BLADE DAMPER TYPICAL DIFFUSER CONNECTION NOT TO SCALE G 6" DIRT LEG G RE: PLBG. UNIT ROOFTOP 2" BLOCK EQUIP. MANUFACTURER ROOF CURB NEOPRENE GASKET BY PIPING AT UNIT & RUN FULL SIZE TO SPLASH TRAP COIL CONDENSATE SPLASH BLOCK ROOF CANT STRIP & RE: ARCH. FLASHING WAFFLE ISOLATION PAD LOW DUROMETER NEOPRENE CONNECTION FLEXIBLE RIGID FIBERGLASS 2" THICK 3# DENSITY RE: STRUCT. DECK SUPPORT METAL DECK ACOUSTICAL INSULATION LEVEL CURB SUPPORT BUILDING STRUCTURE RE: STRUCT. AVOID CONTACT W/ NOT TO SCALE ROOFTOP CURB INSTALLATION DETAIL DUCTWORK PER PLANS. FULL WIDTH OF CURB FOR CONTINUATION ROOF JACK DETAIL N.T.S. 12" 10" GALV. 1/2" MESH SCREEN RAINHOOD SHALL BE 18 GAUGE GALV. WELDED SEAM 2" COUNTERFLASHING SHEETMETAL SCREW (COAT WITH PITCH) 16 GAUGE CHANNEL 12" HIGH X 2" DEEP 2" RIGID INSULATION THRU BOLT W/WASHERS STRUCTURAL SUPPORTS - EXHAUST OR FRESH AIR DUCT WITH FRAME STEEL WITH CAULKED JOINTS. COAT WITH PITCH. DIM. SHALL MATCH DUCT SIZE SHOWN ON PLAN. REFERENCE STRUCTURAL DRAWINGS ROOFING ROOF DECK HVAC DETAILS M-004 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G DIM ROOF APPROX WT LB APPROX OPER REMARKS FILTER DATA TYPE QUANT/ EFF SIZE % 1,2 1 2. FAN TO BE INTERLOCKED WITH ROOM LIGHT SWITCH 1. COOLING COIL CAPACITY BASED ON ARI STANDARD CONDITIONS: 80 FDB/67 FWB, 95 F AMBIENT AT CONDENSER. BURNER SHALL BE DESIGNED TO FIRE ON NATURAL GAS, 6" WC. 830 BTU/CF. 2. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE LOSSES FOR UNIT CASING, FILTERS, OR COILS. 3. 4. RTU-2 COOLING 9.89 --- --- 62.4 --- 1 SUPPLY FAN DATA RETURN/EXHAUST FAN DATA SYMBOL MFR RTU-1 TRANE MODEL YHC060 @ 5300' CFM OA 700 TOTAL @ 5300' CFM 2,000 @ SL IN WC ESP 0.8 RPM FAN APPROX 967 HP MIN CFM @ 5300' 1.0 --- IN WC @ SL ESP --- COMPR 1 NO COIL DATA COIL SERVICE HEATING @ SL AREA INPUT SQ FT FACE MBH --- 130.0 OUTPUT COOL TOTAL MBH @ 5300' 83.2 @ SL MBH KW --- --- STEPS NO 1 APPROX RPM HP FAN MIN --- --- PACKAGED ROOFTOP HEATING AND COOLING UNIT SCHEDULE APPROX ROOF OPER FILTER DATA APPROX TYPE QUANT/ SIZE PLEATED 16"x25"x2" EFF % MERV 8 LB WT DIM CURB 84"x46" 1,000 ELEC REMARKS 208V-3Ø AMP MOCP 32.1/45.0 MCA/ EER 15.0 PROVIDE 100% OUTDOOR AIR ECONOMIZER 5. PROVIDE RETURN AIR DUCT SMOKE DETECTOR 6. PROVIDE RETURN AIR AND OUTDOOR AIR CO2 DETECTORS AND CONTROL FOR OUTSIDE AIR 7. PROVIDE CONDENSER COIL HAIL GUARDS 4/ 1,2,3,4,5,6,7 COOLING 9.89 --- --- 62.4 --- 1 TRANE YHC060 2,000 500 0.8 967 1.0 --- --- 1 HEATING --- 130.0 83.2 --- --- 1 --- --- PLEATED 208V-3Ø 32.1/45.0 15.0 16"x25"x2" MERV 8 84"x46" 1,000 4/ 1,2,3,4,5,6,7 CEILING TOILET EF-3 CABINET ACME VQ150 --- 100 0.375 710 120V-1Ø --- 3.1 100 WATTS DIRECT BACKDRAFT 7"Ø EF-4 2 ROOF MTD HOOD 2 UPBLAST ACCUREX 2,600 1.4 1,446 XRUB-181HP-15 18 --- --- 1.5 208V-3Ø BELT NONE --- 1 CEILING TOILET CABINET ACME VQ150 100 0.375 710 --- --- 120V-1Ø 3.1 100 WATTS DIRECT BACKDRAFT 7"Ø 2 ACCESSORIES SQUARE TO ROUND ADAPTER --- SYMBOL TYPE MODEL OMNI OMNI CD-1 CD-2 CEILING DIFFUSER DIFFUSER CEILING 272RL 50F SR-1 CG-1 GRILLE CEILING REGISTER SIDEWALL FRAME LAY-IN FLANGE FLANGE LAY-IN MATERIAL FINISH DAMPER OPPOSED BLADE STEEL STEEL OFF-WHITE ENAMEL ENAMEL OFF-WHITE TYPE OPPOSED STEEL BLADE ENAMEL OFF-WHITE ALUMINUM OFF-WHITE NONE ENAMEL AIR DEVICE SCHEDULE MFR REMARKS TITUS TITUS TITUS TITUS --- --- --- --- OPPOSED BLADE HVAC SCHEDULES M-003 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G IDENTIAL TO THOSE LISTED OR SCHEDULED ON THE DRAWINGS OR SPECIFICATIONS, SUBMITTALS NOT INCLUDING SUCH MARKINGS WILL BE RETURNED NOT REVIEWED. SUBMITTING SUBCONTRACTOR SHALL ALLOW FIFTEEN (15) DAYS, FOR REVIEW AND COMMENT. FIELD LABEL ALL MECHANICAL EQUIPMENT AND PIPING AS INDICATED ON THE PLANS PER MECHANICAL AND LOCAL CODE REQUIREMENTS. INDICATE DIRECTION OF FLOW ON PIPING. PROVIDE 2” DEEP AUXILIARY DRAIN PAN WITH SEPARATE DRAIN LINE UNDER HEATING AND COOLING COILS (AIR HANDLING UNITS, FAN COIL UNITS, INLINE PUMPS, ETC.) WHERE CONDENSATION OR LEAKAGE CAN OCCUR. BASIC MATERIALS: PROVIDE MECHANICAL SYSTEM CONTROLS, CONTROLLERS, CONTROL TRANSFORMER, DISCONNECTS, STARTERS, CONTROL WIRING, ASSOCIATED CONTROL POWER WIRING, AND ALL WORK NECESSARY FOR A COMPLETE AND OPERATIONAL MECHANICAL SYSTEM. PROVIDE SUPPLEMENTAL STEEL AND SUPPORTS AS REQUIRED FOR INSTALLATION OF MECHANICAL MATERIALS, EQUIPMENT, AND APPARATUS. PROVIDE VIBRATION ISOLATION ON ALL MECHANICAL EQUIPMENT. INSTALL FLEXIBLE DUCT CONNECTORS ON ALL AIR HANDLING UNIT SUPPLY OUTLET AND RETURN INLET. ALL WORK IN FINISHED AREAS SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED AS EXPOSED ON THE PLANS. PRIOR TO THE INSTALLATION OF ANY EXPOSED WORK THIS CONTRACTOR SHALL VERIFY AND OBTAIN ARCHITECTURAL APPROVAL OF LOCATION AND EXTENT. BALANCE ALL SUPPLY AND EXHAUST OUTLETS TO AIRFLOW SHOWN. FINAL BALANCE MAY HAVE UP TO 10% DISCREPANCY OF THE CFM INDICATED ON THE PLANS. IF THERE IS AN AIR BALANCE DISCREPANCY GREATER THAN 10%, BALANCE CONTRACTOR SHALL CONTACT ENGINEER. PROVIDE MANUAL DAMPERS ON DIRECT DRIVE UNITS AS REQUIRED TO MEET SPECIFIED AIR QUANITITIES. CERTIFIED TEST AND BALANACE REPORT SHALL BE PROVIDED TO ENGINEER FOR REVIEW AND AVALIABLE ON-SITE PRIOR TO FINAL MECHANICAL INSPECTIONS CONFIRM ACTUAL VOLTAGES, PHASE AND CHARACTERISTICS OF EXISTING EQUIPMENT AND APPARATUS FURNISHED BY TENANT, OTHER TRADES, AND/OR DIVISIONS. CONFIRM PRIOR TO ROUGH-IN. IF DISCREPANCIES ARE NOTED TO THE INSTRUCTIONS OF THESE PLANS AND SPECIFICATIONS, SUBMIT THE NOTED DISCREPANCIES TO THE ARCHITECT FOR DIRECTION PRIOR TO PROCEEDING. PROVIDE DUCT SMOKE DETECTORS FOR AUTOMATIC EQUIPMENT SHUTOFF IN AIR-MOVING SYSTEMS THAT RETURN IN EXCESS OF 2000 CFM TO ENCLOSED SPACES WITHIN BUILDING PER MECHANICAL HAVING JURISDICTION. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE AIR HANDLING UNIT AUTOMATIC SHUT-DOWN WIRING AND DUCT/SMOKE DETECTOR WIRING WHEN REQUIRED. DETECTORS SHALL BE COMPATIBLE WITH BUILDING FIRE ALARM SYSTEM. SMOKE, FIRE AND COMBINATION FIRE/SMOKE DAMPERS SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. UNITS SHALL BE 120V AND ALL 120V WIRING SHALL BE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. SMOKE, FIRE AND COMBINATION FIRE/SMOKE DAMPERS FURNISHED SHALL BE COMPATIBLE WITH BUILDING FIRE ALARM SYSTEM. FIRE/SMOKE DAMPERS SHALL BE FURNISHED WITH REMOTE COMMAND STATION EQUIPPED WITH TEST SWITCH, THERMAL TEST RESET SWITCH, OPEN/CLOSE PILOT LIGHT INDICATORS. FIRE/SMOKE DAMPERS FURNISHED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR. THE CONTRACTOR SHALL LOCATE AND FURNISH FOR INSTALLATION BY OTHERS, ALL ACCESS PANELS AS REQUIRED FOR ACCESS TO VALVES, DAMPERS, MOTORS, ETC. AND THE PROPER SERVICING OF EQUIPMENT AND LINES INSTALLED UNDER THIS CONTRACT. ALL MATIRIAL LOCATED IN CEILING PLENUMS SHALL BE SUITABLE FOR RETURN AIR PLENUM. PIPING HEATING AND CHILLED WATER PIPING SHALL BE SCHEDULE 40 BLACK STEEL WITH THREADDED OR WELDED JOINTS REFRIGERATION PIPING SHALL BE TYPE ACR COPPER WITH SILVER SOLDERED JOINTS. FIRE STOP ALL PIPING MATERIALS PASSING THROUGH FIRE RATED STRUCTURES OR FIRE RATED ASSEMBLIES IN ACCORDANCE WITH THE REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. USE CURRENTLY LISTED U.L. CLASSIFIED PRODUCTS, TESTED BY ASTM E814. USE FOR ALL APPLICABLE PIPE PENETRATIONS THROUGH FIRE RATED FLOORS, WALLS, OR FLOOR CEILING ASSEMBLIES IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS. DUCTWORK DUCTWORK SHALL BE GALVANIZED SHEET METAL INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. INSTALL TURNING VANES IN ALL ELBOWS. ALL SPIN-IN FITTINGS SHALL BE PROVIDED WITH MANUAL VOLUME DAMPERS. ALL EXPOSED ROUND DUCTWORK SHALL BE SPIRAL DUCT. DUCT SIZES SHOWN ON THE DRAWINGS ARE NET INSIDE FREE AREA. EQUIPMENT FLEXIBLE DUCTWORK CONNECTION NOT TO EXCEED 5 INCHES IN LENGTH WITH A MAX. 25 FLAME/50 SMOKE INDEX. FLEXIBLE DUCTWORK TO AIR DEVICES SHALL HAVE A MAXIMUM STRETCHED LENGTH OF 5 FEET. SUITABLE FOR RETURN AIR PLENUM. LOW PRESSURE (<2” STATIC PRESSURE) SHEETMETAL DUCTWORK SHALL BE SEALED WITH WELDS, GASKETS, MASTIC ADHESIVES, MASTIC-PLUS-EMBEDED FABRIC. OR TAPES. MEDIUM PRESSURE (>2” AND <3” STATIC PRESSURE) SHEETMETAL DUCTWORK SHALL BE SEALED WITH SMACNA SEAL CLASS “A” DUCT SEALANT ALL FLUE GAS DUCTWORK TO BE METALBESTOS TYPE B VENTING OR EQUAL UNLESS OTHERWISE NOTED ON PLANS. INSULATION ALL ROUND CONCEALED RIGID SUPPLY DUCTWORK SHALL BE EXTERNALLY WRAPPED IN 1.5” THICK GLASS FIBER INSULATION WITH FIRE RETARDANT VAPOR BARRIER (MINIMUM R-8) ALL RECTANGULAR DUCTWORK SHALL BE LINED WITH 1.5” THICK 2 POUND DENSITY (MINIMUM R-8) GLASS FIBER ACOUSTIC DUCT LINER. ALL DUCTWORK EXPOSED TO OUTDOOR AMBIENT TYPE CONDITIONS SHALL BE EXTERNALLY WRAPPED IN 3” RIGID INSULATION (MINIMUM R-12) AND COVERED WITH MINIMUM 24 GAGE SHEET METAL COVER. ALL DUCTWORK LOCATED IN RETURN AIR PLENUM OR UNCONDITIONED SPACE SHALL BE WRAPPED IN 1.5“ THICK INSULATION (MINIMUM R-8). ALL COLD AND HOT WATER PIPING SHALL HAVE A MINIMUM CONDUCTANCE VALUE BETWEEN 0.21 AND 0.28 CHILLED WATER PIPING SHALL BE INSULATED WITH 1 INCH THICK FIBER GLASS INSULATION WITH AN ALL-SERVICE JACKET. CONDENSATE DRAIN PIPING SHALL BE INSULATED WITH ½-INCH THICK FIBER GLASS INSULATION WITH AN ALL-SERVICE JACKET. REFRIGERATION SUCTION LINES SHALL BE INSULATED WITH ½ INCH FOAM PLASTIC CLOSED CELL INSULATION. SEAL ALL JOINTS. AIR INLETS AND OUTLETS FURNISH AND INSTALL AIR INLETS AND OUTLETS AS SCHEDULED ON THE PLANS. ACCEPTABLE MANUFACTURERS ARE CARNES, METALAIRE, PRICE, OR TITUS. OUTLETS SHALL HAVE A WHITE BAKED ENAMEL FINISH TO MATCH CEILING OR WALL. FURNISH AND INSTALL ROOF CURBS AND BACKDRAFT DAMPERS. EXHAUST FANS FURNISH AND INSTALL CENTRIFUGAL EXHAUST FANS AS SCHEDULED ON THE PLANS. ACCEPTABLE MANUFACTURERS ARE ACME, COOK, CARNES, GREENHECK, OR TWIN CITY. FURNISH AND INSTALL UNITS COMPLETE WITH ALL OPERATIONAL AND SAFETY CONTROL NECESSARY FOR PROPER OPERATION. PACKAGE GAS/ELECTRIC SINGLE ZONE ROOFTOP UNITS FURNISH AND INSTALL PACKAGE GAS/ELECTRIC SINGLE ZONE ROOFTOP UNITS AS SCHEDULED ON THE PLANS. ACCEPTABLE MANUFACTURERS ARE TRANE, CARRIER, LENNOX OR YORK. FURNISH AND INSTALL UNIT COMPLETE WITH ALL OPERATIONAL AND SAFETY CONTROLS FOR SATISFACTORY OPERATION. FURNISH AND INSTALL FACTORY FURNISHED PROGRAMMABLE THERMOSTAT. MOUNT AT +48-INCHES AFF. FURNACES AND SPLIT SYSTEM DX COOLING UNITS FURNISH AND INSTALL NATURAL GAS FURNACE UNITS AS SCHEDULED ON THE PLANS. ACCEPTABLE MANUFACTURERS ARE TRANE, CARRIER, LENNOX OR YORK. FURNISH AND INSTALL ELECTRIC DIRECT EXPANSION CONDENSING UNITS AND MATCHING INDOOR EVAPORATOR COILS OF THE SAME MANUFACTURER AS THE MATCHING FURNACE UNIT. PROVIDE REFRIGERANT LINE SETS SIZED PER MANUFACTURER’S RECOMMENDATIONS. FURNISH AND INSTALL UNIT COMPLETE WITH ALL OPERATIONAL AND SAFETY CONTROLS FOR SATISFACTORY OPERATION. FURNISH AND INSTALL FACTORY FURNISHED PROGRAMMABLE THERMOSTAT. MOUNT AT +45-INCHES AFF. INSPECT AND REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO ATTEMPTING TO SET UNITS. PROVIDE 4-INCH THICK CONCRETE PAD FOR CONDENSING UNIT. PROVIDE SECONDARY DRAIN PAN FOR HORIZONTAL MOUNTED FURNACE/COOLING COIL UNIT. TERMIANTE DRAIN TO NEAREST APPROVED RECEPTOR. GAS UNIT HEATERS FURNISH AND INSTALL NATURAL GAS FIRED HORIZONTAL UNIT HEATERS AS SCHEDULED ON THE PLANS. UNIT HEATERS SHALL BE AS MANUFACTURED BY TRANE, REZNOR, OR STERLING. HEATERS SHALL BE AGA CERTIFIED AND INSTALLED IN ACCORDANCE WITH MANUFACTURER’S REQUIREMENTS. FURNISH AND INSTALL UNITS COMPLETE WITH ALL OPERATIONAL AND SAFETY CONTROLS FOR SATISFACTORY OPERATION. FURNISH AND INSTALL FACTORY FURNISHED SPACE THERMOSTAT WITH AUTO ON AND HEAT, OFF SELECTION. MOUNT AT +45-INCHES AFF. MAKE UP AIR UNITS FURNISH AND INSTALL NATURAL GAS FIRED MAKE UP AIR UNITS AS SCHEDULED ON THE PLANS. MAKE UP AIR UNIT SHALL BE AS MANUFACTURED BY CAPTIVEAIRE, TRANE, REZNOR, OR STERLING. FURNISH AND INSTALL UNIT COMPLETE WITH ALL OPERATIONAL AND SAFETY CONTROLS FOR SATISFACTORY OPERATION. FURNISH AND INSTALL FACTORY FURNISHED DISCHARGE OPERATIONAL THERMOSTAT AND OPERABLE 100% OUTDOOR AIR INTAKE DAMPER. CONTROL SYSTEM FURNSIH AND INSTALL A COMPLETE SYSTEM OF ELECTRIC/ELECTRONIC CONTROL FOR THE SYSTEMS INSTALLED TO PROVIDE THE FOLLOWING SEQUENCES OF OPERATION. SYSTEMS SHALL BE INDEPENDENT AND STAND ALONE IN OPERATION AND SEQUENCE. SINGLE ZONE ROOFTOP UNITS AND FURNACE/CONDENSING UNITS A 7-DAY PROGRAMMABLE THERMOSTAT SHALL CONTROL THE OPERATION OF THE UNIT. DESIRED OCCUPIED AND UNOCCUPIED HEATING AND COOLING SETPOINTS ARE PROGRAMMED VIA THE TERMOSTAT. FAN OPERATION IS DETERMINED BY THE POSITION OF THE FAN ‘ON-AUTO’ SWICH. AS WELL AS BY THE MODE OF OCCUPANCEY, FAN SHALL RUN CONTINUOULSY IN OCCUPIED MODE. HEATING AND COOLING OPERATION AS DESCRIBED HEREIN ASSUMES THE SYSTEM ‘HEAT-AUTO-COOL-OFF’ SWITCH IS IN THE ‘AUTO’ POSITION ELECTRIC HEAT LOCAL ELECTRIC UNIT HEATERS SHALL BE CONTROLLED BY LOCAL SPACE THERMOSTATS WITH HEAT OFF, FAN AUTO AND CONTINUOUS SWITCHES OR SELF CONTAINED UNIT SPACE THERMOSTATS AS APPROPRIATE. MINI-SPLIT SYSTEMS UNIT SHALL BE CONTROLLED THROUGH REMOTE THERMOSTAT. EXHAUST FANS TOILET AND JANITOR ROOM EXHAUST FANS SHALL BE INTERLOCKED WITH LIGHT SWITCH. KITCHEN HOOD EXHAUST FANS SHALL BE INTERLOCKED WITH MAKE-UP AIR UNITS, PROVIDE PACKAGE EXHAUST/MAKE-UP AIR CONTROL PANEL MOUNTED ON WALL IN KITCHEN GAS UNIT HEATERS UNIT SHALL BE CONTROLLED BY UNIT MOUNTED ELECTRIC HEATING THERMOSTAT. MAKEUP AIR UNIT UNIT SHALL BE CONTROLLED PACKAGE EXHAUST/MAKE-UP AIR CONTOL PANEL MONTED ON WALL IN KITCHEN, SUPPLY DUCT MOUNTED DISCHARGE AIR THERMOSTAT SHALL CONTROL THE MODULATING GAS BURNER AND EVAPORATIVE COOLER TO MAINTAIN DISCHARGE TEMPERATURE, SET AT 65 DEGREE F ADJUSTABLE. COMPLETION: CLEAN INSULATION COVERING, DUCTS, PIPES, EQUIPMENT AND ACCESSORIES TO RECEIVE PRIME COAT OF PAINT. CLEAN EQUIPMENT RECIVED WITH PRIME COAT TO RECEIVE FINAL COAT. REPLACE AIR FILTERS IF UNITS WERE OPERATED DURING CONSTRUCTION. CLEAN DUCTS. BLOWERS, AND COILS IF UNITS WERE OPERAED WITHOUT FILTERS DURING CONSTRUCTION. INSTRUT OWNER IN OPERATION AND MAINTENANCE OF MECHANICAL SYSTEMS. MINIMUM PARTICIPANTS SHALL INCLUDE MECHANICAL CONTRACTOR AND CONTROLS CONTRACTOR REPRESENTATIVES. AFTER TESTS AND ADJUSTMENTS HAVE BEEN MADE AND SYSTEM IS PRONOUNCED SATISFACTORY FOR PERMANENT OPERATION, REFINISH DAMAGED FINISHES AND LEAVE EVERYTHING IN PROPER WORKING ORDER AND APPEARANCE. ON COMPLETION OF WORK. REMOVE TOOLS, SCAFFOLDING, DEBRIS. ETC. FROM GROUNDS AND LEAVE PREMISES CLEAN. OPERATION AND MAINTENANCE MANUALS: PRIOR TO COMPLTION OF PROJECT, SUBMIT THREE (3) SETS OF MAINTENANCE MANUALS COVERING OPERATION AND MAINTENANCE OF MECHANICAL EQUIPMENT WITH MOVING OR MOVABLE PARTS, INCLUDING PLUMBING SYSTEMS INSTRUCTIONS SHALL BE IN PAMPHLET OR TYPEWRITTEN FORM IN THREE RING BINDERS. INSTRUCTIONS FOR EACH UNIT SHALL BE INDICATED BY SEPARATE TAB. INCLUDE CERTIFIED TEST AND BALANCE REPORT. INCLUDE STARTING. TOPPING. LUBRICATION, PREVENTATIVE MAINTENANCE SCHEDULE. AND ADJUSTMENT INFORMATION FOR EACH PIECE OF EQUIPMENT. INCLUDE GUARANTEES AND WARRANTIES OF ALL EQUIPMENT. INCLUDE AS-BUILT DRAWINGS OF COMPLETED HVAC AND PLUMBING SYSTEMS HVAC SPECIFICATIONS HVAC SPECIFICATIONS M-002 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G AT 1/8” PER FOOT (1 PER 100). 14. PIPING AND DUCTWORK INSULATION SHALL BE RUN CONTINUOUSLY THROUGH NON-RATED FLOORS, WALLS AND PARTITIONS, UNLESS OTHERWISE NOTED. 15. NO PIPING SHALL BE SMALLER THAN ½” UNLESS OTHERWISE NOTED. 16. RUN-OUTS SHALL PITCH DOWN IN DIRECTION OF FLOW A MINIMUM ” PER OF 1/8 FOOT (1PER 100). 17. FOR PIPE SIZES NOT INDICATED ON PLANS SEE EQUIPMENT CONNECTION DETAILS, FLOW DIAGRAMS, RISER DIAGRAMS AND SCHEDULES. 18. PROVIDE UNION OR FLANGED CONNECTIONS AT EACH PIECE OF EQUIPMENT AND ON BOTH SIDES OF CONTROL VALVES AND PRESSURE REGULATING VALVES. PROVIDE SHUT-OFF VALVES ON BOTH SIDES OF AUTOMATIC VALVES. 19. RELIEF VALVE DRAIN PIPING SHALL BE EXTENDED ” TO ABOVE 6 FINISHED FLOOR UNLESS OTHERWISE NOTED. 20. FLOOR MOUNTED EQUIPMENT IN THE MECHANICAL ROOM SHALL BE LOCATED ” THICK ON 6 CONCRETE PADS WITH CHAMFERED EDGES UNLESS OTHERWISE NOTED. 21. PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE SPECIFICATION. ADDITIONAL SUPPORTS OR HANGERS SHALL BE ADJACENT TO ELBOWS, TO PREVENT WEIGHT OF PIPING BEING PLACED ON THE EQUIPMENT. 22. CORRECT SETTING ON BALANCING FITTINGS SHALL BE PERMANENTLY MARKED. 23. LOCATE AND SIZE CONCRETE PADS AND CURBS FOR MECHANICAL EQUIPMENT IN ACCORDANCE WITH ACTUAL EQUIPMENT PURCHASED. 24. FOR LOCATION OF MOTOR STARTERS, SEE ELECTRICAL DRAWINGS. RECTANGULAR SUPPLY RECTANGULAR SUPPLY RECT RETURN/EXH RECT RETURN/EXH ROUND DUCT DOWN DUCT ELBOW WITH RECTANGULAR/ROUND AIR DUCT UP ROUND DUCT UP AIR DUCT DOWN AIR DUCT DOWN AIR DUCT UP BRANCH DUCT RECTANGULAR TURNING VANES 45 TAKE-OFF DUCT RADIUS ELBOW DOUBLE LINE DUCTWORK FLEX CONNECTION (* INDICATES EQ.) SWITCH x PS PRESSURE SENSOR SYMBOL DESCRIPTION CONTROL DEVICES AND DAMPERS DUCT TRANSITION T T S H UNIT MOUNTED WALL MOUNTED COMBINATION FIRE FIRE DAMPER MOTORIZED DAMPER W/LOCKING QUADRANT AND SMOKE DAMPER MANUAL VOLUME DAMPER THERMOSTAT THERMOSTAT HUMIDISTAT SENSOR AIR DUCT UP RECTANGULAR SUPPLY SINGLE LINE DUCTWORK AIR DUCT UP ROUND DUCT UP RECT RETURN/EXH AIR DUCT DOWN RECT RETURN/EXH AIR DUCT DOWN RECTANGULAR SUPPLY ROUND DUCT DOWN BRANCH DUCT 45 TAKE-OFF RECTANGULAR TURNING VANES DUCT ELBOW WITH DUCT RECTANGULAR/ROUND DUCT TRANSITION RADIUS ELBOW FITTING W/DAMPER CONICAL SPIN-IN FITTING CONICAL SPIN-IN FLEXIBLE DUCT MANUAL VOLUME DAMPER W/LOCKING QUADRANT AFG AFF ALP AP BFP CL DNZ CB ABOVE FINISHED GRADE ABOVE FINISHED FLOOR ALARM PANEL BACKFLOW PREVENTER ACCESS PANEL DOWNSPOUT NOZZLE CATCH BASIN CENTERLINE MECHANICAL CONTRACTOR NORMALLY CLOSED EC EL FPC FCO (E) KEC IE GC ELECTRICAL CONTRACTOR FIRE PROT. CONTRACTOR FLOOR CLEAN OUT KIT. EQ. CONTRACTOR INVERT ELEVATION GENERAL CONTRACTOR ELEVATION EXISTING NTS NIC (N) LCO MANHOLE LINE CLEAN OUT NOT TO SCALE NORMALLY OPEN NOT IN CONTRACT MC NC NEW MH NO THERMOSTATIC MIXING VALVE POINT OF CONNECTION SAFETY RELIEF VALVE WALL CLEAN OUT PUBLIC SERVICE COMPANY PRESSURE REDUCING VALVE SURFACE CLEAN OUT POC PRV PSCO SCO SRV TYP WCO TMV TYPICAL SYMBOL DESCRIPTION P/T CONNECT NEW TO EXISTING MECHANICAL / PLUMBING REFERENCE BUBBLE DESIGNATION RISER BUBBLE EQUIPMENT DESIGNATION DETAIL NUMBER OR SECTION LETTER REFERENCE DRAWING NUMBER SYMBOL DESCRIPTION SYMBOL DESCRIPTION NOT ALL ITEMS LISTED BELOW ARE USED ON THIS SET OF DRAWINGS PIPING SYMBOLS BALANCING VALVE/ BALL VALVE OS&Y GATE VALVE GLOBE VALVE BUTTERFLY VALVE CHECK VALVE SHUT-OFF VALVE GAS VALVE VALVE SOLENOID VALVE MIXING VALVE PRESSURE REDUCING FLOW SWITCH BREAKER RBFP REDUCED PRESSURE HVAC LEGEND FLOW MEASURING DEVICE ATMOSPHERIC VACUUM BACKFLOW PREVENTER # * GENERAL # * SHT.# # UNION STRAINER PRESSURE GAUGE STRAINER WITH BLOW-OFF VALVE THERMOMETER PRESSURE AND TEMPERATURE TAP ECCENTRIC REDUCER AREA/FLOOR DRAIN ABBREVIATIONS FLEXIBLE CONNECTOR SLOPE DOWN REMOVE EXISTING ARROW IN LINE INDICATES PIPE BOTTOM PIPE CONNECTION OF FLOW INDICATES DIRECTION PUMP PIPING DOWN PIPING UP PIPING CAP OR PLUG CONCENTRIC REDUCER PIPING SYMBOLS RELIEF VALVE VTR VENT THROUGH ROOF HVAC PIPING SYMBOL DESCRIPTION CHILLED WATER SUPPLY HOT WATER RETURN HWS HOT WATER SUPPLY HWR CHS LOW PRESSURE HIGH PRESSURE HIGH PRESSURE STEAM CONDENSATE CONDENSATE PUMPED CONDENSATE LOW PRESSURE STEAM CONDENSER RETURN CONDENSER SUPPLY CHILLED WATER RETURN FUEL OIL VENT FUEL OIL RETURN FUEL OIL SUPPLY REFRIGERANT HOT GAS REFRIGERANT SUCTION REFRIGERANT LIQUID EQUIPMENT DRAIN LPC HPS HPC PC CS CHR CR LPS FOS FOR FOV RL RS RHG D EXPANSION JOINT TEMPERATURE CONTROL AUTOMATIC 3-WAY TEMPERATURE CONTROL AUTOMATIC 2-WAY ALIGNMENT GUIDE VALVE VALVE PLUG VALVE PIPE ANCHOR FLOW SWITCH STEAM TRAP STEAM TRAP INVERTED BUCKET TRAP B FLOAT & THERMOSTATIC THERMOSTATIC STEAM MANUAL AIR VENT POINT OF DISCONNECT /DEMO EQUIP-X M SD DUCT SMOKE DETECTOR VENTILATION REQUIREMENTS ZONE: FOOD SERVICE AREA SYSTEM: NEW ROOFTOP HVAC UNIT RTU-1 & 2 ZONE FLOOR AREA: 265 sf ZONE DESIGN POPULATION: 13 occ OA REQ'D PER UNIT AREA: 0.18 cfm/sf OA REQ'D PER PERSON: 7.5 cfm/occ SYSTEM VENTILATION EFFECTIVENESS RATIO: 0.8 OUTSIDE AIR REQUIRED FOR ZONE = 182 cfm ZONE: DINING AREA SYSTEM: NEW ROOFTOP HVAC UNIT RTU-1 ZONE FLOOR AREA: 591 sf ZONE DESIGN POPULATION: 43 occ OA REQ'D PER UNIT AREA: 0.18 cfm/sf OA REQ'D PER PERSON: 7.5 cfm/occ SYSTEM VENTILATION EFFECTIVENESS RATIO: 0.8 OUTSIDE AIR REQUIRED FOR ZONE = 536 cfm ZONE:KITCHNE AREA SYSTEM: NEW ROOFTOP HVAC UNIT RTU-2 ZONE FLOOR AREA: 480 sf ZONE DESIGN POPULATION: 10 occ OA REQ'D PER UNIT AREA: 0.18 cfm/sf OA REQ'D PER PERSON: 7.5 cfm/occ SYSTEM VENTILATION EFFECTIVENESS RATIO: 0.8 OUTSIDE AIR REQUIRED FOR ZONE = 202 cfm HVAC LEGEND & GENERAL NOTES M-001 SHEET TITLE PROJECT NO: DRAWN BY: CHK'D BY: DATE DESCRIPTION ENGINEERING STAMP CONTRACTOR SHALL NOTIFY MCDONALD CONSULTING + DESIGN, I N C . I N W R I T I N G O F A N Y DISCREPANCIES, IN THE DRAWINGS OR SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION OF ANY A F F E C T E D W O R K S O T H A T A D D I T I O N A L I N F O R M A T I O N , CORRECTIONS OR CLARIFICATIONS MAY BE PROVIDED BY MCDONALD CONSULTING + DESIGN, I NC. BROTHER BBQ FORT COLLINS 501 S. Taft Hill Rd. Fort Collins, CO 80521 Brothers BBQ Nick O'Sullivan 720.289.3679 McDonald Consulting + Design 10698 Amesbury Way Highlands Ranch, Colorado 80126 P: 303.875.9293 pmcdonald@mcdonaldconsulting.us CLIENT PROJECT SHEET NUMBER 2020036 PFM PFM ISSUE 04.01.2020 Permit/Construction DATE DESCRIPTION REVISIONS . . MARK L I C E N S E D R E E N I G N E L A N O I S S E F O R P O D A R O L O C 33310 P E T E R F M c D O N A L D NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY PETER F. McDONALD, PE A M D G