HomeMy WebLinkAboutSupporting Documentation - Electrical - 10/15/2025 WORD\DATA\FORMS\C-1.DOC REV.August 14, 2020 CUSTOMER OWNED SERVICE INFORMATION FORM (C-1) City of Ft. Collins Electric Utility  700 Wood St.  P.O. Box 580  Ft. Collins, CO 80522 (970)221-6700 or fax (970)221-6619 Service voltages available are (not all voltages are available at all locations):  120/240 V. 1 phase, 3 wire  120/208 V. 3 phase, 4 wire  120/208 V. 1 phase, 3 wire (network)  277/480 V. 3 phase, 4 wire  Primary 13,200 V. Grd Y /7620  120/240 V. 3 phase, 4 wire (special utility permission required) For CT’d meters, Light and Power will provide the meter socket and CT’s to the electrical contractor. CT’s cannot be placed in the transformer, but may be located in a building mounted cabinet (provided by owner) or in the owner’s switchgear. In no case, can meters be mounted on the transformer. · Cold sequencing is required for all commercial services that are direct metered. · If CT’d metering, the owner must provide and install a - 1” conduit from the CT location to the electric meter. Please complete the following completely and legibly: Date Submitted: _____________________________________ Voltage Requested: _____/_____  1 phase OR  3 phase Building Main (not fuse) Size: ____________________ Amps Number of Conduits: _______ Size of Conduits:_________ Number of Cables: ________ Size of Cables: ___________ Electric Heat:  Yes _________kW  No Business Name: ____________________________________ Site Address: ______________________________________ Owners Name: _____________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Email: ____________________________________________ General Contractor: _________________________________ Individual: _________________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Email: ____________________________________________ Electrical Contractor: ________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Firm: ______________________________________________ Email: _____________________________________________ Number of CT’d meters: __________ at ___________Amps each Number of Self-Contained meters: _____ at ________Amps each Largest Motor: ________ H.P. 1 Phase __________ H.P. 3 Phase Will any generating system (including photo-voltaics) be installed?  Yes (contact utility for requirements)  No If Yes, this will be for:  emergency service  parallel generation Will a fire pump be installed?  Yes  No Form Completed by: Name: ________________________________________________ Company:_____________________________________________ Mail Address: _________________________________________ City: _________________________________________________ State & Zip: ___________________________________________ Phone: _______________________________________________ Email: ________________________________________________ For Office Use Only Transformer Size: _________________________________kVA Fault Current at Transformer: _______________________Amps 100% Construction - Cont. # ____________ Paid: ____________ A.T.E. Date: _____________________ Engineering Approval by: ______________ Date: _____________ Metering Approval by: _________________ Date: _____________ Prospect Ridge Ft. Collins, Colorado Building A RESIDENCE LOAD CALCULATIONS UNIT 1A LIGHTING 726 SF x 3 VA/SF N.E.C. 220.12 = 2,178 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 30,558 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 20,558 VA @ 40%NEC 220.82(B)= 8,223 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2-TON 13.5 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 103 AMPS = 24,823 VA *** NON-COINCIDENTAL LOAD UNIT 1B LIGHTING 726 SF x 3 VA/SF N.E.C. 220.12 = 2,178 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 30,558 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 20,558 VA @ 40%NEC 220.82(B)= 8,223 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2-TON 13.5 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 103 AMPS = 24,823 VA *** NON-COINCIDENTAL LOAD UNIT 2A LIGHTING 946 SF x 3 VA/SF N.E.C. 220.12 = 2,838 VA Page 1 of 5 Prospect Ridge Ft. Collins, Colorado Building A SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,218 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,218 VA @ 40%NEC 220.82(B)= 8,487 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,087 VA *** NON-COINCIDENTAL LOAD UNIT 2B LIGHTING 1,053 SF x 3 VA/SF N.E.C. 220.12 = 3,159 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,539 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,539 VA @ 40%NEC 220.82(B)= 8,616 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,216 VA *** NON-COINCIDENTAL LOAD UNIT 2C LIGHTING 1,011 SF x 3 VA/SF N.E.C. 220.12 = 3,033 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA Page 2 of 5 Prospect Ridge Ft. Collins, Colorado Building A REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,413 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,413 VA @ 40%NEC 220.82(B)= 8,565 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,165 VA *** NON-COINCIDENTAL LOAD UNIT 3A LIGHTING 1,278 SF x 3 VA/SF N.E.C. 220.12 = 3,834 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 32,214 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 22,214 VA @ 40%NEC 220.82(B)= 8,886 VA HEAT PUMP - 8KW HEAT 43.3 AMPS X 1 N.E.C. 220-82(C)= 10,392 VA HP -COND UNIT 3-TON 19.2 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 122 AMPS = 29,278 VA *** NON-COINCIDENTAL LOAD BUILDING LOAD CALCULATIONS LIGHTING 1A 726 SF x 3 VA / SF x 0 = 0 VA LIGHTING 1B 726 SF x 3 VA / SF x 18 = 39,204 VA LIGHTING 2A 946 SF x 3 VA / SF x 10 = 28,380 VA LIGHTING 2B 1,053 SF x 3 VA / SF x 3 = 9,477 VA LIGHTING 2C 1,011 SF x 3 VA / SF x 0 = 0 VA LIGHTING 3A 1,278 SF x 3 VA / SF x 4 = 15,336 VA Page 3 of 5 Prospect Ridge Ft. Collins, Colorado Building A SMALL APPLIANCE 3,000 VA x 35 = 105,000 VA LAUNDRY 1,500 VA x 35 = 52,500 VA CLOTHES DRYER 5,000 VA x 35 = 175,000 VA DISPOSAL 830 VA x 35 = 29,050 VA DISHWASHER 1,150 VA x 35 = 40,250 VA MICROWAVE 1,500 VA x 35 = 52,500 VA REFRIGERATOR 900 VA x 35 = 31,500 VA WATER HEATER 18.75 AMPS X 35 = 157,500 VA RANGE 10,000 VA x 35 = 350,000 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 18 = 102,960 VA HP -COND UNIT 2-TON 13.5 AMPS X 18 = 0 VA *** HEAT PUMP - 5KW HEAT 27.5 AMPS X 13 = 74,360 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 13 = 0 VA *** HEAT PUMP - 8KW HEAT 43.3 AMPS X 4 = 36,026 VA HP -COND UNIT 3-TON 19.2 AMPS X 4 = 0 VA *** SUBTOTAL = 1,299,043 VA DEMAND CALCULATIONS N.E.C. 220 RESIDENTIAL TOTAL 1,299,043 VA @ 30% TABLE 220.84 = 389,713 VA 1083 AMPS HOUSE PANEL H: EXTERIOR LIGHTING 3500 VA @ 125% = 4,375 VA INTERIOR LIGHTING 1000 VA @ 125% 4 = 5,000 VA RECEPTACLES (MISC) 180 VA @ 100% 20 = 3,600 VA HEAT PUMP - 5KW HEAT 27.5 A X 100% 4 = 22,880 VA HEAT PUMP EXTERIOR 2.5-TON 16.3 A X 100% 5 = 0 VA *** BASEBOARD HEAT 1500 VA @ 100% 6 = 9,000 VA GARAGE DOOR OPENERS 0.5 HP @ 100% 11 = 12,430 VA RECEPTACLES (GARAGES) 180 VA @ 100% 11 = 1,980 VA CAVITY HEAT 3000 VA @ 100% 6 = 18,000 VA CAR CHARGER 9000 VA @ 125% 5 = 56,250 VA MISC 10000 VA @ 100% 1 = 10,000 VA HOUSE PANEL LOAD 399 AMPS = 143,515 VA ELEVATOR LOAD LIGHTING 500 VA @ 125% = 625 VA RECEPTACLES (MISC) 1500 VA @ 100% = 1,500 VA HP-3 7056 VA @ 100% = 7,056 VA BLOWER 0.5 AMPS x 1 = 60 VA ELEVATOR 24390 VA @ 100% = 24,390 VA 25% LARGEST MOTOR 24390 VA @ 25% = 6,098 VA ELEVATOR SUMP 1130 VA @ 100% = 1,130 VA SUBTOTAL 113 AMPS = 40,859 VA HOUSE LOAD = 184,374 VA 512 AMPS Page 4 of 5 Prospect Ridge Ft. Collins, Colorado Building A OVERALL ELECTRICAL SERVICE TO BUILDING RESIDENTIAL SERVICE = 389,713 VA HOUSE SERVICE AND ELEVATOR = 184,374 VA MISC SERVICE FOR FUTURE REVISIONS TOTAL SERVICE TO THE BUILDING 1,595 AMPS = 574,086 VA Page 5 of 5 WORD\DATA\FORMS\C-1.DOC REV.August 14, 2020 CUSTOMER OWNED SERVICE INFORMATION FORM (C-1) City of Ft. Collins Electric Utility  700 Wood St.  P.O. Box 580  Ft. Collins, CO 80522 (970)221-6700 or fax (970)221-6619 Service voltages available are (not all voltages are available at all locations):  120/240 V. 1 phase, 3 wire  120/208 V. 3 phase, 4 wire  120/208 V. 1 phase, 3 wire (network)  277/480 V. 3 phase, 4 wire  Primary 13,200 V. Grd Y /7620  120/240 V. 3 phase, 4 wire (special utility permission required) For CT’d meters, Light and Power will provide the meter socket and CT’s to the electrical contractor. CT’s cannot be placed in the transformer, but may be located in a building mounted cabinet (provided by owner) or in the owner’s switchgear. In no case, can meters be mounted on the transformer. · Cold sequencing is required for all commercial services that are direct metered. · If CT’d metering, the owner must provide and install a - 1” conduit from the CT location to the electric meter. Please complete the following completely and legibly: Date Submitted: _____________________________________ Voltage Requested: _____/_____  1 phase OR  3 phase Building Main (not fuse) Size: ____________________ Amps Number of Conduits: _______ Size of Conduits:_________ Number of Cables: ________ Size of Cables: ___________ Electric Heat:  Yes _________kW  No Business Name: ____________________________________ Site Address: ______________________________________ Owners Name: _____________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Email: ____________________________________________ General Contractor: _________________________________ Individual: _________________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Email: ____________________________________________ Electrical Contractor: ________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Firm: ______________________________________________ Email: _____________________________________________ Number of CT’d meters: __________ at ___________Amps each Number of Self-Contained meters: _____ at ________Amps each Largest Motor: ________ H.P. 1 Phase __________ H.P. 3 Phase Will any generating system (including photo-voltaics) be installed?  Yes (contact utility for requirements)  No If Yes, this will be for:  emergency service  parallel generation Will a fire pump be installed?  Yes  No Form Completed by: Name: ________________________________________________ Company:_____________________________________________ Mail Address: _________________________________________ City: _________________________________________________ State & Zip: ___________________________________________ Phone: _______________________________________________ Email: ________________________________________________ For Office Use Only Transformer Size: _________________________________kVA Fault Current at Transformer: _______________________Amps 100% Construction - Cont. # ____________ Paid: ____________ A.T.E. Date: _____________________ Engineering Approval by: ______________ Date: _____________ Metering Approval by: _________________ Date: _____________ Prospect Ridge Ft. Collins, Colorado Building B RESIDENCE LOAD CALCULATIONS UNIT 1A LIGHTING 726 SF x 3 VA/SF N.E.C. 220.12 = 2,178 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 30,558 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 20,558 VA @ 40%NEC 220.82(B)= 8,223 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2-TON 13.5 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 103 AMPS = 24,823 VA *** NON-COINCIDENTAL LOAD UNIT 1B LIGHTING 726 SF x 3 VA/SF N.E.C. 220.12 = 2,178 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 30,558 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 20,558 VA @ 40%NEC 220.82(B)= 8,223 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2-TON 13.5 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 103 AMPS = 24,823 VA *** NON-COINCIDENTAL LOAD UNIT 2A LIGHTING 946 SF x 3 VA/SF N.E.C. 220.12 = 2,838 VA Page 1 of 5 Prospect Ridge Ft. Collins, Colorado Building B SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,218 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,218 VA @ 40%NEC 220.82(B)= 8,487 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,087 VA *** NON-COINCIDENTAL LOAD UNIT 2B LIGHTING 1,053 SF x 3 VA/SF N.E.C. 220.12 = 3,159 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,539 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,539 VA @ 40%NEC 220.82(B)= 8,616 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,216 VA *** NON-COINCIDENTAL LOAD UNIT 2C LIGHTING 1,011 SF x 3 VA/SF N.E.C. 220.12 = 3,033 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA Page 2 of 5 Prospect Ridge Ft. Collins, Colorado Building B REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,413 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,413 VA @ 40%NEC 220.82(B)= 8,565 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,165 VA *** NON-COINCIDENTAL LOAD UNIT 3A LIGHTING 1,278 SF x 3 VA/SF N.E.C. 220.12 = 3,834 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 32,214 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 22,214 VA @ 40%NEC 220.82(B)= 8,886 VA HEAT PUMP - 8KW HEAT 43.3 AMPS X 1 N.E.C. 220-82(C)= 10,392 VA HP -COND UNIT 3-TON 19.2 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 122 AMPS = 29,278 VA *** NON-COINCIDENTAL LOAD BUILDING LOAD CALCULATIONS LIGHTING 1A 726 SF x 3 VA / SF x 1 = 2,178 VA LIGHTING 1B 726 SF x 3 VA / SF x 15 = 32,670 VA LIGHTING 2A 946 SF x 3 VA / SF x 16 = 45,408 VA LIGHTING 2B 1,053 SF x 3 VA / SF x 6 = 18,954 VA LIGHTING 2C 1,011 SF x 3 VA / SF x 0 = 0 VA LIGHTING 3A 1,278 SF x 3 VA / SF x 4 = 15,336 VA Page 3 of 5 Prospect Ridge Ft. Collins, Colorado Building B SMALL APPLIANCE 3,000 VA x 42 = 126,000 VA LAUNDRY 1,500 VA x 42 = 63,000 VA CLOTHES DRYER 5,000 VA x 42 = 210,000 VA DISPOSAL 830 VA x 42 = 34,860 VA DISHWASHER 1,150 VA x 42 = 48,300 VA MICROWAVE 1,500 VA x 42 = 63,000 VA REFRIGERATOR 900 VA x 42 = 37,800 VA WATER HEATER 18.75 AMPS X 42 = 189,000 VA RANGE 10,000 VA x 42 = 420,000 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 16 = 91,520 VA HP -COND UNIT 2-TON 13.5 AMPS X 16 = 0 VA *** HEAT PUMP - 5KW HEAT 27.5 AMPS X 22 = 125,840 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 22 = 0 VA *** HEAT PUMP - 8KW HEAT 43.3 AMPS X 4 = 36,026 VA HP -COND UNIT 3-TON 19.2 AMPS X 4 = 0 VA *** SUBTOTAL = 1,559,892 VA DEMAND CALCULATIONS N.E.C. 220 RESIDENTIAL TOTAL 1,559,892 VA @ 28% TABLE 220.84 = 436,770 VA 1213 AMPS HOUSE PANEL H: EXTERIOR LIGHTING 5000 VA @ 125% = 6,250 VA INTERIOR LIGHTING 1000 VA @ 125% 4 = 5,000 VA RECEPTACLES (MISC) 180 VA @ 100% 20 = 3,600 VA HEAT PUMP - 5KW HEAT 27.5 A X 100% 4 = 22,880 VA HEAT PUMP EXTERIOR 2.5-TON 16.3 A X 100% 5 = 0 VA *** BASEBOARD HEAT 1500 VA @ 100% 6 = 9,000 VA GARAGE DOOR OPENERS 0.5 HP @ 100% 15 = 16,950 VA RECEPTACLES (GARAGES) 180 VA @ 100% 15 = 2,700 VA CAVITY HEAT 3000 VA @ 100% 6 = 18,000 VA CAR CHARGER 9000 VA @ 125% 5 = 56,250 VA MISC 10000 VA @ 100% 1 = 10,000 VA HOUSE PANEL LOAD 418 AMPS = 150,630 VA ELEVATOR LOAD LIGHTING 500 VA @ 125% = 625 VA RECEPTACLES (MISC) 1500 VA @ 100% = 1,500 VA HP-3 7056 VA @ 100% = 7,056 VA BLOWER 0.5 AMPS x 1 = 60 VA ELEVATOR 24390 VA @ 100% = 24,390 VA 25% LARGEST MOTOR 24390 VA @ 25% = 6,098 VA ELEVATOR SUMP 1130 VA @ 100% = 1,130 VA SUBTOTAL 113 AMPS = 40,859 VA HOUSE LOAD = 191,489 VA 532 AMPS Page 4 of 5 Prospect Ridge Ft. Collins, Colorado Building B OVERALL ELECTRICAL SERVICE TO BUILDING RESIDENTIAL SERVICE = 436,770 VA HOUSE SERVICE AND ELEVATOR = 191,489 VA MISC SERVICE FOR FUTURE REVISIONS TOTAL SERVICE TO THE BUILDING 1,745 AMPS = 628,258 VA Page 5 of 5 WORD\DATA\FORMS\C-1.DOC REV.August 14, 2020 CUSTOMER OWNED SERVICE INFORMATION FORM (C-1) City of Ft. Collins Electric Utility  700 Wood St.  P.O. Box 580  Ft. Collins, CO 80522 (970)221-6700 or fax (970)221-6619 Service voltages available are (not all voltages are available at all locations):  120/240 V. 1 phase, 3 wire  120/208 V. 3 phase, 4 wire  120/208 V. 1 phase, 3 wire (network)  277/480 V. 3 phase, 4 wire  Primary 13,200 V. Grd Y /7620  120/240 V. 3 phase, 4 wire (special utility permission required) For CT’d meters, Light and Power will provide the meter socket and CT’s to the electrical contractor. CT’s cannot be placed in the transformer, but may be located in a building mounted cabinet (provided by owner) or in the owner’s switchgear. In no case, can meters be mounted on the transformer. · Cold sequencing is required for all commercial services that are direct metered. · If CT’d metering, the owner must provide and install a - 1” conduit from the CT location to the electric meter. Please complete the following completely and legibly: Date Submitted: _____________________________________ Voltage Requested: _____/_____  1 phase OR  3 phase Building Main (not fuse) Size: ____________________ Amps Number of Conduits: _______ Size of Conduits:_________ Number of Cables: ________ Size of Cables: ___________ Electric Heat:  Yes _________kW  No Business Name: ____________________________________ Site Address: ______________________________________ Owners Name: _____________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Email: ____________________________________________ General Contractor: _________________________________ Individual: _________________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Email: ____________________________________________ Electrical Contractor: ________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Firm: ______________________________________________ Email: _____________________________________________ Number of CT’d meters: __________ at ___________Amps each Number of Self-Contained meters: _____ at ________Amps each Largest Motor: ________ H.P. 1 Phase __________ H.P. 3 Phase Will any generating system (including photo-voltaics) be installed?  Yes (contact utility for requirements)  No If Yes, this will be for:  emergency service  parallel generation Will a fire pump be installed?  Yes  No Form Completed by: Name: ________________________________________________ Company:_____________________________________________ Mail Address: _________________________________________ City: _________________________________________________ State & Zip: ___________________________________________ Phone: _______________________________________________ Email: ________________________________________________ For Office Use Only Transformer Size: _________________________________kVA Fault Current at Transformer: _______________________Amps 100% Construction - Cont. # ____________ Paid: ____________ A.T.E. Date: _____________________ Engineering Approval by: ______________ Date: _____________ Metering Approval by: _________________ Date: _____________ Prospect Ridge Ft. Collins, Colorado Building C RESIDENCE LOAD CALCULATIONS UNIT 1A LIGHTING 726 SF x 3 VA/SF N.E.C. 220.12 = 2,178 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 30,558 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 20,558 VA @ 40%NEC 220.82(B)= 8,223 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2-TON 13.5 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 103 AMPS = 24,823 VA *** NON-COINCIDENTAL LOAD UNIT 1B LIGHTING 726 SF x 3 VA/SF N.E.C. 220.12 = 2,178 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 30,558 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 20,558 VA @ 40%NEC 220.82(B)= 8,223 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2-TON 13.5 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 103 AMPS = 24,823 VA *** NON-COINCIDENTAL LOAD UNIT 2A LIGHTING 946 SF x 3 VA/SF N.E.C. 220.12 = 2,838 VA Page 1 of 5 Prospect Ridge Ft. Collins, Colorado Building C SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,218 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,218 VA @ 40%NEC 220.82(B)= 8,487 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,087 VA *** NON-COINCIDENTAL LOAD UNIT 2B LIGHTING 1,053 SF x 3 VA/SF N.E.C. 220.12 = 3,159 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,539 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,539 VA @ 40%NEC 220.82(B)= 8,616 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,216 VA *** NON-COINCIDENTAL LOAD UNIT 2C LIGHTING 1,011 SF x 3 VA/SF N.E.C. 220.12 = 3,033 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA Page 2 of 5 Prospect Ridge Ft. Collins, Colorado Building C REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,413 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,413 VA @ 40%NEC 220.82(B)= 8,565 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,165 VA *** NON-COINCIDENTAL LOAD UNIT 3A LIGHTING 1,278 SF x 3 VA/SF N.E.C. 220.12 = 3,834 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 32,214 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 22,214 VA @ 40%NEC 220.82(B)= 8,886 VA HEAT PUMP - 8KW HEAT 43.3 AMPS X 1 N.E.C. 220-82(C)= 10,392 VA HP -COND UNIT 3-TON 19.2 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 122 AMPS = 29,278 VA *** NON-COINCIDENTAL LOAD BUILDING LOAD CALCULATIONS LIGHTING 1A 726 SF x 3 VA / SF x 0 = 0 VA LIGHTING 1B 726 SF x 3 VA / SF x 17 = 37,026 VA LIGHTING 2A 946 SF x 3 VA / SF x 6 = 17,028 VA LIGHTING 2B 1,053 SF x 3 VA / SF x 4 = 12,636 VA LIGHTING 2C 1,011 SF x 3 VA / SF x 8 = 24,264 VA LIGHTING 3A 1,278 SF x 3 VA / SF x 3 = 11,502 VA Page 3 of 5 Prospect Ridge Ft. Collins, Colorado Building C SMALL APPLIANCE 3,000 VA x 38 = 114,000 VA LAUNDRY 1,500 VA x 38 = 57,000 VA CLOTHES DRYER 5,000 VA x 38 = 190,000 VA DISPOSAL 830 VA x 38 = 31,540 VA DISHWASHER 1,150 VA x 38 = 43,700 VA MICROWAVE 1,500 VA x 38 = 57,000 VA REFRIGERATOR 900 VA x 38 = 34,200 VA WATER HEATER 18.75 AMPS X 38 = 171,000 VA RANGE 10,000 VA x 38 = 380,000 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 17 = 97,240 VA HP -COND UNIT 2-TON 13.5 AMPS X 17 = 0 VA *** HEAT PUMP - 5KW HEAT 27.5 AMPS X 18 = 102,960 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 18 = 0 VA *** HEAT PUMP - 8KW HEAT 43.3 AMPS X 3 = 27,019 VA HP -COND UNIT 3-TON 19.2 AMPS X 3 = 0 VA *** SUBTOTAL = 1,408,115 VA DEMAND CALCULATIONS N.E.C. 220 RESIDENTIAL TOTAL 1,408,115 VA @ 29% TABLE 220.84 = 408,353 VA 1134 AMPS HOUSE PANEL H: EXTERIOR LIGHTING 3500 VA @ 125% = 4,375 VA INTERIOR LIGHTING 1000 VA @ 125% 4 = 5,000 VA RECEPTACLES (MISC) 180 VA @ 100% 20 = 3,600 VA HEAT PUMP - 5KW HEAT 27.5 A X 100% 4 = 22,880 VA HEAT PUMP EXTERIOR 2.5-TON 16.3 A X 100% 5 = 0 VA *** BASEBOARD HEAT 1500 VA @ 100% 6 = 9,000 VA GARAGE DOOR OPENERS 0.5 HP @ 100% 14 = 15,820 VA RECEPTACLES (GARAGES) 180 VA @ 100% 14 = 2,520 VA CAVITY HEAT 3000 VA @ 100% 6 = 18,000 VA CAR CHARGER 9000 VA @ 125% 5 = 56,250 VA MISC 10000 VA @ 100% 1 = 10,000 VA HOUSE PANEL LOAD 410 AMPS = 147,445 VA ELEVATOR LOAD LIGHTING 500 VA @ 125% = 625 VA RECEPTACLES (MISC) 1500 VA @ 100% = 1,500 VA HP-3 7056 VA @ 100% = 7,056 VA BLOWER 0.5 AMPS x 1 = 60 VA ELEVATOR 24390 VA @ 100% = 24,390 VA 25% LARGEST MOTOR 24390 VA @ 25% = 6,098 VA ELEVATOR SUMP 1130 VA @ 100% = 1,130 VA SUBTOTAL 113 AMPS = 40,859 VA HOUSE LOAD = 188,304 VA 523 AMPS Page 4 of 5 Prospect Ridge Ft. Collins, Colorado Building C OVERALL ELECTRICAL SERVICE TO BUILDING RESIDENTIAL SERVICE = 408,353 VA HOUSE SERVICE AND ELEVATOR = 188,304 VA MISC SERVICE FOR FUTURE REVISIONS TOTAL SERVICE TO THE BUILDING 1,657 AMPS = 596,657 VA Page 5 of 5 WORD\DATA\FORMS\C-1.DOC REV.August 14, 2020 CUSTOMER OWNED SERVICE INFORMATION FORM (C-1) City of Ft. Collins Electric Utility  700 Wood St.  P.O. Box 580  Ft. Collins, CO 80522 (970)221-6700 or fax (970)221-6619 Service voltages available are (not all voltages are available at all locations):  120/240 V. 1 phase, 3 wire  120/208 V. 3 phase, 4 wire  120/208 V. 1 phase, 3 wire (network)  277/480 V. 3 phase, 4 wire  Primary 13,200 V. Grd Y /7620  120/240 V. 3 phase, 4 wire (special utility permission required) For CT’d meters, Light and Power will provide the meter socket and CT’s to the electrical contractor. CT’s cannot be placed in the transformer, but may be located in a building mounted cabinet (provided by owner) or in the owner’s switchgear. In no case, can meters be mounted on the transformer. · Cold sequencing is required for all commercial services that are direct metered. · If CT’d metering, the owner must provide and install a - 1” conduit from the CT location to the electric meter. Please complete the following completely and legibly: Date Submitted: _____________________________________ Voltage Requested: _____/_____  1 phase OR  3 phase Building Main (not fuse) Size: ____________________ Amps Number of Conduits: _______ Size of Conduits:_________ Number of Cables: ________ Size of Cables: ___________ Electric Heat:  Yes _________kW  No Business Name: ____________________________________ Site Address: ______________________________________ Owners Name: _____________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Email: ____________________________________________ General Contractor: _________________________________ Individual: _________________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Email: ____________________________________________ Electrical Contractor: ________________________________ Mail Address: ______________________________________ City: ______________________________________________ State & Zip: ________________________________________ Phone: ____________________________________________ Firm: ______________________________________________ Email: _____________________________________________ Number of CT’d meters: __________ at ___________Amps each Number of Self-Contained meters: _____ at ________Amps each Largest Motor: ________ H.P. 1 Phase __________ H.P. 3 Phase Will any generating system (including photo-voltaics) be installed?  Yes (contact utility for requirements)  No If Yes, this will be for:  emergency service  parallel generation Will a fire pump be installed?  Yes  No Form Completed by: Name: ________________________________________________ Company:_____________________________________________ Mail Address: _________________________________________ City: _________________________________________________ State & Zip: ___________________________________________ Phone: _______________________________________________ Email: ________________________________________________ For Office Use Only Transformer Size: _________________________________kVA Fault Current at Transformer: _______________________Amps 100% Construction - Cont. # ____________ Paid: ____________ A.T.E. Date: _____________________ Engineering Approval by: ______________ Date: _____________ Metering Approval by: _________________ Date: _____________ Prospect Ridge Ft. Collins, Colorado Building D RESIDENCE LOAD CALCULATIONS UNIT 1A LIGHTING 726 SF x 3 VA/SF N.E.C. 220.12 = 2,178 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 30,558 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 20,558 VA @ 40%NEC 220.82(B)= 8,223 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2-TON 13.5 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 103 AMPS = 24,823 VA *** NON-COINCIDENTAL LOAD UNIT 1B LIGHTING 726 SF x 3 VA/SF N.E.C. 220.12 = 2,178 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 30,558 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 20,558 VA @ 40%NEC 220.82(B)= 8,223 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2-TON 13.5 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 103 AMPS = 24,823 VA *** NON-COINCIDENTAL LOAD UNIT 2A LIGHTING 946 SF x 3 VA/SF N.E.C. 220.12 = 2,838 VA Page 1 of 5 Prospect Ridge Ft. Collins, Colorado Building D SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,218 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,218 VA @ 40%NEC 220.82(B)= 8,487 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,087 VA *** NON-COINCIDENTAL LOAD UNIT 2B LIGHTING 1,053 SF x 3 VA/SF N.E.C. 220.12 = 3,159 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,539 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,539 VA @ 40%NEC 220.82(B)= 8,616 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,216 VA *** NON-COINCIDENTAL LOAD UNIT 2C LIGHTING 1,011 SF x 3 VA/SF N.E.C. 220.12 = 3,033 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA Page 2 of 5 Prospect Ridge Ft. Collins, Colorado Building D REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 31,413 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 21,413 VA @ 40%NEC 220.82(B)= 8,565 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 1 N.E.C. 220-82(C)= 6,600 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 105 AMPS = 25,165 VA *** NON-COINCIDENTAL LOAD UNIT 3A LIGHTING 1,278 SF x 3 VA/SF N.E.C. 220.12 = 3,834 VA SMALL APPLIANCE LOAD 1,500 VA x 2 N.E.C. 220.52(A) = 3,000 VA DISPOSAL 830 VA x 1 N.E.C. 220.14 = 830 VA DISHWASHER 1,150 VA x 1 N.E.C. 220.14 = 1,150 VA REFRIGERATOR 900 VA x 1 N.E.C. 220-14 = 900 VA MICROWAVE 1,500 VA x 1 N.E.C. 220.14 = 1,500 VA WATER HEATER 18.75 AMPS X 1 N.E.C. 220-14 = 4,500 VA LAUNDRY LOAD 1,500 VA x 1 N.E.C. 220-52(b) = 1,500 VA DRYER 5,000 VA x 1 N.E.C. 220-54 = 5,000 VA RANGE N.E.C. 220.55 = 10,000 VA SUBTOTAL = 32,214 VA DEMAND FACTOR CALCULATIONS: FIRST 10,000 VA @ 100% = 10,000 VA BALANCE 22,214 VA @ 40%NEC 220.82(B)= 8,886 VA HEAT PUMP - 8KW HEAT 43.3 AMPS X 1 N.E.C. 220-82(C)= 10,392 VA HP -COND UNIT 3-TON 19.2 AMPS X 1 N.E.C. 220.82(C) = 0 VA *** TOTAL LOAD 120 / 240V 1ph 122 AMPS = 29,278 VA *** NON-COINCIDENTAL LOAD BUILDING LOAD CALCULATIONS LIGHTING 1A 726 SF x 3 VA / SF x 0 = 0 VA LIGHTING 1B 726 SF x 3 VA / SF x 12 = 26,136 VA LIGHTING 2A 946 SF x 3 VA / SF x 8 = 22,704 VA LIGHTING 2B 1,053 SF x 3 VA / SF x 3 = 9,477 VA LIGHTING 2C 1,011 SF x 3 VA / SF x 0 = 0 VA LIGHTING 3A 1,278 SF x 3 VA / SF x 4 = 15,336 VA Page 3 of 5 Prospect Ridge Ft. Collins, Colorado Building D SMALL APPLIANCE 3,000 VA x 27 = 81,000 VA LAUNDRY 1,500 VA x 27 = 40,500 VA CLOTHES DRYER 5,000 VA x 27 = 135,000 VA DISPOSAL 830 VA x 27 = 22,410 VA DISHWASHER 1,150 VA x 27 = 31,050 VA MICROWAVE 1,500 VA x 27 = 40,500 VA REFRIGERATOR 900 VA x 27 = 24,300 VA WATER HEATER 18.75 AMPS X 27 = 121,500 VA RANGE 10,000 VA x 27 = 270,000 VA HEAT PUMP - 5KW HEAT 27.5 AMPS X 12 = 68,640 VA HP -COND UNIT 2-TON 13.5 AMPS X 12 = 0 VA *** HEAT PUMP - 5KW HEAT 27.5 AMPS X 11 = 62,920 VA HP -COND UNIT 2.5-TON 16.3 AMPS X 11 = 0 VA *** HEAT PUMP - 8KW HEAT 43.3 AMPS X 4 = 36,026 VA HP -COND UNIT 3-TON 19.2 AMPS X 4 = 0 VA *** SUBTOTAL = 1,007,499 VA DEMAND CALCULATIONS N.E.C. 220 RESIDENTIAL TOTAL 1,007,499 VA @ 34% TABLE 220.84 = 342,550 VA 952 AMPS HOUSE PANEL H: EXTERIOR LIGHTING 3500 VA @ 125% = 4,375 VA INTERIOR LIGHTING 1000 VA @ 125% 4 = 5,000 VA RECEPTACLES (MISC) 180 VA @ 100% 20 = 3,600 VA HEAT PUMP - 5KW HEAT 27.5 A X 100% 4 = 22,880 VA HEAT PUMP EXTERIOR 2.5-TON 16.3 A X 100% 5 = 0 VA *** BASEBOARD HEAT 1500 VA @ 100% 6 = 9,000 VA GARAGE DOOR OPENERS 0.5 HP @ 100% 7 = 7,910 VA RECEPTACLES (GARAGES) 180 VA @ 100% 7 = 1,260 VA CAVITY HEAT 3000 VA @ 100% 6 = 18,000 VA CAR CHARGER 9000 VA @ 125% 3 = 33,750 VA MISC 10000 VA @ 100% 1 = 10,000 VA HOUSE PANEL LOAD 322 AMPS = 115,775 VA AMENITY / COMMON AREA LIGHTING LEASING 750 SF x 3.5 VA/SF @ 125% = 3,281 VA LIGHTING FITNESS 1,420 SF x 3.5 VA/SF @ 125% = 6,213 VA LIGHTING AMENITY 2,535 SF x 3.5 VA/SF @ 125% = 11,091 VA RECEPTACLES (MISC) 4,705 SF x 5 VA / SF @ 100% = 23,525 VA HEAT PUMP - 5KW HEAT 27.5 A x 10.0 208V @ 100%= 57,200 VA HP COND - 3T 19.2 A x 10.0 208V @ 100%= 0 VA *** MISC POWER 4,705 SF x 10.0 VA/SF @ 100% = 47,050 VA AMENITY AREA = 148,359 VA *** NON-COINCIDENTAL LOAD 412 AMPS ELEVATOR LOAD LIGHTING 500 VA @ 125% = 625 VA Page 4 of 5 Prospect Ridge Ft. Collins, Colorado Building D RECEPTACLES (MISC) 1500 VA @ 100% = 1,500 VA HP-3 7056 VA @ 100% = 7,056 VA BLOWER 0.5 AMPS x 1 = 60 VA ELEVATOR 24390 VA @ 100% = 24,390 VA 25% LARGEST MOTOR 24390 VA @ 25% = 6,098 VA ELEVATOR SUMP 1130 VA @ 100% = 1,130 VA SUBTOTAL 113 AMPS = 40,859 VA HOUSE LOAD = 304,993 VA 847 AMPS OVERALL ELECTRICAL SERVICE TO BUILDING RESIDENTIAL SERVICE = 342,550 VA HOUSE SERVICE AND ELEVATOR = 156,634 VA AMENITY AREA = 148,359 VA MISC SERVICE FOR FUTURE REVISIONS TOTAL SERVICE TO THE BUILDING 1,799 AMPS = 647,542 VA Page 5 of 5