Plans - Electrical Plan - 07/09/2025
LEVEL 00 0" LEVEL 01 0" LEVEL 02 0" LEVEL 03 0" LEVEL 04 0" 480/277V,3Ø4W 3000A MCCB SCCR 65 kA MSB1-MAIN 480/277V,3Ø4W 3000A MLO SCCR 65 kA MSB1-DISTRIBUTION 480/277V,3Ø4W 3000A MCB BD-1 50A TR-R1 112.5KVA 480:120/208V 120/208V,3Ø4W 400A MCB SCCR 65 kA RDP1A 120/208V,1Ø3W 125A MLO SCCR 65 kA UP B-P2 CBCB 700A TR-R2 300KVA 480:120/208V 120/208V,3Ø4W 1000A MCB SCCR 65 kA RDP2A 120/208V,1Ø3W 125A MLO SCCR 65 kA UP B-P3 CBCB 700A ROOF 0" TR-R3A 300KVA 480:120/208V 120/208V,3Ø4W 1000A MCB SCCR 65 kA RDP3A 120/208V,1Ø3W 125A MLO SCCR 65 kA UP B-P4 CBCB 700A TR-R4 300KVA 480:120/208V 120/208V,3Ø4W 1000A MCB SCCR 65 kA RDP4 120/208V,1Ø3W 125A MLO SCCR 65 kA UP TR-R 2500KVA 480/277V SECONDARY TR-R3B 112.5KVA 480:120/208V 120/208V,3Ø4W 400A MCB SCCR 65 kA RDP3C DS-R3B NFNF 600A DS-R2B NFNF 600A TR-R2B 112.5KVA 480:120/208V 120/208V,3Ø4W 400A MCB SCCR 65 kA RDP2C 120/208V,3Ø4W 500A MCB SCCR 65 kA RDP1C TR-R1B 150KVA 480:120/208V FDS-R1B FUFU 800A 120/208V,3Ø4W 500A MCB SCCR 65 kA RDP3B 120/208V,3Ø4W 500A MCB SCCR 65 kA RDP4B 120/208V,3Ø4W 500A MCB SCCR 65 kA RDP2B TR-R2B.1 112.5KVA 480:120/208V 120/208V,3Ø4W 400A MCB SCCR 65 kA RDP2C.1 120/208V,3Ø4W 400A MCB SCCR 65 kA RDP3C.1 TR-R3B.1 112.5KVA 480:120/208V TR-R1B.1 150KVA 480:120/208V 120/208V,3Ø4W 500A MCB SCCR 65 kA RDP1C.1 UTILITY PROVIDED DPM DPM DPM DPM ELECTRICAL -RISER DIAGRAM NOTES: 1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE COMPONENTS OF THE ELECTRICAL DISTRIBUTION SYSTEM. REFER TO ELECTRICAL DRAWINGS, DETAILS, DISTRIBUTION / PANEL / EQUIPMENT / EQUIPMENT CONNECTION SCHEDULES, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. 2. SHORT CIRCUIT CURRENT RATINGS (SCCR) FOR EQUIPMENT ARE MINIMUM REQUIREMENTS FOR BUSS BRACING AND DEVICE RATING. ALL EQUIPMENT SHALL BE FULLY RATED UNLESS SPECIFICALLY NOTED AS SERIES RATED. 3. TRANSFER SWITCHES (SCCR) RATINGS ARE INTENDED AS WITHSTAND AND CLOSE RATINGS (WCR). 4. THE BASIS OF DESIGN: THE CONTRACTOR SHALL BE RESPONSIBLE FOR DERATING AND SIZING CONDUCTORS AND CONDUITS TO EQUAL OR EXCEED AMPACITY OF THE BASIS OF DESIGN CIRCUITS WHEN ALTERNATIVE METHODS OR MATERIALS OTHER THAN THE BASIS OF DESIGN ARE APPLIED. a. RACEWAY: EMT UNLESS OTHERWISE NOTED b. FEEDER CHARACTERISTICS: ALL CURRENT CARRYING CONDUCTORS SHALL BE COPPER UNLESS NOTED OTHERWISE. CONDUCTOR SIZES ARE BASED ON AMERICAN WIRE GAUGE AWG AND KCMIL THOUSANDS OF CIRCULAR MIL. REFER TO SPECIFICATION SECTION 25 05 13 WIRE AND CABLE FOR ADDITIONAL INFORMATION c. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER. d. CONDUCTORS (MOTORS): COPPER e. CONDUCTOR LENGTHS LISTED IN RISER DIAGRAMS AND SCHEDULES ARE FOR ENGINEERING CALCULATIONS AND SHALL NOT BE USED FOR BIDDING PURPOSES. f. [AL] INDICATES ALUMINUM CONDUCTOR g. [BLANK] OR [CU] INDICATES COPPER CONDUCTOR h. [CI] INDICATES CIRCUIT INTEGRITY CIRCUIT. FEEDER ROUTED OUTSIDE BUILDING OR 2 HOUR FIRE RATED. 5. PROVIDE GROUNDING ELECTRODE AND BONDING SYSTEM PER CODE REQUIREMENTS. PROVIDE THE FOLLOWING MINIMUM CONNECTIONS AND COMPONENTS. REFER TO SPECIFICATION SECTION 26 05 26 GROUNDING AND BONDING AND DETAILS WHEN APPLICABLE: a. ELECTRICAL GROUND FIELD b. CONCRETE-ENCASED GROUNDING ELECTRODE (UFER) c. METALLIC WATER MAIN d. BUILDING STEEL, EFFECTIVELY GROUNDED e. INTERSYSTEM BONDING TERMINAL [IBT] f. GROUND RING ENCIRCLING STRUCTURE 6. DRY TYPE TRANSFORMER AND SEPARATELY DERIVED SYSTEMS. PROVIDE GROUNDING ELECTRODE CONDUCTOR FOR SEPARATELY DERIVED SYSTEM. ROUTE TO STRUCTURAL BUILDING STEEL WHEN AVAILABLE. OTHERWISE ROUTE TO MAIN GROUNDING ELECTRODE SYSTEM. 7. PROVIDE O.Z. GEDNEY OR EQUAL GROUND BUSHING FOR ALL SERVICE AND FEEDER RACEWAYS BONDED TO GROUND BUS WITH CONDUCTOR SIZED TO MAXIMUM FEEDER GROUND CAPACITY. 8. CONDUCTORS AND GROUND SIZES ON THE LINE AND LOAD SIDES OF ALL DISCONNECT SWITCHES SHALL BE IDENTICAL UNLESS NOTED OTHERWISE. 9. REFER TO COVER SHEET FOR ADDITIONAL EQUIPMENT TAG INFORMATION (SPD-#, M-#, ETC). 10. REFER TO GROUNDING ELECTRODE SYSTEM AND BONDING DETAILS a. EGC –EQUIPMENT GROUNDING CONDUCTOR b. GEC –GROUNDING ELECTRODE CONDUCTOR c. SSBJ –SUPPLY SIDE BONDING JUMPER 11. CIRCUIT BREAKER CHARACTERISTICS AND ACCESSORIES: a. [CB] INDICATES CIRCUIT BREAKER b. [FU] INDICATES FUSED SWITCH c. [NF] INDICATES NON-FUSED SWITCH d. [MLO] INDICATES MAIN LUG ONLY e. [MCB] INDICATES MAIN CIRCUIT BREAKER f. [MCCB] INDICATES MOLDED CASE CIRCUIT BREAKER g. [LSIGM] INDICATES FEATURES PROVIDED WITH SOLID STATE CIRCUIT BREAKER [LONG TIME (W/DELAY), SHORT TIME (W/DELAY), INSTANTANEOUS, GROUND FAULT METER (CBM)] h. [LSIA] INDICATES FEATURES PROVIDED WITH SOLID STATE CIRCUIT BREAKER [LONG TIME (W/DELAY), SHORT TIME (W/DELAY), INSTANTANEOUS, GROUND FAULT ALARM (NO GROUND FAULT TRIP)] i. [GF] INDICATES GROUND FAULT RELAY j. [AER] INDICATES ARC ENERGY REDUCTION SYSTEM k. [100% RATED] INDICATES INSULATED CASE BREAKER RATED FOR FULL CONTINUOUS CAPACITY OF CIRCUIT BREAKER NAMEPLATE l. [DRAW] INDICATES DRAWOUT DEVICES m. [LOCK] INDICATES PADLOCK HASP n. [RED] INDICATES RED HANDLE o. [SHUNT] INDICATES SHUNT TRIP BREAKER p. [KIRK] CAPTURED KEY INTERLOCK SWITCH 12. ENERGY METER AND MANAGEMENT SYSTEM a. [BCPM] INDICATES BRANCH CIRCUIT POWER METER (SPECIFICATION 26 09 13) b. [CBM] INDICATES CIRCUIT BREAKER C.T. METER (SPECIFICATION 26 09 13) c. [DEM] INDICATES DIGITAL ENERGY METER (SPECIFICATION 26 09 13) d. [DPM] INDICATES DIGITAL ENERGY METER W/ POWER QUALITY ANALYSIS (SPECIFICATION 26 09 13) e. [EMMS] INDICATES ENERGY METER AND MANAGEMENT SYSTEM (SPECIFICATION 26 09 13) f. [MPM] INDICATES MOTOR PROTECTIVE MONITOR (SPECIFICATION 26 09 13) g. [RMMD] INDICATES REMOTE ENERGY MANAGEMENT AND MANAGEMENT DISPLAY (SPECIFICATION 26 09 13) h. [TTM] INDICATES TRANSFORMER TEMPERATURE MONITOR (SPECIFICATION 26 09 13) ELECTRICAL DISTRIBUTION AND PANEL SCHEDULE NOTES: 1. BRANCH PANEL KEY: a. *A = ARC FAULT CIRCUIT INTERRUPT b. *G = GROUND FAULT CIRCUIT INTERRUPT c. *I = ISOLATED GROUND d. *P = PADLOCK HASP e. *R = RED HANDLE f. *S = SHUNT TRIP g. *NB = NEW BREAKER h. *RB = REPLACE EXISTING BREAKER WITH NEW BREAKER i. *EB = EXISTING BREAKER j. *M = [CBM] CIRCUIT BREAKER METER -PROVIDE *EM WHEN NOT AVAILABLE (SPECIFICATION 26 09 13) k. *EM = [DEM] DIGITAL ENERGY METER -ADD ON (SPECIFICATION 26 09 13) THE ' ELECTRICAL DISTRIBUTION & PANEL SCHEDULE NOTES' may be moved to the electrical panel schedule sheets or remain here and referenced pending designer preferences] NOTES TO SPECIFIER: 7600 E ORCHARD ROAD SUITE 250-S GREENWOOD VILLAGE, CO 80111 P: 303.796.6000 www.imegcorp.com REF. SCALE IN INCHES 0 1 2 IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG. ©2025 IMEG CONSULTANTS CORP. PROJECT NUMBER: SHEET TITLE: DRAWN BY: CONSULTANT: SHEET: PRELIMINARY NOT FOR CONSTRUCTION Suite 300 www.lrsarchitects.com Portland OR 97209 A R C H I T E C T S 720 NW Davis 503.221.1121 PROJECT #25000169.00 7/ 9 / 2 0 2 5 1 2 : 5 0 : 0 0 P M A u t o d e s k D o c s : / / 2 2 4 0 2 3 - T o u c h m ar k F o r t C o l l i n s / 2 2 4 0 2 3 _ T F C O _ M E P _ R 2 5 . r v t Author E500 ELECTRICAL DIAGRAMS - RESIDENTIAL Project Status Touchmark Sr Living/Fort Collins, CO/New 4710 Cinquefoil Lane Fort Collins, CO 80528 25000169.00 1/22/25 NO SCALE 1 RISER DIAGRAM BP-RDP1 CB 250A LEVEL 00 0" LEVEL 01 0" LEVEL 02 0" LEVEL 03 0" LEVEL 04 0" 480/277V,3Ø4W 2500A MCCB SCCR 65 kA MSB2-MAIN 480/277V,3Ø4W 2500A MLO SCCR 65 kA MSB2-DISTRIBUTION ROOF 0" TR-HDP 750KVA 480:120/208V 120/208V,3Ø4W 2500A MCB SCCR 65 kA HDP 120/208V,3Ø4W 100A MCB SCCR 65 kA RP 120/208V,3Ø4W 100A MCB SCCR 65 kA LP 120/208V,3Ø4W 250A MCB SCCR 65 kA MP 120/208V,3Ø4W 250A MLO SCCR 65 kA R1A 120/208V,3Ø4W 400A MLO SCCR 65 kA M1A 120/208V,3Ø4W 100A MLO SCCR 65 kA L1A 120/208V,3Ø4W 2000A MCB BD-2 CB-R1 CBCB 250A CB-L1 CBCB 100A CB-M1 CBCB 400A 120/208V,3Ø4W 300A MLO SCCR 65 kA R1B 120/208V,3Ø4W 200A MLO SCCR 65 kA L1B 120/208V,3Ø4W 500A MLO SCCR 65 kA M1B 480/277V,3Ø4W 500A MLO SCCR 65 kA KH TR-K 150KVA 480:120/208V 120/208V,3Ø4W 500A MLO SCCR 65 kA KL 480/277V,3Ø4W 1200A MCB SCCR 65 kA GDP GEN-800 480/277V,3Ø4W 800kW/1000kVA LEGALLY REQUIRED 480V 4 POLES 250A ATS-LR N E EMERGENCY 480V 4 POLES 800A ATS-EM N E OPTIONAL STANDBY 480V 4 POLES 600A ATS-OS N E 480/277V,3Ø4W 250A MCB SCCR 65 kA HLRA 480/277V,3Ø4W 800A MCB SCCR 65 kA HEM 480/277V,3Ø4W 600A MCB SCCR 65 kA HOS 120/208V,3Ø4W 250A MCB SCCR 65 kA R3 120/208V,3Ø4W 100A MCB SCCR 65 kA L3 120/208V,3Ø4W 400A MCB SCCR 65 kA M3 CB-L3 CBCB 100A CB-R3 CBCB 250A CB-M3 CBCB 400A 480/277V,3Ø4W 800A MCB SCCR 65 kA HM1 CB-GDP CBCB 1200A TR-C 2000KVA 480/277V SECONDARY GENSET LOAD LOAD BANK PORTABLE GENSET K INTERLOCK 480/277V 1200 A GCC TR-LRA1 30KVA 480:120/208V 120/208V,3Ø4W 100A MCB SCCR 65 kA LRA1 TR-LRA2 30KVA 480:120/208V 120/208V,3Ø4W 100A MCB SCCR 65 kA LRA2 TR-KOS 75KVA 480:120/208V 120/208V,3Ø4W 200A MLO SCCR 65 kA KOS TR-OS 112.5KVA 480:120/208V 120/208V,3Ø4W 400A MCB SCCR 65 kA LOS 120/208V,3Ø4W 100A MCB SCCR 65 kA UPS-B 120/208V,3Ø4W 100A MCB SCCR 65 kA OSB 120/208V,3Ø4W 100A MLO SCCR 65 kA UPS-A 120/208V,3Ø4W 100A MLO SCCR 65 kA OSA 480/277V,3Ø4W 150A MCB SCCR 65 kA HLRB TR-LRB1 30KVA 480:120/208V 120/208V,3Ø4W 100A MCB SCCR 65 kA LRB1 TR-LRB2 30KVA 480:120/208V 120/208V,3Ø4W 100A MLO SCCR 65 kA LRB2 480/277V,3Ø4W 100A MCB SCCR 65 kA HLRA2 480/277V,3Ø4W 100A MCB SCCR 65 kA HLRB2 120/208V,3Ø4W 500A MCB SCCR 65 kA LEM TR-EM 150KVA 480:120/208V 120/208V,3Ø4W 100A MCB SCCR 65 kA UPS-C 120/208V,3Ø4W 100A MCB SCCR 65 kA OSC 120/208V,3Ø4W 125A MCB SCCR 65 kA LEM1 120/208V,3Ø4W 125A MCB SCCR 65 kA LEM2 120/208V,3Ø4W 125A MCB SCCR 65 kA LEM3 120/208V,3Ø4W 125A MCB SCCR 65 kA LEM4 120/208V,3Ø4W 60A MCB SCCR 65 kA LEM5B 120/208V,3Ø4W 125A MCB SCCR 65 kA LEM5 120/208V,3Ø4W 60A MCB SCCR 65 kA LEM1B 120/208V,3Ø4W 60A MCB SCCR 65 kA LEM2B 120/208V,3Ø4W 60A MCB SCCR 65 kA LEM3B 120/208V,3Ø4W 60A MCB SCCR 65 kA LEM4B 120/208V,3Ø4W 175A MCB SCCR 65 kA R3B 120/208V,3Ø4W 100A MCB SCCR 65 kA L3B 120/208V,3Ø4W 250A MCB SCCR 65 kA M3B 480/277V,3Ø4W 800A MCB SCCR 65 kA HM2 UTILITY PROVIDED DPMDPMDPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM DPM BP BP BP BP BP BP 7600 E ORCHARD ROAD SUITE 250-S GREENWOOD VILLAGE, CO 80111 P: 303.796.6000 www.imegcorp.com REF. SCALE IN INCHES 0 1 2 IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG. ©2025 IMEG CONSULTANTS CORP. PROJECT NUMBER: SHEET TITLE: DRAWN BY: CONSULTANT: SHEET: PRELIMINARY NOT FOR CONSTRUCTION Suite 300 www.lrsarchitects.com Portland OR 97209 A R C H I T E C T S 720 NW Davis 503.221.1121 PROJECT #25000169.00 7/ 9 / 2 0 2 5 1 2 : 5 0 : 0 1 P M A u t o d e s k D o c s : / / 2 2 4 0 2 3 - T o u c h m ar k F o r t C o l l i n s / 2 2 4 0 2 3 _ T F C O _ M E P _ R 2 5 . r v t Author E501 ELECTRICAL DIAGRAMS - COMMERCIAL Project Status Touchmark Sr Living/Fort Collins, CO/New 4710 Cinquefoil Lane Fort Collins, CO 80528 25000169.00 1/22/25 NO SCALE 1 RISER DIAGRAM