HomeMy WebLinkAboutSupporting Documentation - Water Adequacy - 06/26/2025 3200 Windy Hill Rd Suite 200E Project No. 2550-00271 Atlanta, GA 30339 June 26, 2025 To: Zhen Wu – NELSON From: Jesse Naughton – Salas O’Brien Copies: Robert Zendejas, Matt Berry, Ryan Mills – Salas O’Brien Subject: Bank of America S. College & Drake – Water Sizing Justification Letter Pages: 1 The following calculations are based on AWWA M22 Design Manual, 2021 International Plumbing Code, and local jurisdiction code amendments. Below is a list of the plumbing fixtures within the scope of this project: One (1) Break Sink One (1) Mop Sink Two (2) Public Lavatories Two (2) Public Water Closets with Flush Valves One (1) Drinking Fountain Based on Tables E103.3(2) & E103.3(3) of the 2021 International Plumbing Code, Total Water Supply Fixture Units: 28 WSFU Peak Water Supply Demand: 25 GPM *Estimated Continuous Flow: 20 GPM *Fixtures are in back-of-house area, and are not intended to be used often. As such, the estimated continuous flow is based on the flowrate of one water closet. Based on Table E104.1 of the 2021 International Plumbing Code, and the information noted above, this site will require a 1” min. water meter and service line with a 1-1/2” feed from the meter to the building. Energetically yours, Jesse Naughton, P.E. SVP, Mechanical Engineer Engineered for Impact™ 6/26/25