HomeMy WebLinkAboutPlans - Electrical Plan - 02/14/20251 ONE LINE DIAGRAM
NTSSCALE:
ONE LINE DIAGRAM GENERAL NOTES:
1.E.C. TO FIELD VERIFY EXISTING CONDITIONS
2.ALL EQUIPMENT IS NEW.
3.ALL EXTERIOR EQUIPMENT TO BE WEATHERPROOF
4.FIELD VERIFY INSTALLATION REQUIREMENTS WITH UTILITY PRIOR TO
ANY ROUGH-IN.
5.THE E.C. SHALL PROVIDE LABELING OF ALL DISCONNECTING MEANS IN
ACCORDANCE WITH NEC 110.22:
5.a.PROVIDE LABEL ON EACH DISCONNECTING MEANS PER NEC
110.22(A)
5.b.SERVICE EQUIPMENT SHALL BE LABELED WITH THE MAXIMUM
AVAILABLE FAULT CURRENT AND DATE PER NEC 110.24(A).
5.c.WHERE ANY SERIES RATED COMBINATION SYSTEMS ARE UTILIZED,
PROVIDE LABEL ON EQUIPMENT CLOSURE INDICATING THE SERIES
RATED SYSTEM COMPONENTS INCLUDING FUSE AND BREAKER
TYPES AND RATINGS IN ACCORDANCE WITH NEC 110.22(B) AND
110.22(C): CAUTION -- SERIES COMBINATION SYSTEM RATED ____
AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.
ONE LINE DIAGRAM KEYED NOTES:
1.PROVIDE CONCRETE PAD FOR UTILITY COMPANY PAD MOUNT TRANSFORMER. REFER TO
UTILITY COMPANY STANDARD FOR INSTALLATION AND USE FOR REQUIREMENTS.
2.PROVIDE GROUNDING ELECTRODE CONDUCTORS, GROUNDING ELECTRODES FOR GROUND
RODS, WATER SERVICE, BUILDING STEEL, AND CONCRETE ENCASED GROUNDING
ELECTRODES, AND ALL CONNECTIONS AS REQUIRED PER NEC 250 PART III.
3.PROVIDE A TYPE I or TYPE II SURGE PROTECTION DEVICE (SPD) TRANSIENT VOLTAGE SURGE
SUPPRESSOR (TVSS) IN ACCORDANCE WITH NEC 230.67(A). THE SPD MAY BE AN INTEGRAL
PART OF THE SERVICE EQUIPMENT OR LOCATED IMMEDIATELY ADJACENT THERETO, OR, PER
NEC EXCEPTION, AT EACH NEXT LEVEL DISTRIBUTION EQUIPMENT DOWNSTREAM TOWARDS
THE LOAD.
4.PROTECT FIRE PUMP NORMAL AND EMERGENCY FEEDERS PER NEC 695.6(A)(2). FEEDER SHALL
BE INSTALLED UNDERGROUND AND/OR OUTSIDE OF BUILDING OR ENCASE IN CONCRETE
WHERE ROUTED THROUGH BUILDING
#
LEVEL 1
PAD MOUNTED UTILITY
TRANSFORMER 208/120V,
3-PHASE, 4W
4000S/4
T
PANEL
H1
400A/3P 2-400A/3P
SPACE
400/4
1
METER
UTILITYM
MAIN SWITCHBOARD 'MSB', 4000A
208/120V, 3PHASE,4W, 85KAIC, NEMA 3R>800G
N
G
800A/3P
R1-1
UTILITY METER MAX.
AVAILABLE FAULT
CURRENT =
(FUSE LET-THRU)
7,000 A
R1-1 METER STACK
NEMA 3R
65 k AIC
M
M
M
M
M
M
M
M M
800/4
ALUMINUM
1
SPD
3
BOND AND GROUND PER NEC 250
·BUILDING STEEL and
COLD WATER PIPE, 3/0Cu
·UFER, #4Cu
·GROUND ROD, #6Cu
2
M M
UNIT
PANEL
TYPICAL
125/3
(TYPICAL FOR
EACH UNIT)
42 k AIC
125A/2P WITH HOT SEQUENCE UTILITY
METER PER UTILITY, TYPICAL
M
LEVEL 2
MMMM
M
M
M
M PANEL
EV
400A/3P
400/4
2
PANEL
H4
400A/3P
400/4
4
LEVEL 3
LEVEL 4
ROOF
70/4
ELEV 1
100A/3P
100A/3P
3
H
SHUNT
TRIP
70FRN
S
SECONDARY CONNECTION
CABINET 208/120V,
3-PHASE, 4W, 4000A 2000A/3P
PROVIDE ARC FLASH
REDUCTION REQUIRED
PER 2023 NEC
2000A/3P
(2) 2" CONDUIT TO
FUTURE SOLAR
6
M
M
M
M
M
800A/3P
R1-2
UTILITY METER MAX.
AVAILABLE FAULT
CURRENT =
(FUSE LET-THRU)
7,000 A
R1-1 METER STACK
NEMA 3R
65 k AIC
M
M
M
M
M
M
M
M M
800/4
M MM
MMMM
M
M
M
M
M
M
M
M
M
800A/3P
R1-2
UTILITY METER MAX.
AVAILABLE FAULT
CURRENT =
(FUSE LET-THRU)
7,000 A
R1-1 METER STACK
NEMA 3R
65 k AIC
M
M
M
M
M
M
M
M M
800/4
M MM
MMMM
M
M
M
M
M
M
M
M
MM
400S/4
FP
ALUMINUM
>800G
MSB
5
4000S/4
COPPER
ALL WORK TO BE INSTALLED INSIDE
FIRE PUMP ROOM PER NEC 695
300/4
FIRE PUMP GENERAL NOTES:
1.FIRE PUMP SIZE AND REQUIREMENTS SHALL BE
DETERMINED BY THE PROVIDER.
2.SEPARATE SERVICE FOR FIRE PUMP MUST BE
APPROVED BY CITY OF FORT COLLINS LIGHT
AND POWER AND BUILDING DEPARTMENT PRIOR
TO ANY WORK.
3.FIRE PUMP INSTALLATION SHALL COMPLY WITH
ALL NEC REQUIREMENTS, RE: NEC ARTICLE 695.
4.PROVIDE PLACARD ON EACH SERVICE
DISCONNECT LOCATION DENOTING ALL OTHER
SERVICES, FEEDERS, AND BRANCH CIRCUITS
SUPPLYING THE BUILDING IN ACCORDANCE
WITH NEC 230.2(E).
5.PROVIDE SEPARATE PRICE FOR ALL
ELECTRICAL WORK ASSOCIATED WITH THE FIRE
PUMP SYSTEM.
208/120V,
3PH, 4W,
42kAIC
FIRE
PUMP
CONTROL
CABINET
JOCKEY
PUMP
CONTROL
CABINET
FIRE PUMP
50HP(VERIFY)
VERIFY FLA
VERIFY LRA
JOCKEY PUMP
2HP(VERIFY)
VERIFY FLA
>800G
4
4
N
G
1200A Class L
1200A/3P
METER
UTILITY M
BOND AND
GROUND PER
NEC 250
AMERICAN
MIDWEST POWER
COMBINATION C.T.
& DISCONNECT
1200A 208/120V,
3PH, 4W, 85kAIC
Feeder Schedule
3000/W
2000/W
1600/W
1200/W
1000/W
800/W
760/W
600/W
500/W
400/W
380/W
300/W
250/W
225/W
200/W
175/W
150/W
125/W
110/W
100/W
90/W
80/W
70/W
60/W
50/W
40/W
30/W
20/W
This table indicates minimum conductor size for feeders
of the ampacity indicated where #/W indicates the #-Ampacity
and W-numbers of wire, #S/W indicates no ground.
All conductors shall be Copper unless noted otherwise.
* Conductor Ampacities shall be based on table 310.15(B)(16)
60 degree column up to 100 Amps and 75 degree column
above 100 Amps unless otherwise permitted by NEC. Ampacity
rating shall be selected in accordance NEC 110.14 (C).
The master electrician shall be responsible for ensuring
that no feeders or branch circuits are installed in a manner
or sized in such a way as to violate the NEC.
Service Ground Table
150G
200G
300G
500G
800G
>800G
Service Ground Conductors sized Per NEC Table 250.66
Equipment Ground Conductors sized Per NEC Table 250.122
All conductors shall be Copper unless noted otherwise.
The service ground chart indicates the minimum Service
Ground Conductor based on #G where # is the ampacity from
the chart above, and the equipment ground chart indicates the
minimum equipment grounding conductor size #EG where
# is the rating/ setting of the overcurrent device protecting the
conductors and equipment.
Where discrepancies occur between the Feeder Schedule
Schedule and the Grounding Tables, the larger conductor
shall be used unless otherwise permitted by the NEC.
The installation shall meet all NEC 250 grounding and bonding
requirements including 250.4 Path for Fault Current. Provide
complete raceway systems metallically joined, connected, and
fittings as required for electrical continuity per NEC 300.10
8[W-500kcmil, 400kcmil, 3-1/2"C]
6[W-400kcmil, 250kcmil, 3"C]
5[W-400kcmil, 4/0G, 3"C]
4[W-350kcmil, 3/0G, 3"C]
3[W-400kcmil, 2/0G, 3"C]
3[W-300kcmil, 1/0G, 3"C]
2[W-500kcmil, 1/0G, 3-1/2"C]
2[W-350kcmil, #1G, 3"C]
2[W-250kcmil, #2G, 3"C]
2[W-3/0, #3G, 2"C]
W-500kcmil, #3G, 3-1/2"C
W-350kcmil, #4G, 3"C
W-250kcmil, #4G, 3"C
W-4/0, #4G, 2-1/2"C
W-3/0, #6G, 2"C
W-2/0, #6G, 2"C
W-1/0, #6G, 2"C
W#1, #6G, 1-1/2"C
W#2, #6G, 1-1/4"C
*60 Degree
W#1, #6G, 1-1/2"C
W#2, #8G, 1-1/4"C
W#3, #8G, 1-1/4"C
W#4, #8G, 1-1/4"C
W#4, #10G, 1-1/4"C
W#6, #10G, 1"C
W#8, #10G, 1" C
W#10, #10G, 3/4"C
W#12, #12G, 3/4"C
#6
#4
#2
1/0
2/0
3/0
Equipment Ground Table
20EG
60EG
100EG
200-1200A per Above
1600EG
2000EG
*75 Degree
W#3, #6G, 1-1/4"C
W#3, #8G, 1-1/4"C
W#4, #8G, 1-1/4"C
W#4, #8G, 1-1/4"C
W#6, #10G, 1"C
W#8, #10G, 1" C
W#8, #10G, 1" C
W#10, #10G, 3/4"C
W#12, #12G, 3/4"C
#12
#10
#8
4/0
250kcmil
Feeder Schedule - Aluminum
3000S/W
2000/W
1600/W
1200/W
1000/W
800/W
750/W
600/W
500/W
400/W
350/W
300/W
250/W
225/W
200/W
175/W
150/W
125/W
110/W
100/W
90/W
80/W
70/W
60/W
50/W
40/W
30/W
20/W
This table indicates minimum conductor size for feeders
of the ampacity indicated where #/W indicates the #-Ampacity
and W-numbers of wire, #S/W indicates no ground.
All conductors shall be Aluminum unless noted otherwise.
* Conductor Ampacities shall be based on table 310.15(B)(16)
60 degree column up to 100 Amps and 75 degree column
above 100 Amps unless otherwise permitted by NEC. Ampacity
rating shall be selected in accordance NEC 110.14 (C).
The master electrician shall be responsible for ensuring
that no feeders or branch circuits are installed in a manner
or sized in such a way as to violate the NEC.
Service Ground Table
150G
200G
300G
500G
1000G
>1000G
Service Ground Conductors sized Per NEC Table 250.66
Equipment Ground Conductors sized Per NEC Table 250.122
All conductors shall be Aluminum unless noted otherwise.
The service ground chart indicates the minimum Service
Ground Conductor based on #G where # is the ampacity from
the chart above, and the equipment ground chart indicates the
minimum equipment grounding conductor size #EG where
# is the rating/ setting of the overcurrent device protecting the
conductors and equipment.
Where discrepancies occur between the Feeder Schedule
Schedule and the Grounding Tables, the larger conductor
shall be used unless otherwise permitted by the NEC.
The installation shall meet all NEC 250 grounding and bonding
requirements including 250.4 Path for Fault Current. Provide
complete raceway systems metallically joined, connected, and
fittings as required for electrical continuity per NEC 300.10
14[W-350kcmil, 3"C]
7[W-500kcmil, 400kcmil G, 3-1/2"C]
8[W-250kcmil, 350kcmilG, 3"C]
4[W-500kcmil, 250kcmil G, 3-1/2"C]
4[W-350kcmil, 4/0G, 3"C]
3[W-400kcmil, 3/0G, 3"C]
3[W-350kcmil, 2/0G, 3"C]
2[W-500kcmil, 2/0G, 3-1/2"C]
2[W-350kcmil, 1/0G, 3"C]
2[W-250kcmil, #1G, 3"C]
2[W-4/0, #1G, 2-1/2"C]
W-500kcmil, #2G, 3-1/2"C
W-350kcmil, #2G, 3"C
W-300kcmil, #2G, 3"C
W-250kcmil, #4G, 2-1/2"C
W-4/0, #4G, 2"C
W-3/0, #4G, 2"C
W-2/0, #4G, 2"C
W-1/0, #4G, 2"C
*60 Degree
W-1/0, #6G, 2"C
W-1/0, #6G, 2"C
W#1, #6G, 1-1/2"C
W#2, #6G, 1-1/4"C
W#2, #8G, 1-1/4"C
W#4, #8G, 1-1/4"C
W#6, #8G, 1" C
W#8, #8G, 3/4"C
W#10, #10G, 3/4"C
#4
#2
1/0
3/0
4/0
250
Equipment Ground Table
20EG
60EG
100EG
200-1200A per Above
1600EG
2000EG
*75 Degree
W#1, #6G, 1-1/2"C
W#2, #6G, 1-1/4"C
W#2, #6G, 1-1/4"C
W#3, #6G, 1-1/4"C
W#4, #8G, 1-1/4"C
W#6, #8G, 1" C
W#8, #8G, 1" C
W#10, #8G, 3/4"C
W#12, #10G, 3/4"C
#10
#8
#6
350kcmil
400kcmil
ALUMINUM FEEDER BID ALTERNATE: PROVIDE SEPARATE PRICE FOR ALUMINUM
MAIN FEEDERS WHERE INDICATED ON THE ONE LINE DIAGRAM ONLY. ANY USE
OF ALUMINUM CONDUCTORS SHALL BE APPROVED BY THE OWNER.
4000/W 11[W-500kcmil, 500kcmil, 3-1/2"C]4000S/W 13[W-500kcmil, 800kcmil G, 3-1/2"C]
PROJECT NAME:302 CONIFER
BUILDING DEVELOPMENT REVIEW -
LEGAL DESCRIPTION: LOT 13, BLK 5,REPLAT NO. 1 OF EVERGREEN PARK
BDR240019 - 302 CONIFER STREET
2024 Santulan Architecturec
ISSUE DATE: 11/15/2024
ISSUE DATE
BDR SUBMITTAL 1 2024.11.15
BDR SUBMITTAL 2 2025.02.14
Front Range Electrical Engineering
3333 S. Wadsworth Blvd. Suite D210, Lakewood, CO 80227
Fax: 720.638.8870 Ph: 303.985.0548
ONE LINE DIAGRAM
SHEET E1.0