HomeMy WebLinkAboutTHE MARK - FDP240013 - SUBMITTAL DOCUMENTS - ROUND 2 - Supporting Documentation (2)C-1 Form Supplemental Information
Johnson Drive Apartments
255 Johnson Drive
Fort Collins, Colorado 80525
Proposed Northwest Transformer
Proposed Southeast Transformer
Service 1 of 5
Apartment Units
(Unit Meter Center 1 of 4)
Service Main Size 1000 Amps
Number of Conduits 3
Size of Conduits 3”
Number of Cables 12
Size of Cables 400 kcmil CU
Service 2 of 5
Apartment Units
(Unit Meter Center 2 of 4)
Service Main Size 800 Amps
Number of Conduits 3
Size of Conduits 3”
Number of Cables 12
Size of Cables 300 kcmil CU
Number of Meters
Self-Contained CT’d
Quantity Amps Quantity Amps
88 100 0 -
Service 3 of 5 – Disconnect 1 of 2
Apartment Units
(Unit Meter Center 3 of 4)
Service Main Size 1000 Amps
Number of Conduits 3
Size of Conduits 3”
Number of Cables 12
Size of Cables 400 kcmil CU
Service 3 of 5 – Disconnect 2 of 2
House Service
Service Main Size 2500 Amps
Number of Conduits 7
Size of Conduits 3”
Number of Cables 28
Size of Cables 500 kcmil CU
Service 4 of 5 – Apartment Units
Service Main Size 1200 Amps
Number of Conduits 3
Size of Conduits 3”
Number of Cables 12
Size of Cables 500 kcmil CU
Service 5 of 5 – Fire Pump
Service Main Size 200 Amps
Number of Conduits 1
Size of Conduits 2”
Number of Cables 4
Size of Cables #3/0 CU
Number of Meters
Self-Contained CT’d
Quantity Amps Quantity Amps
104 100 1 2500
2 175
1 200