Loading...
HomeMy WebLinkAboutTHE MARK - FDP240013 - SUBMITTAL DOCUMENTS - ROUND 2 - Supporting Documentation (2)C-1 Form Supplemental Information Johnson Drive Apartments 255 Johnson Drive Fort Collins, Colorado 80525 Proposed Northwest Transformer Proposed Southeast Transformer Service 1 of 5 Apartment Units (Unit Meter Center 1 of 4) Service Main Size 1000 Amps Number of Conduits 3 Size of Conduits 3” Number of Cables 12 Size of Cables 400 kcmil CU Service 2 of 5 Apartment Units (Unit Meter Center 2 of 4) Service Main Size 800 Amps Number of Conduits 3 Size of Conduits 3” Number of Cables 12 Size of Cables 300 kcmil CU Number of Meters Self-Contained CT’d Quantity Amps Quantity Amps 88 100 0 - Service 3 of 5 – Disconnect 1 of 2 Apartment Units (Unit Meter Center 3 of 4) Service Main Size 1000 Amps Number of Conduits 3 Size of Conduits 3” Number of Cables 12 Size of Cables 400 kcmil CU Service 3 of 5 – Disconnect 2 of 2 House Service Service Main Size 2500 Amps Number of Conduits 7 Size of Conduits 3” Number of Cables 28 Size of Cables 500 kcmil CU Service 4 of 5 – Apartment Units Service Main Size 1200 Amps Number of Conduits 3 Size of Conduits 3” Number of Cables 12 Size of Cables 500 kcmil CU Service 5 of 5 – Fire Pump Service Main Size 200 Amps Number of Conduits 1 Size of Conduits 2” Number of Cables 4 Size of Cables #3/0 CU Number of Meters Self-Contained CT’d Quantity Amps Quantity Amps 104 100 1 2500 2 175 1 200